Course Outline
Program Outline: 1) Latest initiatives to reduce building energy use (ASHRAE building labeling, etc.) 2) Choices a) Ventilation system type b) Energy-saving air handling unit (AHU) ideas that are common to all system types 3) System-specific energy-saving options a) Constant-volume air handlers b) VAV air-handling systems 4) Dedicated outdoor-air systems a) Describe dual wheel unit (enthalpy wheel) b) Deliver air cold rather than neutral 5) Overview of air cleaning a) Particulate filters b) Gaseous air cleaners c) Biologicals
Presenter Biographies
Trane is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-AIA members available on request. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
2009 Trane
Copyrighted Materials
This presentation is protected by U.S. and international copyright laws. Reproduction, distribution, display, and use of the presentation without written permission of Trane is prohibited.
2009 Trane, Inc. All rights reserved.
2009 Trane
Todays Topics
Latest initiatives to reduce building energy use Energy-saving ideas for air-handling systems
Constant-volume air-handling units VAV air-handling systems
2009 Trane
Todays Presenters
Industry 32%
computers 1% cooking 5% electronics 7% wet clean 5% refrigeration 8% cooling 12% lights 11% water heat 12% heating 31% other 4%
Buildings 40%
18% Commercial
Transportation 28%
cooking 2% computers 3% refrigeration 4% office equipment 6% ventilation 6% water Heat 7% cooling 13% heating 14% lights 26% other 13%
2009 Trane
2009 Trane
2009 Trane
Energy Only
10
2009 Trane
11
2009 Trane
F
Unsatisfactory
D
Poor
C
Fair
B
Good
AVery Good
A
High Perform
A+
Net Zero
150
125
100
75
50
25
15
30
50
75
100
12
2009 Trane
80
Building EQ
60
ASHRAE 90.1-2010?
40
20
Net Zero
13 2009 Trane
Use high-efficiency fans (if you have a choice) Consider air-to-air energy recovery Use factory-supplied operating controls
To coordinate (e.g., reduce simultaneous heating/cooling) To optimize (e.g., demand-controlled ventilation)
15
2009 Trane
7 hp
1 2
6 hp
3.5 hp
3 4
3 hp
16
2009 Trane
10
EA
Summer sensible heat water vapor Winter sensible heat water vapor
OA
17
2009 Trane
Zone-level DCV
Saves energy at part load Required by Std 90.1 (Section 6.4.3.9) for zones with more than 40 people/1000 ft2
18
2009 Trane
11
Recover total energy (both sensible and latent) Use controls to your advantage
Coordinate (eliminate simultaneous heating/cooling) Optimize (for instance, demand controlled ventilation)
19
2009 Trane
12
21
2009 Trane
Basic System
RA
T space
constantspeed fan
EA
OA
MA
SA
22
2009 Trane
13
23
2009 Trane
OA
SA
24
2009 Trane
14
T T
OA
SA
25
2009 Trane
single-zone VAV
Benefits
Lower operating cost by reducing fan speed at part load Reduced sound levels at part load Improved dehumidification since the system continues to supply cool, dry air at part load Typical applications: larger zones with variable occupancy (gymnasiums, cafeterias, lecture halls, auditoriums, churches, arenas)
26
2009 Trane
15
T T
CO2
OA
SA
27
2009 Trane
28
2009 Trane
16
29
2009 Trane
OA
RH T
SA
RA
RA cooling coil
30
2009 Trane
17
Benefits
Improved dehumidification performance Smaller footprint since bottom coil module is sized for recirculated air only (not mixed air)
or keep same footprint and reduce fan power
31
2009 Trane
32
2009 Trane
18
MA'
water vapor
MA
RA
CA
51F DB 49F DP 55F DB 42F DP
SA
cooling coil
33
2009 Trane
How It Works
high ability to hold water vapor
Type I Type II
low
relative humidity, %
34
2009 Trane
19
OA
OA RA MA
MA'
MA
RA
CA
SA
CA
50
b ul -b et 60
MA' MA
OA
80 60 40 20
CAreheat SA RA
50 60 70 80 dry-bulb temperature, F 90 100
30
40
110
series wheel requires: less cooling tons no reheat warmer coil temp than Cool + Reheat
80
tu ra pe 70 F , re
180 humidity ratio, grains/lb of dry air 160 140 120 100
51F 43F
30 40
50
CA
b ul -b et 60
m te
MA' MA RA
90
OA
80 60 40 20
CA reheat SA
40 50
30
60 70 80 dry-bulb temperature, F
100
110
20
Benefits
Extends the application of mechanical (vapor-compression) cooling equipment
Lowers achievable dew point by 5F to 10F
Typical applications: zones that require lower dew points (surgery rooms, supermarkets, laboratories, pharmacies, libraries, museums, archive storage)
37 2009 Trane
21
39
2009 Trane
Multiple-Zone VAV
EA RA
space T
OA MA supply air temp determines AHU cooling capacity
SA
variablespeed fan
space T
40
2009 Trane
22
41
2009 Trane
supply fan
42
2009 Trane
23
Fan-Pressure Optimization
static pressure sensor supply fan
43
2009 Trane
fan-pressure optimization
static pressure
1 in.wc.
y erg en
gs vin a s
0 90
80 0
rp m
m rp
rp m
44
2009 Trane
24
Fan-Pressure Optimization
static pressure sensor supply fan
45
2009 Trane
fan-pressure optimization
Benefits
Part-load energy savings Lower sound levels Better zone control Less duct leakage Reduced risk of fan surge Factory-installation and -commissioning of duct pressure sensor Operator feedback to "tune the system"
46
2009 Trane
25
demand-controlled ventilation
CO2
elevators
47
2009 Trane
ventilation optimization
OCC
elevators
48
2009 Trane
26
ventilation optimization
SA
RA
CO2
TOD
CO2
OCC
TOD
OCC
DDC VAV controllers Required ventilation (TOD, OCC, CO2) Actual primary airflow (flow ring)
49
2009 Trane
ventilation optimization
Benefits
Saves energy during partial occupancy Lower installed cost, less maintenance, and more reliable than installing a CO2 sensor in every zone
Use zone-level DCV approaches where they best fit (CO2 sensor, occupancy sensor, time-of-day schedule) Combine with ventilation reset at the system level
50
2009 Trane
27
51
2009 Trane
VAV system
9%
11%
17%
18%
80
60
40
20
Houston
typical system
Los Angeles
Philadelphia
St. Louis
52
2009 Trane
28
Drawbacks
Increases reheat energy Fewer hours when economizer provides all necessary cooling (compressors shut off)
53
2009 Trane
54
2009 Trane
29
Challenges
Minimize comfort problems due to dumping Avoid condensation on air distribution system components
55
2009 Trane
dumping
56
2009 Trane
30
Avoiding Condensation
Properly insulate and vapor-seal ductwork, VAV terminals, and supply-air diffusers Use an open ceiling plenum return, if possible Maintain positive building pressure to minimize infiltration of humid outdoor air Monitor indoor humidity during unoccupied periods and prevent it from rising too high During startup, slowly ramp down the supply-air temperature to pull down indoor humidity Use linear slot diffusers to increase air motion
58 2009 Trane
31
9%
11%
17%
18%
40
20
Houston
typical system
Los Angeles
Philadelphia
St. Louis
59
2009 Trane
60
2009 Trane
32
62
2009 Trane
33
CA
CA
SA
SA
RA
63
2009 Trane
Dew point required 60% space RH 50% space RH Dew point capability packaged DX rooftop mechanical dehumidifier chiller + AHU
desiccant
64
2009 Trane
34
65
2009 Trane
dedicated OA unit
b ul -b et 60
m te
50 30 40
30
40
50
60 70 80 dry-bulb temperature, F
90
100
110
35
dedicated OA system
Demand-Controlled Ventilation
OA VFD CA
dedicated OA unit
VAV box
CA OCC CA
SA
CO2
SA
67
2009 Trane
36
OA''
OA'
OA
CA CA'
EA'
cooling coil
EA
69
2009 Trane
70
2009 Trane
37
How It Works
high
relative humidity, %
71
2009 Trane
70F DB 77 gr/lb 69% RH 68F DB 86 gr/lb 51F DB 54 gr/lb 54F DB 45 gr/lb 45F DP
40 30
b ul -b et w 60 e, ur at r pe 70 m te F
80
OA'' CA CA'
OA
100 80 60 40 20
OA''
50
OA' EA
CA
CA'
30
40
50
60
70
80
90
100
110
dry-bulb temperature, F
72
2009 Trane
38
Total-energy wheel
73
2009 Trane
RA'
CA CA'
RA damper (open)
EA damper (closed)
cooling coil
RA
74
2009 Trane
39
75
2009 Trane
Alternate Configuration
parallel Type III desiccant wheel total-energy wheel
EA
EA'
EA''
CA CA'
OA'
OA
cooling coil
76
2009 Trane
40
78
2009 Trane
41
Gases
Organic (VOC) Non-Organic (carbon dioxide, carbon monoxide, ozone)
79
2009 Trane
Bioaerosols
Ultraviolet Light (UVc) Photocatalytic Oxidation
80
2009 Trane
42
Particulate Filters
Type of Particle Diameter Settling Time Human hair 5 seconds Observable dust in air >10 seconds Bacteria 1 to 5 minutes Viruses 10 days Note: Spores, bacteria, and virus sizes are for the typical complete unit. When entrained in the air, they may be smaller (fragments) or larger (attached to debris) Source: ASHRAE Handbook 2009
81
2009 Trane
6 Deep Very low pressure drop 0.03 in.wc. Media life: ~ 15 years, UV Bulbs ~ 15 months No measureable ozone
82
2009 Trane
43
Photo-catalysis
83
2009 Trane
Flash file
Flash file
84
2009 Trane
44
85
2009 Trane
In Summary.
Air cleaning is a complex issue but getting easier to understand and control Best to know the contaminants of concern and where they are coming from Have a goal in mind Consider all available technologies Understand the maintenance requirements Evaluate from an effectiveness and total cost of ownership perspective
86
2009 Trane
45
Conclusion
Summary
Common energy saving strategies Less airflow/pressure loss Energy recovery Optimizing controls Single-zone choices (one-zone VAV, split dehumidification, Type III desiccant wheel) Multiple-zone VAV choices (fan-pressure optimization, ventilation optimization, low temperature supply air) 100% OA choices (chilled water dedicated outdoor-air units, dual wheel energy recover with Type III desiccant) Air Cleaning technologies (particle filters, photo-catalytic oxidation)
88
2009 Trane
46
Subscribe at www.trane.com/engineersnewsletter
89 2009 Trane
ENL Archives
Insightful topics on HVAC system design: Chilled-water plants Air distribution Refrigerant-to-air systems Control strategies Industry standards and LEED Energy and the environment Acoustics Ventilation Dehumidification
www.trane.com/bookstore
90
2009 Trane
47
91
2009 Trane
48
Bibliography
Air-Handling Systems, Energy and IAQ
Industry Standards and Handbooks
American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). ANSI/ASHRAE IESNA Standard 62.1-2007: Ventilation for Acceptable Indoor Air Quality. Available at www.ashrae.org/bookstore American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE). ANSI/ASHRAE IESNA Standard 90.1-2007: Energy Standard for Buildings Except Low-Rise Residential Buildings. Available at www.ashrae.org/bookstore American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc. (ASHRAE). 1996. Cold Air Distribution System Design Guide. Atlanta, GA: ASHRAE.
Bibliography
Air-Handling Systems, Energy and IAQ
Trane Engineers Newsletters Live Broadcasts
available to purchase from <www.trane.com/bookstore> CO2-Based Demand-Controlled Ventilation, Engineers Newsletter Live broadcast, APP-CMC024-EN (DVD), 2005. Improving Dehumidification in HVAC Systems, Engineers Newsletter Live broadcast, APP-CMC030-EN (DVD), 2007. Lowering Supply-Air Temperatures, Engineers Newsletter Live broadcast, APP-CMC003-EN (DVD), 2000.
Analysis Software
Trane Air-Conditioning and Economics (TRACE 700). Available at <www.trane.com/Commercial/DNA/View.aspx?i=1136>
Product Literature
Performance Climate Changer Available at <http://www.trane.com/webcache/ah/central%20station%20air%20handlers %20(clch)/sales/clch-slb017-en_04012009.pdf> Trane Catalytic Air Cleaning System (CLCH-SLB018-EN) Available from eLibrary
50