Protection Products

ulti-Functio M l a nR ric ela e m ys u N

Catalogue

Selection Guide Product Range


Feeder Protection Model Argus 1 Argus 2 Argus 7 Argus 8 Delta Delta Lite Motor Protection Model Rho 3 Busbar Protection Model DAD - N Transformer Protection Model Duobias M Micro TAPP Description Transformer protection & automation system Automatic voltage control of transformers Description High impedance differential protection Description Motor protection Description Overcurrent and earth fault protection Directional overcurrent and earth fault protection Check synchronising relay Voltage & Frequency protection Feeder Manager Feeder Manager

Feeder/Line Differential Protection Model Solkor - N Description Feeder differential protection, automation & control system

Feeder Protection ARGUS 1 Overcurrent and


earth fault protection
Features & Benefits IDMTL phase overcurrent protection (51P) 3 DTL phase overcurrent protection (50P) IDMTL earth fault protection (51N) 3 DTL earth fault protection (50N) 2-stage circuit breaker failure (50BF) 2 instantaneous or DTL SEF/ REF stages with harmonic rejection (50N/64R) 8 independent setting groups Upto 9 programmable digital (status) input & upto 11 programmable output contacts Trip circuit supervision (95) CT supervision Circuit breaker maintenance Fault recorder Disturbance recorder and sequential events recorder Ammeter function Status & trip LEDs LCD display (16-characters, 2 lines) Fibre-Optic / RS485 Communication Port Communication protocol compatible with IEC 608-70-5-103 or MODBUS RTU

Applications Radial feeders Capacitor banks Industrial plants Transformers & Reactors

Argus 1

Feeder Protection ARGUS 2 Bi-Directional overcurrent


and earth fault protection
Features & Benefits IDMTL phase fault directional overcurrent protection (51/67) 3 DTL phase directional overcurrent protection (50/67) IDMTL voltage/current polarised directional earth fault protection (51N/67N) 3 DTL voltage/current polarised directional earth fault protection (50N/67N) 2- stage circuit breaker failure (50BF) 2 instantaneous or DTL SEF/ REF stages with harmonic rejection (50N/64R) Optional under/over voltage protection (27/59) Upto 9 programmable digital (status) input & upto 11 programmable output contacts Trip circuit supervision (95) CT supervision Circuit breaker maintenance Fault recorder Disturbance recorder and sequential events recorder Ammeter function (Complete metering function on specific models) Status & trip LEDs LCD display (16-characters, 2 lines) Fibre-Optic / RS485 Communication port Communication protocol compatible with IEC 608-70-5-103 or MODBUS RTU

Applications Parallel feeders Ring feeders Distribution feeders Transformers

Argus 2

Feeder Protection ARGUS 7 Check synchronising relay


Features & Benefits Check & system synchronising (25) with independent settings Under voltage blocking Differential blocking Upto 4 programmable digital (status) inputs & upto 7 programmable output contacts Configurable dead bus and/or dead line charge Integral manual close guard feature Split system detection Close records Disturbance recorder and sequential events recorder Status & trip LEDs LCD display (16-characters, 2 lines) Fibre-Optic / RS485 Communication Port Communication protocol compatible with IEC 608-70-5-103

Applications Check & system synchronising (25)

Argus 7

Feeder Protection ARGUS 8 Voltage & Frequency protection


Features & Benefits Four independent voltage elements, each of which can be set as either under voltage (27) or over voltage (59) protection Negative sequence over voltage (47) protection Neutral voltage displacement protection Four independent frequency elements, each can be set for under frequency (81U) or over frequency (81O) protection 1, 2 or 3-phase measurement with four independent voltage elements Independent time delay for each element Upto 9 programmable digital (status) inputs & upto 11 programmable output contacts Trip circuit supervision (95) Circuit breaker maintenance Fault recorder Disturbance recorder and sequential events recorder Status & trip LEDs LCD display (16-characters, 2 lines) Fibre-Optic / RS485 Communication port Communication protocol compatible with IEC 608-70-5-103 or MODBUS RTU

Applications Capacitor bank Ungrounded / High impedance earthed systems AC Generators Transmission lines Distribution feeders

Argus 8

Feeder Protection DELTA Feeder Manager


Features & Benefits Directional/Non-directional phase over current protection (50/51P , 67P) Directional/Non-directional derived earth fault protection (50/51N, 67N) Directional/Non-directional measured earth fault protection (50/51N, 67N) Sensitive earth fault/restricted earth fault protection (50N/64R/87G) Negative sequence over current protection (46IT+DT) Under/over voltage protection (27/59) Under/over frequency protection (81) Negative sequence over voltage protection (47) Neutral overvoltage protection (59NIT+NDT) Thermal overload protection (49) Check synchronisation (25) Cold load pickup Upto 27 programmable digital (status) inputs & upto 21 programmable output contacts Auto reclose (79) Broken conductor detection (46) Circuit breaker failure protection (50BF) Voltage transformer supervision Current transformer supervision Trip circuit supervision (95) Fault recorder Disturbance recorder and sequential events recorder Comprehensive metering functions Upto 32 programmable status and trip LEDs with text legend Mimic display Local/remote/out-of-service key switch Fibre-Optic and RS232 Communication port Communications protocol compatible with IEC 60870-5-103 or MODBUS RTU IRIG-B time synchronization Full programmable scheme logic using ReyLogic

Applications Integrated protection, control, monitoring & metering of distribution feeders

Delta

Feeder Protection DELTA LITE Feeder Manager


Features & Benefits Directional/Non-directional phase over current protection (50/51P , 67P) Directional/Non-directional derived earth fault protection (50/51N, 67N) Directional/Non-directional measured earth fault protection (50/51N, 67N) Sensitive earth fault/restricted earth fault protection (50N/64R) Negative sequence over current protection (46IT+DT) Under/over voltage protection (27/59) Under/over frequency protection (81) Negative sequence over voltage protection (47) Neutral overvoltage protection (59NIT+NDT) Thermal overload protection (49) Check synchronisation (25) Cold load pickup Upto 27 programmable digital (status) inputs & upto 29 programmable output contacts Auto reclose (79) Broken conductor detection (46) Circuit breaker failure protection (50BF) Voltage transformer supervision Current transformer supervision Trip circuit supervision (95)

Fault recorder Disturbance recorder and sequential events recorder


Comprehensive metering functions Upto 32 programmable status and trip LEDs LCD display (20-characters, 2 lines) Fibre-Optic and RS232 Communication port Communications protocol compatible with IEC 60870-5-103 or MODBUS RTU IRIG-B time synchronization Programmable logic using Rey Logic

Applications Integrated protection, control, monitoring & metering of distribution feeders

Delta Lite

Motor Protection RHO 3 Motor protection


Features & Benefits Thermal overload protection (49) Short circuit protection (50) Earth fault protection (50N) Stall and locked rotor protection (48) Phase unbalance protection (46) Undercurrent detection (37) Optional 8 thermistor or Resistance Temperature Detector (RTD) inputs Restart inhibit protection Limitation of number of starts Upto 9 programmable digital (status) inputs & upto 7 programmable output contacts Trip circuit supervision (95) CT supervision Earth fault trip inhibit for contactor control application Circuit breaker failure protection (50 BF)

Fault recorder Disturbance recorder and sequential events recorder Comprehensive metering function
Status and trip LEDs

LCD display (16-characters, 2 lines) Fibre-Optic / RS485 Communication port


Communications protocol compatible with IEC 60870-5-103 or MODBUS RTU

Applications Protection and management of medium and large motors and driven equipment Ideally suited for pumps, conveyors, compressors, fans etc.

Rho 3

Impedance and Busbar Protection DAD N High impedance


differential protection
Features & Benefits High impedance, phase segregated differential protection (87) Upto 27 programmable digital (status) inputs & Upto 29 programmable output contacts 3 analogue inputs Upto 8 setting groups Trip circuit supervision (95) Open circuit current transformer supervision IRIG-B time synchronization Input characteristic rejects DC offset transients and provides excellent harmonic rejections Programmable logic using ReyLogic

Fault recorder Disturbance recorder and sequential events recorder


Metering functions 16/32 programmable status and trip LEDs

LCD display (16 characters, 2 lines)


Fibre-Optic and RS232 Communication port Communications protocol compatible with IEC 60870-5-103

Applications High impedance busbar protection with CT supervision

DAD-N

Transformer Protection DUOBIAS M Transformer


Protection & automation system
Features & Benefits Two-winding and three-winding power transformer, triple slope biased-differential protection (87) Second harmonic magnetising current inrush restraint Differential highset protection (87HS) IDMTL/DTL phase and ground overcurrent protection for HV and LV windings (50/51P , 50/51N) Thermal overload protection (49)* Neutral voltage displacement protection (59N)* Over and under voltage protection (27/59)* Under frequency protection (81)* Overexcitation protection Volts/frequency (24)* Integral restricted earth fault protection for each winding (64R) Upto 27 programmable digital (status) inputs & upto 29 programmable output contacts Circuit breaker failure protection (50BF)* Trip circuit supervision (95) Integrated current amplitude and vector group compensation which removes the needs for interposing CTs Fault recorder Disturbance recorder and sequential events recorder Comprehensive metering functions 16/32 status and trip LEDs LCD display (20 characters, 2 lines) Fibre-Optic and RS232 Communication port Communication protocols compatible with IEC-60870-5-103 and MODBUS RTU IRIG-B time synchronization Programmable logic using ReyLogic
* These are optional functions

Applications Comprehensive protection, monitoring and control package for 2-winding and 3-winding power transformers

Duobias M

Transformer Protection Micro TAPP Automatatic voltage


control of transformers
Features & Benefits Automatic voltage control of power transformers through on-load tap changer Enhanced TAPP (Transformer automatic paralleling package) principle for voltage control User-specified system power factor eliminates errors associated with other circulating current schemes Load drop compensation Coupling control to minimise circulating current Tap-stagger to allow circulating current for network operation purposes Multiple settings groups to allow application of voltage offsets for load reduction and network operation Detection of low system frequencies to facilitate system voltage reduction by tapping down Homing feature enabling transformers to be tapped to the correct busbar voltage prior to switching in to or out of service Tap position indication accepts inputs from either analogue or numerical sender units Runaway prevention to lock out the tap-changer and prevent runaway due to electrical or mechanical failure VT Fuse monitor. Negative Phase Sequence (NPS) voltage element detects blown VT fuses to prevent incorrect voltage control Pseudo-VTTm feature for voltage control on remote side of transformer Self monitoring Events, short-term waveforms and long-term system data recording I2 counter Tap changer operations counter Tap position indicator Fibre-Optic / RS232 Communication port Communication protocol compatible with IEC 60870-5-103 LCD display (40 characters, 8 lines)

Applications Automatic voltage control & monitoring system of power transformers Voltage control on remote side of transformer for embedded generation, traction & induction furnaces

Micro TAPP

Feeder/Line Differential Protection SOLKOR N Feeder differential protection,


automation & control system
Features & Benefits Three pole current differential protection with two stage bias characteristic (87) Current differential protection Three pole, phase fault overcurrent protection - IDMTL or DTL with highsets (50/51P) Earth fault overcurrent protection - IDMTL or DTL with highsets (50/51N) Magnetising inrush detector to provide additional restraint Intertripping from internal or external initiation Upto 9 programmable digital (status) inputs & upto 7 programmable output contacts Ratio correction for mis-matched line current transformer ratios Communication link supervision Trip circuit supervision (95) Circuit breaker fail protection (50BF) I2 counter Fault recorder

Disturbance recorder and sequential events recorder


Local & Remote current metering LCD display (16-characters, 2 lines) Fibre-Optic Communication port Communications protocol compatible with IEC-60870-5-103

Applications Differential protection for overhead lines and cable feeders

Solkor N

The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may differ slightly from that described and illustrated in this publication.
CAT/PPMF/12-05/Rev 0 IMAGIC CREATIVES

HOSUR WORKS

#98, Sipcot Industrial Complex, Hosur 635 126, India. Tel: +91 4344 401600/01/02 Fax: +91 4344 276397

BANGALORE WORKS

#17/3 Arakere, Bannerghatta Road, Bangalore-560 076, India. Tel: +91 80 26581023 / 3268 Fax: +91 80 26580642 Email: blrworks@easunreyrolle.net
AUTOMATION DIVISION EXPORTS DIVISION

SWITCHGEAR WORKS

Ernavur, Chennai-600 057, India. Tel: +91 44 25733715/358 Fax: +91 44 25733468 Email: switchgear@easunreyrolle.net

Ashirwad, #25, 29th Main, 4th B Cross, BTM Layout 2nd Stage, Bangalore-560 076, India. Tel: +91 80 26685496/51311405 Fax: +91 80 26685446 Email: smabp@easunreyrolle.net

#17/3 Arakere, Bannerghatta Road, Bangalore-560 076, India. Tel: +91 80 26581023 / 3268 Fax: +91 80 26580642 Email: exports@easunreyrolle.net

Sales Offices
Mumbai Delhi Kolkata

Tel: +91 22 22022270/22855415 Fax: +91 22 22825703 Email: mumbai@easunreyrolle.net


Bangalore

Tel: +91 11 25747321/25747322 Fax: +91 11 25747320 Email: delhi@easunreyrolle.net


Chennai

Tel: +91 33 22848320 Fax: +91 33 22848326 Email: kolkata@easunreyrolle.net


Secunderabad

Tel: +91 80 26685496/51311405 Fax: +91 22 26685446 Email: blroffice@easunreyrolle.net


Bhopal

Tel: +91 44 24346425/24347608 Fax: +91 44 24346435 Email: chennai@easunreyrolle.net

Telefax: +91 40 27817847 Email: hyderabad@easunreyrolle.net

Telefax: +91 755 2684221 Email: bhopal@easunreyrolle.net

Corporate Office Easun Reyrolle Limited. 98 Sipcot Industrial Complex Hosur 635 126 India. Tel: +91 4344 401600/01/02 Fax: +91 4344 276397 www.easunreyrolle.com