Professional Documents
Culture Documents
EverExceed
12-250G / E8G250-12
GELLED VALVE REGULATED LEAD ACID BATTERY (GVR) FOR CYCLING APPLICATIONS 12V 194 AH @ 5 HR RATE 12V 250 AH @ 20 HR RATE
FEATURES
Exceptional energy storage capacity combined with long life - BCI Classification Thick positive plate design for maximum service float life - 12 year design life @ 20C(68F)
R
UL Recognized component .
Spill-proof and leak-proof Maintenance-free (no topping up) during the whole service life due to EverExceed GEL technology Flame-arresting one-way pressure-relief vent for safe and long life Electrolyte in solid gel form will not stratify - no equalization charge required Increased durability and deep cycle ability for heavyduty applications Fully tank formed grid Lead Calcium Tin plate ensures voltage matching between cells Shelf life up to 2 years at 20C (68F), very low gassing due to internal gas recombination Can be used in any orientation. Upright, side or end mounting recommended
1.5hr
147
2hr
164
3hr
178
4hr
186
5hr
194
8hr
216
10hr
225
12hr
230
20hr
250
1.75
12-250G Specifications
Cells Per Unit 6 Voltage Per Unit 12.84 Weight 176 lbs 80 kg Electrolyte SG = 1.280 CCA at -18C 1500 Amps Short Circuit Current 6300 Amps Ohms Imped 60 Hz () 0.0020
Capacity
250 Ah @ 20 hr. rate to 1.75 volts per cell @ 68F (20C). 194 Ah @ 5 hr. rate to 1.75 volts per cell @ 20C (68F). -40F (-40C) to +140F (60C). +68F (+20C) to +77F (25C). 13.5 to 13.8 VDC/unit Average at 77F (25C). 0.25C20 amperes (62.5 amperes @ 100% depth of discharge) @ 20 hr. rate. 14.1 to 14.4 VDC/unit Average at 77F (25C). 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Maximum voltage allowed = 1.4% RMS (4% P-P). Maximum current allowed = 12.5 amperes RMS (C/20). EverExceed Deep Cycle Gel Range batteries may be stored for up to 24 months at 68 F (20C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. Inter unit connectors racks and cabinet systems are available. Threaded copper alloy insert terminal
Applicable Operating Temperature Range Ideal Operating Temperature Range Floating Charging Voltage Recommended Maximum Charging Current Limit Equalization and Cycle Service Charging Voltage Maximum AC Ripple (Charger)
Self Discharge
1.5
172 182 185
2
150 154 157
3
107 112 114
4
84.3 88.9 90.6
5
70.2 74.0 75.4
8
49.4 52.0 52.9
10
40.8 43.2 44.1
12
34.8 37.0 37.7
20
22.8 24.2 24.7
24
19.6 20.6 20.9
1.5
89.7 95.2 97.5
2
75.5 80.2 82.1
3
54.5 57.9 59.3
4
43.0 45.6 46.7
5
35.6 37.8 38.7
8
24.9 26.3 27.0
10
20.5 21.9 22.5
12
17.5 18.6 19.1
20
11.4 12.2 12.5
24
9.79 10.3 10.6
Note: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.