Identification * NF/LAG/WPL
Finished Standard * Exposed Faces: Matt White / Off White * Other colour is option
PRODUCT INFORMATION
The above louver is capable to have a feature in weather - resisting proof. Approximately 60% Free area in construction NF/LAG/WPL Louver also be available in clip on application or semi-knock down upon request
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR DIFFUSERS SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 15/11/2001 NAM FOONG (M) SDN BHD (8070-T) Weather Proof Louvre - Noise Test 1200mm x 1200mm SOUND POWER LEVEL, dB re 1E-12 W OCTAVE BAND CENTRE FREQUENCY (Hz) 125 250 500 1000 2000
TEST CONDITIONS Qs (l/s) 1443 1863 2393 2664 3009 3231 Ps (Pa) 10 17 28 34 44 49 NR
4000
8000
20 26 34 41 44 46
LEGEND Qs Ps < > NR Primary Air Flow Rate (l/s) Supply Static Pressure (Pa) Insufficient margin above background noise to allow accurate determination Length of throw greater than that able to be measured Noise Rating number based upon room absorption of 10 dB
ACOUSTIC AND AIRFLOW PERFORMANCE TEST OF AIR DIFFUSERS SUPPLIED BY TESTED BY TEST DATE CLIENT UNIT : : : : : NAM FOONG (M) SDN BHD (8070-T) VIPAC ENGINEERS & SCIENTISTS LTD 15/11/2001 NAM FOONG (M) SDN BHD (8070-T) Weather Proof Louvre - Water Test 1200mm x 1200mm
TEST CONDITIONS Qs (l/s) 1443 1863 2393 2664 3009 3231 Qv (m3/s) 1.4 1.8 2.4 2.7 3.0 3.2 Ps (Pa) 10 17 28 34 44 49 Vc (m/s) 1.00 1.29 1.66 1.85 2.09 2.24 Qw (l/h) 74.0 74.0 74.0 74.0 74.0 74.0 Qd (l/h) 0.06 0.12 0.60 2.40 E (%) 100 100 99.9 99.8 99.4 97.7
LEGEND Qs Qv Ps Vc Qw Qd E Primary Air Flow Rate (l/s) Air Flow Rate (m3/s) Supply Static Pressure (Pa) Core Velocity (m/s) Water Supply Rate (l/h) Water Penetration Rate (l/h) Louvre Effectiveness (%)
PERFORMANCE NOTES
The test set up and measurements were taken in general accordance with the following standards :HEVAC Technical Specification 4th edition (Laboratory testing and rating of weather louvers when subjected to simulated rain) Air Movement and Control Association (AMCA Publication 511-91 REV. 10/1996). International Standard ISO 3741 Clause 8.3 (Method 11) (Acoustics Determination of Sound Power Levels of Noise Sources Precision Methods for Broad Band Sources in Reverberation Rooms).
TEST SET UP AND PROCEDURE Reverberation Test Room has a volume of 170m3 has been qualified in accordance with the procedures in ISO 3741 for determination of sound power in octave bands with Centre Frequencies from 125 Hz to 8000 Hz. The Units under test were set up in the Air Distribution (Reverberation) Test Chamber and connected to a quiet air supply. The units were supplied with ambient temperature air at the specified airflow. The environmental test conditions in the reverberation chamber varied for each test within the following ranges : Test Air Temperature Room Air Temperature Barometric Pressure Relative Humidity 18 degrees C 2.0 degree C 20 degrees C 2.0 degree C 1040 millibar 5 millibar 60 10%
100
SP (Pa) 10 1000
10000
1 0.00 74
2 0.00 74
3 0.06 74
4 0.12 74
5 0.60 74
6 2.40 74
Water Penetration Rate Vs Core Velocity 2.5 Water Penetration Rate (l/h) 2.0 1.5 1.0 0.5 0.0 1.0 - 0.5 1.5 2.0 2.5
1.2
1.4
1.6
1.8
2.0
2.2
2.4