Chapter1Introduction............................................................................................................................ 3 1.1BriefIntroductionofPerformanceFeatures ............................................................................. 3 1.2SystemStructure ....................................................................................................................... 3 1.3OperatingMode ........................................................................................................................ 4 1.4FunctionsandCharacteristics ................................................................................................... 6 Chapter2InstallationInstruction ........................................................................................................... 8 2.1UnloadingandUnpacking ......................................................................................................... 8 2.2SiteSelection ........................................................................................................................... 12 2.3InstallationofUPS ................................................................................................................... 12 2.4CableSelectionandConnection ............................................................................................. 13 2.5BatteryConnection ................................................................................................................. 15 Chapter3Operation ............................................................................................................................. 18 3.1IntroductionofOperationInterface ....................................................................................... 18 3.2OperationforPoweronofSingleMachine............................................................................. 19 3.3OperationforPoweroff .......................................................................................................... 27 3.4OperationforEmergencyPoweroff ....................................................................................... 28 3.5OperationforMaintenanceBypass ........................................................................................ 28 3.6EnquiryOperation ................................................................................................................... 29 3.7OperationsforUserConfiguration.......................................................................................... 37 Chapter4InstallationandOperationofParalleledMachine ............................................................... 49 4.1InstallationofParalleledSystem ............................................................................................. 49 4.2On/OffofParalleledMachines................................................................................................ 50 4.3EnquireOperationofParalleledSystem ................................................................................. 51 Chapter5:UPSRepairingandMaintenance ......................................................................................... 53 5.1UPSRepairingandMaintenance ............................................................................................. 53 5.2Troubleshooting ...................................................................................................................... 54 5.3MaintenanceAssurance .......................................................................................................... 58 5.4TechnicalSpecifications .......................................................................................................... 58 Appendix1:LampSignalReferenceList ............................................................................................... 61 Appendix2:PortofCommunicationInterface ..................................................................................... 63 Appendix3:DialSwitchSetofModuleandCharger ............................................................................ 65

PREFACE
Thankyouforusingourproducts. Our company is engaged in developing and manufacturing products of uninterrupted power system which is a kind of power product with high quality and can meet various performance requirements.

Note:
This manual contains instruction of mounting, application, and operation of UPS. It shall read this manual carefully before mounting the system and it is not allowed to take any operations on UPS before finishing reading all safety instruction and operation instruction. This manual contains significant information, please obey all warnings and operation instructions stated by the manual andmachine,andthemanualshallbekeptwell.

Safety
Theuninterruptedpowersystemmustbegroundedbeforeoperation. Battery shall be replaced by qualified maintenance personal. The battery is toxic waste according to laws, so wasted battery shall be recovered by its classification in accordance with requirementofenvironmentalprotection.

Warning
Selling of this product is only for partner who has general information on UPS products. It is necessarytoknowsomeothermountingrequirementsormeasurestopreventaccident. Any content of the manual shall not be modified without allowance of manufacturer and any offendersmustbeinvestigated.Ourcompanyreservestherightoffinalinterpretation.

Chapter1Introduction
1.1BriefIntroductionofPerformanceFeatures
900II1060KVA(3/3)seriesisakindofhighfrequencyUPSwiththreeinletandthreeoutlet designedbyfulldigitalcontroltechnology.Thedesignofunitbreaksconventionaldesignthoughtof towertypemachine,replacedbyadvancedmodulardesignideawhichcanensurecompactnessof layoutandimprovereliabilityoftheunit.Electricalperformanceof900II1060KVA(3/3)seriesis advantageousandprotectionofsoftwareandhardwareofitisperfect.Itisapplicablefordifferent powergridandcansupplysafeandreliablepowerfordifferentloads.

1.2SystemStructure
Componentsofthesystemmainlyinclude:LCDdisplayscreen,communicationport,power module,charger,battery(optional),inputbreaker,outputbreaker,maintenancebypassbreaker, groundrow,Nrow,andsoon.Itssystemstructurechartisshowninfigure1.1andfigure1.2.

Figure1.1Structureof900II1030KVAseries

Figure1.2Structureof900II4060KVAseries

1.3OperatingMode
900II1060KVAisakindofonlinedoubleconversionUPS,itsoperatingmodesareasfollows: Mainpowersupplymode Batterymode Bypassmode Maintenancemode(manualbypass) Frequencyconvertermode

1.3.1Mainpowermode Theworking modethatalternatingcurrentpowerofrectifiercircuitforUPSissuppliedbymain power, direct current power for inverter is supplied after corrected by PFC power factor, and continuous and uninterrupted alternating current power for load is provided by inverter circuit is called main power mode. The charger will start automatically after power on of inverter to supply powerforbattery.

Maintenancebypass

Bypass

Main power input

AC/DC rectification

DC/DCboost

DC/ACinverter

Output

BATTERY

Charger

Figure1.3WorkingProcessChartunderMainPowerMode 1.3.2Batterymode

The working mode that battery power is boosted through battery booster circuit, and then supplied to load through inverter circuit is called battery mode. When main power fault occurs, the systemwillswitchtobatterymodeautomaticallyandpowersupplyforloadisnotinterrupted.When main power recoveries, the system will switch to main power mode automatically without any manualoperationandpowersupplyforloadisnotinterrupted.Switchingtimeofmainpower mode andbatterymodeis0ms.
Maintenancebypass

bypass

Mainpowe input

AC/DC rectification

DC/DCboost

DC/ACinverter

Output

BATTERY

Charger

Figure1.4WorkingProcessChartunderBatteryMode 1.3.3Bypassmode

Iffaultsuchasinvertercircuitfaultandinvertercircuitoverload,orswitchingtobypassmode byhandoccurs,theUPSwillswitchtheloadfromsideofinvertertosideofbypassandpowersupply fortheloadisnotinterrupted.

Maintenancebypass

Bypass

Mainpower input

AC/DC rectification

DC/DCboost

DC/ACinverter

Output

BATTERY

Charger

Figure1.5WorkingProcessChartunderBypassMode 1.3.4Maintenancemode(manualbypass)

IfitneedstomaintainorrepairtheUPS,itcanclosethemanualbypassswitchtoswitchtheUPS tothesideofmaintenancebypassandthepowersupplyforloadisnotinterrupted.Inthatcase,the mainpowerwillnotpasstheinternalcomponentsofmachinebutconnecttheinputterminaland outputterminaldirectlysothatwecanmaintainorrepairtheUPS.

Figure1.6WorkingProcessChartunderMaintenanceBypassMode 1.3.5Frequencyconvertermode

UPScanbesettofrequencyconvertermodewhichcanprovidestableoutputfrequencyof50Hz or60Hz.Inputfrequencyrangeofmainpoweris40Hz 70Hz.UPSwilloutputthesetoutput frequencyandthebypassmodeisineffectiveunderfrequencytransformermode.Whenmainpower isabnormal,thesystemwillswitchtobatterymodeautomaticallyandstilloutputwiththeset outputfrequency.

1.4FunctionsandCharacteristics
DSPfulldigitalcontroltechnology; Pureonlinedoubleconversionframework,strongloadcapability; Input power factor is as high as more than 0.99, low harmonic current, environmental protection,highefficient,andenergysaving; Wide input voltage range, 50/60 Hz power system selfadoption suitable for all grid under any circumstance; Support frequency modes of 50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output which

canmeetspecialrequirementsofuser; Advanced N+X wireless parallel connection redundant technique, high parallel reliability and smallcirculation; Parallelmachinessharethebatterygroupwhichcansavecellinvestmentfromuser; Digitalchargerwithflexiblechargingparametersetandbatterypiecesselection; Advancedbatteryintelligentmanagementtechnology whichcanprolongworkinglifeofbattery effectively; Supportcoldstartofbatteryandautomaticstartofnormalpowerwhichcanmeetusers applicationrequirements; Easily damaged components are completely isolated with air flue which can improve reliability ofthesystemeffectively; Easilydamagedcomponentscanbechangedinmodulelevel,fieldreplacementisfastand convenientandmodulecostislow; Perfecthardwareandsoftwareprotectionfunction(breaker,Fuse,hardwareprotection,and softwareprotection),superselfdiagnosis,andrichhistoricrecordenquiry; 5.7inchLCDtouchwidescreendisplay,friendlyhumanmachineinterface; Manycommunicationports,includingRS232,RS485,USB,drycontactcardandSNMPsmart cardtrough.

Chapter2InstallationInstruction
2.1UnloadingandUnpacking
Usershallcheckthepackagetoconfirmitisundamagedafterreceivingtheproduct;thenopen thepackagetocheckwhethertheequipmentisundamaged,andpleasecontactthecarrieratonceif itisdamaged. 2.1.1Openofcabinetpackage 1)Putthepackingboxvertically;

Figure2.1PackingBoxPlacement 2)Openthetopplateofpackingboxandthentakeoutthefoam;

Figure2.2UnsealthePackingBox 3)Unsealsideplatesofpackingboxandthentakeoutthefoams.

Figure2.3UnsealedCabinet Tips:Itshallbecarefulwhenunsealingtopreventscratchforthemachinebody. Checkwhetherthequalifiedcertificate,instructionbook,CDdisk,andkeysforfrontandback doorsarecompleteornotafteropeningthepackingbox. 3.1.2Openofmodulepacking 1)Placethepackingboxinstable;

10

Figure2.4OuterPackingofModule

2)Cutofftheplasticbelts,removethescotchtape,andthenopenthepaperbox;
paperbox Foampacking

Figure2.5ModuleUnpacking 3)Removecoveroffoampacking,theequipmentwithplasticpackingwillappear;

Coveroffoampacking

Paperbox

Foampacking

Equipment

Figure2.6TakingoutofModule

11

4)Finally,takeouttheequipmentwithplasticpacking,andthenremovetheplasticpacking. Tips:appendixesalongwithcabinetandmodulesshallbekeptwell,especialthatthemanual andCDdiskcontainmuchimportantsafetyinstruction,pleasedonotoperatetheequipment beforereadingthewholesafeoperationinstruction.Allwarningsandoperationsshownby machineandmanualshallbeobeyedstrictly.

2.2SiteSelection
Placedlocationmustbestable; EnoughventilationspacemustbeleftbetweenallsurfacesofUPSandwalls; Befarawayfromhotsourceandcorrosivematerials,avoidthesunshine; Keep normal working temperature and elevation height (working temperature: 0 40,itneedstobeappliedbyderatingifelevationheightexceeds1500m); Keep clean working environment, avoid environment with moisture, flammable gas, flammableliquid,orcorrosivematerial; Weightcapabilityoffloortomachineandbatterygroupshallbeconsideredbefore mounting.

2.3InstallationofUPS
1.PutUPSmachineinspecificlocation. LocationofplacingtheUPSshallbeproperinordertoensuresafetyapplicationofUPS.Itshall beplacedinplacewithcleanenvironmentwithoutmoisture,flammablegas,flammableliquidor corrosivematerialandsunshine.Usercanputitonassignedlocationwithassistantofhumanforce orequipmentandshallpayattentiontospacesbetweenUPSandsurroundingthingswhenmounting sothatitishelpfulforventilationandheatdissipation.Minimumspaceisshowninfigure2.7(unit: mm):

Figure2.7CabinetPlacementChart

12

2.InsertthepowermoduleintoUPSinlocationshowninFigure1.1andthenfixthemodule withHuangguanscrew. Tips: 1.Moduleissoheavythatitneedsmorethan2personstoputitintothecabinet. 2.Itshallbeslowwheninsertingthemoduleuntilitisinsertedfully.

2.4CableSelectionandConnection
2.4.1Selectionofcable Whenselectingconnectingcableforthesystem,itissuggestedtoselectthewirediameterof cableaccordingtomaximumpowerconfigurationof900II1060KVAsystemandcomplyinglocal connectionrulesandenvironmentalcondition(temperatureandphysicalsupportmedia).Thecable shallbeselectedaccordingtomaximumsteadystatealternatinganddirectcurrentsof900II10 60KVA,anditsselectionconditionsarelistedintable2.1: Table2.1CableConfigurationTable

UPSratedpower 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA

Rated380Vinput Output Inputcurrentwhenitis currentwhen fullloadandcharger outputsmaximumpower itisfullload 24A 15A 31A 23A 39A 30A 53A 46A 78A 61A 107A 91A

Discharging currentof32 pieces batteries 28A 41A 55A 83A 110A 165A

2.4.2Connectionofcable Batteryinput(longtermmachine),mainpowerinput,bypassandoutputcableshallbe connectedwithUPSaccordingtothepathsshowninFigure2.8.

Outputinletwiringchannel Bypasswiringinletchannel Mainpowerinputinletwiringchannel Batteryinletwiringchannel

Chart for System Base

Figure2.8InletandOutletWiringChannelof900II1060K

13

Connectionofcableis: 1.Openthedistributionboardtoexposethecopperrows.

Figure2.9FrontViewofCabinet 2.Phasesshowninfollowingfigurearelinebanksofmainpowerinput,bypassinput,battery inputandoutputcableafterpassingtheinletandoutletwiringchannels.

Figure2.10DistributionWiringDiagramof900II1030KVAseries

14

Figure2.11DistributionWiringDiagramof900II4060KVAseries Tip:pleasetightentheinputandoutputcablesandwiringrow. 3.Recoverthedistributionpanel

2.5BatteryConnection
2.5.1Batteryconnectionoflongtermmachine Batterygroupforthismachineispositiveandnegativebatterygroupframework,totalnumber ofbatterycanbeselectedfrom32to40(evennumber),andquantitiesofpositiveandnegative batteriesshallbethesame. Batteryconnectionchartisshowninfigure2.12:

Figure2.12BatteryConnectionChart

15

Asshowninfigure2.12,connectallbatteriesinseries,andleadaNlinefrommiddleconnection pointofbatterygroups,soitshallbethreelinestogetherwithpositiveandnegativeendsofbattery grouptoconnectwithbatteryconnectingterminalsofUPS.Batteriesbetweenpositiveendof batterygroupandNlinearecalledpositivebatteries,andbatteriesbetweennegativeendofbattery groupandNlinearecallednegativebatteries.Usercanselectthecapabilityandnumberofbattery accordingtoitsdemand.ItmustaddanalternatingcurrentbreakerbetweenbatterygroupandUPS toplayaroleofcurrentlimitingprotectionandopenandclosethebatterygroupwhenmaintaining. 2.5.2Installationandmaintenanceofbatteryforstandardmachine 1.Installationofbatterypack: 1)Openthebatterypackpanelinfrontofcabinettoexposethebatterypack.

Figure2.13BatteryPack Note:itneedstoturnonthechargersolelybeforeinstallingthebatteryforthefirsttimetoinspect whethertheoutputvoltageofchargerisnormal. 2)Removethesetscrewsofbatterypackandextractthebatterypack. 3)PutbatteriesintobatterypackasshowninFigure2.14(batterypositiveandnegative terminalsmustbelocatedontherightsideofthebatterypackwheninstallingthebatteries).

4)Putthebatterypackwithbatteriestocorrespondinglocationandlockthesetscrews.

+ -

Figure2.14RightViewofBatteryPack

16

+ -

+ -

5)Measurewhetherthevoltageofeverybatterypackisnormal,thenmeasurewhetherthe sideleadterminalisshortcircuit,ifallofthemisnormal,connectthebatterypackwithUPS accordingtotheconnectingmethodshowninfollowingfigure2.15

Figure2.15ConnectingDiagramofBatteryPack 6)Recoverthebatterypackpanel.

Maintenanceofbatterypack: 1) SwitchtheUPStomaintenancebypassmode. 2) Removethebatterypackpaneltoexposethebatterypack. 3) Cutofftheconnectinglineofbatterypack(asshowninFigure2.15). 4) Takeawaythesetscrewofbatterypackandthentakeawaythebatterypack. 5) Replacethebatteryaccordingtothedemand. 6) Recoverthebatterypack. Thefollowingsafetynotesshallbenotedallthetimewhenmountingandmaintainingthe batteries: 1). Electric shock may occur when mounting the batteries, high shortcircuit current may cause fire; 2). Voltage of battery groups can be 480Vdc which may cause death, so please obey safety attentionsforvoltageoperation; 3).Onlyqualifiedpersonalcanmountandmaintainthebatteries; 4).Wearprotectiveeyeweartopreventaccidentcausedbyelectricarc; 5).Takeoffring,watch,necklace,bracelet,andotheraglets; 6).Usetoolswithinsulatedhands; 7). It shall break down the breaker of battery when connecting lines between UPS and battery. It must ensure that the sequence and polarity of connection are correct after finished connection; 8).Pleasecontactcustomerservicedepartmentofourcompanyiftheuserneedstochangethe numberofusedbatteriesduringnormalapplication.Pleasedonotoperateitsolely.

17

Chapter3Operation
ThischapterdescribesallenquiriesandsettingoperationsofUPStakenbyoperator,including startingofUPS,poweroffofUPS,allenquiryoperations,andparametersetting,etc. Tips:instructionmanualmustbereadcarefullybeforeimplementingthefollowingoperations toavoidpersonalinjuryorequipmentdamagecausedbymisoperation.

3.1IntroductionofOperationInterface
AsshowninFigure3.1,operationinterfacemainlycontains:LEDindicatorlight,5.7inch multifunctionalLCDtouchwidescreenandoperationbutton.
Indicatorlight Operationbutton

TAB FAULT UP BYPSS DOWN BATTERY NOMAL ENTER

EPO

CANCEL COLD START

LCDwidescreen

Coldstart

Figure3.1MonitoringInterface DefinitionsoficonsonpanelsilkscreenandLCDscreenarelistedintable3.1: Monitoringpanel LEDindicatorlight Table3.1Silkscreen/IconIllustration Icon/Silkscreen Meaning FAULT Warn BYPASS Powersuppliedbybypass BATTERY Powersupplierbybattery NOMAL Powersuppliedbymainpower Setting Charger Battery On/Off Inputparameter Outputparameter Returntomaininterface Returntopreviousmenu

18

IconsonLCD touchscreen

Pagedown Pageup History Selftestandmuteoff Recordenquiry

Operationbuttons

TAB UP DOWN ENTER CANCEL COLDSTART EPO

Switchoftouch/buttoncontrol Cursorup Cursordown Confirm Return to touchcontrol from button control Coldstart Emergencypoweroff

LCDscreensupportstwokindsofcontrolmodes,buttoncontrolandtouchcontrol. 1.Buttoncontrol PressbuttonofTABunderanyinterfacetoswitchtobuttoncontrolmode,theselectedicon isdisplayedinreverse,movethecursorbypressingbuttonofUPorDOWN,pressENTERto selecttheiconwherecursorlocatesat,andpressCANCELtoreturntotouchscreencontrolmode. 2.Touchcontrol TakeoperationsbyclickingcorrespondingiconsonLCDscreen.

3.2OperationforPoweronofSingleMachine
Note: Itshallcheckwhetherallscrewsarefastenedandallconnectionsarecorrectornotbefore startingthemachine.Input,output,andbatterybreakersshallbeinoffstate. Forlongtermmachine,itshallsetthechargerparameterss(inChapter3.7.9)beforestarting, andbatterypiecesandgroupsshallbematchwiththebatterygroup.(Setbyprofessionalpersonal ofourcompany) 3.2.1Startundermainpowermode 1.Startmainpowermodedirectly 1)Connectthemainpower ClosetheinputandbypassbreakerandUPSconnecttothemainpowerandbypass.TheUPS screenstartstoworkandthenLOGOinterfaceoccurs.

19

Figure3.2LogoInterface Itwillberefreshedtomaininterfaceafter1s.

Figure3.3MainInterface

Clicktheiconofbatterytocheckwhetherthebatterysetismatchwithactualbattery configuration(detailoperationcanbeseenin3.6.5). 2)StartUPS ClickiconofOn/OffinmaininterfacetopoptheinterfaceofOn/Off. IfitisthefirsttimetostarttheUPS,userneedtoentertheUPSonpassword,thenumberis 19841219.Afterthistime,nopasswordisneededtostarttheUPS.

20

Figure3.4UPSONpassword

ClickiconofINVONandthenUPSstartstopoweronundermainpower.

Figure3.5On/OffInterface ProcessofstartingUPSundermainpowermodewillbefinishedafteratime,andthenthe indicatorlightinfrontpanelofpowermoduleison. Thechargerstartstopoweronautomaticallyafterthepowermoduleisstarted,andthe startingofchargermoduleisfinishedafteratime. 3)Closebatteryandoutputbreakers Closethebatterybreak(longtermmachine)andoutputbreakerafterstartingofUPSunder mainpowerisfinished,andthentheUPSstartnormaloperation. EnergyflowafteritisstartedundermainpowermodeisshowninFigure3.6:

21

Figure3.6OperationsunderMainPower 2.Switchfrombypassmodetomainpowermode IftheUPSisworkingunderbypassmode,clicktheOn/Officoninmaininterfacetopopthe On/Offinterface.

Figure3.7On/OffInterface ClickiconofTOINV,theUPSwillbegintostartthemainpowermode,andstartingunder mainpowermodewillbefinishedafteratime. 3.2.2Startingunderbatterymode Ifmainpowerisfault,UPScanbeturnedonbybatterymodedirectly. 1.Closebatterybreaker,inputbreakerandbypassbreakerandconnectthebattery. 2.PressbuttonofCOLDSTARTincontrolpaneltoturnontheLCDscreen.LCDscreendisplays maininterface. 3.PressENTERfor2stobuildworkingpowerforpowermodule,andthenthefanofmodule startstorotate.Clickthebatteryicontocheckwhetherthebatterysetisthesamewithactual batteryconfiguration(Detailedoperationisshownin3.6.4and3.6.5).

22

Figure3.8MainInterface 4.ClickOn/OfficoninmaininterfacetopoptheOn/Offinterface.ClickiconofINVON,and thestartingunderbatterymodewillbefinishedafteratime.

Figure3.9On/OffInterface 5.Closeoutputbreaker,andthentheUPSoutputisnormalandstartingbybatteryisfinished. Itsenergyflowisshowninfigure3.10:

23

Figure3.10BatteryMode 3.2.3Startingunderbypassmode

Itcanswitchtobypassmodedirectlyundermainpowermodeorunderthecasethatmain powerisavailablebuttheUPShasnotbeenstartedyet. 1.Startthebypassmodefromstandbymode(mainpowerisavailablebuttheUPShasnotbeen startedyet). TheUPShasnotbeenstartedcurrently,anddisplayofitsmaininterfaceisshowninFigure3.11: Clickthebatteryicontocheckwhetherthebatterysetisthesamewithactualbattery configuration.

Figure3.11MainInterface 1)ClickOn/OfficoninmaininterfacetopoptheOn/Offinterface.

24

Figure3.12On/OffInterface

2)ClickiconofBYPON,UPSwillenterthebypassmode,andthebypassmodeisstarted.The chargerwillstartautomaticallyafteratime. 3)Closebatterybreaker(longtermmachine)andoutputbreaker,andthebypassstartstooutput normally. Itsenergyflowchartisshowninfigure3.13:

Figure3.13BypassMode 2.Switchtobypassfrommainpowermode TheUPSisworkingundermainpowermodecurrently,clickiconofOn/Offinmaininterfaceto poptheOn/Offinterface.

25

Figure3.14On/OffInterface ClickiconofTOBYP,andthenthesystemwillenterintobypassmode. 3.2.4Startcharger

1.ChargerwillstartautomaticallytochargethebatterywhenUPSisstartedundermainpower modeorbypassmode. 2. If the charger is off and needs to be restarted, when the UPS is in main power mode or bypass mode, it can click the On/Off icon in main interface to pop the On/Off interface, click icon of CHGONbelowtheCHG_ON/OFF,andthenthechargerwillbestarted. 3.Clicktheiconofchargerinmaininterfacetochecktheworkingstateofcharger.

Figure3.15On/OffInterfaceofCharger 3.2.5Startingbymanualselftest

InordertoensurethebatterystateofUPSandprolongworkinglifeofbattery,itneedsto chargeandreleaseelectricityofthebatteryperiodicallytoensurethatthebatterycansupplypower forUPSnormallywhenmainpowerfailssuddenly. Clickiconofselftestandmuteoffinmainscreen,thepoppedinterfacesincludeTEST10S, TEST10M,TESTLOW,CLRTEST,andMUTE.Clickoneofthefirstthreeoptionstoselectthe selftesttime.Selectdifferentselftesttimesaccordingtothetimeofactualtestperiod.

26

Figure3.16SelftestandMuteoffInterface

3.3OperationforPoweroff
3.3.1Poweroffunderlinemode TheUPSisworkingundermainpowermodecurrently. ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.ClickiconofSHUTtoshut downtheUPS,andthechargerwillbeoffautomaticallyatthesametime.

Figure3.17InterfaceofPoweroffunderMainPower 3.3.2Poweroffunderbatterymode TheUPSisworkingunderbatterymodecurrently. ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.ClickiconofSHUTtoshut downtheUPS. 3.3.3Poweroffunderbypassmode TheUPSisworkingunderbypassmodecurrently.

27

Click icon of On/Off in main interface to pop the On/Off interface. Click icon of BYP OFF to shutdowntheUPS,andthechargerwillbeoffautomaticallyatthesametime. 3.3.4Poweroffthecharger 1.Thechargerwillbeoffautomaticallyifthemachineispoweredoffundermainpowermode orbypassmode. 2.Poweroffthechargerwhenthemachineisworkingundermainpowermodeorbypassmode: 1)ClickiconofOn/OffinmaininterfacetopoptheOn/Offinterface.

Figure3.18PowerOffInterface 2)ClickiconofCHGOFFbelowCHGON/OFFtopoweroffthecharger.

3.4OperationforEmergencyPoweroff
Emergencypoweroff(EPO)switchisusedtopowerofftheUPSunderemergencysituation (suchasfire,flood,etc.).PressbuttonofEPOinmonitoringpanel,theUPSwillcutoffoutputatonce andcutoffthepowerinseveralseconds. Ifitneedstopoweronthemachineagain,itshalltakethepoweronoperationaftercuttingoff themainpowerinputbreakerandbypassbreakerfor30s.

3.5OperationforMaintenanceBypass
3.5.1Startofmaintenancebypass 1.SelectoptionofOn/OffinLCDmaininterface,selecticonofTOBYPinOn/Offinterface,and confirmtheUPSisworkingunderbypassmodeinLCDscreen.

28

Figure3.19BypassMode 2.Openthecoverofmaintenancebypassbreaker,closethemaintenancebypassbreaker,cut offtheinput,output,andbatterybreakers,andthentheUPSentersintomaintenancebypassmode. Itsenergyflowisshowninfigure3.20,andthencutofftheinputandbypassbreakers.

Figure3.20MaintenanceBypassMode

3.5.2Exitofmaintenancebypassmode 1.Closetheinputbreakerandbypassbreaker,thepowermodulebuildsworkingpowerand switchestobypassmodebyhand,chargerstartsautomatically. 2. Close the output breaker and battery breaker, cut off maintenance bypass breaker, put back the baffle of maintenance bypass breaker back, and then the warning maintenance cover is open inLCDscreendisappears. 3.SelectoptionofOn/OffinLCDmaininterface,selectTOINVinOn/Offinterface,thepower modulewillstarttheinverterafter20s,andthenUPSwillbeworkingundermainpowermode.

3.6EnquiryOperation
EnquiryoperationisaparametertoinquirytheworkingconditionandsettingofUPS.

29

3.6.1Enquiryofinputinformation ClickI\Pinmaininterfacetopoptheinputparameterinterface.Theinputparameter interfacewilldisplayinformationincludinginputvoltage,inputfrequency,bypassvoltage,bypass frequency,UPStemperature,etc.

Figure3.21InputParameterInterface 3.6.2Enquiryofoutputinformation

ClickO/Pinmaininterfacetopoptheoutputparameterinterface,andtheninformation includingoutputvoltage,outputcurrent,outputfrequency,activepower,apparentpower,andload factorofthreephaseswillbedisplayed.

Figure3.22OutputParameterDisplay 3.6.3Enquiryofinformationofcharger

Clickiconofchargerinmaininterfacetoinquiryinformationofcharger. Informationofchargerincludes:stateofchargerandparameterofcharger(canbeswitchedby buttonofpageuporpagedown). Theinterfaceofchargerstatewilldisplay:operatingmodeofcharger,chargertemperature, positive/negativechargervoltage,andpositive/negativechargercurrent.

30

Figure3.23InterfaceofChargerState Itcanswitchtointerfaceofchargerparameterbypressingbuttonofpageupordown,andthe followinginformationwillbedisplayed:floatchargevoltage,evenchargevoltage,temperature compensationsetting,positive/negativechargingspeed,andmaximumpositive/negativecharging current.

Figure3.24InterfaceofChargerParameter 3.6.4Enquiryofbatteryinformation

Clickiconofbatteryinmaininterfacetoenterintointerfaceofbatteryparameter.Itwilldisplay: piecesandgroupsofbattery,connectionstate,batteryvoltage,batterytemperature,batteryremain time,batteryremaincapability,batterytemperature,timeofnextselftest.

31

Figure3.25DisplayofInterfaceofBatteryparameter 3.6.5Enquiryofcurrentwarn ClickiconofWARNinmaininterfacetopopcurrentwarninginformation.Itcanswitchthe warninterfacebetweenpowermoduleandchargerbybuttonofpageupandpagedown.

Figure3.26WarnInterface 3.6.6Enquiryofhistory

ClickiconofHISTORYinmaininterfacetopoptheinterfaceofUPShistory.Itcontains:FAULT, WARNING,ATATUS,andOPERATE.

32

Figure3.27InterfaceofHistory 1.FAULT: FAULTrecordsallfaultsoccurredduringoperationofUPS.

Figure3.28InterfaceofFault 2.WARNING WARNINGrecordsreasonsforallwarnswhenwarnsoccurredforUPS.

33

Figure3.29InterfaceofWarning

FAULTandWARNINGcanrecord2100piecesatmostandtheearliestrecordswillbereplaced bynewrecordifnumberofallrecordsexceeds2100.Allrecordsarelistedbyinvertedorderoftime. 3.OPERATE OPERATErecordsalloperationsofUPStakenbyuser.

Figure3.30DisplayChartofInterfaceofOperate 4.STATUS STATUSrecordsallworkingmodeofUPSunderdifferentperiods.

34

Figure3.31DisplayChartofInterfaceofStatus OPERATEandSTATUScansave768piecesatmostandtheearliestrecordswillbereplacedby newrecordifnumberofallrecordsexceeds768.Allrecordsarelistedbyinvertedorderoftime. 5.Enquiryrecord Clickiconofenquiryrecordinfourinterfacesabovetopoptheinterfacesofrecordenquiry. Entertherecordtime,itcaninquiryrecordsbeforeandaftertheenteredtime. 3.6.7Enquiryofcurrentinformation Clickiconofsettinginmaininterfacetopopthesettinginterface.

Figure3.32SettingInterface

ClickiconofSETINFOtopopthecurrentsettinginterfaceofUPS.Informationcontainedin theinterfaceincludes:cabinetNo.,statusofconvertermode,statusofcharger,statusofautostart, testmode,andcontacttelephone.

35

Figure3.33DisplayofCurrentSettingInterface Clickthepageuporpagedowntopopthewarrantyinterfacewhichcaninquirethewarranty periodofcomponentssuchasbatterytoremindtheusertoreplace.

Figure3.34DisplayofWarrantyInterface

3.6.8Enquiryofsysteminformation Clickiconofsettinginmaininterfacetopopthesettinginterface.ClickiconofSYSINFOto popthesysteminformationofthemachine,including:sequencenumber,model,softwareversion, producer,telephone,andwebsite.

36

Figure3.35InterfaceofSystemInformation

3.7OperationsforUserConfiguration
Warn:operationforuserconfigurationisusedforsettingUPSparameters,and nonprofessionalpersonalshallnottakeanysettingoperations. ClickiconofUSERCONFinsettinginterfacetopopthepasswordinputinterfaceofuserset.

Figure3.36PasswordInputInterface Entercorrectpassword(initialpasswordis666666)topoptheuserconfigurationinterface, including:LANGUAGE,TIME,SELFTEST,PROTOCOL,PASSWORD,CALIB,andPHONE.

37

Figure3.37UserConfigurationInterface 3.7.1Languageset LCDdisplayscreencanprovidethelanguageofEnglish.

Figure3.38LanguageSetInterface 3.7.2Timeset

ClickiconofTIMESETinusersetinterfacetoenterintotimesetinterface.Itcanchangethe displayedtimeofUPSbyenteringcurrenttime.

38

Figure3.39TimeSetInterface 3.7.3Autoselftestset

ClickiconofSELFTESTinusersetinterfacetopoptheselftestsetinterface. Itsdisplayisshowninfigure3.40,autoselftestinterfaceincludes:onandoffofselftest,run cycleofselftest,anddurationofselftestforeverytime.

Figure3.40SelftestSet Selectproperselftestdurationandtimebydemand. 3.7.4ProtocolSet

ClickiconofPROTOCOLinusersetinterfacetopoptheprotocolsetinterface.

39

Figure3.41ProtocolSetInterface Therearetwooptionalcommunicationports,RS232andRS485. ClickiconofRS232,andthencommunicationportsetinterfacewillbepopped.

Figure3.42CommunicationPortSetInterface Portpropertyshallbesetbydemand. 3.7.5Passwordset

ClickiconofPASSWORDinusersetinterfacetopopthepasswordsetinterface.

40

Figure3.43PasswordSetInterface Thepasswordisrequiredwhenenteringuserconfigurationinterface. Enteroldpasswordandnewpasswordaccordingtorequirementtochangethepasswordof enteringUserConfigurationInterface(initialpasswordis666666). 3.7.6Calibrate Ifthetouchclickisnotsosensible,itcanrecoverthesensitivityoftouchscreenthrough CALIBRATE. ClickiconofCALIBRATEinsetinterfacetopopthecalibrateinterfaceoftouchscreen.Click specifiedsiteaccordingtoorder,andthenthesensitivityoftouchscreenwillberecovered.

Figure3.44CalibrateInterfaceofTouchScreen Note:objectusedtoclickthetouchscreenshallnotbetoosharpwhencalibrating,otherwise itwilldamagethescreen. 3.7.7Telephoneset ItcanchangethecontacttelephoneofagencybyTELSET.

41

Figure3.45Telephonesetinterface 3.7.8Muteoff

Clickiconofbatteryselftestandmuteoffinmaininterfacetopopinterfaceofbatteryselftest andmuteoff.ClickMUTOFFinselftestinterfacetomutethewarningsound.

Figure3.46InterfaceofSelftestandMuteoff

3.7.9 Advanced setting Note:Itisforbiddentoentertheadvancedsettinginterfacewithouttheallowanceofthe Customerservice,otherwisegreatdamagemayoccur. ClicktheiconofADVANCEDinsettinginterfacetopopthepasswordinputinterface.

42

Figure3.47Passwordinputinterface Entercorrectpassword(initialpasswordis19841219)topoptheadvancedsettinginterface.

Figure3.48Advancedsettinginterface AdvancedsettingincludeMODELCHGCONFSYSCONFWARRANTYOPENSET OTHERSETCOMDATAandOUTCOEF. 1) MODEL ClicktheiconofMODELtopopthemodelsettinginterface.

43

Figure3.49Advancedsettinginterface RUNMODE:tochoosetheworkingmodeuserneeded,singleorparallel. INTYPE:tochoosetheinputtypebytheconditionuseroffered,ifthemainpowerand bypassarethesameACsource,choosesingle,ifnotchoosedouble. CABNUM:iftheuserwanttobuildaparallelsystem,thecabinetsshouldbesetthenumber from1to6,iftheuserjustwantasingleUPS,thenumbershouldbesetas1. OUTTYPE:wecansettheoutputtypeas3/3(3phaseinputand3phaseoutput)or3/1(3 phaseinputand1phaseoutput). UPSS/N:thisnumberistheserial number and forbiddenbeingchanged. 2. CHGCONF ClicktheiconofMODELtopopthemodelsettinginterface. Wecanconfigurethechargerparameterandthebatteryparameterinthisinterface.

Figure3.50Chargerconfigureinterface CHGSTATE: ifthisoptionissetasopen,thechargerisallowedtostart,otherwisethe chargercannotstart. TEMPCMP:thisfunctionhasnotopenyet. BATNUM:forstandardmachine,thenumbershouldbesetas16,forlongbackupmachine, thenumberiscounttothemountofbatteriesuseroffered. BATGROUP:thisparameterrefertothenumberofbatterygroups. BATCAPACITY:itshouldmatchthebatterycapacityuseroffered. CHGRATE:chargercurrent=chargerrate*batterygroups*batterycapacity.

44

SYSCONF Clicktheiconof SYSCONF topopthesystemconfigureinterface.

Figure3.51Systemconfigure 1)CONVERT:tostartthefrequencyconvertermodeornot. 2)AUTOSTART:whenitisopen,theUPSwillstartautomaticallywhenthemainpowerresupply aftertheUPSshutdowninbatterymode. 3) OUTFREQ:tosettheoutputfrequency,itcanbesetas50Hzor60Hz. 4) OUTVOLT:tosettheoutputvoltage. 5) BYP VOLT: to set the range of bypass voltage, if the bypass power voltage is beyond it, UPS willbeforbiddentostartbypassmode. 6) BYP FREQ: to set the range of bypass frequency, if the bypass power frequency is among it, theoutputfrequencywilljustfollowthebypassfrequency,ifnot,theoutputfrequencywillbe50Hz or60Hz. 4 WARRANTY Clicktheiconof WARRANTY topopthewarrantyinterface.

Figure3.52Warrantyinterface Clickthe BAT or CAP tothewarrantysettinginterface.

45

Figure3.53BATwarrantyinterface Theninputthetimewhenthebattery(capacitance)isreplacedandthelifeofthebattery (capacitance),theUPSwillwarnyouifthebattery(capacitance)isuptothewarrantydate. WhenstartingtheUPSfirsttime,updatetheinstalltimeofthebatteryandcapacitance. 5 OPENSET ClicktheiconofOPENSETtopoptheopensetinterface.

Figure3.54Opensetinterface 1)OPENPWD:ifitisopen,theuserneedinputthepasswordwhenstartingtheUPSnexttime, aftertheUPSisstarted,thissetwillturntocloseautomatically. 2)LOCKPWD:ifitisopen,nopasswordsisneededtointerviewanyinterface. 3)BYPENA:ifitisopen,bypassmodecannotbestarted. 6 OTHERSET ClicktheiconofOTHERSETtopoptheothersetinterface.

46

Figure3.55Othersetinterface 2. DEFAULT:restorethefactorysetting. 3. FIRMWARE:toupdatetheSoftware. 4. CLRLOG:clearhistory. 7 COMDATA ClicktheiconofCOMDATAtopopthecomdatainterface.

Figure3.56Comdatainterface ThesecondrowistheworkingmodeoftheUPS,1meansstandbymode,2meansbypass mode,3meansmainpowermode,4meansbatterymode. TheforthrowistheBUSvoltageoftheBUSline,whentheUPSworksnormally,theBUSline shouldbe360V. ThefifthrowistheinvertervoltageoftheUPS. Thesixthrowistheversionofthepowermodule 8 OUTCONF ClicktheiconofOUTCONFtopoptheoutputparameterinterface.

47

Figure57Parametersetinterface Clickthemoduleneededtobeadjustedtopoptheparameterinterface

1) INVVOLTSET:toadjusttheoutputvoltage. 2) OUTVOLTSET:toadjustthedigitalwhichisdisplayedintheoutputinterface(chapter3.6.2) oftheLCDscreen.

48

Chapter4InstallationandOperationofParalleledMachine
Themachinesupportsparalleledmachineextendedoperationwithmaximumextendednumber ofmachinesis6andmaximumextendedpoweris360KVA.

4.1InstallationofParalleledSystem
1.Connectthemainpowerinput,bypassinput,outputandbatteryofUPSwhichisreadyfor parallelaccordingtofigure4.1,andthenconnecttothemainpower,bypass,battery(onlyconnect thebatteryinparallelforstandardmachine)andload.

Figure4.1ConnectionChartofParalleledMachines

2.Asshowninfigure4.2,connecttheparalleledportsofcommunicationportsforUPSreadyfor parallelwithparallelwire,anditcanparallel6machinesatmost.

Figure4.2CommunicationConnectionChartofParalleledMachines Note:

49

1. AlltheparalleledUPSshouldsharethesamebatteries,bypassandmainpower.Thesame phaseoftheoutputshouldbeconnectedinparallel.Otherwisegreatdamagemayoccur. 2. Itneedstodetectwhetherthewiringiscorrectornotafterparallelofoutput,bypass, batteryandloadisfinished. 3. Lengthdifferenceofallthesinglemachineoutputlinesmustbelessthan10m.

4.2On/OffofParalleledMachines
4.2.1Parallelon/offofparalleledmachines Setthecabinetsnumberfrom1n(n6)inmodelsettinginterface(asshowninchapter3.7.9). Closeallinputbreakers,bypassbreakers,batterybreakersandoutputbreakersofparalleled machines,anditsmaininterfaceisshownasfigure4.3:

Figure4.3MainInterfaceofParalleledMachines ClickiconofOn/OfftopoptheOn/Offinterface.

Figure4.4On/OffInterfaceofParalleledMachines ClickSYSTEMinOn/Offinterfacetotakeon/offoperationofparalleledmachines(samewith on/offoperationofsinglemachineinchapter3).

50

Figure4.5On/OffInterface Note:allbreakersshallbeclosedwhenpoweronorpowerofftheparalleledmachines. 4.2.2Singleon/offofparalleledmachines ClickiconofOn/OfftopoptheOn/Offinterface,asshownbelow:

Figure4.6On/OffInterfaceofParalleledMachines SelectUPSn(n6)foron/offoperationtoenterintotheOn/OffinterfaceofUPS. Takeon/offoperation(samewithon/offoperationofsinglemachineinchapter3).

4.3EnquireOperationofParalleledSystem
4.3.1Informationenquireofsinglemachineforparalleledsystem ClickUPSn(n6)inmaininterfacetoenterintothesubordinateinterfaceofparalleled system.

51

Figure4.7InformationInterfaceofSingleMachine Thisinterfacecanenquiretheinformationoninputandoutputbatteryandchargerofthis singlemachine. 4.3.2Informationenquireofwholeunitforparalleledsystem Clickrelatediconinmaininterfacetotaketheenquireoperation(samewiththatinchapter3).

52

Chapter5:UPSRepairingandMaintenance

5.1UPSRepairingandMaintenance
5.1.1PowerandfeaturesofloadshallbeconsideredwhenusingUPS Rated output power of UPS is the key parameter to express how much power load the product can drive, it changes along with alteration of load power factor, for example, 1 KVA UPS maybe cannotdrive1KVAload.UPSshallnotbeunderfullloadconditioninordertoprolongworkinglifeof UPS. Load capability of standby UPS shall be 6070 of rated power, and that of online UPS shall be 7080 of rated power. At the same time, the UPS shall not work under over under loadingconditionforalongtime. 5.1.2EnsureinductionstrokeprotectionofUPS Lightening stroke is the natural enemy of all electrical equipments, so it must ensure the effective shielding and ground protection of UPS against lightening stroke. Lightening stroke may cause inductive high potential pulse due to electromagnetic induction. The high potential pulse may enter into the UPS along with power line or communication line, while there are so many microelectronic devices such as CMOS integrated circuit modules and CPU used for control in the UPS which are very sensitive to electromagnetic pulse of lightening, therefore, the devices are very easytobedamaged. AlthoughourUPShaseffectiveshielding and goodprotectiongroundmeasure, user still needs to adopt lightening protection and overvoltage protection for power line and communicationline(suchasremotemonitoringsingleline). 5.1.3Notesforusing,repairingandmaintenance It must obey theproduct introduction when usingUPS. Related stipulations in usingmanual can ensure all firing lines, zero lines, and earth lines meet requirements, so user shall not change its orderwithoutallowance. Any operation shall strictly comply with correct order of power on and off. It shall avoid excessive fluctuation of voltage output of UPS caused by sudden increasing or reducing of load so thattheUPScannotworkinnormal. It is strictly forbidden to power on and off the UPS frequently. It requires for 30s after the UPSispoweredoffandbeforestartingitagain,otherwise,faultmayoccurredforUPS. Itisforbiddentooperateunderoverload.MaximumstartingloadofUPSshallbecontrolled within 80%, and the inverter tube may be damaged under inverter condition if it is operated under overload condition. Experience proves that the best operation mode is to control the load within 30~60%ofratedoutputpowerformostUPSpowers. Discharging requirement of battery: in general, the UPS is equipped with protection measures for discharging of battery, but the battery will recover to certain voltage after it is discharged so that the protection is powered off, and it is not allowed to restart the machine, otherwise, it may cause overdischarging of battery. The battery shall be used normally after it is recharged. For new bought UPS (or for UPS stored for a long time), it only can be operated after the batteryischarged.Otherwise,thestandbytimewillnotbeensured.

53

For UPS without power off for a long time, its battery shall be discharged for every 3~6 monthsandthenrechargedagain.Itcanprolongtheworkinglifeofbatterybythisway. For UPS stored for a long time, it shall be started and charged for every 3~6 months, otherwise,itmaydamagethehostandbatteryofUPS. ItshallmaintaintheUPSperiodically.Cleandustinsidethemachine,measurethevoltageof batterygroup,checkrunningoffans,andinspectandadjustsystemparametersofUPS. 5.1.4Batterymanagement This system allows the charging system to be with high liability and without high frequency clutterwhichcanavoideffectofhighfrequencywavetobatterylife;avoidoverheatofbatterywhen charging,andprolongworkinglifeofbattery. User can set the battery parameter by monitoring display screen (battery management parameter must be set by professional personal, please notify the customer service personal if user needs to change these parameters), and the system can take intelligent management for battery accordingtousersetandactualstatusofbatterygroup. Chargemodeofthisseriesofproductssystemisthreestagecharge: Stage1:recharge90%capabilityofbattery Chargewithequalizingchargingvoltageandmaximumchargingcurrent; Stage2:rechargethebalance10%capabilityofbattery Turntostage2toequalizingchargefor1minuteandfloatingchargefor1minutewhenvoltage reachesto13.85Vofeverybattery. Stage3:Maintainbatterycapability Itwillswitchtostage3afteritcontinuesfor360cycleinstage2andchargethebatterywith floatingchargesotatthebatteryquantitycanbemaintainedmorethan99%. Battery groupof 900II1060K seriesproductisshared by allmodulesin UPS(includingcharging and discharging). It can use one group of battery or several groups of batteries to increase the standbytimeofsystemaccordingtousersrequirement. Tips: it must take off metal objects such as ring and watch before replacing the battery, use screwdriver with insulated handle, do not put any tool or other metal object on the battery. It is normalphenomenontoappearsmallsparkatjointwhenconnectingthebattery,butitwillnotcause any harm to personal safety and UPS. Do not cause short circuit or reverse connection on positive andnegativeofbattery.

5.2Troubleshooting
Faults of UPS can be known by inquiring history records of UPS, and common problems during operationofUPScanbesolvedbycontrastingtable4.1. Table5.1Fault/WarnRemoval ProblemType Warningof charger
Charger Fail Battery Disconnected

Fault/Warning
Battery Overcharged

Solution Power off the charger and contact customerservicepersonal. Power off the charger and contact customerservicepersonal Check whether charger is started or not

54

Bat Num setting error Over Temperature ChargeVolt setting error ChargeCurr setting error Charger Fanlock Buck Soft Start Fail Input Fuse Fail

Contactcustomerservicepersonal toresetthebatterypiece Unnecessarytosolveit Contactcustomerservicepersonal tochangetheset. Pleasecontactcustomerservice personalifthechargerfanis damaged Poweroffthechargerandcontact customerservicepersonal. Contactcustomerservicepersonal toreplacethefuse Poweroffthechargerandcontact customerservicepersonal Check whether the battery connectioniscorrectandcorrectit 1. Check whether threephase normalpowerisinbalance. 2.Checkwhetherthefluctuationof threephasenormalpowerisin normal. Contactcustomerservicepersonal Cutofftheinputbreaker,andstart themachineafter30s.Please contactthecustomerservice personalifproblemstillexists.

Faultofcharger

Output Fuse Fail Charger ShortCircuit Battery Reverse

UPSfault

Bus Volt High Bus Volt Low

Bus Imbalance Bus Short circuit Bus Softstart Fail

Inv Softstart Fail Inverter Volt High Inverter Volt Low

Contact the customer service personal

R phase Out Short S phase Out Short T phase Out Short RS phase Out Short ST phase Out Short TR phase Out Short R Reactive Abnormal S Reactive Abnormal T Reactive Abnormal

1. Check whether the output connectionisshortcircuitornot. 2.Checkwhethertheloadisshort circuitornot.

Contactthecustomerservice personal

55

Overload Fail

1.Poweroffsecondaryload 2. Reallocate the load so that outputs of three phases are balance. 3.CutoffUPSinputbreakerfor30s, thenstartagain. Ensure environmental temperature is within working range of UPS. Cut off the UPS for 30s, and then start again. Contactthecustomerservice personal Checkwhetherthecommunication lineisconnectedcorrectly Checkwhetherthebypassphase sequenceconnectionofcabinetis normalornot Contactthecustomerservice personal 1. Check whether set of dial switch inbackofmoduleis1~2. 2.Checkwhethersetofdialcodes inbackofmoduleisconflict. 1.Checkwhethertheinputpoweris normal. 2.Checkwhetherthethreephase inputlinesareconnectedcorrectly. Check whether the input power is normal. 1. Check whether the back terminal ofmoduleisnormal. 2. Check whether the terminal connected cabinet and module is normal. Check whether the input breaker is closedornot. Check whether the output breaker isclosedornot. Please contact the customer service personal. Unnecessary for treatment under maintenancebypassmode

Overtemp Fault Power Set Fault Inverter Fault Relay Stick Death Line SCR Fault Can Bus Fault Bypass wiring error Power Set Fault Total Reactive Fault

Id Error

BypassPhaseError Line Phase Error Bypass Loss Bypass Freq Abnormal

N Line Loss

Input CB Open Output CB Open Output Overvolt Maint CB Cover Open

56

Maint CB Cover Open

Battery Volt Low

Battery Open Ovload Fail UPS Over Current UPS Over Load Eeprom Fail UPS Fan Lock
Epo Active

Charger Offline Can Fail Comm Syn Sig Fail Comm Syn Pulse Fail Id Error

1. Unnecessary for treatment under maintenancebypassmode. 2.Checkwhetherthescrewof maintenancecoverisfastenedor notunderotheroperationmode. 1. Check whether the battery and chargerarenormalornot. 2.Checkwhetherthebatteryset matcheswithactualconfiguration. 3.Pleasedismantlethesecondary loadassoonaspossibleifitisunder batterymode. 1. Check external battery breaker is closedornot 2.Checkwhetherthebatteryis connectedwell 1.Closethesecondaryload 2.Reallocatetheloadsothat outputsofthreephasesare balance. Forbiddentopoweron,andcontact thecustomerservicepersonal. Contactthecustomerservice personalifitismodulefault. ConfirmwhetherthebuttonofEPO ispressedornot.Pleasecheckthe screwinleftsideofmoduleis fastenedornotifitisnotpressed. Checkwhetherthechargeris mounted. Checkwhetherthecommunication lineisconnectedwellornot Checkwhetherthesetofdialswitch inconnectingpanelin correspondingmodulelocationof cabinetiscorrectornot.

IDerrorofpowermodule
R phase PFC Fail S phase PFC Fail T phase PFC Fail Bypass STS Open Bypass STS Short

Contacttheconsumerservice personal

57

5.3MaintenanceAssurance
Underconditionofcomplyingrulesofstorage,mounting,using,andoperation,wehaveliability todebug,repairorchangeelementsandcomponentstimelyfreeofchargeiftheproductis damagedduetopoorqualityorimproperoptionorcannotoperatenormallywithinthreeyearssince itisdelivered;wehaveresponsibilitytoprovidepaidlifemaintenancefortheproductifitisoutof thewarrantyperiod. Servicecommitmentofourcompanyis:warrantedforthreeyearsandmaintainedforalllife. Thefollowingcasesarenotincludedinwarrantyrange: 1.Artificialfault; 2.Outofwarrantyperiod; 3.Productwhoseproductionserialnumberischangedorlost; 4.Damageorlosscausedbyforcemajeureandexternalcauses; 5.DismantleorchangetheUPSwithoutauthority; 6.Breachoperation/applicationstipulationsofUPS; 7.Thebatteryisdischargeddeeplyordamagedbymanual.

5.4TechnicalSpecifications
Table5.2TechnicalSpecifications 9010II 9015II 9020II 9030II 10KVA 15KVA 20KVA 30KVA

Model Nominalcapacity Input Ratedinputvoltage Load50% 50% load70% 70% load100% Inputmode Inputpowerfactor Totalharmonic distortion(THDi) Ratedfrequency ACmainpowerinput Bypassvoltagerange Output Outputpowerfactor Ratedvoltage Stabilizedvoltage precision Dynamicvoltage transientrange Totalharmonic distortion(THDV) Outputvoltagedirect currentcomponent Outputcurrentpeak factor

9040II 40KVA

9060II 60KVA

380Vac 204~520Vac 242~520Vac 304~520Vac Threephasefivewiresystem 0.99 3% 50Hz/60Hzselfadoption 40~70Hz 380Vac*(120%)Settable 0.9 380Vac 1% 5%(0100%loadfluctuation) 1%(resistiveload); 3%(nonlinearload) 100mv 3:1

58

Model Outputfrequency Batterymode Frequencytracking rate Phaselockaccuracy Inverteroverload capability Bypassoverload capability Mainpowermode Batterymode Batterymode Mainpowermode System Workingefficiencyof unit Batteryconfiguration

9010II 9015II 9020II 9030II 9040II 9060II Mainpowermode:synchronouswithmainpower;batterymode: 50Hz/60Hz 50Hz/60Hz 1Hz/s 1 100%<load125%,switchtobypassafter10minutes; 125%<load150%,switchtobypassafter1minute; Load>150%,switchtobypassafter0.5s 150%,operateforlongtime;>150%,continuefor10s 0ms 0ms

93%(50%load) 192V~240V(positive/negativebatterygroupwith16,17,18,19and20 piecesforeachgroupforoption,32pieces12V/7AHor12V/9AHare equippedforstandardmachine,thebatteryspacecanallow64pieces batteriesatmost) 12A 24A 6 0~40 <1500m(Shallbereducedusingifexceedingthisheight) 25~55 60dB EN6204011 IEC6100042 Level3 IEC6100043 Level3

Maximumcharging current Maximumparalleled machines Workingtemperature range Workingelevation height Storagetemperature Noisein1mfrom ground Safety Electrostatic discharge Sustained electromagnetic sensitivity Voltageflash compatibility Surgeinterference Electromagnetic interference UPScabinetsize Weight(kg) Color Controlpanel

IEC6100044 Level3 IEC6100045 Level4 EN620402(>25A)classA 600mm*800mm*1280mm 164 174 190 Black 5.7inchmultifunctionalLCDtouchwidescreen 164

158

210

59

Model Audiblealarm Port Optionalelement

9010II 9015II 9020II 9030II 9040II 9060II Alarmofbatterymode;warnwhenvoltageofbatteryistoolow;alarmof fanfault,etc. USB,RS232,RS485anddrycontact(standardequipped) SNMPcard,Paralleledmachinecard

60

Appendix1:LampSignalReferenceList
Mode Standbymode Fault/Warning Phase sequence is error, and main power bypass is abnormal Disconnectionofbattery StatusofLED Thefaultlight twinklesonce2sand lastsfor1/4s Thefaultlight twinklesonce4sand lastsfor1/4s Nofault Allisoff Some module is under fault Thebypasslightison, mode faultlighttwinkles once1sandlastsfor 1/4s Chargerisnotstarted Thebypasslightison, faultlighttwinkles once8sandlastsfor 1/4s Overload Thebypasslightison, faultlighttwinkles once2sandlastsfor 1/4s Phasesequenceiserror Thefaultlight twinklesonce2sand lastsfor1/4s Disconnectionofbattery Thebypasslightison, faultlighttwinkles once4sandlastsfor 1/4s Bypassisnormal Thebypasslightison, faultlighttwinkles once4sandlastsfor 1/4s Nootherfault Thebypasslightison, faultlighttwinkles once2mandlastsfor 1/4s Some module is under fault Thenormallightison, mode faultlighttwinkles once1sandlastsfor 1/4s Chargerisnotstarted Thenormallightison, faultlighttwinkles once8sandlastsfor 1/4s Overload Thenormallightison, faultlighttwinkles Statusofbuzzer Buzzonce2sand lastfor1/4s Buzzonce2sand lastfor1/4s Nosound Buzzonce1sand lastfor1/4s

Bypassmode

Buzzonce8sand lastfor1/4s

Buzzonce2sand lastfor1/4s

Buzzonce2sand lastfor1/4s Buzzonce4sand lastfor1/4s

Buzzonce4sand lastfor1/4s

Buzzonce2sand lastfor1/4s

Mainpower mode

Buzzonce1sand lastfor1/4s

Buzzonce8sand lastfor1/4s

Buzzonce2sand lastfor1/4s

61

Battery self test

Faultmode

Frequency conversion mode Poweroff Communicati on is abnormal

Buzzonce1sand lastfor1/4s Buzzonce2sand lastfor1/4s Othersarenormal Twinkle in turn for Nosound every2s Bypass and output are Bypass light is on, Buzzallthetime normal fault light is on all the time Bypassandoutputare Faultlightisonallthe Buzzallthetime abnormal time Some module is under fault Thenormallightison, Buzzonce1sand mode faultlighttwinkles lastfor1/4s once1mandlastsfor 1/4s Nofault Thenormallightison Nosound Allisoff Nosound Allisoff Nosound

once2sandlastsfor 1/4s Disconnectionofbattery Thenormallightison, faultlighttwinkles once4sandlastsfor 1/4s Nootherfault Normallightison Some module is under fault Fault light is on all the mode time Lowvoltageofbattery Battery light twinkles once1s Overload Allisoff

Buzzonce4sand lastfor1/4s

Nosound Buzzallthetime

62

Appendix2:PortofCommunicationInterface
Thereareseveralcommunicationportsfor900II1060KVAsystem,asshowninFigure1:

Figure1Chartof900II1060KCommunicationPort 1.SNMPNetworkCardPort(optionalfitting) TheLANportcommunicationneedstobesetas:

Connectthecomputerandsystemwithnetworkcable.Itcanusetwistedpairnetworkcableto connectthecomputerdirectlyorusedirectnetworkcabletoconnectthecomputerthrough switchboard. 2.RS232Port Itsmaximumtransmissionrangeis50mwhenthebaudrateis9600. RS232interfacedefinition(othersarenotconnected): Stitch 2 Definition 3.RS485Port Itsmaximumtransmissionrangeis500mwhenthebaudrateis9600. RS485providesdifferentportsfortwokindsofconnectingmodes,oneisRJ45networkcable port,andtheotherisdoublepinport. RJ45networkport(othersarenotconnected): RXD 3 TXD 5 GND

63

Stitch Definition Doublepinport: Stitch Definition 4.USBPort

3 A

5 B

1 A

2 B

TheUSBportisspecialportforUPSmart2000Imonitoringsoftware. 5.InspectionPortofBatteryTemperature Thechargermodulecancollectbatterytemperatureatanytimetoprovidetemperature compensationthroughinspectionportofbatterytemperature. 6.PassiveOutputDryContact 900II 1060K UPS is equipped with a dry contact card which contains 7 groups of independent passive output dry contacts with three connecting terminals for every dry contact, and from left to right which are: normally closed terminal, common terminal, and normally open terminal. The passivedrycontactiscontrolledbyrelay, andthecommonterminalandnormallyclosedterminalof relay will be connected when defined status of dry contact is false; the relay will start operation at oncewhendefinedstatusofdrycontactistrue,andthecommonterminalwillbedisconnectedwith normallyclosed terminal ofrelay,and be connected with normallyopen terminal. User can select to connectthenormallyopenterminalornormallyclosedterminalaccordingtoactualdemand. Identifier INV LINELOSS OVERLOAD BYPASS FAULT BAT.LOW ALARM Meaning Inverteroutput Mainpowerisabnormal Overloadofoutput Bypassoutput Systemfault Warningofbatterylowvoltage Systemalarm

64

Appendix3:DialSwitchSetofModuleandCharger
1. DialSetofAddressforModuleInputPowerConnector Dependingonthepowersegment,theDIPswitchintheinputpowerconnectorcanbesetas follows: Dialswitch(0meansOFFand1meansON) 10KVA 15KVA 20KVA 30KVA 40KVAupper partmodule 40KVAlower partmodule 60KVAupper partmodule 60KVAlower partmodule 1 1 1 1 1 1 0 1 0 2 0 0 0 0 0 1 0 1 3 0 0 0 0 0 0 0 0 4 0 0 0 0 0 0 0 0

Figure2DialSetofAddress 2. DialSetofHardwareProtectionforCharger Setthesetdialswitchofbatterypiecesofcommunicationportinterfacesothatitcanbethe samewithactualbatterypiecestoprotectthebattery. Dialswitchisprotectedbyacover,soitshalltakeawaythecoverbeforeadjustthebattery pieceofdialswitch. Dialswitchsetsforallbatterypiecesare: Dialswitch(0meansOFFand1meansON) 20piecesof batteries 19piecesof batteries 18piecesof batteries 17piecesof batteries 1 0 1 1 1 2 0 0 1 1 3 0 0 0 1 4 0 0 0 0

65

16piecesof 1 1 1 batteries Forexample,figure3refertothesetof16piecesofbatteries.

Figure3Thesetof16piecesofbatteries