TECHNICAL INFORMATION

S10K SONIC CHLORINATOR

INTRODUCTION The S10k chlorinator is an all vacuum operated, sonically regulated unit. Direct cylinder mounting puts the vacuum-regulating valve right at the source, reducing gas pressure to a vacuum immediately. It provides for economic low capacity gas feed applications for municipal and industrial water and wastewater treatment and disinfection, swimming pools and industrial process water. Its ability to handle all water treatment gases as well as its flexible mounting configurations for cylinders, manifolds or ton containers provides versatility for all installations. Two basic arrangements are available in capacities of 200 and 500 pounds per day of chlorine gas. With fewer internal parts, you can be confident that the S10k will provide reliable, dependable service. FEATURES Positive Indication of Operating Status Built-in Automatic Switchover Built-in switchover eliminates the need for external switching devices. The nonisolating feature allows cylinders to be
standby* operating empty off

Unique Secondary Check The 500 PPD regulator includes a unique secondary check designed to confine gas under pressure should the primary valve seat not completely due to contamination. This minimizes the possibility of venting gas to atmosphere.

design is used for ammonia cylinders. A ton container kit includes a drip leg, to trap initial spurts of liquid, a heater for evaporation and a replaceable filter. Handles all Water Treatment Gases The unit can handle all typical water treatment gases e.g. chlorine, sulfur dioxide, carbon dioxide and ammonia. Detachable Rotameters Two sizes of rotameters, 3 and 5, are available in 15 capacities between 1.2 500 PPD chlorine (comparable capacities for other gases). These flowmeters can be integral to the unit, or mounted remote, fo rinstallation flexibility. Rotameters can be ganged together for multiple points of application.

emptied thoroughly, for complete gas consumption.

Easy to read icons provide positive indication of cylinder status. The operator can tell at a glance whether the container is in the standby status (for automatic switchover) operating, empty or off. Positive Shutoff An OFF position on the face of the regulator allows for positive shutoff. Containers can be changed without admitting air, dirt or moisture into the control unit and without shutting off the injector. Captive Universal Yoke Mounting A unique self aligning captive yoke clamp makes it easy to line up and connect the chlorinator to the gasketed outlet of a container valve. The rugged yoke is designed to Chlorine Institute recommendation per drawing 189. A similar captive yoke

TECHNICAL DATA

Easy to Install, Operate and Maintain The S10k chlorinator is simple in design, compact and easy to handle. Injector installation only requires connecting to a water supply and running plastic tubing to a main or open channel. A knob adjustment on the rotameter changes gas feed rate, which is indicated on a high resolution 3" or 5" scale. Accuracy Gas feed is 4% of the indicated flow. Operating Range Manual 20:1 for any flowmeter. Automatic 10:1. Control Modes Manual control, start-stop or program, flow proportional, direct residual, compound-loop, multiple rate control and multiple point operation. Distance, Supply to the Control Unit For flexibility, it is not necessary to install the vacuum regulating valve close to the control unit. It can be up to several hundred feet from the gas control unit, depending on maximum feed rate, the diameter of the connecting pipe or tubing and system performance requirements. Injector Operating Water Injector operating water must be reasonably clean. Injectors are fixed-throat differential type. Maximum inlet pressure

is 300 psi to a maximum of 100 F; 150 psi to a maximum of 130 F. Pressure at Application Point Maximum pressure with hose or polyethylene tubing is 75 psi. High pressure hose or rigid pipe will allow application against back pressure of 75 to 160 psi. A solution pump after the injector will allow application against higher pressure. Swimming Pools For non-residential swimming pool applications a unique package is available. AUTOMATIC CONTROL The S10k can accommodate automatic feed rate control from simple to complex schemes. The control system consists of an actuator and either SCU (Signal Conditioning Unit) or PCU (Process Control Unit). SCU (see TI 40.100UA) Operating Modes: Flow proportional, manual Inputs: 4-20 mA DC (from flow transmitter) Outputs: Control out to actuator; also 4-20 mA output for retransmission of gas feed rate (actuator position) Control Capability: Dosage and flow scaling PCU (see TI 40.200UA) Operating Modes: Direct residual feed back, compound loop, feed forward, flow proportional, manual Ranges: Setpoints up to 50 mg/l and center-zero capability for dechlorination

Control Logic: Proportional and integral with lag Alarms: 4 user-configurable alarms for 16 different conditions OPTIONS Related options include: cylinder valves and connections; header valves with manifolding and connections; vent; injector water and injector outlet lines and clamps; main connections; solenoid valves; water line pressure gauge; high vacuum pressure switch and alarm; gas mask; chlorine detectors; on line analysers; two cylinder scales; residual test kits; injector vacuum gauges; spare parts. Chlorine Gas Warning All unattended chlorine gas containers and chlorination equipment should be monitored for leaks. Sensitive chlorine detectors, which respond quickly to chlorine in the atmosphere, should be installed at each site. See Technical Data Sheet TI 50.130UA for further details. Carbon Dioxide Warning Because of the high pressure in carbon dioxide containers, the vacuum regulating valve cannot be mounted directly on the container. A pressure reducing valve and pressure relief valve must be installed between the container and the vacuum regulating valve.

TECHNICAL DATA

Association recommendations. Compliance Gas feeders, controller and actuator are designed to conform to all applicable NEC and NEMA specifications and Chlorine Institute and Compressed Gas
Connections Pipe and plastic tubing sizes. Vacuum Regulating Valves Tubing to 200 lb 500 lb

7-1/8 Shipping Weight Gas metering unit - 5 lb. Automatic panel - 16 lb.

OVERALL DIMENSIONS Chlorinator: 3 Rotameter - 7-7/8 x 7 x 11-3/4 5 Rotameter - 8-1/4 x 12 x 13 Automatic panel - 25-1/4 x 7-3/8 x

control unit

3/8 x 1/2

1/2" x 5/8"

container valve

gas inlet is yoke connection to a cylinder or header valve or, with optional adapter, to a ton container valve Injectors

Connection water inlet

200 lb 3/4 male NPT or 3/4 flexible pipe

500 lb 1 female NPT 3/4" NPT with adaptors for 3/4, 1, or 1-1/2 pipe or hose

water outlet

same as inlet

Gases and Capacities* Maximum capacity Chlorine lb/24 hour 1.2/4/10/20/50/ 100/150/200 Carbon Dioxide lb/24 hour 1/3/8/15/40/80/ 120/150 Sulfur Dioxide lb/24 hour 1.2/4/10/20/50/ 100/150/200 Ammonia lb/24 hour 0.5/2/5/9/25/ 50/70/100

3 tube 200 PPD

5 tube 500 PPD

3/10/20/30/50/ 75/100/150/200/ 250/300/400/500

2.4/8/15/24/35/58/ 75/116/150/ 200/230/300/390

3/10/20/30/50/ 75/100/150/200/ 250/300/400/475

1.4/4.5/9/14/35/ 45/70/90/120/ 140/190/240

*A selection of tubes in metric calibrations are also available on request

S10K CHLORINATOR EQUIPMENT SPECIFICATION

1.0 GENERAL DESCRIPTION The gas feeder shall be a Wallace & Tiernan Products S10k. It shall be a vacuum operated sonically regulated type system consisting of a vacuum regulator, flowmeter with rate valve and injector. It shall have a maximum capacity of (200) (500) ( ) pounds per day (chlo) rine) (sulfur dioxide) (ammonia) (carbon dioxide) and sized to feed ( PPD. It shall be (manually) (automatically) controlled having a feed range of (20:1 manual) (10:1 automatic) and the capability to control within 4% of the indicated feed rate. 2.0 VACUUM REGULATOR 2.1 Design The (cylinder) (manifold) (ton container) mounted vacuum regulator shall be rated for (200PPD) (500 PPD) ( PPD) of chlorine ( ). It shall consist of a vacuum regulator designed to reduce full supply pressure to a vacuum without venting. A self aligning yoke shall be provided as an integral part of the vacuum regulator. The unit shall include a selector knob and icons to indicate the chlorine gas container status. An off position shall be provided to isolate the diaphragm and internal components from atmospheric air when the operator changes containers. It shall contain internal pressure relief. [It shall contain a drip leg with removable filter and 110 volt heater for mounting on a ton container]. The 500 PPD unit shall include a secondary

check to prevent gas under pressure from venting into the atmosphere. The check valve shall close in the event of leakage past the primary valve. 2.2 Automatic Switchover An automatic switchover system shall be furnished to change over to a new supply as the on-line supply is depleted. A pair of vacuum regulating valves with built-in switchover capability shall be furnished. The regulator valve shall include a mechanical detent to keep the standby gas supply ready for on-line service. When the switchover is accomplished gas shall continue to be drawn from the former source until the container(s) are empty. A separate switchover device will not be acceptable. Each regulator shall include easy to read indication of stand-by, operating, empty and off position. 3.0 CONTROL UNIT A (3 inch) (5 inch) flowmeter assembly with a V-notch rate valve shall be furnished and shall be capable of local or remote mounting. There shall be provisions for interlocking flowmeter frames for multiple feed points. The flowmeter tube shall be serviceable without removing the frame from its mounting. 4.0 INJECTOR Each gas feeder shall have a PVC (3/4) (1) inch fixed throat injector rated (200 PPD) (500 PPD) to generate the operating vacuum for the system. The 4

injector shall be capable of feeding against a back pressure of ( with an operating pressure of ( psi. It shall include built-in double check valve protection to prevent water from back flooding into the vacuum regulator. The injector shall include an integral mounting bracket. It shall be capable of mounting in either the vertical or horizontal plane. 5.0 AUTOMATIC CONTROLS Each gas feeder shall be provided with an integral automatic control system consisting of a dedicated electronic controller, a V-notch positioner, a 5 rotameter and a V-notch chamber. The positioner shall move the V-notch plug and shall contain a reversible motor with thermal overload protection, mechanical override, feedback potentiometer, selectable contacts and front accessibility for service. The positioner, V-notch chamber and 5 rotameter shall be mounted remote from the gas storage area. The positioner and controller shall be housed in NEMA 4X enclosures. 5.1 SCU Flow Proportional Controller The Flow Proportional Controller shall be microprocessor-based with a NEMA 4X enclosure. It shall accept a 4-20 mA process variable input signal. The user interface shall include a membrane keypad and backlit LCD display. ) psi )

Equipment specifications continued on page 5.

S10K CHLORINATOR EQUIPMENT SPECIFICATION

The display shall be scrollable to five operating menus as follows: (1) Main Menu shall display values (2) Setup Menu (3) Input and Output options (4) Diagnostic Menu for trouble shooting (5) Calibration Menu. Dosage can be set from 10 to 400% of intput. An isolated 4-20 mA output signal shall be provided for control, flow or actuator position. The controller shall be an SCU (Signal Conditioning Unit) as manufactured by Wallace & Tiernan Products.

Four configurable alarm relays shall be provided to select from 16 different alarm conditions. The controller shall have password protection to prevent tampering. The unit shall be capable of computer interface via RS485 serial communication. An isolated 4-20 mA output signal shall be provided for control, flow or actuator position. The controller shall be a PCU (Process Control Unit) as manufactured by Wallace & Tiernan Products. 6.0 ACCESSORIES
1 Injector - Capacity to 500 PPD

OR 5.2 PCU Compound Loop Controller The Compound Loop Controller shall be microprocessor based and capable of accepting 3 input signals: flow, residual and one spare. It shall have a membrane keypad, digital LED display of residual, LED bar graph display of percent valve position and 16 character alphanumeric LED display of all operating and setup parameters. The user shall be able to select from six modes of operation: (1) direct residual control (2) compound loop control (3) dual signal feed forward control for dechlorination (4) center zero control for dechlorination (5) flow proportional control (6) manual control.

A vacuum switch shall be supplied to actuate on loss of gas pressure. It shall be designed for mounting integral to the vacuum regulator and shall be supplied with one normally opened, normally closed contact rated at 10 amps.

3/4 Injector - Capacity to 200 PPD

TECHNICAL INFORMATION

S10K SONIC CHLORINATOR

Taking care of the world's water.


Wallace & Tiernan Products 1901 West Garden Road Vineland, NJ 08360 856.507.9000 tel 856.507.4125 fax www.wallaceandtiernan.usfilter.com
Literature # TI 25.200 UA 9/99 1999 United States Filter Corporation

Progressive changes in design may be made without prior announcements.