AC UPS BATTERY RACK SIZING TABLE - RIBs

Battery Type BATTERY VOLTAGE Nominal Cell voltage No of Cells End Cell Voltage Battery Ah = SBM 220 1.2 175 1.1 Ni-Cd Volts Volts Nos Volts

Inv kVA x 1000 x PF x BT x TC x AF Inverter Efficiency x No of Cells x V Cell End Ampere Hours Inverter kVA Power Factor Inverter Efficiency Cell end of discharge V Number of Cells Battery back-up time Temperature Compensation Battery aging factor

Ah Inv kVA PF V Cell End Cells BT TC AF

0.8 0.85 1.1 175 1 1 1.25

V/cell Nos hour

CALCULATIONS AREA UPS Load (kVA) 50-RIB-01 60-RIB-02 20-RIB-01 30-RIB-01 10-RIB-03 10-RIB-04 30-RIB-02 60-RIB-01 50-RIB-02 60-RIB-03 13.26 13.26 28.57 13.26 28.57 70.4 13.26 13.26 13.26 13.26

Considering Selected Future (kVA) Standard Size (kVA) 16.32 16.32 35.71 16.32 35.71 86.73 16.32 16.32 16.32 16.32 20 20 40 20 40 100 20 20 20 20

Battery Ah Selected (Calculated) Size (Ah) 122 122 244 122 244 611 122 122 122 122 138 138 277 138 277 625 138 138 138 138

BATTERY RACK DETAILS: Battery Block Dimensions Type (Ref Annex I) SBM-138 (H) (W) (L1) (L2) 405 195 115

Rack Total No of Arrangement cells / Step / Tier 2 Tier 2 Step =88/2/2 22 Nos

Battery Rack Length

BATTERY RACK (W)

=22x115 2530 mm

500 mm

Bottom tier 22+22 Top tier 22+22 SBM-277 (H) (W) (L1) (L2) 405 195 228 Bottom tier 11+11+11+11 Top tier 11+11+11+11 SBM-625 (H) (W) (L1) (L2) 405 195 268 2 Tier 3 Step =175/3/2 30 Nos =30x195 (Note 2 940 mm 5850 mm 2 Tier 4 Step =88/4/2 11 Nos =11x228 2508 mm 930 mm

Bottom tier 30+30+30 Top tier 28+28+29 Enclosures 1) Annexure I - Dimensions of M Range batteries
2) Annexure II - Battery Rack Dimensions for 2 tier, standard floor mounted racks - Normal connection 3) Annexure III - Battery Rack Dimensions for 2 tier, standard floor mounted racks -Crosswise connection

4) Annexure IV - Battery Rack diagrams 5) Annexure V Notes: 1 Dimension of Battery Room for 10-RIB-04 is to be re-checked. 2 Due to terminal arrangement of SBM 625 battery, width-to-width connection considered. Other cases the same is length-to-length connection (Ref Annexure V) 3 Above are for 1 Set of batteries. 2 set of Batteries (Dual Redundant) are required as per drg no 3481-8532-70-0030

1 of 6

20 kVA UPS (50-RIB-01, 60-RIB-02, 30-RIB-01, 30-RIB-02, 60-RIB-01, 50-RIB-02, 60-RIB-03)

800 mm

2530 mm Battery Set 1

1000 mm

500 mm

1000 mm Battery Set 2 1000 mm

Battery type SBM - 138


Room Size = 4530 mm x 3600 mm (approx)

800 mm

2 of 6

40 kV UPS (20-RIB-01, 10-RIB-03)


2508 mm 750 mm Battery Set 1 930 mm 1000 mm

800 mm Battery Set 2 1000 mm 930 mm

750 mm

Battery type SBM - 277


Room Size = 4508 mm x 4160 mm (approx)

3 of 6

100 kVA UPS (10-RIB-04)


5850 mm 800 mm Battery Set 1 940 mm 800 mm 1000 mm Battery Set 2 940 mm 800 mm

800 mm

Battery type SBM - 625


Room Size = 7450 mm x 4480 mm (approx)

4 of 6

AC UPS BATTERY RACK SIZING TABLE - CCB


Battery Type BATTERY VOLTAGE Nominal Cell voltage No of Cells End Cell Voltage Battery Ah = SBM 400 1.2 318 1.1 Ni-Cd Volts Volts Nos Volts

Inv kVA x 1000 x PF x BT x TC x AF Inverter Efficiency x No of Cells x V Cell End Ampere Hours Inverter kVA Power Factor Inverter Efficiency Cell end of discharge V Number of Cells Battery back-up time Temperature Compensation Battery aging factor

Ah Inv kVA PF V Cell End Cells BT TC AF

0.8 0.85 1.1 318 1 1 1.25

V/cell Nos hour

CALCULATIONS UPS Load Considering AREA (kVA) Future (kVA) CCB - UPS 163.26 208.08

Selected Standard Size (kVA) 220

Battery Ah Selected (Calculated) Size (Ah) 740 740

BATTERY RACK DETAILS: Battery Block Dimensions Type (Ref Annex I) SBM-740 (H) (W) (L1) (L2) 405 195

Rack Total No of Arrangement cells / Step / Tier =318/2/2/4 20 Nos 115 (Note 4) Bottom tier 20+20 Top tier 20+20 2 Tier 2 Step

Battery Rack BATTERY Length RACK (W)

=20x195 3900 mm (Note 2)

930 mm

Enclosures 1) Annexure I - Dimensions of M Range batteries


2) Annexure II - Battery Rack Dimensions for 2 tier, standard floor mounted racks - Normal connection 3) Annexure III - Battery Rack Dimensions for 2 tier, standard floor mounted racks - Crosswise connection

4) Annexure IV - Battery Rack diagrams 5) Annexure V Notes: 1 Dimension of Battery Room for CCB is to be re-checked. 2 Due to terminal arrangement of SBM 740 battery, width-to-width connection considered. Other cases the same is length-to-length connection (Ref Annexure V) 3 Above are for 1 Set of batteries. 2 set of Batteries (Dual Redundant) are required as per drg no 3481-8532-70-0030 4 For CCB, due to large no of Cells, each Battery has been considered distributed in 4 racks.

5 of 6

220 kVA UPS (CCB)


800 mm 3900 mm 800 mm 3900 mm 800 mm 930 mm Battery Set 1 750 mm 930 mm 750 mm 930 mm Battery Set 2 750 mm 930 mm

Battery type SBM - 740


Room Size = 9500 mm x 7570 mm (approx)

800 mm

6 of 6