Professional Documents
Culture Documents
TRANSFORM THE SMARTMAX INTO A POWERFUL COST-EFFECTIVE MINI REMOTE TERMINAL UNIT
Turn your Smartmax M2M HSPA Smart Modem Solution into a cost-effective mini RTU with the I/O Interface Controller. When used in conjunction with Maxons Smartmax Modem for data telemetry, the I/O Interface Controller provides wide-ranging flexibility for system integrators and users for automating and controlling innumerable field applications. Local or remote programming of the I/O Interface Controller can be done via the Smartmaxs builtin Web Interface. The fully featured web interface includes programming of the DNP3 settings and I/O status updates via SMS. The SmartMax connects directly to the IO board via a ribbon connection, while the I/O controller can be wired to collect data automatically and connect directly to sensors, meters, loggers or process equipment.
2 Analogue Inputs 4 Digital Outputs 1 Pulse Input DNP3/SMS Settings configurable via web page inside Smartmax Modem. I/O Board controllable via DNP3, SMS, or using inbuilt web page.
The Mini I/O Controller MA-3020 is a fully labelled , robust enclosure that secures the I/O Board. This solution provides an all-in-one product.
*N ot
to
SDK (Software Development Kit) is available for the Smartmax HSPA Modem (Product Code: MA-2010)
081112
Frequency Bands
WCDMA/HSPA 850MHz, 900MHz, 1900MHz, 2100MHz GSM/GPRS/EDGE 850MHz, 900MHz, 1800MHz and 1900MHz
General Features
Packet Data 2 Way SMS
Connection Specifications
6 Digital Inputs Characteristics VIH (Input voltage high range): 2 ~ 24V VIL (Input voltage low range): -2 ~ 0.8V Ri (Input impedance): more than 5 k Rd (Internal pull-up): 47 k for short to ground detection Input chatters are filtered by S/W setting
Metering
Remote SMS diagnostics & reset Embedded TCP/IP, UDP/IP STACK In-built periodic reset External DC Powered Support VPN Server and Client Mode
Water
Dynamic DNS Supports DNP3 (Outstation) using extension I/O board Rugged Metal Casing for industrial use In-Built Web Interface Programmable scheduler to control WAN connection Telnet support
1 Pulse at Input 0 Frequency range 0 ~ 1000 Hz Accuracy (25C) 0.05 % of span Temperature stability 0.005 % / C Input impedance 47k 4 Digital Outputs MOSFET switch to ground Ro (Output resistance): less than 300 m VOpen (maximum allowed output voltage on open): 24 VDC IOut (maximum allowed switching current to ground): 1A
Road Signs
Save and restore modem configuration from a file FOTA - Firmware upgrade over the air External antenna connectivity to maximise HSPA coverage External LED to show Network and Connection status
Security
Connections
6 x Digital Inputs (INPUT 0 ~ INPUT 5 in terminal block) 4 x Digital Outputs (OUTPUT 0 ~ OUTPUT 3 in terminal
block)
Switching time < 10 msec Chatter free 2 Analog Inputs 12bit resolution Accuracy: Typical 0.25% ; Worst Case 1% Maximum sampling rate: 10 sample/sec Input signal type: one of 0~20mA, 0~5V, or 0~10V (The input type is selected by the jumper PULSE on the connected Smartmax and INPUT# on the I/O board) Input impedance for the signal type 0 ~ 20mA < 100 Input impedance for the signal type 0 ~ 10VDC > 10K
Transport
1 x Case Open 1 x Battery (Monitor Battery Level) 1 x 20 Pin Terminal Block (SmartMax Interface)
Power
Environmental Specifications
Normal Operation Temperature Extreme Operation Temperature -20 to 60 C -25 to 75 C
Compliance
www.maxon.com.au
RoHS Compliant
Dimensions
210mm X 1100mm X 650mm (with connectors)
F | +612 8707 3001 E | sales@maxon.com.au 36A Gibson Avenue, Padstow NSW Australia 2211 www.maxon.com.au