Home News Automation Downloads Energy Savers FAQ Genset Links Linux Motor Control Motor Starters Power Factor Single Phase Motors Slip Ring Motors Soft Starters Variable Speed AC Drives DC Drives Ventilation Favorite Books Book Store Forum (Q&A) Guestbook Featured Software Software Library Classified Ads Donate Contact Us Technology Warehouse Advertise Here

Power Factor Calculations.


Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively the current is being converted into useful work output and more particularly is a good indicator of the effect of the load current on the efficiency of the supply system. There are two types of power factor, displacement power factor and distortion power factor. Only displacement power factor can be corrected by the addition of capacitors. Displacement Power factor. The Line Current comprises two components of current, a real component indicating work current, and a reactive component which is 90 degrees out of phase. The reactive current www.celem.com indicates either inductive or capacitive current and does not do any work. The Real current, or in phase current, generates Power capacitor for wireless energy transfer Power (KW) in the load and reactive current does not like induction charging. generate power in the load. The effect of the reactive curent is measured in KVARs. The composite line current is measured in KVA. The vectors can be represented as two equivilant triangles, one triangle being the real current, the reactive current and the composite (line) current. The cosine of the angle between the line current phasor and the real current represents the power factor. The second identical triangle is made up of the KW KVA and KVAR vectors. For a given power factor and KVA (line current) the KVAR (reactive current) can be calculated as the KVA times the sine of the angle between the KVA and KW.

Celem power capacitor.

Three phase calculations:


KVA = Line Current x Line Voltage x sqrt(3) / 1000 KVA = I x V x 1.732 / 1000 KW = True Power pf = Power Factor = Cos() KW = KVA x pf = V x I x sqrt(3) x pf KVAR = KVA x Sine() = KVA x sqrt(1 -pf x pf)
www.lmphotonics.com/pwrfact1.htm 1/3

12/14/13

Power Factor Calculations

Single phase calculations:


KVA = Line Current x phase Voltage /1000 KVA = I x V / 1000 KW = True Power pf = Power Factor = Cos() KW = KVA x pf = V x I x sqrt(3) x pf KVAR = KVA x Sine() = KVA x sqrt(1 -pf x pf)
Motor Starter Motor Control Three Phase Motor Induction Motor

To calculate the correction to correct a load to unity, measure the KVA and the displacement power factor, calculate the KVAR as above and you have the required correcion. To calculate the correction from a known pf to a target pf, first calculate the KVAR in the load at the known power factor, than calculate the KVAR in the load for the target power factor and the required correction is the difference between the two. i.e. Measured Load Conditions: KVA = 560 pf = 0.55 Target pf = 0.95 (1) KVAR = KVA x sqrt(1 - pf x pf) = 560 x sqrt(1 - 0.55 x 0.55) = 560 x 0.835 = 467.7 KVAR (2) KVAR = KVA x sqrt(1 - pf x pf) = 560 x sqrt(1 - 0.95 x 0.95) = 560 x 0.3122 = 174.86 KVAR (3) Correction required to correct from 0.55 to 0.95 is (1) - (2) = 292.8 KVAR (= 300 KVAR)
3 Phase Generator Capacitor Kvar Load Calculation Load Generator

The new Beamex MC6


www.beamex.com Advanced, highaccuracy field calibrator and communicator.

To calculate the reduction in line current or KVA by the addition of power factor correction for a known initial KVA and power factor and a target power factor, we first calculate the KW from the known KVA and power factor. From that KW and the target power factor, we can calculate the new KVA (or line current). i.e. Initial KVA = 560 Initial pf = 0.55 Target pf = 0.95 (1) KW = KVA x pf = 560 x 0.55 = 308 KW (2) KVA = KW / pf = 308 / 0.95 = 324 KVA => KVA reduction from 560 KVA to 324 KVA => Current reduction to 57% (43% reduction) Bookmark This Page! Please post a link to this page using the following HTML coding...
< F O N TF A C E = " a r i a l ,h e l v e t i c a "S I Z E = " 1 " > P o w e rF a c t o r C a l c u a t i o n s < B R > b y< AH R E F = " h t t p : / / w w w . L M P h o t o n i c s . c o m / p w r f a c t 1 . h t m " > P o w e rF a c t o r C a l c u l a t i o n s < / A > < / F O N T >
New Zealand supplier of Power Factor Equipment

Power Factor Correction Power Factor Controllers

www.lmphotonics.com/pwrfact1.htm

2/3

12/14/13

Power Factor Calculations

Questions and/or comments on this page

Motor Control Mailing List.


Join the Motor control mailing list to discuss motor control technology and problems with like minded experts.

Motor Control Forum


Online forum for discussion of motor control technologies.

Visits since 20 April 2007 [an error occurred while processing this directive] tagcloudKeywords(); ?>

Home Books Software Power factor Motor Control Motor Starters Soft Starters Variable Speed Advertise Energy Savers

L M Photonics Ltd | P.O. Box 13 076, Christchurch, New Zealand | phone : (NZ) +64 274 363 067

www.lmphotonics.com/pwrfact1.htm

3/3

You might also like