ABB
Data schedule: SF6 Circuit Breaker
Tender: 13Q19253031 , Item: 70 General data Type Type of operation Number of poles Min temperature Max temperature Max altitude

C C m

LTB 245E1 1 Pole Operation 3 25 40 1000

Ratings and guaranteed performance in accordance with IEC 62271100 Rated voltage Rated insulation levels Rated lightning impulse withstand voltage to earth across the open circuit breaker Rated switching impulse withstand voltage to earth across the open circuit breaker Rated power frequency withstand voltage to earth across the open circuit breaker Rated frequency Rated normal current Rated shortcircuit breaking current DC component First poletoclear factor Rated transient recovery voltage for terminal faults Rated characteristics for short line fault Peak factor RRRV factor Surge impedance Rated peak making current Rated duration of shortcircuit current Rated out of phase characteristics Out of phase making and breaking current Voltage factor Rated line charging breaking current Rated cable charging breaking current Rated operating sequence Mechanical endurance class Operating times Opening time Break time Closing time Constructional features Number of breaks per pole Gas mixture Total mass of gas Volume of gas Max. working pressure Filling pressure at +20C Alarm pressure Blocking pressure Bursting disc HV terminal ms ms ms kV 245

kVpeak kVpeak kVpeak kVpeak kV kV Hz A kA % kVpeak

1050 1050 460 460 60 2000 40 60 1.5 420 1.6 0.24 450 104 3 10.0 2 125 250 O0.3sCO3minCO M2 17 2 40 <28

kV/s/kA Ohm kApeak s kA A A

1 0.8 MPa SF6 kg 26 liter 3 x 158 MPa (gauge) 0.80 MPa (abs) 0.80 MPa (abs) 0.72 MPa (abs) 0.70 No IEC(40) 9hole + NEMA(44.5) 4hole

06/28/2013 03:32:06 PM
Heater in packing boxes Breaker position indication (OI) Dimension print Seismic/Reinforced Insulators Type of insulators and colour Min nominal creepage distance phasetoearth Min nominal creepage distance across open breaker Operating mechanism Number of drives Motor charged spring operating mechanism Whether fixed trip or tripfree (IEC Publ.60050(441)) Operating voltage Heater voltage Motor voltage Power required at rated supply voltage by Closing coil Opening coil Motor Heating element, continuously Heating elements, connected by thermostat Number of auxiliary contacts making and breaking Manual trip Type of terminals supply Type of terminals signals TCS resistor Circuit diagram TCS resistor 'ICC' Circuit diagram 'ICC' Yes ABIERTOCERRADO YellowYellow 1HSB435452M202 0.5g IEC 62271300 Brown porcelain 6523 6370

2/2

mm mm

VDC VAC VDC W W kW W W

3 BLK 222 Tripfree 220 220 220 200 200 0.9 70 140 12NO+12NC Yes, internal Entrelec M6/8 STA (disconnectable) Entrelec M4/6 YES without resistor 1HSB543212GKF YES without resistor 1HSB543212GKE

ABB AB 2007. All rights to this document and its information are reserved. Any form of reproduction, use, or disclosure to third parties or unauthorised persons without our prior written consent is strictly forbidden.