Professional Documents
Culture Documents
VLF cable diagnosis with the partial discharge mapping system PHG TD - PD or PD portable
Using partial discharge measurement with source localisation, direct allocation of partial discharge activity on cable segments, joints or cable terminations is enabled. The partial discharge measurement is based on a VLF truesinus voltage waveform. VLF truesinus cable testing (PHG 70 or PHG 80) PD level measurement PD source localisation Display of PD activity over the cable length Menu guided control software On site PD calibration provided according to IEC 60270
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
1/9
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
2/9
Essential characteristics of the partial discharge localisation system High resolution High noise suppression Menu guided control surface (MS Windows) PD level measurement and PD source localisation Display of PD activity over the cable length Convenient connecting technique Automatic measurement of fault positions
The partial discharge pulses are subject to the damping of the cable. Therefore the level to be measured is dependent on the distance of the partial discharge source. For partial discharge source location only the time delay between the first and the reflected pulse is important. In most cases the partial discharge source is not located in the cable insulation itself, but in the accessories. Would the partial discharge source be located within the cable insulation, this would lead to a breakdown within shortest time. Practical measurement had proven that most of the partial discharge sources are located in the joints. Partial discharge sources outside the joints are rare and in those cases mostly defects on the sheath. This leads to the fact that for on-site partial discharge diagnosis partial discharge levels in the range of some 100 pC are relevant only. Most important is the knowledge of the location of the partial discharge source.
Technical data
PD localisation Measuring range Propagation rate Sampling rate PD detection limit Accuracy of localisation Resolution 10 12800 m at 80m/s 50 120m/s 100 Mega Sample/s (10ns) typically 20pC 1% of the cable length +/- 0.1pC; +/- 0.1m
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
3/9
Experience on paper mass cables The PD measurement on paper mass cables is the same as on plastic cables regarding the measurement technique. The most important difference exists in the interpretation of the results. From its design a paper mass cable has a lot of PD within its insulation. In contradiction to a plastic cable this is not harmful to the insulation. The voids in the insulation open and close frequently due to the thermal expansion and viscosity of the insulation mass. The harmlessness of this is proven by paper mass cables showing nC of PD but being in operation since more than 80 years. This background PD level of the cable itself depends on type, manufacturer, manufacturing year and condition of the cable and ranges between some 10 pC and some nC without being risky to the cable. As already described for the plastic cables, the PD measurement at paper mass cables is done in order to locate defects in joints and terminations. In some cases defects of the sheath (corrosion of the lead sheath) were detected. In comparison to plastic cables, the paper mass cables were never routine PD tested at the manufacturer. Therefore the interpretation of the results and the operation risk are much more difficult compared to plastic cables. Only comparison between the cables of different phases and of same type and manufacturing year enable an interpretation. Additional to that the measurement itself is more difficult. Many of the (non-risky) discharges in the cable are recorded by the measurement system. Each impulse shows the equivalent position of the source. This leads to a distribution of many pulses all over the cable length. In order to locate a defect which shows up with a PD level higher than this background noise , many recordings are required. Measurement systems with automatic position recognition are to be favoured. Practical experience of the authors in Germany, Austria, Italy, Russia, Ukraina and other countries have shown, that despite of the above described difficulties a reliable identification of PD sources was possible. Even sheath defects could be identified. Additional to that, lead corrosion at railway crossings and river crossings were detected. Therefore PD location and measurement on paper mass cables is also recommended in order to increase the reliability of the grid.
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
4/9
Connection diagram:
The length of the connection between the coupling capacitor and the cable is an essential influence on the measurement. Every inductive loop that is created, is an impedance that is blocking the hF-PD impulses. Therefore one important point is to keep the ground line straight and to make the high voltage connection not longer than the standard cable of 1.2m.
The ground line has to be connected in a direct line from the closest accessible point of the screen to the grounding clamp of the coupling capacitor.
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
5/9
disconnected completely and shielded with corona hoods. Only without the connected switch gear, the influence of partial discharge of the substation can be eliminated.
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
6/9
Calibration procedure
During calibration, a defined signal is sent into the cable. The returning signal that is detected via the PD mapping system has suffered a certain damping and therefore lost energy. The relation between the defined input signal and the remaining returning value is defining a factor that is used for the definition of the PD level during the measurment. Only in this way, it is possible to determine the real PD value at the point where it is created. The calibrator has to be connected directly to the connection point at the termination!
Calibration value:
the calibration value at the calibrator has to be set, - so that the far end can be seen
Software settings:
- gain level: The setted gain level has to allow that the expected value of partial discharge can be displayed without reaching the overrange value. Partial discharges recorded with overload are cut. Only the area under the PD curve is calculated to be the PD charge. trigger level: frequently triggering at the incoming pulses ~ 50%
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
7/9
The calibration is only possible, if the parallel path of screen and core are provided all along the cable. Every PD impulse can be seen like a traveling echometer impulse. Every impedance change and every end of the parallel lines are indicated. Therefore, in case of no successful calibration, make sure that all connections are done properly. Even corrusion in the arrangement of the shielding can be a problem.
Corrosion
Furthermore, in case of crossbonded HV cables, the link-boxes need to be crossed over directly as the change of impedance otherwise is too high.
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
8/9
Critical value of partial discharge values: XLPE cables Critical value in the joints: ~ 4000pC
headoffice@baur.at www.baur.at
T +435522/4941-0 F +435522/4941-3
07/2006
9/9