You are on page 1of 125

WTX2.

4-02 Digital Microwave System

Dec. 8, 06

Table of contents
A. Foreword .................................................................................................................... 6

1 - Structure of manual...................................................................................................... 7 2 - Safety instructions........................................................................................................ 7 3 - List of abbreviations ..................................................................................................... 9 B. Description ............................................................................................................... 10

1 - General description.....................................................................................................11 2 - Feature .......................................................................................................................11 3 - System Configuration................................................................................................. 12

3.1 - RF channel frequency arrangement ...................................................12 3.2 - Unprotected Configuration..................................................................12


4 - Description of units .................................................................................................... 13

4.1 - The Modem Unit .................................................................................13 4.2 - The Transceiver Unit...........................................................................16


5 - Technical Parameters................................................................................................. 19

5.1 - System Transmitter.............................................................................19 5.2 - System Receiver.................................................................................19 5.3 - Radio branch system ..........................................................................19 5.4 - Base-band Interface ...........................................................................20 5.5 - Auxiliary interface (optional)................................................................20 5.6 - Alarm And Remote Alarm....................................................................20 5.7 - Power .................................................................................................20 5.8 - Environmental Condition.....................................................................21 5.9 - Dimension...........................................................................................21 5.10 - MTBF................................................................................................21
C. Installation................................................................................................................ 24

1 - Delivery ...................................................................................................................... 25

1.1 - Checking the configuration .................................................................25

1.2 - Labels on the boxes............................................................................25 1.3 - Storage ...............................................................................................26 1.4 - Before Installation Task List ................................................................26
2 - Indoor part installation................................................................................................ 30

2.1 - Installation ..........................................................................................30 2.2 - Unpacking...........................................................................................31 2.3 - Installation The Equipment .................................................................32 2.4 -Signal lines ..........................................................................................36
3 - Outdoor part installation ............................................................................................. 42

3.1 - Antenna installation.............................................................................42 3.2 - Antenna connection ............................................................................44 3.3 - Transmission Line Installation.............................................................45 3.4 - Equipment grounding..........................................................................47
4 - System testing ........................................................................................................... 48

4.1 - Testing ................................................................................................48 4.2 - BER (Bit Error Rate) testing................................................................51


D. Operation and configuration..................................................................................... 52

1 - Instruction .................................................................................................................. 53

1.1 - Note ....................................................................................................53 1.2 - Equipment front panel Instruction .......................................................54 1.3 - Standby page......................................................................................56
2 - Menu operation .......................................................................................................... 57

2.1 - Introduction.........................................................................................57 2.2 - State Menu .........................................................................................58 2.3 - Setup Menu ........................................................................................73
3 - Menu structure ........................................................................................................... 85 E. Maintenance............................................................................................................. 86

1 - Preventive Maintenance ............................................................................................ 87

1.1 - Routine Maintenance..........................................................................87

1.2 - Routine Checking Of Operation Conditions ........................................87 1.3 -Test on the measurement point ...........................................................87 1.4 -The supervision ...................................................................................87 1.5 - Keeping maintenance log ...................................................................88
2 - Corrective maintenance ............................................................................................. 88 3 - Analyzing Modem Unit alarm indicators ..................................................................... 88

3.1 - Using the LCD on Modem Unit to trace alarms ..................................89 3.2 - Using the LCD on MODEM Unit to trace alarms.................................91
4 - System Troubleshooting and maintenance ................................................................ 94

4.1- Tx Troubleshooting and maintenance:.................................................94 4.2 - RX troubleshooting and maintenance.................................................97 4.2 - RX troubleshooting and maintenance.................................................98 4.3 - E1 I/O interface troubleshooting and maintenance: ..........................101 4.4 - Troubleshooting and maintenance of monitor and display keyboard 102 4.4 - Troubleshooting and maintenance of monitor and display keyboard 102
5 - 2.4GHz Transceiver Unit troubleshooting and maintenance .................................... 105

5.1 - Power troubleshooting and maintenance..........................................105 5.2 - Troubleshooting and maintenance of display and inspection............106 5.3 - Tx troubleshooting and maintenance................................................109 5.4 - Troubleshooting and maintenance of no Rx gain.............................. 110 5.5 - Troubleshooting and maintenance of LO in trouble .......................... 112
6 - Troubleshooting and maintenance of Modem Unit....................................................113

6.1 - ALM analysis .................................................................................... 113 6.2 - Troubleshooting and maintenance of IF Tx alarm (TIF [ALM]).......... 115 6.3 - Troubleshooting and maintenance of 2M code input alarmIN1~4 [ ALM] .................................................................................................... 116 6.4 - Troubleshooting and maintenance of Rx IF alarm (RIF [ALM]) ...... 116 6.5 - Troubleshooting and maintenance of Rx de-modulation alarm (SYN [ALM] / FLS [ALM])................................................................................. 117

6.6 - Troubleshooting and maintenance of EOW ...................................... 119 6.7 - Troubleshooting and maintenance of display and monitoring ...........120
F. Service ................................................................................................................... 121

1 - TECHNICAL SUPPORT........................................................................................... 122 2 - WARRANTY ............................................................................................................ 123 Appendix 1 - List of application alarms.......................................................................... 124 Appendix 2 - RX/TX level and Voltage corresponding graph ........................................ 125

A.

Foreword

1 - Structure of manual
This manual provides for users a sound knowledge of how to operate and install microwave links. With it, you should quickly be able to operate the equipment. It is not intended to replace the training services that we provide for your particular needs. The manual is divided into seven sections followed by appendixes and index. Foreword Description Installation Operation and configuration Maintenance Service Appendixes

2 - Safety instructions
2.1 - General rules
The following general safety precautions must be observed by the installer and the operator. We assume no liability for the customers failure to comply with these requirements. Ground the equipment: for safety equipment, ground the equipment by joining the station ground wire to the equipment ground terminal. Do not operation the equipment in an explosive, dusty, dankish and heavy airflow atmosphere or in presence of flammable gasses or fumes. For protection against fire: make use of fuse of the same current rating and type. Dangerous voltages: users must not remove equipment covers or shields. The installation and maintenance procedures described in this manual are for use by service-trained personnel only. Do not operate equipment in the way which may make the equipment damaged: Ensure to return back to the standby page after completion of operation. Users operation is limited to [1.T/R State] and [2.M/D State]. Other items are set

by the technician or the manufacture. To ensure normal operation of the equipment, please do not do any change. Whenever it is possible that the safety protection features built into this equipment have been impaired, isolate from the power supply and do not use the equipment until safe operation will be verified by service-trained personnel. If necessary, return the equipment to the manufacturer for service or repair.

3 - List of abbreviations
MNEMONIC ENGLISH MNEMONIC ENGLISH High Density Binary 3 Code

AGC ALC FEC BER QPSK LO RX SD EOW M/D State TX State EOW Setup CAP Setup M Q D

Automatic Gain Control Automatic Level Control Forward Error Correction Bit Error Rate Quadrature Keying Local Oscillator Receiver Space Diversity Engineering Order Wire Modem Unit state Transmitter state Engineering number Setup Capacity Setup Medium power Capacity 4E1 Capacity 2E1 order wire Phase Shift

HDB3

LED IF RF TX FD T/R State Rx State

Light Emitting Diode Intermediate frequency Radio Frequency Transmitter Frequency Diversity Transceiver Unit state Receiver state

H L T S

High power Low power Capacity 3E1 Capacity 1E1

B.

Description

1 - General description
WTX2.4-02 is a family of digital point-to-point microwave radio system, designed to satisfy various digital transmission needs of public and private networks for a large range of applications.

WTX2.4-02 family covers the frequency range from 23002500MHz It covers the following capacity: 12Mb/s 22Mb/s 42Mb/s

It is today used worldwide in: Cellular networks Fixed access networks for Public Telecom, including: Infrastructure of Wireless IP networks Direct complementary point-topoint access in LMDS networks Private networks Utility networks. Security/Defense networks

2 - Feature
QPSK Modulation and coherent demodulation. The spectrum efficiency is optimized with the use of QPSK modulation with digital filtering. The modulation-demodulation (Modem Unit) with forward error correction (FEC) to improve the availability and quality of the radio link. A comprehensive supervision is also available to monitor the radio link operation and its maintenance. Transceiver unit is divided into several separated modules. such as frequency synthesize oscillator, power amplifier, high quality LNA (low noise amplifier) and TX-Rx mixer, etc.

The Modem Unit is designed with the use of a large number of large-scale integrated circuits and FPGA devices. The performance and reliability is furthermore increased by it.

WTX2.4-02 is fully compliant with the international requirements (ITU-R) and national regulations. Including 2Mb/s interface, spurious emissions, etc.

Small dimensions of the 191U for Transceiver Unit and Modem Unit allows for easy installation and maintenance in standard 19racks, and save a lot of space.

A 64kbit/s digital service telephone channel, interface as RJ11 (two-wire)

3 - System Configuration
3.1 - RF channel frequency arrangement
RF channel frequency arrangement of WTX2.4-02 is compliant with the international requirements (CCIR, REC.933), the frequency arrangement list is hereafter. Please consult factory for other frequency arrangement requested.

Frequency Range (MHz) 2300~2500

Max. Capacity (Mb/s) 42.048

Central frequency (MHz) 2394

Channel numbers 20

TX/Rx separations (MHz)

94

ft =f0-90+4n fr =f0+4+4n ft/fr :RF transmitter frequency/RF receiver frequency f0: central frequency 2394MHz n: channel

3.2 - Unprotected Configuration


WTX2.4-02 unprotected (1+0) radio terminal is made up of the following elements.

Elements Transceiver Unit Modem Unit

Quantity 1 1

E1 I/O

Modem Unit

Transceiver Unit

Figure 1 Block diagram of 1+0

4 - Description of units
4.1 - The Modem Unit 4.1.1 - The Modem Unit consists of the following sub unit (refer to Figure 2 ) Multiplex/demultiplex Bit insertion/extractor FEC code/decode QPSK modulator/demodulator Display, control and communication Power supply

4.1.2 - Service bit including One 64kbit/s signal for EOW One 64kbit/s signal provides users with low speed data channel (optional).

4.1.3 - Description of Function Modem Unit change base band signals and auxiliary data signals from exchanger or digital terminal into combined serial signals by multiplex, these combined signals forms

I,Q parallel signals and clocks after FEC coded and thus to complete QPSK modulation.

Transceiver Unit converts the microwave signals back to QPSK signals. QPSK signals are sent to Modem Unit through IF cable and then are demodulated into I, Q signals, the clock is also recovered. The IF Modem Unit recovers serial combined signals after finishing decoding these signals respectively into 12Mb/s, 22Mb/s, 42Mb/s base-band signals and auxiliary data according different signals, and changes them back again into standard base-band signals to output.

nE1input...

Multiplex

Bit Insertion

FEC code

I Q

QPSK Modulator

IF Filter IF output

364kb/s service bit

nE1 output...

Demultiplex

Bit Extractor

FEC decode

I Q

QPSK Demodulator

IF input

48V

Power supply

12V 12V 5V LCD Display and Control Transceiver unit

Figure 2

Block diagram of Modem Unit

4.2 - The Transceiver Unit


4.2.1 - The Transceiver Unit consists of the following sub unit (refer to Fig 7) Transmitter: TX amplifier TX local oscillator Up-converter(mixed) Single-band filter Power amplifier TX channel filter

Receiver RX channel filter LNA Single-band filter Down-converter(mixed) Rx IF Amplifier AGC Rx local oscillator

4.2.2 function description The TX IF from the Modem Unit is up converted in order to provide the final transmission frequency. The output power is continuously monitored through the control and fed to the modem Unit.

The microwave signal from the modem Unit is amplified at first, through a LNA and then is down-converted. The resulting IF is amplified and is finally fed to the Modem Unit.

When the TX IF signal from the Modem Unit loses, the centre frequency of RF will export from RF port.

48V

Power supply

12V 12V

IF input

TX IF amplifier Power adjust Tx state


Tx LO state

Power amplifier

RF output

Modem unit

Control and communication

Tx Local oscillator Rx Local oscillator RF input

Rx state Auto gain control RX IF amplifier

IF output

Low noise amplifier

Figure 3

Block diagram of Transceiver Unit

5 - Technical Parameters
5.1 - System Transmitter
Output power: +17+26dBm adjustable (accuracy 1dBm) IF frequency: 70MHz 7KHz IF input signal level: 0dBm 1dBm Modulation mode: QPSK Error correction coding: k=7 3/4 mode Tx local oscillator frequency stability 10 ppm Spurious emission: -30 dBm

5.2 - System Receiver


Noise figure: 3dB (from Receiver input) Normal receiver signal level: -40dBm Threshold: -86 dBm (error rate 110-6) IF frequency: 70MHz IF output level: 0 dBm1dBm AGC dynamic range:>50dB( -35-86dBm) Modulation mode: DCQPSK Error correction coding: FEC coding Rx local oscillator stability: 10 ppm

5.3 - Radio branch system


Antenna, feeder interface: N type (female) Impedance: 50 Return loss:>17dB Direction insertion loss: 3dB (fo 8.5MHz) Branch filter: 7-resonator ceramic filter

19

5.4 - Base-band Interface


Capacity: 12048kb/s, 22048kb/s, 42048kb/s Frequency tolerance: 50 ppm Line code shape: HDB3 Interface characteristics: impedance, level, code type compliance with ITU-TG.703 Jitter characteristics compliance with ITU-TG.823 G.921 Cable length allowed: 0150m Socket: DB25 or BNC

5.5 - Auxiliary interface (optional)


Data interface: RS232 Data rate: 2.4kb/s, 4.8kb/s, 9.6kb/s, 19.2kb/s EOW(Engineering Order Wire) interface: RJ11 EOW: 64kb/s PCM mode EOW: dialing for sel-call mode Subscriber line extension interface Center order terminal is connected directly to with exchanger Subscriber terminal is connected to telephone Ethernet data interface: 10 BASE, rate 1.92Mbps Operational mode: occupies an E1 interface (selectable from 1 to 4 E1)

5.6 - Alarm And Remote Alarm


Alarm led Alarm led illuminating indicates local equipment generating alarm signals. Remote alarm led Illuminating indicates remote equipment generating alarm signals.

5.7 - Power
Input voltage: -48VDC (allowed variation range -36-72 VDC )
20

Modem Unit output voltage: +5V, +12V, -12V Transceiver Unit output voltage: +12V, -12V Switching output voltage: +12V, +5V, -5V Consumption: 35W

5.8 - Environmental Condition


Working temperature: 540C : All technical index are guaranteed 045C : Normal operation is guaranteed. Storage temperature: -40+55C Relative humidity: no more than 85% Note: Storage area must be well ventilated, dry, without erosion gas

5.9 - Dimension
Modem Unit, Transceiver Unit dimension: Width high length =482.6mm (19) 44.45mm 320mm

5.10 - MTBF
MTBF 100000 hours

21

Digital Microwave Radio SystemHs


No 1 2 3 4 5 6 7 8 Item operation frequency range Tx/Rx local frequency stability output powertypical system gain RF input leveltypical AGC dynamic range transmission capacity Demodulation base-band interface bit rate interface code signal level impedance service channel voice frequency channel frequency band output level output impedance 2300 to 2500MHz 10ppm >25 dBm 111dB -40dBm More than 50dB-35~-86 dBm 42.048mbps Coherent demodulation ITU-T G.703 2.048mbps 50ppm HDB3 VO-P=2.37V 75 ohm unbalanced 1 EOW2-WIRE ITU-T G712 0.3 to 3.4KHz -6dBm~-35.5dBm 600 ohm, balanced Tx power RX level (Indication range: -35dBm~-86dBm) Tx local oscillator Rx local oscillator Intermediate Frequency 70MHz20ppm (BNC) 8MHz refer to Figure 4 70MHz 0dBm1dB -86dBm BER110-6 -48VDC (-36 to -72VDC) Approx 100w (1 station HS configuration) 5+40 -5+45 -25+55 Less than 90% at +45 Less than 90% at +50 Less than 90% at +50
22

Specs

10

11

12

measurement points

13 14 15 16 17 18 19

channel space Branch filter parameters Intermediate Frequency IF level Threshold power supply power consumption temperature range guaranteed operation workable operation transport and storage relative humidity guaranteed operation workable operation transport and storage

20

21

22 23 24 25 26

Weight system configuration TX/RX separation antenna connection Etc

Approx 26kg (1 station HS configuration) 1+0 94MHz N type connector transmitter must output RF center Frequency If TIF loss

Figure 4 Branch filter parameters


center frequency

8MHz(4MHz) Insert loss 12MHz(6MHz) 3dB Tx: Rx: 3dB 3dB

20MHz(10MHz)

40dB

23

C.

Installation

24

1 - Delivery
When you receive the equipment in its packaging: Check the condition of the packaging. If damaged, make your reservations known to the carrier as quickly as possible.

1.1 - Checking the configuration


As a rule, the packaging of equipment is The hop equipment is enclosed in the wooden boxes, in other words, two paper boxes enclosed; one end equipment is enclosed in each paper box. The materialness is as following:

No. 1 2 3 4 5 6 7 8 9 10 Modem Transceiver E1 I/O cable kit Power connector kit Fuse IF connection 50 cable (N) Telephone Set Technical handbook Test report

Item

Quantity 1 1 1 1 3 2 1 1 1 1

1.2 - Labels on the boxes

TRANSCEIVER UNIT

(1) (3)

TX 2418MHz RX 2324MHz CHANNEL 09 NO. R

(2) (4)

25

DESCRIPTION Modem Transceiver Appendix

No. M R

QTY 1 1 1

(1) (2) (3) (4)

TX Frequency of the Transceiver Unit RX Frequency of the Transceiver Unit

Channel of the Transceiver Unit


Serial number of the equipment

1.3 - Storage
If installation is to be deferred, the type of packaging will define the equipment storage conditions: Cardboard boxes should be warehoused indoors, in a dry, well aired room. Wooden or plywood boxes may be stored outdoors, provided that they are protected from rain and the suns rays.

1.4 - Before Installation Task List


There are several tasks that should be accomplished prior to installing the system. This section briefly describes the following: - Site selection - Line-of-sight and path clearance determination - Anticipated RSL calculation - Fade margin calculation - Availability calculation - Frequency plan determination - Power supply planning - Antenna purchase
26

NOTE: Only directional antennas should be used with the system. These can be grid or solid parabolic antennas (minimum 2 foot 0.6 meter). Flat panel antennas are also acceptable if the beam width is kept to a minimum.

1.4.1 Site Selection Requirements The system site must have: - Access to the appropriate power Close proximity to the telephone you wish to interconnect Line-of-sight to the other location with adequate clearance Location for mounting the antennas

1.4.2 line-of sight and path clearance guidelines The system will not operate properly unless they have line-of-sight between their corresponding antennas. The transmission will not pass through trees or other obstacles. Factors to consider include: - Earth curvature - Future growth of trees - Height of building

In addition to the line-of-sight requirement, a well-engineered path will also have additional path clearance to allow for signal loss due to patial obstructions, atmospheric ducting and ground reflections. To maximize radio reception, 0.6 times the first Fresnel zone should be calculated and this distance added to the path clearance (in addition to or buildings).

1.4.3 RSL calculation and link budget The received signal level (RSL) can be estimated using the following formula: RSL(dBm) = Pout FL1+G1+G2 FL2 - Lp
27

Where:

Pout is the transmitter output power ( in dBm) FL1 is the feeder loss of the transmit side ( in dB) G1 is the gain of the transmit antenna ( in dB) G2 is the gain of the receive antenna ( in dB) FL2 is the feeder loss of the receive side ( in dB) Lp is the path loss, defined by: Lp(dB)=96.6 + 20log10F + 20 log10D

Where:

F = frequency in GHz D = distance of path in miles

The link budget is very important for determining any potential problems during installations. If you have calculated the expected RSL, you can see if it has been achieved during installation, and troubleshoot if necessary.

1.4.4 Fade Margin Calculation The fade margin is the difference between the actual received signal and the systems threshold. Using the formula provided in section 1.4.3, the anticipated RSL can be calculated. Compare this RSL to the specified threshold of the system and calculate the fade margin as the difference between the two signal levels.

Dispersive fade margin is another factor that many microwave path engineers may use to plan their link budget. For the system, the dispersive fade margin is in excess of 45dB and therefore is not a determining factor in path planning. This excellent dispersive fade margin performance is important because the RF signal has considerably wide bandwidth.

1.4.5 Availability Calculation Availability of the microwave path is the measure of the time that the link will operate without producing an excessive BER due to multipath fading. In the absence of direct interference, availability is affected by the following: - Path length
28

- Fade margin - Frequency - Terrain (smooth, average, mountainous) - Climate (dry, temperate, hot/humid)

Depending on the type of traffic carried over the link, the system designer may wish to design for a specific availability. For example, if the data or voice traffic that is carried by the radio is critical then it may be designed for a very high availability. To improve availability, for example, the fade margin can be increased by making the path shorter, or by using higher gain antennas in conjunction with lower loss feeders(by using high quality transmission line or shortening feed length).

1.4.6 Frequency plan determination When configuring system in a hub or repeater configuration, careful engineering of the system frequency plans and antenna locations should be performed in order to minimize potential interference between the nearby systems. As a rule of thumb, do not place identical frequency plan system (e.g. two A channel systems) at the same site. In most cases, it is desirable to use a different frequency plan (e.g. A versus B). However, with careful engineering, placing more than one system of the same frequency channel plan at the same site can be accomplished. In fact, the frequency plan is designed to allow complex hub configurations that may require reusing the same frequency plan. When designing these types of configurations, antenna size and antenna location are critical. If Identical channel plans must be used at the same site, the system channel (e.g. A1 and A2) should be used at a site to minimize interference. Using alternate channels (e.g. A1 and A2) is less likely to be successful (and therefore not recommended) due to the high level of transmitter to receiver isolation required from the antenna system.

1.4.7 Power Supply Planning The system must have access to a supply of appropriate power. Typically negative ground 48 volt supply is used. For DC, be sure the cable is of sufficient gauge to carry the
29

necessary current.

Before installing the system, plan for the continuous power consumption needs in accordance with the specifications. It is also wise to plan for backup power for critical communication circuits (including the system). Backup power allows the system and associated equipment to continue operation when primary power is interrupted.

1.4.8 Antenna Planning Using the path planning tools, proper antenna size can be determined which will yield the desired path performance. In general, the larger the antenna that is used with the system, the better the link will perform. Larger antennas have narrower beamwidth and higher gain, which will yield better link performance (higher fade margin, better availability) and improve immunity to interference (due to the smaller beamwidths). However, larger antennas are more costly to purchase and difficultly install than smaller antennas, in some cases requiring special equipment for installation. All of these factors should be taken into consideration when selecting antennas.

2 - Indoor part installation


The following tools may be required for the installation: - Cross tip screwdriver - Small spanner - Big spanner - Digital Voltmeter

2.1 - Installation
Installation work begins with unpacking and should follow the steps blow. Step 1. Unpacking Step 2. Installing the equipment Step 3. Connecting the cables

30

2.2 - Unpacking
2.2.1 -Check the shipment container for damage, if not, put up unpacking, pay attention not to damage the contents or the container.

2.2.2 -Checking The Contents When unpacking, check each of the contents against the packing list to find missing or damaged components, keep shipment container for possible re-use until all the contents are checked to be in satisfactory conditions.

2.2.3 - Labels on the equipment 2.2.3.1 - Labels on the Transceiver Unit

TRANSCEIVER UNIT

(1)

(2) (4)

TX 2418MHz RX 2324MHz CHANNEL 09 NO. R009

(3) (5)

(1) Name of the equipment (2) TX Frequency of the Transceiver Unit (3) RX Frequency of the Transceiver Unit (4) Channel of the Transceiver Unit (5) Serial number of the equipment

R 009

R:

Transceiver

Serial number of the equipment

31

2.2.3.2 Labels on the Modem Unit

MODEM UNIT CAPACITY 4E1 NO. M007

(1) (2) (3)

(1) Name of the equipment (2) Hardware Capacity:22Mbit/s (3) Serial number of the equipment

M 007

M:Modem Unit
Serial number h i

2.3 - Installation The Equipment


2.3.1 environmental condition of installation

The equipment operates with natural ventilation in environmental conditions from 0 to 40 degree C. it is designed for indoor operation only. Installing the equipment in the following places should be to avoid.

subject to heavy vibration directly exposed to the sun with high humidity subject to dust

2.3.2 -Recommended installation methods WTX2.4-02 equipment must be installed on a standard 19 inches rack. First, mount the
32

rack-mount-brackets on both side of the main body cabinet, using the cabinet mounting bows, then, install the equipment on the rack. 2.3.2.1-Rack installation sketch: including M8 bolt,8 nut 8 spring washer 8 flat washer( see the following figure), upper bracketlower bracketcolumn

M8 bolt 8 nut 8 spring washer 8 flat washer

2.3.2.2 - The equipment mounting pole installation sketch Mounting pole is installed on right and left side of equipment, see the following figure:

33

M3 bolt

Mounting pole is installed at the middle (or front) of right and left side of equipment according to demand. Recommended installation methods are that it is installed at the middle of the equipment with M3 bolt.

The equipment is installed on the rack.(see the following figure)

34

35

2.4 -Signal lines


2.4.1 E1 I/O Cable kit E1 signal I/O Cable kit is connected with E1 I/O interface on the modem Unit

(connection kit refer to the following page).

Serial number 1 2 3

Name Cable SYV-75-2-2 Cable socket BNC-KY32Y-1 DB25A/M

36

E1 I/O Cable kit DB25A/M Port Pin Assignments DB25A/M Connector Pin Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Signal Name

E1out1 GND E1out2 GND E1out3 GND E1out4 GND NC NC NC NC NC E1IN1 GND E1IN2 GND E1IN3 GND E1IN4 GND NC NC NC NC

37

connecting with modem unit

38

2.4.2 Power connection kit:

-48Vpower connector

-V(A3)

GND(A2)

+V(A1)

If equipment use 48V, Connect GND and +V to Power Ground, connect V to 48V power

39

2.4.3 IF connection: Unit

the cable which connects the Modem Unit with the Transceiver

Serial number 1 2

Name Cable socket BNC-75J4C Cable SYV-75-2-1

40

2.4.9 EOW telephone handset connection

Note: telephone handset must be connected with the modem unit

41

3 - Outdoor part installation


3.1 - Antenna installation
The antenna installation consists of mounting the antenna on the tower, building roof or other location that provides line of sight path clearance to the far location. In general, antennas smaller than 4 feet diameter are not recommended for urban areas due to their higher interference susceptibility.

Antennas should be ordered with a suitable mounting kit specific to the site requirements, for example specifying round or angle tower leg adaptors, or a roof tripod.

If wind-loading may be a problem for an outside mounted antenna, a grid antenna can reduce the wind load compared to a solid dish, although the antenna discrimination capability, for example at hub locations, will be degraded. However, vertical vs. horizontal discrimination, if required, may be improved by using grid antennas.

The antenna must be very rigidly mounted, with adequate room for azimuth and elevation adjustment. The antenna polarization must be the same at both ends of the link, either vertical or horizontal.

In general, antenna mountings require a support pipe to which upper and lower support brackets are attached with U bolts. The antenna and optional elevation and azimuth adjustment rods are then mounted onto the support brackets. The whole structure must be adequately grounded, in case of lightning. The antenna system must always be installed according to the manufactures instructions.

42

Mounting Poledimension:

76mm or 114mm

76mm or 114mm

Figure 1 Mounting Pole dimension

43

Fitting the top U bolt on the 114 mm tube

1) Offer the threaded U bolt (M10) item on the 114 mm tube. 2) Fit casting on the bracket. 3) Fit the washers, item and nuts (HM10) item on the threaded bracket. 4) Tighten the nuts using a 17 mm flat wrench and the plate will be distorted.

3.2 - Antenna connection


The equipment is equipped with an N-type female connector at the antenna port, ANTENNA at the rear of the shelf. A jumper cable (or pigtail) fitted with two N-type male connectors should be used to connect the antenna port with the antenna transmission line.

A low loss 50 ohms cable (for example 1/2, 7/8foam or air coax ) is recommended for the antenna transmission line between the top of the rack and the antenna. The return loss presented by the transmission line at the top of the rack should be as possible (20 dB, minimum recommended). The length of the antenna transmission line should be kept as short as possible (to minimize losses).

44

Antenna Installation sketch

Grid Antenna U bolts Casting Plumb pull pole

Feed

Jumper cable

antislip baffle Feeder cable

3.3 - Transmission Line Installation


The co-axial transmission line (cable) may be prepared by first being cut to the approximate length allowing some excess and an N-type male connector installed on the antenna end (expect for large or high performance antennas with 7/8EIA flange

45

connectors).

The cable is then pulled through the cable ducts, trays or conduit (as required) to the antenna, while being careful not to kink or damage the cable in any way.

The cable should be supported in a tray on horizontal runs and by hangers on vertical runs. Hangers should be spaced according to the manufacturers instructions.

The cable should be grounded using a special grounding kit that attaches to the outer copper conductor. Grounds must be installed at the antenna, at the bottom of the tower (if applicable) and where the transmission line enters the building. Long cable runs should be grounded every 100 feet. In case of high lighting incidence, lightning dissipaters should be attached to antennas. In addition, co-axial, in-line, spark-gap type, lightning suppressors should be added at the bottom of the co-ax cable.

After installation, the cable is terminated with a second N-type male connector attached at the equipment end.

Prior to operation, the electrical integrity of the cable and connectors can be checked with a simple DC detector between the center conductor and outer conductor.

The transmission line should ideally be connected directly to the antenna at one end and to the RF port of the equipment at the other end. However, a jumper cables may be required to avoid sharp bends in the transmission line or undue stress on the connection.

46

3.4 - Equipment grounding

Grounding kit

Necessary only if D>80m

D 10 cm In door

Feeder grounding; cut the outer layer of the feeder cable about 10cm length, expose the metal part. Connect one end of the grounding kit to the metal part and seal with tape, connect the other end to protected ground.

47

4 - System testing

4.1 - Testing

Transceiver

Transceiver

Modem Unit Station A

Modem Unit Station B

4.1.1 install station A with the antenna facing to station B. 4.1.2 install station B with its antenna facing to station A. Check the system is well grounded and the polar are correctly connected before powering the system. The standby page is displayed as Fig 1

SYS Initialize Loading...


Fig 1 Fig 2 will be displayed on the screen seconds later.

TX: + RX: -

dBm dBm

[NOR] [NOR]

Fig 2 Because the antenna is not fine adjusted, the screen may display case, the antenna should be readjusted according to level graph. RX: - LOW in this

48

The procedure of adjustment is as following 1. Connect the red probes of multimeter (set in DC range) to pin 4 of the DB9 head attached to the equipment. pin 9 is ground.

(voltage)

A
Pin 9

Pin 1 1 6 Pin 6

(voltage)

49

The best RX level of the equipment is 40dBm. Recommend to set normal RX level between 55 ~ -40dBm. The respective RX level can be easily checked out according to voltage graph. 2. Fix station B antenna, adjust station A antenna, slowly adjust elevation. Observe AGC voltage while adjusting to make it be optimum. Then adjust azimuth make it reach maximum. Adjust station B antenna the same way, after antennas are well adjusted. Look at the LCD screen of the modem Unit and check that if TX power and RX level indication are normal, if there is any warning on the Modem Unit panel. When everything is normal, perform bit error test.(refer to Bit Error Test). After adjusting the antenna, if AGC level is very low, on the LCD screen, RX Low will be displayed. It may because too much loss of space or blocking space. Increasing the antenna diameter and TX power may resolve the problem. If there is blocking object, increase the height of the antenna or change the station location to avoid to be blocked.

50

4.2 - BER (Bit Error Rate) testing


Bit error rate (BER) testing is the preferred way to evaluate a radio links performance. It can be performed from point -to-point or in loopback mode (which tests both directions of the radio path). Figure 1 illustrates a typical BER test configuration for loopback testing (which may include the radios path instead of in-line attenuators).

When performing BER testing, make sure of the following step: a) b) Remark: Connect BER tester to data input/output connector(s). Connect data input/output of the remote equipment with the cable. The BER tester pattern must be set up as 215-1, and test code must be set

up as HDB3.

Antenna

Antenna

WTX2.4-02

RF

RF
WTX2.4-02

BER tester

Figure 1

Loopback BER Test Configuration

51

D.

Operation and configuration

52

1 - Instruction
1.1 - Note
All operations are based on systems work normally without warning. If there is a warning or abnormality on screen, please refer to the maintenance section. All legends with under line are defaulted cursor position.

53

1.2 - Equipment front panel Instruction


1.2.1 - Modem Unit front panel

Power LED: Indicates status of -48VDC on the circuit board. Power LED illuminating indicates -48VDC is present on the board. Power switch: ON means power on the circuit board. OFF means no power. LCD screen EOW: Engineering order wire interface. Alarm LED: Alarm LED illuminating indicates LOCAL equipment (including Modem Unit and RF Transceiver Unit) generating alarm signals. RMT Alarm LED: Lighting indicates remote equipment (including Modem Unit and RF Transceiver Unit) generating alarm signals. 70MHz: IF carrier wave (70 MHz3KHz, 0dBm1dB).

54

1.2.2 Transceiver Unit front panel

Power LED: Indicates status of -48VDC on the circuit board. Power LED illuminating indicates -48VDC is present on the board. Power switch: ON means Power on the circuit board. OFF means no power. TLO: TX local oscillator frequency measurement point (-6dBm2dB). RLO: RX local oscillator frequency measurement point (-6dBm2dB). DETECT: Detect interface (refer to Appendix 2).

55

1.3 - Standby page


After installation by technician, check the system is well grounded, power supply is correctly connected, then power the system, standby page (Fig 1) will be displayed on the LCD screen of Modem Unit.

SYS Initialize Loading...


Fig 1 The system is initializing, all system parameters are being loaded, please wait. The standby page will be displayed seconds later. The following describes different standby pages according to respective equipment.

1.3.1 - Modem Unit standby page

Tx: + 25 dBm Rx: - 65 dBm


Fig 2

[NOR] [NOR]

On this page, present TX value and alarm, RX value and alarm are displayed on the same link equipment.

1.3.1.1 - Tx and Rx Tx: Output power of Transceiver Unit. the normal display range is 1726 dBm. If TX value is less than 15 dBm, TX: loss is displayed in the first line. Rx: Receiver signal level of Transceiver Unit. the normal display range is -35 -86 dBm. If RX value is less than -88 dBm, RX: low is displayed in the second line.

56

1.3.1.2 - The brackets on the screen show the current Tx power and Rx carrier wave alarm signals. NOR indicates Tx power and Rx carrier wave are normal; ALM is alarm indication.

1.3.1.3 This screen(refer to Fig 3) indicates the current TX power alarm signal and RX level alarm signal are OFF.

Tx: + 26 dBm Rx: - 65 dBm


Fig 3 1.3.1.4 When alarm signal appears, refer to maintenance section.

2 - Menu operation
2.1 - Introduction
On this menu, the local and the remote Modem Unit, Transceiver Unit status check, the local Modem Unit parameter, service number setting, the local Transceiver Unit TX power setting. All above operation are limited to the technician. On the standby page, get the master menu by selecting the Up/Down keys (Fig 4)

A. State B.Setup
Fig 4 The master menu includes the following 3 sub-menus; get the sub-menus by selecting Up/Down keys:

"A. State "B. Setup


2.1.1 - State Menu

" "

57

The State Menu is used to check the status of the Modem Unit and the Transceiver Unit, including local and remote equipment. The detailed operation is in section 2.2. 2.1.2 - Setup Menu Setup Menu is used to setup capacity of the local Modem Unit, output power of the local Transceiver Unit, the local EOW. The detailed operation is in section 2.4 CautionThe Setup Menu is only limited to the local equipment operation

2.2 - State Menu


Put the cursor on "A. State " by moving the Up/Down keys. Select the Enter

key to call up the menu. Fig 5 is displayed on the screen.

>Local >Remote
Fig 5

[ [

] ]

The cursor is defaulted on the first line. The user put the cursor keys, then press the Enter key to select a specific equipment.

by moving the Right

for example If the user wants to select the local equipment ( or link), he can put the cursor on the Right keys, then press the Enter key to select the local

first line by moving the equipment ( or link).

>Local

If the user wants to select the remote equipment ( or link), he can put the cursor on Right keys, then press the Enter key to select the

the second line by moving the remote equipment ( or link).

>Remote [

The state menu of the local equipment is as same as that of the remote equipment, so, we take the following operation done on the local equipment (or link) as an example. Put the cursor on the first line by moving the Right keys. Then select the Enter key to select equipment, Fig 6 is displayed on the screen.
58

1. T/R State 2. M/D State


Fig 6

Fig 6 indicates Unit has already communicated with the local equipment ( or link), the local equipment (or link) status including Modem Unit and Transceiver Unit can be checked.

2.2.1 T/R State Menu The T/R State Menu is used to check TX power, RX level, Tx power alarm and RX level alarm of the Transceiver Unit, below is the different status of the local equipment (or link).

Put the cursor on 1 of the first line by moving Right keys. Then select the Enter key to call up the T/R State Menu, Fig 7 is displayed on the screen.

1.1 Tx Level 1.2 Rx Level


Fig 7

59

The T/R State menu includes 4 sub-menus: TX power, RX level, Tx power alarm and RX level alarm of the Transceiver Unit. Moving the Up/Down keys to get the following 4 menus

"1.1 Tx Level "1.2 Rx Level "1.3 Tx State "1.4 Rx State

" " " "

2.2.1.1 Tx Level The menu is used to show the current TX power of the Transceiver Unit. Put the cursor on the "1.1 Tx Level up "1.1 Tx Level " by moving the Up/Down keys, then select the Enter key to call " menu, Fig 8 is displayed on the screen.

Tx Level
Fig

26
Fig 8

dBm

The screen shows that the current TX power of the Transceiver Unit is 26dBm.

2.2.1.2 Rx Level The menu shows the current RX level of the Transceiver Unit. Put the cursor on the "1.2 Rx Level " by moving the Up/Down keys, then select the Enter key to call up "1.2

Rx Level menu. Fig 9 is displayed on the screen.

Rx Level 65
Fig 9 The screen shows that the current RX level of the Transceiver Unit is 65dBm.

dBm

60

2.2.1.3 Tx State The menu shows the current TX power alarm signal of the Transceiver Unit. Put the cursor on the "1.3 Tx State key to call up "1.3 Tx State " by moving the Up/Down keys, then select the Enter " menu. Fig 10 is displayed on the screen.

1.3.1 1.3.2

TLO TPW
Fig 10

[NOR] [NOR]

The detailed signals see the following table.

Name
TLO TPW

Meaning
Tx local oscillator alarm Tx power alarm, if Tx power is less than 4dB of setup value, alarm appears.

State
NOR: normal ALM: alarm NOR: normal ALM: alarm

The alarm signal may be switched off during test to avoid wrong decision and wrong operation. The alarm signals above both have on and off states. Put the cursor onto the alarm signals required and press the Enter key to call up the page of Fig 12 (for example).

For a instance of TLOput the cursor on the first line, then press the Enter key to call up the page of Fig 11.

1.3.1 Opt. [

TLO On

[ On ] Off ]

Fig 11

61

The cursor is defaulted on On of the second line. It may be selected on or off by the Right key, and the cursor in the second line will move accordingly. The brackets in the first line of the screen shows the switch state of the current selected signal, here, the TLO is turned on, means the switch is enable, When signal alarm switch is enable, if signal alarms, the alarm LED will immediately light on. Please revert back to previous menu, Fig 12 is displayed on the screen.

1.3.1 1.3.2

TLO TPW
Fig 12

[ALM] [NOR]

Now, put the cursor on Off by the Right key, then press the Enter key to close alarm signal. Fig 13 is displayed on the screen.

1.3.1 Opt. [

TLO On

[ Off ] Off ]

Fig 13

Now, signal TLO is OFF, means signal TLO alarm is inhibited,. If there is TLO signal alarm, the alarm LED will not light on. Please revert back to previous menu, Fig 14 is displayed on the screen.

1.3.1 1.3.2

TLO TPW
Fig 14

[Off] [NOR]

62

2.2.1.4 Rx State The menu is used to show the current RX level alarm signal of the Transceiver Unit. Put the cursor on the "1.4 Rx State Enter key to call up "1.4 Rx State " by moving the Up/Down keys, then select the " menu. Fig 15 is displayed on the screen.

1.4.1 1.4.2

RLO RSL

[NOR] [NOR]

Fig 15 The details see the following table.

Name
RLO

Meaning
Rx local oscillator alarm Rx level alarm, if Rx level is less than -82dBm, alarm appears.

State
NOR: normal ALM: alarm

RSL

NOR: normal ALM: alarm

All signals above have on and off state. Put the cursor onto the alarm signals required and press the Enter key to call up the page of Fig 16(for example). Take RLO as an exampleput the cursor on the first line, then press the Enter key to call up the page of Fig 17.

1.4.1 Opt. [

RLO On

[ On ] Off ]

Fig 16 The cursor is defaulted on On of the second line Opt. [ On Off ], It may be

selected on on or off by the Right key, and the cursor in the second line will move accordingly. The brackets in the first line of the screen shows the current switch state of selected signal, the picture shows the RLO is turned on, means the RLO switch is enable. When signal alarm switch is enable, if signal alarms, the alarm LED will immediately light on. Please revert back to previous menu, Fig 17 is displayed on the
63

screen.

1.4.1 1.4.2

RLO

[ALM]

RSL [NOR]
Fig 17

Now, put the cursor on Off by the Right key, then press the Enter key to close alarm signal. Fig 18 is displayed on the screen.

1.4.1 Opt. [

RLO On

[ Off ] Off ]

Fig 18

Now, signal RLO is OFF, means the RLO alarm signal is inhibited,. If there is a RIF signal alarm, the alarm LED will not light on. Please revert back to previous menus; Fig 19 is displayed on the screen.

1.4.1 1.4.2

RLO

[Off]

RSL [NOR]
Fig 19

64

2.2.2 M/D State Menu The M/D State Menu is used to check alarm signal of the Modem Unit (or link). This example shows status of the Modem Unit (or link). Put the cursor on the first line by selecting the Up/Down keys, then select the Enter key to call up M/D State Menu. Fig 21 is displayed on the screen.

2.1 MOD State 2.2 DEM State


Fig 21

M/D State menu includes two sub-menus: modulate state and demodulate state. See
the following figure.

"2.1 MOD State "2.2 DEM State

" "

2.2.2.1 MOD State The menu is used to show the current modulation alarm of the Modem Unit. Put the cursor on the "2.1 MOD State the Enter key to call up "2.1 MOD State " by moving the Up/Down keys, then select

" Fig 22 is displayed on the screen.

2.1.1 2.1.2

TIF

[NOR]

TSL [NOR]
Fig 22

The details see the following table.

65

Name
TIF

Meaning
Tx IF alarm

State
NOR: normal ALM: alarm as described in section 3.2 NOR: normal ALM: alarm as described in section 3.2 NOR: normal ALM: alarm as described in section 3.2 NOR: normal ALM: alarm as described in section 3.2 NOR: normal ALM: alarm as described in section 3.2 NOR: normal ALM: alarm as described in section 3.2

TSL

Transmitting signal loss

IN1

The first E1 loss alarm. When capacity is 1E1, the alarm appears The second E1 loss alarm. When capacity is 2E1, the alarm appears The third E1 loss alarm. When capacity is 3E1, the alarm appears The fourth E1 loss alarm. When capacity is 4E1, the alarm appears

IN2

IN3

IN4

All signals above have on and off states. Put the cursor onto the alarm signals required and press the Enter key to call up the page of Fig 22 (for example). Take TIF as an exampleput the cursor on the first line, then press the Enter key to

call up the page of Fig 23( for example).

2.1.1 Opt. [

TIF On

[ On ] Off ]

Fig 23

The cursor is defaulted on On of the second line Opt. [ On

Off

],

It may be

selected on or off by the Right key, and the cursor in the second line will move accordingly. The brackets in the first line of the screen are showing the current switch state of the selected signal. On the picture the TIF is turned on, meaning the switch is available. When signal alarm switch is enable, if signal alarms, the alarm LED will immediately light on. Please revert back to previous menu, Fig 24 is displayed on the
66

screen.

2.1.1 2.1.2

TIF

[ALM]

TSL [NOR]
Fig 24

Now, put the cursor on Off by the Right key, then press the Enter key to close alarm signal. Fig 25 is displayed on the screen.

2.1.1 Opt. [

TIF On

[ Off ] Off ]

Fig 25

Now, signal TIF is OFF, means TIF signal alarm is inhibited. If there is a TIF signal alarm, the LED will not light on. Please revert back to previous menu; Fig 26 is displayed on the screen.

2.1.1 2.1.2

TIF

[Off]

TSL [NOR]

Fig 26

67

2.2.2.2 DEM State The menu is used to show the current demodulation alarm signal of the Modem Unit. Put the cursor on the "2.2 DEM State Enter key to call up "2.2 DEM State " by moving the Up/Down keys, then select the " menu. Fig 27 is displayed on the screen.

2.2.1 2.2.2

RIF ERR
Fig 27

[NOR] [NOR]

The details see the following tablet of Modem Unit.

Code
2.2.1

Name
RIF

Meaning
Rx IF alarm

State
NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section

2.2.2

ERR

Bit error alarm

2.2.3

FLS

Frame synchronization loss alarm Remote terminal alarm

2.2.4

RMT

The details see the following tablet of Modem Unit.

68

Code
2.2.1

Name
RIF

Meaning
Rx IF alarm

State
NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section NORnormal ALM: alarm See maintenance section

2.2.2

ERR

Bit error alarm

2.2.3

FLS

Frame synchronization loss alarm Remote terminal alarm

2.2.4

RMT

All signals above have on and off state. Put the cursor onto the alarm signals required and press the Enter key to call up the page of Fig 28( for example).Take RIF as an exampleput the cursor on the first line, then press the Enter key. Fig 28 is displayed on the screen.

2.2.1 Opt. [

RIF On

[ On ] Off ]

Fig 28

The cursor is defaulted on On of the second line Opt. [ On

Off

],

It may be

selected on or off by the Right key, and the cursor in the second line will move accordingly. The brackets in the first line of the screen shows the current switch state of the selected signal, on this picture, the RIF is turning on, means the switch is available. When signal alarm switch is available, if signal alarms, the alarm LED will immediately light on. Please revert back to previous menu, Fig 29 is displayed on the screen.

2.2.1 2.2.2

RIF ERR
Fig 29
69

[ALM] [NOR]

Now, put the cursor on Off by the Right key, then press the Enter key to close alarm signal. Fig 30 is displayed on the screen.

2.2.1 Opt. [

RIF On

[ Off ] Off ]

Fig 30

Signal RIF is OFF, at present means signal RIF alarm is inhibited, If there is a alarm, the alarm LED will not light on. Please revert back to previous menu; Fig 31 is displayed on the screen.

2.2.1 2.2.2

RIF ERR
Fig 31

[Off] [NOR]

70

2.2.3 Remote state operation If the user wants to select the remote equipment (or link), he can put the cursor on the second line by moving the Right keys and press the Enter key to call up the menu. Please refer to 2.2.3.1 for the detailed operation see the following figure 32. >Remote [

] ] ]

>Local >Remote

[ [

Fig 32

2.2.3.1 Requests remote equipment (or link) state. Put the cursor on the second line by moving the Right keys, then press the Enter key. Fig 33 is displayed on the screen.

Remote

state

Waiting
Fig 33

Fig 33 indicates Unit is communicating with the remote equipment (or link), Please wait for few seconds, one of the following two figures will be displayed on the screen.

1. T/R State 2. M/D State


Fig 34

Fig 34 indicates Unit has already communicated with the remote equipment (or link), the remote equipment state (including Modem Unit and Transceiver Unit) can be checked.

Refer to section 2.2.1and 2.2.2 for the rest operation.

71

Users may select operation after careful consideration. If users want to keep on operation, then select the Enter key (the cursor is defaulted onYes) to response to the local request. Fig 35 is displayed on the screen.

Remote

state

Waiting
Fig 35

Please wait for a few seconds, one of the following three figures will be displayed on the screen.

1. T/R State 2. M/D State


Fig 36

Fig 36 indicates Unit has already communicated with the remote equipment (or link), the remote equipment state (including Modem Unit and Transceiver Unit) can be checked.

Refer to section 2.2.1and 2.2.2 for the rest operation. Note: If user wants to exit, reverts back to the previous menu by selecting theLeft keys.

72

2.3 - Setup Menu


Setup Menu is used to setup local EOW, TX power of local Transceiver Unit, capacity of local Modem Unit. Put the cursor on "B. Setup then press the Enter key to call up "B. Setup screen. " by moving the Up/Down keys, ". Fig 37 is displayed on the

1. EOW Number 2. PWR Setup


Fig 37 Setup Menu includes 3 sub-menu: local EOW, TX power of local Transceiver Unit, capacity of local Modem Unit. Moving the Up/Down keys to get the following 3 menus.

"1. EOW Number "2. PWR Setup "3. CAP Setup


2.3.1 EOW Number

" " "

EOW Number menu is mainly used to setup local EOW number. Put the cursor on "1. EOW Number "by moving the Up/Down keys, then presses the Enter key to call up ". Fig 38 is displayed on the screen.

"1. EOW Number

EOW: 00

00

Fig 38

The cursor is defaulted on the first 0 of the second line. The first line on the screen shows the local EOW number, the second line shows adjustable range (from 00 to 15) of EOW number. Only when the Local EOW number should be consistent with the remote EOW number, EOW function comes true.
73

On the EOW Setup page, the first line refers to the EOW number of the local equipment. The second line refers to the EOW numbers that user can select by the Right key. The EOW number is increased by one by selecting the Up key, and decreased by one by selecting the Down key. Then press the Enter key to confirm. With the EOW number increasing or decreasing, the EOW number in the first line changes accordingly.

For example, the current EOW number of local equipment is 00, users want that EOW number is 06. put cursor on the second character 0 of the second line by moving the Right key, users continuously press Up until the second 0 of the second line is 6and press the Enter key. Fig 39 is displayed on the screen.

EOW: 06

06

Fig 39 By then the local EOW is successfully changed. If the current EOW number of remote equipment also is 06, EOW function is achieved between local equipment and remote equipment, otherwise EOW function is invalidated. Caution: please do not change the EOW number randomly. And dialing number in fact is #+ EOW number.

74

2.3.2 PWR Setup PWR Setup menu is mainly used to setup local TX power. Put the cursor on "2. PWR Setup "by moving the Up/Down keys, then presses the Enter key to call up. Fig

40 is displayed on the screen.

>Local

Fig 40 Fig 86 asks the user to select specific equipment. PWR Setup is merely limited to the local equipment. If users hope to change power setting of the local equipment, by moving the Right key; press the Enter key to confirm. Fig 41 is displayed on the screen.

Password: 0123456789
Fig 41

Fig 41 shows user inputs PWR Setup password (defaulted password is 0000000). Transceiver Unit Power change may result in link instability. Only technician are authorized to do the change. If users definitely want to change the power, put cursor on 0 by moving the Right keys, press the Enter key to confirm. Fig 42 is displayed on the screen.

Password: * 0123456789
Fig 42

Fig 42 indicates users has already input a digit of the password which is indicated by a* repeat above operation until ******** appear on the first line. One of the following two figures is displayed on the screen.

75

Error Try Again


Fig 43

Tx

Level

[ 25 dBm ]

Opt.

+,

Fig 44 Fig 43 indicates the input password is wrong, Please contact with the technician and gets technical support.

Fig 44 indicates the input password is correct and getting into PWR Setup menu. On this page, the first line is current TX power of the local equipment; the second line is the optional operation to the TX power of local Transceiver Unit as described in the following table.

Operation

Meaning The local Transceiver Unit TX power increased The local Transceiver Unit TX power decreased

Note:

1 Sometimes, it might push + several times to increase local

Transceiver Unit TX power by 1 dBm. This is the normal reaction of the system. 2 The adjustable range of the local Transceiver Unit TX power is 17 ~ 26 dBm. For example, if the users want to make TX power of the local equipment to be maximal, should be according to the following operation step

76

On the PWR Setup page, select one of [+ , - ] by the right key, and then press the Enter key to increase or decrease the preset Tx power. The current Tx value is displayed in the first line.

For example, if users want to reach maximum TX power of the local Transceiver Unit. Please apply to following steps. Step 1 Put the cursor on the "B. Setup press the Enter key to call up "B. Setup "by moving the Up/Down keys, then ". Fig 45 is displayed on the screen.

1. EOW Number 2. PWR Setup


Fig 45

Step 2 Put the cursor on the "2. PWR Setup then press the Enter key to call up 2. PWR Setup screen.

"by moving the Up/Down keys, ". Fig 46 is displayed on the

>Local

Fig 46 Step 3 Put the cursor on "1" by moving the Right keys, then press the Enter key . Fig 47 is displayed on the screen.

Password: 0123456789
Fig 47 Step 4 Put the cursor on "0" by moving the Right keys, then press the Enter key. Fig48 is displayed on the screen.
77

Password: * 0123456789
Fig 48 Step 5 Repeat step 4 to finish input of the password.

Step 6 After finishing password input, one of the following two figure will be displayed on the screen.

Error Try Again


Fig 49

Tx

Level

[ 25 dBm ]

Opt.

+,

Fig 50 Fig 49 shows that the user input password is incorrect, please contact with the technician and get support.

Fig 50 shows that the user input password is correct and successfully get into Power Setup menu.

Step 7 Put the cursor on "+" by moving the Right keys, press the Enter key until Fig 51 is displayed on the screen.

Tx

Level

[ 26 dBm ] DOWN

MAX Value: Fig 51

This page shows that the current local equipments TX Power reaches the maximum value. It will automatically revert back to the Power Setup menu as Fig 52.
78

Tx

Level

[ 26 dBm ]

Opt.

+,

Fig 52 Step 8 The operation is completed.

CAUTION:

The defaulted password is 0000000 only changing of the local Transceiver Unit TX Power is allowed

on thePWR Setup. changing of the Transceiver Unit Power may result in link instability. Only the technicians are authorized to do it.

79

2.3.3 CAP Setup CAP Setup menu is used to setup the local Modem Unit capacity. Put the cursor onto "3. CAP Setup

" by the Up/Down keys and press the Enter key to get into the

menu. Fig 53 is displayed on the screen.

>Local

[]

Fig 53

This page asks the user to select specific equipment. Only may the local Modem Unit capacity be changed on the CAP Setup .If users want to change the local equipment capacity, put the cursor on the1by the Right/Left keys. Fig 54 is displayed on the screen.

Password: 0123456789
Fig 54

This page asks the user to input CAP Setup password (the defaulted password is 8320830). Changing of Modem Unit capacity may result in temporary link interruption, only the technicians are authorized to do it. If the user definitely wants to change the capacity setting, he put the cursor on 8 by the Right keys and then press the Enter key. Fig 55 will be displayed on the screen.

Password: * 0123456789
Fig 55 Fig 55 indicates users has already input a digit of the password which is indicated by a* repeat above operation until ******** (standing for 8320830) appear on the first line. One of the following two figures will be displayed on the screen.
80

Error Try Again


Fig 56

CAP [

2 * E1

Opt. [

1 2

Fig 57 Fig 56 indicates the input password is wrong, Please contact with the technician and get technical support.

Fig 57 indicates the input password is correct and getting into CAP Setup menu. In the example, the first line indicates the current capacity of the local Modem Unit is 2E1, the second line is the optional operation to the capacity of local Modem Unit as described in the following table

Optional capacity
1 2 3 4

Meaning The local Modem Unit capacity is 1E1 The local Modem Unit capacity is 2E1 The local Modem Unit capacity is 3E1 The local Modem Unit capacity is 4E1

81

As a function of the local Modem Unit capacity change, parameters on the standby page will change as detailed in the following table.

Capacity parameters Q D S

Capacity meaning
4E1 2E1 1E1

On the CAP Setup page, select any of the [1 2 3 4] by the Right key to change the preset capacity value. The capacity value on the standby page will change accordingly. For example, if the user wants the local Modem Unit is 1E1, proceed as follows Step 1 Put the cursor on "B. Setup " by the Up/Down keys and then press the

Enter key. Fig 58is displayed on the screen.

1. EOW Number 2. PWR Setup


Fig 58 Step 2 Put the cursor on "3. CAP Setup " by the Up/Down keys and then press

the Enter key. Fig 59 is displayed on the screen.

>Local

Fig 59

Step 3 Put the cursor on "1" by the Right keys and then press the Enterkey. Fig 60 is displayed on the screen.

Password :
82

0123456789

Fig 60 Step 4 Put the cursor on "8" by the Right keys and then press the Enterkey. Fig 61 is displayed on the screen.

Password : * 0123456789
Fig 61 Step 5 Repeat step 4 to finish the input of password: 8320830. Step 6 after inputting the password, one of the following two figure is displayed.

Error Try Again


Fig 62 CAP [ 2 * E1 ]

Opt. [

1 2
Fig 63

Fig 62 shows that the user input password is incorrect, please contact with the technician and get support.

Fig 63 shows that the user input password is correct and successfully get into CAP Setup menu.

83

Step 7 Put the cursor on "1" by the Right /Left keys and then press the Enterkey. Fig 64 is displayed on the screen.

CAP [ Opt. [

1 * E1 1 2 3

] 4 ]

Fig 64

This page shows CAP Setup of the local Modem Unit has been completed. Step 8 Reverting back to the standby page. The local Unit standby page changes to as Fig 65.

WTX-2.4-02S V4.3
Fig 65 Step 9 The operation is completed. CAUTION The defaulted password is 8320830 only changing of the local Modem Unit capacity is allowed on theCAP

Setup.
changing of the capacity of Modem Unit may result in link instability. Only the technicians are authorized to do it.

84

3 - Menu structure
1.1Tx Level 1.2 Rx Level 1.T/R State

>local [ ] 2.M/D State 2.1 MOD State 2.2 DEM State A . St a t e 1.1Tx Level 1.T/R State 1.2 Rx Level

>Remote [ ]

2.M/D State

2.1 MOD State 2.2 DEM State

WTX2.4- 02D V4.3

1.EOW Number B. Setup 2.PWR Setup 3.CAP Setup local [ ] local [ ]

85

E.

Maintenance

86

On detecting a failure, the operator must go to one of the stations on the failed hop, analyze the fault and determine which element has failed.

1 - Preventive Maintenance
It involves inspecting the units and their interconnections (connectors, cables, sockets, etc), as well as all the equipment involved in the operation of the station (power generation equipment, compressor if appropriate, solar panels if appropriate, earthing, etc) and, in case of doubt, checking the suspect parts, taking all the necessary precautions to avoid disrupting data transmission through the link.

1.1 - Routine Maintenance


Since the performance of component parts such as, ICs transistors, resistors tend to change under influence of heat and time, it is recommended that routine maintenance is carried out at a regular interval to find out any changes of condition, which may cause unexpected system break Down some time later.

1.2 - Routine Checking Of Operation Conditions


1.2.1 -Equipment should be kept from dust. 1.2.2 -Check the condition of the cablesconnectors and connections.

1.3 -Test on the measurement point


The Transceiver Unit output power, Received signal level; Tx/Rx local oscillator frequency is measurable at the measurement points of the Transceiver Unit.

1.4 -The supervision


Performance status of both local and remote equipment can be displayed on the LCD screen which built in MODEM unit. The operator analyzes the alarm and initiates appropriate corrective maintenance operations
87

1.5 - Keeping maintenance log


Maintenance log should be kept for each station. All maintenance operation check results, date of the occurrences of failures, remedial action taken, and other necessary things should be logged for reference.

2 - Corrective maintenance
- Check the condition of the cables, connectors and connections, and of all the components that are involved in the operation at the station (power supply, battery, earthing, etc), - Analyze the IDU alarm indicators, - If alarms are indicated, locate them using LCD of the MODEM Unit and analyze them and carry out the necessary corrective procedures (change of unit, module, cable, etc).

3 - Analyzing Modem Unit alarm indicators


The alarm indicators on the Modem Units provide an indication of network elements affected: The ALM LED lighting: the local equipment alarm The RMT LED lighting: the remote equipment alarm

88

3.1 - Using the LCD on Modem Unit to trace alarms


If the following figures appear on the LCD of the Modem Unit

Tx: Rx:
Fig 1

[ALM] [NOR]

Tx: Rx:
Fig 2

[NOR] [ALM]

TRL: TX power alarm TX power low or fading Check whether the IF connection is normal or not If IF connection is normal, disconnect the IF connector, connect Transceiver Unit to the other Modem Unit, check whether TPW is normal or not. If not, change Transceiver Unit.

RX: RX level alarm RX level low Check the antenna, if the antenna is not accurately pointed, repoint and check that the alarm disappears. Abnormal conditions are hampering propagation: presence of a sheet of water or waterlogged ground along the path of the link, reflections from one or more layers of the troposphere caused by abnormal stratification of the atmosphere, a fairly frequent condition in tropical climates, natural screen or construction strongly masking the first Fresnel ellipsoid, rain storms, etc. Check RF cable Check RF connection
89

If not, change Transceiver Unit.

If the following message appears on the LCD of Modem Unit.

Caution! T/R COMM Fault


Fig 3 RUM connection problem: disconnected, incorrectly fastened, cut, short-circuited or bad contact inside a connector. Repair the connection, check its connectors, and change the defective items or the connection. Do not power Transceiver Unit: check whether the power supply LCD of Transceiver Unit is normal or not. Change Modem Unit After use the new Modem Unit, the alarm persists, change Transceiver Unit.

If Fig 4 appears on the LCD.

TX: + RX: Fig 4


connection problem. Change Modem Unit

dBm dBm

90

3.2 - Using the LCD on MODEM Unit to trace alarms


Modem Unit1 Block diagram I 2Mb/s 2

Modulator
Q 1

70MHz To Transmitter 1

Signal rate Adjust and FEC


2Mb/s 10 9 8 7 6

I Q DEM ALC 5

70MHz From Receiver 1

On installation, any channel interference will cause some alarms to be generated, so, make sure the channel hasnt been interfered.

Alarm message TIF

Most probable case and corrective methods TX IF alarm: Modulation IF loss Check the power supply of Modem Unit, otherwise, change the Modem Unit Transmitter signal loss: the output of coding signal loss Check the power supply of Modem Unit, otherwise, change Modem Unit The first E1 loss alarm: the first 2Mb/s data input loss Check the 2Mb/s data input against the installation sheet;
91

TSL

IN1

Check the 2Mb/s data input short circuit or open of the line; Check cable loss; Check the E1 I/O connection; Otherwise, change Modem Unit. 4 IN2 The second E1 loss alarm: the first 2Mbits input loss Check methods is as same as IN1 Receiver signal loss alarm Disconnect IF connector on IF_OUT of Modem Unit and IF_IN of Modem Unit, connect IF_IN to IF_OUT of Modem Unit by IF connection; Check whether RIF on the MODEM Unit LCD is normal; if RIF is normal, check the IF_connector on the RX of Modem Unit; change Transceiver Unit; Otherwise, change Modem Unit. Error alarm, error bit has been in communication. Disconnect IF connector on IF_OUT of Modem Unit and IF_IN of Modem Unit, connect IF_IN to IF_OUT of Modem Unit by IF connection; Check whether ERR is normal; If ERR is normal, the interference in communication exist: otherwise, change Modem Unit. Frame synchronization loss alarm Demodulator frame unlock. Electrical power must be switched off then on. Otherwise, change Modem Unit Remote terminal alarm On the remote menu of the MODEM Unit, check alarm information of the remote equipment. If necessary, the operator must go to the remote station.

RIF

ERR

FLS

RMT

Change Modem Unit:

Disconnect all the connection connected to the equipment you are changing; Change Modem Unit after checking that the characteristics match; reconnect all the connection to the Modem Unit; Power the Modem Unit; Wait for about four second for the terminal to be reconfigured, the alarm LEDs should go off and the equipment LEDs should turn green; Update the stations installation form.(refer to installation manual).

92

Change Transceiver Unit:

Disconnect the Modem Unit-Transceiver Unit connection Change Transceiver Unit Reconnect the Modem Unit-Transceiver Unit connection; Wait for about four second for the terminal to be reconfigured, the alarm LED should go off and the equipment LEDs should turn green. Check that there are no alarms; Update the stations installation form on MODEM Unit LCD.

93

4 - System Troubleshooting and maintenance


4.1- Tx Troubleshooting and maintenance:

4.1.1 When Tx is in trouble, there is Tx power alarm on the LCD of Modem Unit. can be shown as follows:

It is

TXXXdBmALM RXXXdBmNOR
According to the above, the trouble spot should be found.

94

Modem Unit displays

TX19dBmALM Y Check power supply of equipment

Repair power and connection

Normal? Y

Equipment gets right

Check whether IF connection line is normal

Replace or link IF connection

IF connection is normal Y

Equipment gets right

Self-loop check of Modem Unit Modem Unit shows TX25dBmNOR (Transceiver Unit is normal) Y Check Modem Unit

Modem Unit shows TXXXdBmALM (Transceiver Unit is in trouble)

95

1 1

In operating Unit, Alarm of Alarm of operating Alarm of operating Modem Unit shows: Unit shows: Unit shows: 2.1.1 TIFALM 1.3.1 TLOALM 1.3.1 TLONOR 2.1.2 TSLALM 1.2.2 TPWALM 1.2.2 TPWALM Replace Modem Unit Y in trouble with the same one and Link IF connection, then turn on power. (see 6 about maintenance of Modem Unit)

displayALM N display NOR

LO of Tx unit in Transceiver Unit is in trouble

Tx unit or connection in the Transceiver Unit is in trouble.

Equipment gets right

Check whether BNC end is normal and its link with IF connection is normal N Replace BNC end or the same Modem Unit and link IF connection

Replace Transceiver Unit in trouble with the same frequency one or Transceiver Unit and link every connection outside the Transceiver Unit, then turn on power. see 6 about maintenance of Transceiver Unit

Equipment gets right

Equipment gets right

When the equipment is normal, the Modem Unit will show as follows:,

TX25dBmNOR RXXXdBmNOR

4.1.2 - No power output The equipment is normal after checking item 2.1.1. If output signal at the RF interface of the near end does not exist measured with power meter or the Rx level of the remote equipment does not exist, analysis and maintenance should be done as following:

96

Connect power meter at the RF port of unit or inspect Rx level on the remote end from the local end

No output power

Check RF connection

Normal ? Y

Replace RF connection in trouble

Equipment gets right

Operate EP switch on the switching unit N Normal ? Y Switching Unit RF on-off box in trouble Replace Switching Unit or RF on-off box in trouble see 7 about maintenance of switch unit Replace Transceiver Unit or Tx filter with the same frequency one (see 6 about maintenance of Transceiver Unit)

Equipment gets right

97

4.2 - RX troubleshooting and maintenance


Rx trouble includes lower alarm of Rx level and alarm of no Rx level. The First step is to check the antenna direction, installation of antenna and cable, Tx unit on the remote end. If the check shows that all above is normal, then Rx troubleshooting and maintenance should be done on the local equipments. 4.2.1 - Alarm of Rx level or no Rx level

Modem Unit show: RXXXdBmALM XX86dBm or LOW

Check RF connection and connector

Normal Y Check RF N-type cable

Replace RF cable

Equipment gets right N normal Y If RF on-off and subbranch box of switching unit are in trouble, replace switching unit or them see 7 about maintenance of switch unit

If N-type connector is loose

Screw down N-type connector

Equipment gets right Normal? N Turn to check

Transceiver Unit
(see 5 about maintenance of Transceiver Unit)

Y Equipment gets right

98

4.2.2 - No Rx level on the Transceiver Unit: Modem Unit show: RXXXdBmALM XX86dBm or LOW

Check RF connection and connector

normal

Replace RF connection

Equipment gets right

unit alarm state of the local Transceiver Unit will be shown as following: 1.4.1 RLOALMorNOR 1.4.2 RSLALM

RLO ALM

If LO of Rx unit on the Transceiver Unit gives an alarm replace Rx unit or Transceiver Unit with the same frequency ones

LNA of Rx unit on the Transceiver Unit is in troublereplace Rx unit or Transceiver Unit with the same frequency ones

Equipment gets right

99

4.2.3 - IF Rx troubleshooting and maintenance: When Rx level is normal on the Transceiver Unit, IF Rx troubleshooting and maintenance of Modem Unit are shown as following:

Rx alarm state of Modem Unit will be shown as following: 2.2.1 RIFACR1orNOR 2.2.3 SYNALM 2.2.5 FLSALM

Self-loop check of IF signal on the Modem Unit

RIFNOR SYNNOR FLCNOR Y Check IF output signal of Transceiver Unit Operating IF self-loop of Transceiver Unit, the corresponding Modem Unit will show: TX +XXdBmNOR Y NOR?

RIFNOR Y

If demodulation of Modem Unit is in trouble

Replace Transceiver Unit with the same one(see 6 about maintenance of Modem Unit) Equipment gets right

Check IF connection and connector Rx of Modem Unit is in trouble In trouble Y

Replace Transceiver Unit with the same frequency one IF Rx IF of Modem Unit is in toruble, see 5 about maintenance of N Transceiver Unit.

Equipment gets right Replace RF connection

Equipment gets right


100

4.3 - E1 I/O interface troubleshooting and maintenance:


If trouble occurs connecting between equipment and others through E1 interface, please analyze and maintain as the following method. No signal at E1 interface Checking whether four E1 channels connection are normal

Normal ? N N Check E1 I/O connection Checking whether some channel is broken N broken? Y Seal again Equipment gets right Trouble in E1 I/O connection no signal at each E1 interface ? Y

Connect again

Equipment gets right

Replace E1 I/O connection Equipment gets right

101

4.4 - Troubleshooting and maintenance of monitor and display keyboard


4.4.1 - Troubleshooting and maintenance should be done as follows when Modem Unit does not display parameter of the corresponding Transceiver Unit: a When Modem Unit displays Caution T/R com Fault Please check whether RUM connection is connected correctly and work normally. If broken or have some trouble, RUM connection needs to be sealed again or replaced. As Soon as equipment gets right, it will display :

TX25dBm [NOR] RXXXdBm [NOR]


b. when Modem Unit does not display alarm state of the corresponding Transceiver Unit, it will show:

TX25dBm RXXXdBm
This fault means turn-off of Tx or Rx alarm indicator. please operate as follows: Operate MODEM Unit and choose corresponding state display of Tx or Rx. Choosing alarm state ON, it will show as follows: 1.3.1 1.3.2 1.4.1 1.4.2 TLO [ON]

TPW [ON] RLO [ON]

RSL [ON]

Quitting operation, it will show: 1.3.1 1.3.2 1.4.1 1.4.2 TLO TPW RLO [NOR] [NOR] [NOR]

RSL [NOR]

102

Exiting from operation of state display, Modem Unit will display as follows:

TX25dBmNOR RXXXdBmNOR

c. If the Modem Unit does not show the parameter of Transceiver Unit, it will show:

TX RX

dBm dBm

To check the corresponding OAM connection and insure that it is normal. If the connection is broken, please weld it or replace a new one. The equipment gets right.

4.4.3 - Display trouble: a. If there is no display trouble on the LCD of Modem Unit Unit, check the power supply and insure that power switch is normal. Turning on the power switch, its display gets right. b. Open Modem Unit to check if the LCD connection is plugged correctly. Line connecting, the display gets right.

4.4.4 - Trouble of keyboard operation: a. If there is no reaction operating keyboard, please restart the Unit and reset the keyboard control to make it gets right. b. If one key on the keyboard is insensitive or unresponsive, it is key trouble. Please replace the Unit. If problem can not be solved as indicated above, please replace the
103

corresponding Modem Unit and Transceiver Unit. Replaced unit should be returned to the factory to maintain.

104

5 - 2.4GHz Transceiver Unit troubleshooting and maintenance


5.1 - Power troubleshooting and maintenance
5.1.1 No input voltage (-48V) troubleshooting and maintenance Trouble phenomenon: to measure the voltage of pin 2 of the power module P1 on the RF power board with multimeter. Voltage reading is zero. No input voltage Check if 48V input of power supply is normal on the rear panel of Transceiver Unit Y Check if Transceiver Unit fuse is noraml Y Check if 7 pin connector of S6 on the Y power supply board of Transceiver Unit is not inserted or does not meet N Check whether power supply N 5.1.2 - no output voltage (+12V) troubleshooting and maintenance Trouble phenomenon: The input voltage is normal but the yellow LED on the front panel doesnt shine or the voltage of pin 2 of the power module P1 on the RF power board measured with multimeter is zero. No output voltage Y Solder again Equipment is normal Insert tightly and link correctly N Replace it

Check whether 48V output or cable of external power supply is normal ?

Check whether power module P1 pin 7 of RF power board links to GND at the condition of no power N Check whether power module P1 of RF power board is normal N

Check the connection spot between printed circuit board and GND and repair it

Replace it Y
105

Equipment gets right

5.2 - Troubleshooting and maintenance of display and inspection


5.2.1 - troubleshooting and maintenance of Tx and Rx display: Trouble phenomenon: the front panel LCD of IF demodulation displays

TX+dBm RX-dBm

+26dBm cant be changed, -34 dBm cant be changed.

Reading on the LCD does not change Check whether U10 MX584 pin 2 on the power board of 2.4GHz Transceiver Unit is +5V replace chip Check whether U11 MAX840 pin 6 on the power board of 2.4GHz Transceiver Unit is -5V Equipment gets right

Check whether U9 MX5160 pin 5 or 6 on the power board of 2.4GHz Transceiver Unit is 2.4V

Replace U3 MAX114 on the power board of 2.4GHz Transceiver Unit

106

5.2.2 - Troubleshooting and maintenance of Tx and Rx measurement point Trouble phenomenon: the voltage of DB9 pin 2 on the front panel of Transceiver Unit is zero; the voltage of DB9 pin 4 on the front panel of Transceiver Unit is zero. Above both are measured with multimeter.

a. check the RF connection 5 if it isnt inserted correctly.

b. If reading on the front panel LCD of Modem Unit shows that Tx is normal, test whether it is lined correctly between S5 pin 5 and DB9 pin 2 on the front panel of Transceiver Unit or short circuit occurs, then repair it. The trouble of Tx power inspection can be removed.

c. If reading on the front panel LCD of Modem Unit shows that Rx is normal, test whether it is lined correctly between U7(LM1458)pin 1 on the 2.4GHz Transceiver Unit power board and DB9 pin 4 on the front panel of Transceiver Unit or short circuit occurs, then repair it. The trouble of Rx power inspection can be removed.

107

5.2.3 - Troubleshooting and maintenance of Rx and Tx local oscillation inspection: Trouble phenomenon: to connect the microwave frequency meter (with N-SMA conversion connector) with RLO and TLO on the front panel of Transceiver Unit, no frequency is shown. Testing the LO inspection port of Rx and Tx unit, if the frequency can be found, then check SMA-JB3/ SMA-JB3 connection lines. If there is no frequency, analyse should be done according to the flow chart.

Abnormality phenomenon of LO power inspection can be divided into a. reduction b. nonexistence

Check whether SMA-KF3-80 connection line is broken or links to GND

Normal?

Adjust or replace connection

Check coupling board of LO power inspection

Adjust or replace coupling board

Normal?

Check LO

Repair LO if in trouble

LO power inspection is normal

108

5.3 - Tx troubleshooting and maintenance


5.3.1 - No power output troubleshooting and maintenance Trouble phenomenon: to connect the microwave power meter (with N-SMA conversion connector) with Tx port on the rear panel of Transceiver Unit, there is no power output or below the nominal. No power output or below the nominal

Check whether IF signal exists on the connection

test whether power signal exists on the Tx unit Turn to section 5.1 to handle LO

LO power inspection is normal

Check whether two class amplification of power IF amplifier is normal and insure that 70MHz output signal is normal

Check 70MHz IF signal


Its normal ?

Up-convertor is normal ?

test mixer and check whether class1 amplification is normal

Check single-band filter

Turn to single filter repairment

Above is normal

Power amplifier is normal

Repair power supply and insure it works normally

Power amplifier doesnt work Replace PA module and test it again to make it works normally Normal power output of Tx unit

109

5.3.2 - troubleshooting and maintenance if Tx unit power can not be tuned

Tx unit power can not be tuned


Check detector diode and feed through capacitor on the power amplifier module and insure that they are normal

Check whether P-MON detector voltage is normal at the power IF amplifier spot measured with multimeter Replace changeable attenuator Check whether PIN is normal on the power IF amplifier module

Check

changeable resistance

Replace it if in trouble

Tuning of Tx unit power is normal

5.4 - Troubleshooting and maintenance of no Rx gain


5.4.1 - troubleshooting and maintenance of no Rx gain

LO is in lock loss?

Isolator doesnt work?

Rx mixer doesnt work?

LNA doesnt work?

Repair it

Replace it

Repair it, Adjust every parameter again according to adjustment method

Repair it, Adjust every parameter again according to adjustment method

Normal Rx gain

110

5.4.2 - troubleshooting and maintenance of Rx IF amplifier a. Output level is not normal and tune RP3 in no effect. To test MAX840 pin 6 with multimeter, If the voltage isnt -5V ,then MAX840 does not work and replace it or V5/V6 detector diode may be soldered not correctly or broken. b. AGC range not enough A 10UF capacitor should be soldered between the +12V spot of the signal input and GND. To test the N1~N6 integration amplifier with the multimeter ,the voltage of output pin is in the range of 4.9V to 5.2V. If the voltage is not in the range , the capacitors from C4 to C14 should be checked to see whether they are soldered and work correctly and the V1 through V4 diodes are normal. c. AGC shows voltage not normal To test the diode D1, it should be replaced If the diode D1 does not work. Otherwise the feedback resistance should be tested between pin 6 and pin 7 of LM1458 in order to see whether it is 24K.

5.4.3 - LNA troubleshooting and maintenance When the gain is very small and can not be tuned up, first check whether the line on the transition board has been cut off, second check whether the isolator may be installed not correctly or does not work, third check R1 voltage. If R1 voltage is 5V , then N2 is broken and N1 broken if not.

111

5.5 - Troubleshooting and maintenance of LO in trouble


Trouble phenomenon: LO phase loss,locked level is 0V

Check soldering of 8MHz crystal Y it works oscillator and whether Y Y Repair it and it works correctly? N Check pin setting of MC145152 and whether it is soldered correctly? Y N Check soldering of MB510 and whether it workes correctly? Y Finally check loop filter and whether its output level of LM1458 is in the range of 6V8V?

Repair it and it N works correctly?

Repair it and it works

Change value of Finally set LO with required frequency

resistance R10

LO output is normal

112

6 - Troubleshooting and maintenance of Modem Unit


6.1 - ALM analysis
When ALM of Modem Unit shines, connector links of external cable and cable are checked to see if they are normal. Alarm information shown by system should be analyzed in detail if they are normal. 6.1.1 - Tx alarm state: 6.1.2 - Rx alarm state: Operate unit into state display

LOCAL[ ]

M/R STATE

MOD STATE

2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6

TIF[NOR]/ [ALM] IF Tx alarm TSL[NOR]/ [ALM] IF signal alarm IN1[NOR]/ [ALM] no input alarm of subbranch 1 IN2[NOR]/ [ALM] no input alarm of subbranch 2 IN3[NOR]/ [ALM] no input alarm of subbranch 3 IN4[NOR]/ [ALM] no input alarm of subbranch 4

DEM STATE

2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6

RIF[NOR] /[ALM] IF Rx alarm ERR[NOR]/ [ALM] Rx error-code alarm SYN[NOR]/ [ALM] RPD Synchronization loss alarm HSW[NOR]/ [ALM] hitless switching alarm FLS[NOR]/ [ALM] frame synchronization loss alarm RMT[NOR]/ [ALM] remote equipment alarm
113

6.2 - Troubleshooting and maintenance of IF Tx alarm (TIF [ALM])


trouble phenomenonno IF Tx output alarm on the Modem Unit

Replace it if 70M Check whether input signal exists at N crystal oscillator 3JZ1 is the pin 1 of amplifier 3N4 in trouble Y Check whether output of 90power N splitters/combiners is normal Y Check whether output of mixer 3N9 N and 3N8 are normal Y Check whether output of 0 power N splitters/combiners 3N7 is normal Y Check whether output amplifier 3N3 is normal Y Check whether output amplifier 3N2 is normal Y Check whether output of diode 3V1 and 3V2 is normal Y Replace comparator 3N1 N Replace it if diode is in trouble of N Replace it if amplifier is in trouble of N Replace it if amplifier is in trouble Replace it if 0 power splitters/combiners is in trouble Replace it if mixer is in trouble Replace it if 90 power splitters/combiners is in trouble

Alarm disappears? N

Alarm disappears? N

Alarm disappears? N

Alarm disappears? N

Alarm disappears? N

Alarm disappears? N

Alarm disappears? N

Alarm disappears and Modem Unit is normal

115

6.3 - Troubleshooting and maintenance of 2M code input alarmIN1~4 [ ALM]


trouble phenomenon no 2M code stream input on the Modem Unit and no input on the channel corresponding with IN1~4. External cable link and output of external equipment should be carefully checked.

6.4 - Troubleshooting and maintenance of Rx IF alarm (RIF

[ALM])

trouble phenomenon no Rx input on the Modem Unit. IFIN and IFOUT on the Modem Unit are connected using short line with BNC connector at the two ends.

Check whether output of amplifier 7N1 N pin 3 and 7N2 pin 3 are normal Y Check whether positive-going resistance N value of diode 7V1 is normal *power must be turned off in doing abovementioned operation Y

Replace it if amplifier is in trouble

Alarm disappears? N

Replace it if amplifier is in trouble

Alarm disappears? N

Check whether positive-going resistance N Replace it if diode is value of diode 7V2 and 7V3 is normal *power must be turned off in doing in trouble abovementioned operation Y Check whether output of 7N3 pin 1 is N Replace it if resistance normal with the turn of 7RP2 is in trouble Y

Alarm disappears? N

Alarm disappears? N

Replace 7N3 Y Alarm disappears and Modem Unit is normal

116

6.5 - Troubleshooting and maintenance of Rx de-modulation alarm (SYN [ALM] / FLS [ALM])

trouble phenomenonSelf-loop lock loss on the Modem Unit 6.5.1 - Using IF connection to link IFIN and IFOUT of Modem Unit in the way of self-loop. 6.5.2 - Measure base voltage of transistor (V5-8). replace them in trouble. 6.5.3 - Troubleshooting and maintenance

117

Note: The following analysis demands that Tx must be in no trouble.

Check whether output of 70MVCO5JT1 pin 8 is normal Y

Replace it if VCO is in trouble

Alarm disappears? N

Check whether output of amplifier 5N5 pin 4 is normal Y Check whether output of 90 power splitters /combiners 5N4 pin 3 and pin 6 are normal Y Check whether output of mixer 5N2 pin 2 and 5N3 pin 2 are normal Y Check whether pin 7 and pin 8 of comparator5U3 and 5U4 work correctly? Y Check whether pin 4 and pin 9 N of comparator 5U6 and 5U7 work correctly? Y Replace 5U1

Replace it if amplifier is in trouble

Alarm disappears? N

Replace it if 90 power splitters is in trouble

Alarm disappears? N

Replace it if mixer is in trouble

Alarm disappears? N

Replace it if comparator is in trouble

Alarm disappears? N

Replace it if comparator is in trouble

Alarm disappears? N

Alarm disappears and Modem Unitis normal

118

6.6 - Troubleshooting and maintenance of EOW


N Please confirm that ModemUnit is in no trouble again

Check if there is 64k signal input at the pin 1 and pin 9 of 8N17.

Y Normal

Y Check if output at the pin 3 and N pin 8 of NAND gate 8N17 is normal. Y

Replace it if 8N17 is in trouble

normal N

Check if output of PCM 8N15 N is normal Y


Can not dial out

Replace it if its in trouble

normal N

Can not dial in

EOW in trouble

Check whether N Replace it if audio output at the pin 5 amplifier 8N9 is of 8N9 is normal in trouble

Check whether N Replace it if audio output at the pin 5 amplifier 8N10 of 8N10 is normal is in trouble Y
Alarm disappears

Y normal N Replace 8N12

N Replace 8N11

Modem Unit is normal

119

6.7 - Troubleshooting and maintenance of display and monitoring


6.7.1 - Troubleshooting and maintenance in this case like no display on LCD

LCD is in trouble? N

Replace LCD

Pin 6 of LCD 9JP1 is 0V? N 9U1 is in trouble Y 9U3 is in trouble

Replace 9U1

Replace 9U3

LCD display is normal

120

F.

Service

121

1 - TECHNICAL SUPPORT
Manufacturer Support and General Inquires Manufacturer provides service and support in the following ways: E-mail Telephone Hours of operation are from Monday to Friday 9:00AM - 5:30 PM.

To ensure the equipment normal operation, manufacturer provides route selection and design.

Manufacturer provides necessary training on installation and operation.

Manufacture may provide installation and technical supervision on actual requirement.

We promise we receive FAX, telephone about quality problem, after analyzing problem; our technician will get to the site as soon as for domestic customers. Return the defective equipment back to manufacture for prepare for overseas customers.

122

2 - WARRANTY
2.1 - General terms
2.1.1 - All definitions contained in Manufacturer apply to the warranty. 2.1.2 - Manufacturer warrants that for a period of 1 year from the date of purchase from Manufacturer or an authorized reseller, the product will be free from defects in material and workmanship under normal use. If this product is not in good working order as warranted, the sole and exclusive remedy shall be, at Manufacturer's option and expense, to repair the defective product or to provide an equivalent replacement product. All products that are replaced will become the property of Manufacturer. Replacement products may be new or products reconditioned to a like-new condition. 2.1.3 - this warranty dose not applies to Antenna and feeder system and rack, which non-manufacturer provided.

2.2 - Restrictions
This warranty does not apply if the product has been altered, except by Manufacturer has not been installed, operated, repaired, or maintained in accordance with instructions supplied by Manufacturer has been subjected to abnormal physical or electrical stress, misuse, negligence, or accident, or used in ultra hazardous activities.

123

Appendix 1 - List of application alarms


Alarm mnemonic TLO TPW RLO RSL TIF TSL IN1 IN2 IN3 IN4 RIF ERR FLS RMT Tx local oscillator alarm Tx power alarm Rx local oscillator alarm Rx signal alarm Tx IF alarm Transmitting signal loss The first E1 loss alarm The second E1 loss alarm The third E1 loss alarm The four E1 loss alarm Rx IF alarm Error alarm Frame synchronization loss alarm Remote terminal alarm MEANING

124

Appendix 2 - RX/TX level and Voltage corresponding graph

125

You might also like