Precision PLC

Specification Sheet
MODEL

Precision Control Increase throughput Save energy Reduce waste Improve quality Meet Standards AMS2750 CQI-9 PLC Platform IEC 611313 Open platform Dedicated functions Data Recording Secure files

A precision PLC for the heat treatment industry


The E+PLC400 combines the flexibility of a PLC with precise Eurotherm Control, in a new solution designed for heat treatment and other applications requiring precise temperature control. To help meet the demands of this highly regulated industry, Eurotherm also provides secure recording and archiving strategies for compliance to standards. This combination of an open PLC platform with world class Eurotherm Control and Recording, creates a future proof, all-in-one solution, economically adaptable for a variety of applications. Simple configuration, chosen from a comprehensive set of function blocks and libraries aids faster implementation and maintenance of the process. A range of Eurotherm control and recording function blocks, containing IP perfected through over 40 years of experience, help to get the set up right first time. With the added benefit of Eurotherm accurate analogue and digital I/O, tighter tolerances can be achieved, leading to better quality end products and less waste. Putting this together with sophisticated Control, Recording and Archiving strategies results in an all in one solution that enables the process to run at maximum performance while achieving maximum efficiency.

CODESYS is a trademark of 3S-Smart Software Solutions GmbH.

Visit e-brochure here www.eurotherm.com/eplc

Eurotherm Control Inside


The precision offered by the Eurotherm Control strategy is unrivalled, based on custom algorithms perfected over the past forty years. Building this into the E+PLC400 embeds the precision of our external discrete controllers within the flexibility of a PLC, forming a more economical solution. Unlike traditional PLC programming, complicated DIY function block building is a thing of the past and configuration is simply carried out by filling in the required parameters within Eurotherm function blocks in the CODESYS software. Closely integrated with our Setpoint Programmer and Autotune functions, Eurotherm PID enables a fast but stable response in both normal and unexpected situations.
Start up temperature prole showing Eurotherm best in class autotuned response

Setpoint Programmer
Setting up a program is easy using provided spread sheet style templates. These can be shared and stored in a central library then downloaded to the product via comms, HMI or digital event. Further storage for a minimum of 200 programs of 32 segments is set aside onboard, with segment types for Off, Dwell, Ramp Rate, Ramp Time, Wait and Go Back (repeat). The SPP is tightly integrated with Eurotherm control and recording strategies, to provide a comprehensive but quick to implement solution for the smooth running of multiple loops in the process.

100 80 60 40 20 0

overshoot setpoint undershoot

Seg Type Duration Holdback TargetSP EventOuts

1 Time (2) 0 Off (0) 25.00 .... ....

2 Dwell (3) ... 0

... .... ....

3 Time (2) ... 0 Off (0) 75.00 ... .... ....

4 Dwell (3) ... 0

... .... ....

5 Time (2) ... 0 Off (0) 100.00 ... .... ....

...

6 Dwell (3) 0

... .... ....

7 Time (2) 0 Off (0) 60.00 ... .... .... ...

8 Time (2) 0 Off (0) 35.00 ... .... .... ...

9 Dwell (3) ... 0

10 Dwell (3) ... 0

11 Dwell (3) ... 0

... .... ....

... .... ....

... .... ....

12 Time (2) ... 0 Off (0) 0.00 ... .... ....

...

...

Eurotherm Specific Function Blocks


Overshoot Undershoot Eurotherm autotuned response

Flexible CODESYS Software


Fully compliant with IEC 61131-3, the industry recognised CODESYS platform with IDE config tool enables the user to configure and maintain the program in a single PC based tool, that is interoperable with CODESYS enabled PLCs from other suppliers. An extensive range of Libraries, Editors and Graphical Components are available for programming and visualisation of projects. OSCAT libraries are supported and editors include Alarm Configuration, Recipe Manager and the following programming languages : Continuous Function Chart (CFC) Function Block Diagram (FBD) Instruction List (IL) Ladder Logic Diagram (LD) Sequential Function Chart (SFC) Structured Text (ST)

A range of specific Eurotherm Function Blocks containing our well respected IP are selectable from an extensive list of functions and function blocks in the CODESYS libraries. Available blocks include PID, Autotune, Setpoint Programmer, Batch Recording and Archiving, with Zirconia Probe as an option for heat treatment applications. Using our precise, stable control strategies, helps save energy and increase efficiency by getting to the setpoint faster and eradicating overshoot and oscillations which also results in better quality end products, finished to the required high standards.

Secure Recording Strategy


Eurotherm advanced recording and archive strategies are available to ensure the safe capture and storage of valuable process data, in tamper resistant UHH files developed by Eurotherm through years of experience. Up to 30 groups can be recorded, each with up to 127 channels and vital data can be backed up by automatic transfer to USB Media, or multiple servers via FTP. The historical data can be viewed from either a Panel HMI or PC using Eurotherm Review software, Eurotherm Online Service (EOS Director) or a web browser. This best in class form of data recording meets the most stringent of regulatory requirements including AMS2750, CQI-9 and Nadcap.

Autotune
The control parameters in the E+PLC400 can be set manually, but a great advantage is the Autotune function which automatically works out the optimum control settings for the application. Easily performed by the operator, it automatically calculates and sets many parameters, a task that would normally take a skilled engineer several hours to complete manually. The Autotune algorithm gives excellent results over a diverse range of applications making it a great time saving tool for precise configuration of heat treatment and other processes.
Eurotherm Part No. E+PLC400 Provisional October 13 2

E+PLC400 Specification Sheet

Batch Recording
Batch recording for easily traceable records is simply configured in a function block. The Batch information can be entered by the user via the HMI and the resulting files automatically transferred at the end of the batch. The data can then be quickly accessed by searching, using Eurotherm Review software or Eurotherm Online Service (EOS Director).

Live or historical view of batch data

E+PLC400 Connectivity
Simple connectivity with Modbus TCP, RTU Master/Slave and EtherCAT built in. Easily accessible local and remote visualisation of live and historical secure data.

ONSITE VIEW

OFFSITE VIEW

FTP, EOS, EUROTHERM REVIEW, WEB SERVER

E+PLC400

MODBUS TCP, RTU MASTER SLAVE ETHERCAT

Eurotherm Part No. E+PLC400 Provisional October 13

E+PLC400 Specification Sheet

Specification
Base Unit
General
The base unit is fitted with the E+PLC400 processor modules plus additional I/O modules. These modules plug onto terminal units, which provide the wiring interface between the plant or machine and the I/O modules. Bases are available in 4 sizes to suit the number of modules required in a particular system. Communication between the I/O modules and the processor is effected by the use of a passive internal module I/O bus running along the width of the base. Each module position is tracked separately for additional security during live replacement of I/O modules. The base consists of an aluminium extrusion, the internal I/O bus and mounting supports. It is designed to be DIN rail mounted or directly fixed to a bulkhead or mounting plate.

RFI EMC emissions: EMC immunity: Safety

BS EN61326 1: 2006 Class A BS EN61326 1: 2006 Industrial Locations BS EN61010-1/A2; 2001 Installation cat II, Pollution degree 2 Safety earth and screen connections are made to earth terminals at the bottom of the base

Vibration Vibration:

Shock:

IEC61131-2:2007 section 4.2.1 1.75mm peak amplitude 5-8.4Hz; 1g peak amplitude, 8.4-150Hz 30 minutes dwell at resonance in all 3 planes 15g static shock

Mechanical
Based on the number of modules and allowing for future expansion, the E+PLC400 can be supplied in a range of standard base sizes to suit process requirements. The dimensions and weights of the different base sizes are detailed in the table below: Module Capacity (Base Size) Weight (no modules) kg Weight (all modules) kg Height: Depth: Mounting: DIN rail: Casing: Ventilation space: 0 0.2 0.7 4 0.7 1.65 8 1.0 3.1 16 1.6 5.3

Diagnostic LEDs Diagnostic LEDs indicate module diagnostic status. All modules: A green LED at the top indicates the module is powered and operating correctly Analog modules: Red LEDs for each channel to indicate channel failure Digital modules: Yellow LEDs for each channel to indicate the channel state

Communications
Ethernet Supports 10/100baseT Ethernet. Simultaneously it can support Modbus-TCP Master or Slave and EtherCAT. Connectors: RJ45 connector Network medium: Ethernet Cat5 shielded cables Speed: 10/100baseT auto-select Line length (maximum): 100 metres, extendible by repeater Allocation of IP address: Fixed, DHCP Modbus: TCP configurable master or slave Max numbers of slaves: 16 Modbus TCP slaves Isolation: 50V dc; 30V ac (IEEE802.3) RS422/485 Serial Communications Connector: Comms medium: Line impedance: Line length: Max number of slaves: Protocol: RJ45 connector RS422 (5-wire) or RS485 (3-wire), jumper select 120-240 twisted pair 1220m maximum at 9600 bits/sec 16 Modbus TCP Slaves Modbus/J-BUS RTU configurable master or slave

180mm 132 -135 mm with retaining lever raised DIN rail or Bulkhead, mounted vertically Use symmetrical DIN rail to EN5002235 x 7.5 or 35 x 15 Without additional protection IP20 25mm free space above and below

General
Supply voltage range: Power consumption: Fuse rating: Surge current: Module power consumption: Environmental Operating temperature: Storage temperature: Relative humidity: 24V dc 20% < 82W maximum for fully loaded rack 0.5A time lag (Not customer replaceable) 8A maximum See individual module specification

0 to 55C -25C to 85C 5 to 95% (non-condensing)

Note: Use of a communications buffer/isolator is recommended

Mechanical details

132 mm (5.2 in)

0 module prole

Run

AI 2

AI 3

AI 4

AO 2

RLY 8

RLY 8

DIN Rail Cover catch 83.5 mm (3.29 in)

Open cover Max: 160 mm (6.3 in)

Base Size 0 module 4 module 8 module 16 module

A mm (inches) 61.25 (2.41) 162.75 (6.41) 274 (10.8) 477 (18.8)

Eurotherm Part No. E+PLC400 Provisional October 13

E+PLC400 Specification Sheet

180 mm (7.1 in)

Watchdog

1 2

1 2 3

1/2 3/4

1 2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 DI 15 16 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 DI 15 16 16

70 mm (2.75 in)

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

AI2 Two Channel Analog Input


This analog input module is used to monitor analogue signals from a wide range of plant sensors. The mA and TC inputs each require the appropriate terminal unit. The second channel of the AI2 has a special high impedance range for use with zirconia probe inputs for oxygen measurement. No of channels: Input types: mV range: mA range: Volts range: RTD support: Resolution: Ohms range: Hi Ohms range: Pot range: Linearity: Input filtering: Input accuracy: System isolation: Channel isolation: Series mode rejection: Common mode rejection: Power consumption: Input specification TC Linearisation types: RTD LIN Types: CJC system: Initial CJC accuracy: CJC rejection: 2 TC, RTD, Volts, mA, mV, Potentiometer, Pyrometer, Zirconia probe, 150mV to +150mV at input impedance >100M 25mA to +25mA with 5 burden in the terminal unit 10.3V to +10.3V at input impedance 303k, 0 to 1.8V 10M high impedence range (channel 2 only) Support for 2, 3 and 4-wire resistance thermometer devices (RTD) Better than 0.001% of range 0 to 560 2, 3 or 4-wire lead compensation 0 to 6k 2, 3 or 4-wire lead compensation 0% to 100% rotation of 100 to 7k pot Better than 0.01% of range Handled by CODESYS srtategy Electrical input factory calibrated to better than 0.1% of reading 300V RMS or dc (double insulation) 300V RMS or dc (basic insulation) >60dB (47-63Hz) >120dB (47-63Hz) 2W maximum Note: User calibration options can improve performance, limited only by noise and non-linearity.

B, C, D, E, G2, J, K, L, N, R, S, T, U, NiMo/NiCo, Platinel, Ni/NiMo, Pt20%RHPt40%Rh, Custom, Linear, SqRoot, XX3/2, X5/2 Cu10, Pt100, Pt100a, JPt100, Pt1000, Ni100, Ni120, Cu53 Measured by RTD, located beneath the input connector 0.5C typical (1C maximum) Better than 30:1 over operating temperature range

AI3 Three Channel Analog Input


Provides three isolated current input channels specifically designed to meet the requirements of modern two wire transmitters. Each channel has its own isolated 24V supply for transmitter excitation. Each channels 24V dc supply is protected against short circuit and utilises a sophisticated trip system in which the module senses over current and cuts the power. After a period the circuit checks for continued circuit malfunction. No of channels: Input range: Resolution: Linearity: Initial accuracy: Input filtering: Burden resistance: Channel PSU: System isolation: Channel isolation: Series mode rejection: Common mode rejection: Power consumption: 3 28mA to +28mA Better than 0.5uA with 1.6 sec filter time (equivalent: 16 bits ) Better than 1A Factory calibrated to better than 0.1% of reading at 25% Handled by CODESYS srtategy 60 nominal, 50mA maximum current 20-25V dc, current limited 30mA nominal, self-resetting 300V RMS or dc (double insulation) 50V RMS or dc (basic insulation) >60dB (47-63Hz) >120dB (47-63Hz) Current input mode - 2.2W 3 powered loops - 3.7W

Notes: 1. User calibration options can improve performance, limited only by noise and non-linearity. 2. Total burden can be increased to 250 by cutting a link track on the terminal unit.

AI4 Four Channel Analog Input


This analog input module is used to monitor analog signals from a wide range of plant sensors. The mA and TC inputs each require the appropriate Terminal Unit. No of channels: Input types: mA range: Resolution: Input filtering: Initial accuracy: System isolation: Channel isolation: Series mode rejection: Common mode rejection: Power consumption: Input specification TC Linearisation types: CJC system: Initial CJC accuracy: CJC rejection: Eurotherm Part No. E+PLC400 Provisional October 13 4 TC, mV, mA, Pyrometer mV range: 150 to +150mV at input impedance >20M 25 to +25mA with 5 burden in the terminal unit Better than 2V Handled by CODESYS srtategy Electrical input factory calibrated to better than 0.1% of reading Burden resistor 5 1% (fitted to terminal unit) 300V RMS or dc (double insulation) 300V RMS or dc (basic insulation) Ch1 and Ch2 from Ch3 and Ch4 >60dB (47-63Hz) >120dB (47-63Hz) 2W maximum

Notes: 1. User calibration options can improve performance, limited only by noise and non-linearity. 2. Wiring care and sensor choice should be used to prevent ground loops when using non-isolated thermocouples.

B, C, D, E, G2, J, K, L, N, R, S, T, U, NiMo/NiCo, Platinel, Ni/NiMo, Pt20%RHPt40%Rh, Custom, Linear, SqRoot, X3/2, X5/2 Measured by RTD, located beneath the input connector 0.5C typical (1C maximum) Better than 30:1 over operating temperature range 5

E+PLC400 Specification Sheet

AI8 Eight Channel Analog Input (Consult factory for availability)


This analogue input module is used to monitor analogue signals from a wide range of plant sensors. The mA and TC inputs each require the appropriate terminal unit. No of channels: Input types: mV range: mA range: RTD support: Ohms range: Hi Ohms range: Resolution: Linearity: System isolation: Channel isolation: Series mode rejection: Common mode rejection: Power consumption: TC Input specification Linearisation types: CJC system: Initial CJC accuracy: CJC rejection: 8 TC, RTD, mA, mV 80mV to +80mV at input impedance >100K 20mA to +20mA with 3.3 burden in the terminal unit Support for 2 and 3-wire resistance thermometer devices 20 to 500 and 2 and 3-wire lead compensation 200 to 5K 2 and 3-wire-wire lead compensation 10m and 100m (with 0.4s filter) 20ppm of span 300V RMS or dc (double insulation) Installation Category II 300V RMS or dc (basic insulation) Galvanic Isolated in pairs. Installation Category II 60dB (47-63Hz) 120dB (47-63kHz) >120dB @50/60Hz 1.8W maximum

B, C, D, E, G2, J, K, L, N, R, S, T, U, NiMo/NiCo, Platinel, Ni/NiMo, Pt20%RH/Pt40%RH and custom Measured by 2 RTD (Pt100), located beneath the input connector 0.8degC sensed with two PT100 sensors on TU Better than 30:1 over 0C to +55C ambient

AO2 Two Channel Analog Output


This analog output module provides two isolated analog output channels. Each output can be independently configured for current or voltage. No of channels: Current output: Resolution: Voltage output: Resolution: System isolation: Channel isolation: Power consumption: Calibration accuracy: 2 0.1 to 20.5mA; 10V dc max. Compliance with total burden less than 500 Better than 1 part in 10,000 (1uA typical) 0.1V to 10.1V dc; 20mA max. compliance with total load greater than 550 0.3 to 10.3 V dc; 8mA max. compliance with total load greater than 1500 Better than 1 part in 10,000 (0.5mV typical) 300V RMS or dc (double isolation) 300V RMS or dc (basic isolation) 2.2W maximum Better than 0.1% of reading

ZI Zirconia Input
Input types: Analog voltage, Channel 1 - mV (TC), and Channel 2 - (2V Zirconia probe)

Thermocouple Input Specification (Ch1 ONLY) Input range: 77mV to +100mV Calibration accuracy: 0.1% of electrical input, 10V Noise: 5V p-p with 1.6s Filter Resolution: <2V with 1.6s Filter Sensor break detect: 250nA break high, low or off Input impedance: 10M Cold Junction Sensor Specification (Ch1 ONLY) Temperature Range: 10C to +70C CJ rejection: < 30:1 CJ accuracy: 1.3C, 0.5C typ. (Automatic cold junction compensation) Zirconia Input Specification (Ch2 ONLY) Input range: 10mV to +1800mV Calibration accuracy: 0.2% of electrical input Noise: 0.1mV p-p with 1.6s Filter Resolution: <50V with 1.6s Filter Sensor impedance measurement: 0.1k to 100k 2% Input Impedance: >500M Input leakage current: 4.0nA max, 1nA typical General Specifications Power consumption: Common mode rejection: Series mode rejection: System isolation: Channel isolation: Eurotherm Part No. E+PLC400 Provisional October 13 1.8W maximum >80db, 48 - 62Hz >60db, 48 - 62Hz 300V RMS or dc (double insulation) 300V RMS or dc (basic insulation) 6 E+PLC400 Specification Sheet

DI16 Sixteen Channel Digital Input


This digital input module accepts sixteen inputs and can be wired either for voltage input or for contact closure. No of channels: System isolation: Channel isolation: Power consumption: 16 300V RMS or dc (double insulation) Channels share a common connection (C) Logic: 0.75W maximum Contact: 2.0W maximum Max. voltage across any channel: 30V dc Contact Mode Module Internal Isolated Power supply (P): Contact closure: ON state: OFF state: Wetting current: Wetting voltage: Logic Mode Logic inputs: Input current:

16 to18V dc Input resistance threshold <1K typical Input resistance threshold >7K typical >4mA >12V dc

ON state: Input voltage threshold >10.8V dc, 30V maximum OFF state: Input voltage threshold <5.0V dc, 30V minimum 3.8mA @ 12V dc; 2.8mA @ 24V dc

DO16 Sixteen Channel Digital Output


This digital output module provides higher packing density and lower cost per channel. The sixteen digital output module provides sixteen short-circuit protected outputs, which are typically used for control, alarms, or event outputs. Each channel can drive up to 0.7A and can be used for driving solenoids, relays, lamps, fans, thyristor units, single phase Solid State Relays (SSRs), or some three phase SSRs. Voltage supply (external): Leakage current off state: Current output: Channel maximum: Module Thermal Cut-off: Short Circuit Protection: Output voltage: System isolation: Channel isolation: Power consumption: Plant side: 24Vdc +/- 20% <10uA 0.7A/channel 903C, restart: 883C 0.7A to 1.7A per channel >Voltage supply (Vs) less 1V 300V RMS or dc (double insulation) Channels share a common connection Module 0.6W maximum 850W maximum

RLY8 Eight Channel Relay Output


This module provides eight relay outputs. These outputs may require external snubber circuits (application dependent). No of channels: Max current rating: Min rating: System isolation: Channel isolation: Contact life: Mechanical life: De-rating: Power consumption: 8 normally open, AgCdO contacts for best operating life 2A at up to 240V ac; 0.5A at 200V dc, increasing to 2A at 50V dc (resistive) 100mA at 12V 300V RMS or dc (double insulation) 300V RMS or dc (basic insulation) >10 million operations @ 240V ac, 1A rms >600,000 operations @ 240V ac, 2A rms >30 million operations The above ratings summarise the performance with resistive loads. With complex loads further de-rating may be required 2.5W

Relay De-rating AC Voltage


As the AC load becomes more difficult a more significant derating factor is required. The graph below shows the derating to be applied in terms of contact life, assuming the load requirement is predefined.
Reduction factor for inductive ac loads
1 0.9 0.8

DC voltage
DC operation is also limited for difficult loads, particularly where there is significant inductance. Here the working current must be limited as shown where the load time constant (L/R, in ms) is the significant factor.
Max dc load breaking capacity
10

Reduction Factor F

0.7 0.6 0.5 0.4 0.3 1 0.8 0.6 0.4 0.2

F1 = worst case F2 = typical

DC Current (Amps)

1 0.5

a c
100

a = resistive b = 20ms c = 40ms d = 60ms

b
200

0.1 10

d
20 30 40 50

Power Factor (cos ) Contact life = resistive contact life x reduction factor

DC Voltage (Volts)

Eurotherm Part No. E+PLC400 Provisional October 13

E+PLC400 Specification Sheet

Al

so

co

m in g
Visit www.eurotherm.com/eplc for more information

Eurotherm: International sales and support


Contact Information
Eurotherm Head Office Faraday Close, Durrington, Worthing, West Sussex, BN13 3PL Sales Enquiries T +44 (01903) 695888 F 0845 130 9936 General Enquiries T +44 (01903) 268500 F +44 (01903) 265982 Worldwide Offices www.eurotherm.com/global

So

on

www.eurotherm.com
Represented by:

Scan for local contacts

Copyright Eurotherm Limited 2013


Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower, EPack, nanodac, piccolo, versadac, optivis, Foxboro and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners. All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm Limited. Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.

Eurotherm Part No. E+PLC400 Provisional October 13

E+PLC400 Specification Sheet

You might also like