Centrifugal fans
VENTS offers a wide range of domestic fans that combine outstanding performance and reliability with low power consumption and noise levels. These units are the perfect solution for ventilating bathrooms, kitchens, living quarters and other premises of up to 30 m2. VENTS fans are available in manifold modifications with various air capacity, design and functioning. Fan installation example Ceiling Through-the-wall Air duct or ventilation shaft
Window
Room to room
Air duct
How to choose the right fan Effective ventilation depends on fan or ventilation system selection with suitable air capacity that meets your requirements. Some factors to be considered: Ventilated area volume Air exchange by the hour How to calculate ventilated area volume? Calculate the total volume of the premise in m3. Use a simple formula: Length x Width x Height = Volume of the premises m3 A x B x H = V (m3) Air exchange calculation. Ventilated air amount is calculated on an individual basis for each premise. Measured air exchange is calculated with the formula: L = V * K (m3/h), where: V ventilated area volume [m3/h], minimum air exchange per hour, see air exchange table. Example: kitchen with 5 m length, 3 m width and 2.8 m height. Required air volume is 5 3 2,8 = 42 m3. Air exchange rate for kitchen is 6 - 12 times/hour. So, required fan air capacity is: 42 m3*6=252 m3/h.
Fan air capacity [m3/h] 90 - 300 90 - 300 90 - 190 100 - 320 90 - 190
Spigot size of the fan [mm] 100, 125, 150 100 125 100 125 125 150 100 125