Contents
Description
Quick Reference
QUICKLAG
Quick Reference
Eatons QUICKLAG Industrial Circuit Breakers 1 Plug-In, Bolt-On, Cable-In/Cable-Out
Circuit Breaker Type HQP HQP HQP QPHW QPHW QPHW QHPX QHPX QHPX QHPW QHPW QHPW QPGF QPGF Continuous Ampere Rating at 40C 1070 10125 10100 1570 15125 15100 1570 15100 15100 1530 1530 1520 1540 1550 Interrupting Ratings rms Symmetrical Amperes Number of Poles 1 2 2, 3 1 2 2, 3 1 2 3 1 2 3 1 2 Federal Spec. W-C-375b 10a, 11a, 12a 10a, 12a 10b, 11b, 12b 14a 14a 14b 15a 15a 15b 10a, 11a, 12a 10a, 11a, 12a Vac Ratings 120 10,000 120/240 10,000 10,000 22,000 22,000 42,000 42,000 65,000 65,000 10,000 240 10,000 22,000 42,000 65,000 Vdc Ratings 2 2448 5000 5000 5000 5000 5000 5000 5000 5000 62.5
3
Vac 120/240 120/240 240 120/240 120/240 240 120/240 120/240 240 120/240 120/240 240 120 120/240
Vdc 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80
Page Number V4-T1-6 V4-T1-6 V4-T1-6 V4-T1-6 V4-T1-6 V4-T1-6 V4-T1-7 V4-T1-7 V4-T1-7 V4-T1-7 V4-T1-7 V4-T1-7 V4-T1-9 V4-T1-9
5000
3
5000
3
5000
3
5000
Notes 1 QUICKLAG circuit breakers are suitable for application in relative humidity 095% noncondensing. 2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed. 3 62.5 Vac interrupting rating is 3800 AIC 1050A and 2500 AIC 55100A continuous. Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA. For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
1.1
1
80 5000 5000 5000 5000 5000 Page Number V4-T1-9 V4-T1-9 V4-T1-9 V4-T1-9 V4-T1-9 V4-T1-12 V4-T1-12 V4-T1-32 V4-T1-32 V4-T1-32 V4-T1-32 V4-T1-12 V4-T1-12 V4-T1-12 V4-T1-32 V4-T1-32 V4-T1-15 V4-T1-15 V4-T1-12 V4-T1-12 V4-T1-12 V4-T1-13 V4-T1-13 V4-T1-13 V4-T1-13 V4-T1-13 V4-T1-13 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-18 V4-T1-41 V4-T1-41 V4-T1-41 V4-T1-23 V4-T1-23 V4-T1-42
2
Circuit Breaker Type Code P, GF P, GF P, GFEP P, GFEP P, GFEP B B P P P P B B B B B B, AF B, AF, GF B B B B B B B B B B, GF B, GF B, GF B, GF B, GFEP B, GFEP B, GFEP B, GFEP C C C C C C
Vac 120 120/240 120 120/240 120 120 120/240 120 120/240 120 120/240 120/240 120/240 240 120 120/240 120/240 120/240 120/240 120/240 240 120/240 120/240 240 120/240 120/240 240 120 120/240 120 120/240 120 120/240 120 120/240 120/240 120/240 240 120/240 240 120/240
Vdc 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80
62.5
3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
5000
3
5000
3
5000
3
5000
3
Notes 1 QUICKLAG circuit breakers are suitable for application in relative humidity 095% noncondensing. 2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed. 3 62.5 Vac interrupting rating is 3800 AIC 1050A and 2500 AIC 55100A continuous. Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA. For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
V4-T1-3
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-4 Circuit Breaker Type QCF QCF QCR QCR QCR QCHW QCHW QCHW QHCX QHCX QHCX QHCW QHCW QHCW QCGF QCGF QCHGF QCHGF QCGFEP QCGFEP QCHGFEP QCHGFEP Circuit Breaker Type Code C C C C C C C C C C C C C C C, GF C, GF C, GF C, GF C, GFEP C, GFEP C, GFEP C, GFEP
Vac 120/240 240 120/240 120/240 240 120/240 120/240 240 120/240 120/240 240 120/240 120/240 240 120 120/240 120 120/240 120 120/240 120 120/240
Vdc 24, 48, 62.5 24, 48, 62.5 24, 48, 62.5 24, 48, 62.5 24, 48, 62.5 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80 24, 48, 62.5 24, 48, 80
Page Number V4-T1-27 V4-T1-27 V4-T1-27 V4-T1-27 V4-T1-27 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-22 V4-T1-29 V4-T1-29 V4-T1-29 V4-T1-29 V4-T1-29 V4-T1-29 V4-T1-29 V4-T1-29
5000
3
5000
3
5000
Notes 1 QUICKLAG circuit breakers are suitable for application in relative humidity 095% noncondensing. 2 Two-pole DC interrupting ratings based on two poles connected in series. Not UL listed. 3 62.5 Vac interrupting rating is 3800 AIC 1050A and 2500 AIC 55100A continuous. Circuit Breaker Type Codes: P Plug-In; B Bolt-On; C Cable-In/Cable-Out; GF Ground Fault, 5 mA; GFEP Ground Fault, 30 mA. For Types GHBS, GBHS and BABRP solenoid-operated, remote-controlled circuit breakers, see Pages V4-T1-31 to V4-T1-36.
1.1
Page V4-T1-2 V4-T1-6 V4-T1-7 V4-T1-8 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-40
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . . .
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
All products 15100A are HACR rated Switching duty rated for 120 Vac fluorescent light applications
V4-T1-5
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-6
Product Selection
Notes 1 Switching duty rated for 120 Vac fluorescent light applications. 2 For special low-magnetic breaker, order HQP1015L1 or HQP1020L1. 3 Not UL listed.
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Two-Pole 120/240 Vac Catalog Number QHPX2015 QHPX2020 QHPX2025 QHPX2030 QHPX2035 QHPX2040 QHPX2045 QHPX2050 QHPX2055 QHPX2060 QHPX2070 QHPX2080 QHPX2090 QHPX2100
Three-Pole 240 Vac Catalog Number QHPX3015H QHPX3020H QHPX3025H QHPX3030H QHPX3035H QHPX3040H QHPX3045H QHPX3050H QHPX3055H QHPX3060H QHPX3070H QHPX3080H QHPX3090H QHPX3100H
QHPX1020 1
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 3 Carton Quantity 24 12 8 Approximate Weight Lbs (kg) 9.00 (4.1) 9.00 (4.1) 9.00 (4.1) Dimensions 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1 1 1 1 1 1 1 1 1 1 1 1 1
Note 1 Switching duty rated for 120 Vac fluorescent light applications.
V4-T1-7
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-8
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
V4-T1-9 V4-T1-10 V4-T1-10 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-40
QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF, QPHGF, QPGFEP, QPHGFEP
Product Description
QUICKLAG Ground Fault Circuit Breakers, Class A GFCI 5 mA trip sensitivity QUICKLAG Ground Fault Equipment Protectors 30 mA trip sensitivity
QUICKLAG Ground Fault Circuit Breakers, Class A GFCI Built and tested to UL 943 QUICKLAG Ground Fault Equipment Protectors Built and listed to UL 1053
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Product Selection
Ground Fault Circuit Breakers5 mA Sensitivity QUICKLAG Type: QPGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40C 15 20 25 30 40 50 Single-Pole 120 Vac Catalog Number QPGF1015 QPGF1020 QPGF1025 QPGF1030 QPGF1040 Two-Pole 120/240 Vac Catalog Number QPGF2015 QPGF2020 QPGF2025 QPGF2030 QPGF2040 QPGF2050
Ground Fault Equipment Breakers30 mA Sensitivity QUICKLAG Type: QPGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40C 15 20 25 30 40 50 Single-Pole 120 Vac Catalog Number QPGFEP1015 QPGFEP1020 QPGFEP1025 QPGFEP1030 QPGFEP1040 Two-Pole 120/240 Vac Catalog Number QPGFEP2015 QPGFEP2020 QPGFEP2025 QPGFEP2030 QPGFEP2040 QPGFEP2050
V4-T1-9
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Wiring Diagram
Continuous Ampere Rating at 40C 15 20 25 30 40 50 15 20 25 30
Special Application Ground Fault Circuit Protectors5 mA Sensitivity QUICKLAG Type: QPGF 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Single-Pole 120 Vac Catalog Number QPGF1015W1 QPGF1020W1 QPGF1025W1 QPGF1030W1 QPGF1015W2 QPGF1020W2 QPGF1025W2 QPGF1030W2 Two-Pole 120/240 Vac Catalog Number QPGF2015W1 QPGF2020W1 QPGF2025W1 QPGF2030W1 QPGF2040W1 QPGF2050W1
Special Application Ground Fault Circuit Protectors30 mA Sensitivity QUICKLAG Type: QPGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Continuous Ampere Rating at 40C 15 20 25 30 40 50 15 20 25 30 Single-Pole 120 Vac Catalog Number QPGFEP1015W1 QPGFEP1020W1 QPGFEP1025W1 QPGFEP1030W1 QPGFEP1015W2 QPGFEP1020W2 QPGFEP1025W2 QPGFEP1030W2 Two-Pole 120/240 Vac Catalog Number QPGFEP2015W1 QPGFEP2020W1 QPGFEP2025W1 QPGFEP2030W1 QPGFEP2040W1 QPGFEP2050W1
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac. Bell Alarm (W1)contacts change state when breaker trips. Auxiliary Switch (W2)contacts change state when breaker is opened (or tripped) or closed. 14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 Carton Quantity 24 5 Approximate Weight Lbs (kg) 11.00 (5.0) 5.00 (2.3) Dimensions 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
V4-T1-10
1.1
Page V4-T1-2 V4-T1-5 V4-T1-8 V4-T1-12 V4-T1-13 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-40
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . . .
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
All products 15100A are HACR rated Switching duty rated for 120 Vac fluorescent light applications
V4-T1-11
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-12
Product Selection
Notes 1 Switching duty rated for 120 Vac fluorescent light applications. 2 For special low-magnetic breaker, order BAB1015L1 or BAB1020L1. 3 Not UL listed.
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Two-Pole 120/240 Vac Catalog Number HBAX2015 HBAX2020 HBAX2025 HBAX2030 HBAX2035 HBAX2040 HBAX2045 HBAX2050 HBAX2055 HBAX2060 HBAX2070 HBAX2080 HBAX2080 HBAX2090 HBAX2100
Three-Pole 240 Vac Catalog Number HBAX3015H HBAX3020H HBAX3025H HBAX3030H HBAX3035H HBAX3040H HBAX3045H HBAX3050H HBAX3055H HBAX3060H HBAX3070H HBAX3080H HBAX3080H HBAX3090H HBAX3100H
HBAX1020 1 HBAX1025 HBAX1030 HBAX1035 HBAX1040 HBAX1045 HBAX1050 HBAX1055 HBAX1060 HBAX1070
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 3 Carton Quantity 24 12 8 Approximate Weight Lbs (kg) 9.00 (4.1) 9.00 (4.1) 9.00 (4.1) Dimensions 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1 1 1 1 1 1 1 1 1 1 1
Note 1 Switching duty rated for 120 Vac fluorescent light applications.
V4-T1-13
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-14
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
V4-T1-15 V4-T1-16 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-40
10 and 22 kAIC rating at 120V and 120/240V Single-pole AFCI HID ratings for HID (High Intensity Discharge) lighting All models are HACR rated
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Product Selection
QBCAF and QBAF Type AFCIs Effective immediately, Eaton AFCIs are available for use in Sumter panels with a 22 kAIC rating. This higher rated breaker will allow us to win jobs where AFCIs are specified at higher than 10 kAIC. This breaker provides standard thermalmagnetic protection of branch circuits. This product will have the same form, fit and function of the current bolt-on AFCI (QBCAF and QBAF Type). Product scope is below. These breakers are in Bid Manager for Pow-RLine 1a, Pow-R-Line 1a-LX, Pow-R-Line 3a and Pow-RLine 4a panelboards. For series rated combinations, continue to use the less expensive 10 kAIC QBCAF and QBAF offerings. Breakers can also be ordered from Vista.
QBHCAF
Type QBCAF Combination AFCI Single-pole 10 kAIC 15 20 22 kAIC 15 20 Type QBAF Branch Feeder AFCI Single-pole 10 kAIC 15 20 22 kAIC 15 20 Branch Feeder AFCI Branch Feeder AFCI Branch Feeder AFCI Branch Feeder AFCI QBAF1015 QBAF1020 QBHAF1015 QBHAF1020 Combination AFCI Combination AFCI Combination AFCI Combination AFCI QBCAF1015 QBCAF1020 QBHCAF1015 QBHCAF1020
V4-T1-15
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-16
Wiring Diagrams
Single-Pole 120V Load Application Sourced by 120/240 Vac
120/240 Vac Source N A B Line B
1.1
Page V4-T1-5 V4-T1-8 V4-T1-11 V4-T1-14
Contents
Description
QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . . .
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-18 V4-T1-19 V4-T1-19 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-40
Bolt-On Ground Fault and Equipment Protectors, Types QBGF, QBHGF, QBGFEP, QBHGFEP
Product Description
QUICKLAG Ground Fault Circuit Breakers, Class A GFCI 5 mA trip sensitivity QUICKLAG Ground Fault Equipment Protectors 30 mA trip sensitivity
QUICKLAG Ground Fault Circuit Breakers, Class A GFCI Built and tested to UL 943 QUICKLAG Ground Fault Equipment Protectors Built and tested to UL 1053
V4-T1-17
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-18
Product Selection
Ground Fault Circuit Breakers5 mA Sensitivity QUICKLAG Type: QBGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40C 15 20 25 30 40 50 Single-Pole 120 Vac Catalog Number QBGF1015 QBGF1020 QBGF1025 QBGF1030 QBGF1040 Two-Pole 120/240 Vac Catalog Number QBGF2015 QBGF2020 QBGF2025 QBGF2030 QBGF2040 QBGF2050
Ground Fault Equipment Breakers30 mA Sensitivity QUICKLAG Type: QBGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers
Continuous Ampere Rating at 40C 15 20 25 30 40 50 Single-Pole 120 Vac Catalog Number QBGFEP1015 QBGFEP1020 QBGFEP1025 QBGFEP1030 QBGFEP1040 Two-Pole 120/240 Vac Catalog Number QBGFEP2015 QBGFEP2020 QBGFEP2025 QBGFEP2030 QBGFEP2040 QBGFEP2050
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Special Application Ground Fault Circuit Protectors5 mA Sensitivity QUICKLAG Type: QBGF 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Continuous Ampere Rating at 40C 15 20 25 30 40 50 15 20 25 30 Single-Pole 120 Vac Catalog Number QBGF1015W1 QBGF1020W1 QBGF1025W1 QBGF1030W1 QBGF1015W2 QBGF1020W2 QBGF1025W2 QBGF1030W2 Two-Pole 120/240 Vac Catalog Number QBGF2015W1 QBGF2020W1 QBGF2025W1 QBGF2030W1 QBGF2040W1 QBGF2050W1
Special Application Ground Fault Circuit Protectors30 mA Sensitivity QUICKLAG Type: QBGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2)
Continuous Ampere Rating at 40C 15 20 25 30 40 50 15 20 25 30 Single-Pole 120 Vac Catalog Number QBGFEP1015W1 QBGFEP1020W1 QBGFEP1025W1 QBGFEP1030W1 QBGFEP1015W2 QBGFEP1020W2 QBGFEP1025W2 QBGFEP1030W2 Two-Pole 120/240 Vac Catalog Number QBGFEP2015W1 QBGFEP2020W1 QBGFEP2025W1 QBGFEP2030W1 QBGFEP2040W1 QBGFEP2050W1
Wiring Diagram
Bell Alarm and Auxiliary Contact Schematic
Blue Ground Fault Breaker NC Red NO Red Wire Blue Wire Black Wire
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac. Bell Alarm (W1)contacts change state when breaker trips. Auxiliary Switch (W2)contacts change state when breaker is opened (or tripped) or closed. 14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 Approximate Weight Lbs (kg) 11.00 (5.0) 5.00 (2.3) Dimensions 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
1 1 1 1
V4-T1-19
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-20
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
All products 10100A are HACR rated Switching duty rated for 120 Vac fluorescent light applications only
1.1
1 1
Four-Pole 240 Vac Catalog Number QC4015H QC4020H QC4025H QC4030H QC4035H QC4040H QC4045H QC4050H QC4055H QC4060H QC4070H QC4080H QC4090H QC4100H
Product Selection
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Notes 1 Not UL listed. 2 Switching duty rated for 120 Vac fluorescent light applications only. For special low-magnetic breaker, order QC1015L1 or QC1020L1.Non-automatic switches, see Page V4-T1-42.
V4-T1-21
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-22
Two-Pole 120/240 Vac Catalog Number QHCX2015 QHCX2020 QHCX2025 QHCX2030 QHCX2035 QHCX2040 QHCX2045 QHCX2050 QHCX2055 QHCX2060 QHCX2070 QHCX2080 QHCX2090 QHCX2100
Three-Pole 240 Vac Catalog Number QHCX3015H QHCX3020H QHCX3025H QHCX3030H QHCX3035H QHCX3040H QHCX3045H QHCX3050H QHCX3055H QHCX3060H QHCX3070H QHCX3080H QHCX3090H QHCX3100H
Notes 1 Switching duty rated for 120 Vac fluorescent light applications only. Non-automatic switches, see Page V4-T1-42.
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
QUICKLAG Type QCD Miniature Circuit Breakers Flexible power feed QCD breakers are used primarily in HVAC and connection: industrial applications. wire size, position Single-, two- and Same breaker size for three-pole options entire rating range Modular construction Field mountable accessories: DIN mounted finger shroud proof, quick (symmetrical rail 35 x connect terminals 7 .5 DIN/EN 50 022) Other accessories: QCD same profile as jumper unit Type QCR
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 3 Carton Quantity 24 12 8 Approximate Weight Lbs (kg) 9.00 (4.1) 9.00 (4.1) 9.00 (4.1) Dimensions 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1 1 1 1
V4-T1-23
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-24
Single-Pole
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH Product Selection . . . . . . . . . . . . . . . . . . . . . . . . QCR and QCF Options and Accessories . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
Two-Pole
Single-Pole
Two-Pole
Application Description
QCR and QCF circuit breakers are only 1/2-inch (12.7 mm) wide per pole and are excellent for general purpose industrial applications where space savings is required.
1/2-inch (12.7 mm) wide per pole Cable-in/cable-out Black cases with black handles Three position handle: ON, Tripped (center), OFF Thermal-magnetic protection
Built and listed to UL 489 UL File No. E7819 CSA File No. LR48907 Type QCR and QCF circuit breakers are UL listed circuit breakers that are suitable for use as branch circuit protectors All ratings 1560A are HACR rated
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Product Selection
QCR Breaker 10 kAIC Interrupting Ratings 10 QCR1010 QCR1010T 15 QCR1015 6 QCR1015T 6 20 QCR1020 6 QCR1020T 6 25 QCR1025 QCR1025T 30 QCR1030 QCR1030T 35 QCR1035 40 QCR1040 45 QCR1045 50 QCR1050 55 QCR1055 60 7 QCR1060 QCR2010 QCR2010T QCR2010P QCR2015 QCR2015T QCR2015P QCR2020 QCR2020T QCR2020P QCR2025 QCR2025T QCR2025P QCR2030 QCR2030T QCR2030P QCR2035 QCR2035P QCR2040 QCR2040P QCR2045 QCR2045P QCR2050 QCR2050P QCR2055 QCR2055P QCR2060 QCR2060P QCR2015H QCR2015HT QCR2020H QCR2020HT QCR2025H QCR2025HT QCR2030H QCR2030HT QCR3015H QCR3015HT QCR3020H QCR3020HT QCR3025H QCR3025HT QCR3030H QCR3030HT
QCRH1020 6 QCRH1020T
6
Notes 1 Standard breaker terminals are box type lugs. 2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection (#1032 plus/minus terminal screw provided). 3 Breakers with P Catalog Number Suffix are suitable for terminating two 10 AWG Quick-Connect Type Terminals per phase on breaker load side. 4 Breakers with Shunt Trip (extra pole required on breaker right-hand side) are available on single-, two- and three-pole. Contact the Customer Support Center at 1-800-356-1243. 5 Breakers with H Catalog Suffix have 240 Vac construction. 6 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications. 7 60/75C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
V4-T1-25
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-26 Cable-In/Cable-Out, 1/2-Inch Wide
QCF Breaker 10 kAIC Interrupting Ratings 10 QCF1010 QCF1010T 15 QCF1015 5 QCF1015T 5 20 QCF1020 5 QCF1020T 5 25 QCF1025 QCF1025T 30 QCF1030 QCF1030T 35 40 45 50 55 60 6 QCF1035 QCF1040 QCF1045 QCF1050 QCF1055 QCF1060 QCF2010 QCF2010T QCF2015 QCF2015T QCF2020 QCF2020T QCF2025 QCF2025T QCF2030 QCF2030T QCF2035 QCF2040 QCF2045 QCF2050 QCF2055 QCF2060 QCF2015H QCF2015HT QCF2020H QCF2020HT QCF2025H QCF2025HT QCF2030H QCF2030HT QCF3015H QCF3015HT QCF3020H QCF3020HT QCF3025H QCF3025HT QCF3030H QCF3030HT
Notes 1 Standard breaker terminals are box type lugs. 2 Breakers with T Catalog Number Suffix are suitable for line and load side ring terminal connection (#1032 plus/minus terminal screw provided). 3 Breakers with Shunt Trip Attachment (extra pole required on breaker right-hand side) are available. Contact the Customer Support Center. 4 Breakers with H Catalog Suffix have 240 Vac construction. 5 All 15 and 20A single-pole breakers are SWD (Switching Duty) rated for fluorescent lighting applications. 6 60/75C Cu/Al wire on all ratings except 60A, which requires Cu only conductor.
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
QCRFPL1P
QCRFPLMP
QCR Quick-Connect Terminals Factory-installed two-prong quick-connect terminal on breaker load side suitable for terminating two 10 AWG wire with insulated slip-on terminals as shown. Line side terminal is the standard type. Catalog Suffix P
QCRFLOFF
QCRPLOFF
Single-, two- and three-pole 10 kAIC at 120/240 Vac, 1060A 22 kAIC at 120/240 Vac, 1520A 10 kAIC at 240 Vac, 1030A
3 kAIC at 62.5 Vdc (single-pole) 3 kAIC at 130 Vdc (two poles in series) Normal operating environment: 040C 595% humidity (noncondensing)
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-27
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-28
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF, QCHGF, QCGFEP, QCHGFEP
Product Description
QUICKLAG Ground Fault Circuit Breakers, Class A GFCI 5 mA trip sensitivity QUICKLAG Ground Fault Equipment Protectors 30 mA trip sensitivity
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-29
Product Selection
QUICKLAG Type QCGF Single-Pole Ground Fault Circuit Breaker
Ground Fault Circuit Breakers5 mA Sensitivity QUICKLAG Type: QCGF 10,000A Interrupting Capacity Thermal-Magnetic Breakers 15 20 25 30 40 50 QCGF1015 QCGF1020 QCGF1025 QCGF1030 QCGF1040 QCGF2015 QCGF2020 QCGF2025 QCGF2030 QCGF2040 QCGF2050
QUICKLAG Type: QCHGF 22,000A Interrupting Capacity Thermal-Magnetic Breakers 15 20 25 30 QCHGF1015 QCHGF1020 QCHGF1025 QCHGF1030 QCHGF2015 QCHGF2020 QCHGF2025 QCHGF2030
Ground Fault Equipment Protectors30 mA Sensitivity QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity Thermal-Magnetic Breakers 15 20 25 30 40 50 QCGFEP1015 QCGFEP1020 QCGFEP1025 QCGFEP1030 QCGFEP1040 QCGFEP2015 QCGFEP2020 QCGFEP2025 QCGFEP2030 QCGFEP2040 QCGFEP2050
QUICKLAG Type: QCHGFEP 22,000A Interrupting Capacity Thermal-Magnetic Breakers 15 20 25 30 QCHGFEP1015 QCHGFEP1020 QCHGFEP1025 QCHGFEP1030 QCHGFEP2015 QCHGFEP2020 QCHGFEP2025 QCHGFEP2030
Special Application Ground Fault Circuit Protector5 mA Sensitivity QUICKLAG Type: QCGF 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2) 15 20 25 30 40 50 15 20 25 30 QCGF1015W1 QCGF1020W1 QCGF1025W1 QCGF1030W1 QCGF1015W2 QCGF1020W2 QCGF1025W2 QCGF1030W2 QCGF2015W1 QCGF2020W1 QCGF2025W1 QCGF2030W1 QCGF2040W1 QCGF2050W1
Special Application Ground Fault Equipment Protectors30 mA Sensitivity QUICKLAG Type: QCGFEP 10,000A Interrupting Capacity with Bell Alarm (W1) or Auxiliary Switch (W2) 15 20 25 30 40 50 15 20 25 30 QCGFEP1015W1 QCGFEP1020W1 QCGFEP1025W1 QCGFEP1030W1 QCGFEP1015W2 QCGFEP1020W2 QCGFEP1025W2 QCGFEP1030W2 QCGFEP2015W1 QCGFEP2020W1 QCGFEP2025W1 QCGFEP2030W1 QCGFEP2040W1 QCGFEP2050W1
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-30
Wiring Diagram
Bell Alarm and Auxiliary Contact Schematic
Blue Ground Fault Breaker NC Red NO Red Wire Blue Wire Black Wire
Single-throw double-pole contacts are UL and CSA listed for 5A at 250 Vac. Bell Alarm (W1)contacts change state when breaker trips. Auxiliary Switch (W2)contacts change state when breaker is opened (or tripped) or closed. 14-inch (355.6 mm) long 18 AWG pigtail wire leads provided.
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Number of Poles 1 2 Carton Quantity 20 5 Approximate Weight Lbs (kg) 11.00 (5.0) 5.00 (2.3) Dimensions 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0) 15.50 x 6.00 x 4.50 (393.7 x 152.4 x 114.3)
1.1
Page V4-T1-2 V4-T1-5 V4-T1-8 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications. . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . . .
1 1 1 1 1 1 1 1 1 1 1 1 1 1
Application Description
Eatons BABRP, BABRSP, BRRP and CLRP breakers are remotely operated molded case circuit breakers ideally suited for lighting control applications or energy management applications.
Bolt-on line-side terminal (BABRP , BABRSP Type BA) Plug-on line-side terminal (BRRPType BR, CLRP Type CL) Cable connected load-side terminal Four-position control terminal Bi-metal assembly for thermal overload protection Fast-acting short-circuit protection Arc-chute assembly for fast-acting arc extinction Three-position handle: OFF , TRIP (Center), ON
Handle permits manual switching when control power is lost Mechanical trip indicator 15 and 20A breakers SWD (switching duty) rated HID ratings for HID (high intensity discharge) lighting All models HACR rated Status feedback of control circuit (BABRSP) Series rated (BABRP , BABRSP only) BRRP series rated same as BR breakers BABRP , BABRSP same as BA breakers
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-31
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-32 2 2
Product Selection
This 60-inch (1524.0 mm) wire pigtail provides SLBKRPTL1 a connection from a single BABRPs control plug to a customers pushbutton, relay or PLC. Each box contains 12 pigtails. Wires are 22 AWG, 600V. Order in multiples of 12.
30 2 15 20 25 30
1.1
1 1 1
Line Breaker Contact
Wiring Diagrams
Control Circuit for the BABRP and BABRSP
BABRP Remote Contact Load Breaker Contact RM b RM a Yellow RM b Line Load BABRSP Remote Contact
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
RM a Yellow
BKR a
Black
Blue
Black
Red
On Coil
On Coil
Blue
V4-T1-33
Red
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-34 GHBS and GHQRSP
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP. . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC . . .
Page V4-T1-2 V4-T1-5 V4-T1-8 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31
Solenoid OperatorRemote-Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers
Product Description
Eatons GHBS, GBHS and GHQRSP circuit breakers are bolt-on branch circuit breakers designed for use in 277/480 Vac panelboards. In addition to providing conventional branch circuit protection, they include a unique solenoid-operated mechanism that provides for efficient breaker pulse-on and pulse-off operation when used with a suitable controller like Eatons Pow-R-Command lighting control system.
Bolt-on line-side terminal Cable-connected load-side terminal Status switchremote status and breaker status available from internal auxiliary switches Bi-metal assembly for thermal overload protection Fast-acting short-circuit protection Arc-runner and arc-chute assembly for fast-acting arc extinction Three-position breaker handle: OFF , TRIP (Center), ON
Visual indication of the remotely operated contacts position (open, closed or trip) Remote override handle permits manual switching when control power is lost 15 and 20A breakers SWD (switching duty) rated. 15 and 20A breakers HID rated for HID (High intensity discharge) lighting All models HACR rated Series rated with various Eaton main circuit breakers
1.1
1 1 1
Product Selection
GHBSSingle-Pole
1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Notes 1 Continuous current rating at 40C. 2 All UL listed circuit breakers are HID (high intensity discharge) rated.
V4-T1-35
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-36
Wiring Diagrams
Red wire: remote closing Yellow wire: feedback status from power input, maximum 0.50A draw Typical Single-Pole Circuit Breaker Schematic Diagram for GHBS and GBHS Breakers
Circuit Breaker
Operation Mechanism manually operated by external handle allowing ON, OFF and RESET operation. Handle assumes a center TRIP position after performing protective response. Operating/Application Data Ambient temperature: 040C Frequency: 4862 Hz Humidity: 095% noncondensing
Solenoid
Solenoid
Auxiliary
Yellow
Black
Status
On Coil
Off Coil
Power Input
Dimensions
Approximate Dimensions in Inches (mm) Dimensions per Pole
Circuit Breaker Type GHQRSP Width 1.00 (25.4) Height 2 4.63 (117.6) Length 3 2.81 (71.4)
Notes 1 Purchase separate AMP Inc. conductor plug #640426-3. 2 Excluding line terminal. 3 Excluding handle.
Blue
Red
1.1
Page V4-T1-2 V4-T1-5 V4-T1-8 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-38 V4-T1-39 V4-T1-39 V4-T1-40
International Rated
Contents
Description
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers. . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications. . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Special Application Breakers, Types HQP , BA, QC . . . .
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-37
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-38
Product Selection
BAB
3000A Interrupting Capacity (M3) Bolt-On Thermal-Magnetic Circuit Breakers 10 15 16 20 25 30 32 40 50 60 70 90 100 BAB1010E BAB1015E BAB1020E BAB1025E BAB1030E BAB1040E BAB1050E BAB1060E BAB1070E BAB2010E BAB2015E BAB2020E BAB2025E BAB2030E BAB2040E BAB2050E BAB2060E BAB2070E BAB2090E BAB2100E BAB3010E BAB3015E BAB3020E BAB3025E BAB3030E BAB3040E BAB3050E BAB3060E BAB3070E BAB3090E BAB3100E
6000A Interrupting Capacity (M6) Bolt-On Thermal-Magnetic Circuit Breakers 15 20 25 30 40 50 60 70 90 100 BAB1015HE BAB1020HE BAB1025HE BAB1030HE BAB1040HE BAB1050HE BAB1060HE BAB1070HE BAB2015HE BAB2020HE BAB2025HE BAB2030HE BAB2040HE BAB2050HE BAB2060HE BAB2070HE BAB2090HE BAB2100HE BAB3015HE BAB3020HE BAB3025HE BAB3030HE BAB3040HE BAB3050HE BAB3060HE BAB3070HE BAB3090HE BAB3100HE
3000A Interrupting Capacity (M3) Plug-On Thermal-Magnetic Circuit Breakers 10 15 16 20 25 30 32 40 GFMB110B2 GFMB115B2 GFMB116B2 GFMB120B2 GFMB125B2 GFMB130B2 GFMB132B2 GFMB140B2
Note For other 240/415V applications, please contact the Customer Support Center at 1-800-356-1243.
1.1
1 1 1 1 1 1 1 1 1
International Ground Fault Circuit Breakers BS3871 220/380, 240/415 Vac 3000 AIC
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Miniature Circuit Breaker QUICKLAG Type B Number of Poles 1 2 3 QUICKLAG Ground Fault Type PAll Types B and CAll Types P and BAll 1 1 2 20 20 5 11.00 (5.0) 11.00 (5.0) 5.00 (2.3) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0) 12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7) 12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3) Standard Carton Quantity 24 12 8 Approximate Carton Weight Lbs (kg) 9.00 (4.1) 9.00 (4.1) 9.00 (4.1) Approximate Standard Carton 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0)
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-39
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-40
Contents
Description Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . QUICKLAG Plug-On Types HQP , QPHW, QHPX, QHPW QUICKLAG Plug-On Ground Fault and Equipment Protectors, Types QPGF , QPHGF , QPGFEP , QPHGFEP Bolt-On Types BAB, QBHW, HBAX, HBAW . . . . . . . . Bolt-On Arc Fault Circuit Interrupter Types QBAF , QBCAF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bolt-On Ground Fault and Equipment Protectors, Types QBGF , QBHGF , QBGFEP , QBHGFEP . . . . . . . Cable-In/Cable-Out Types QC, QCD, QCHW, QHCX, QHCW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out, 1/2-Inch Wide, Types QCR, QCF , QCRH, QCFH. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable-In/Cable-Out Ground Fault and Equipment Protectors, Types QCGF , QCHGF , QCGFEP , QCHGFEP Solenoid-Operated, Remote-Controlled Latching Types BABRP , BABRSP , BRRP and CLRP . . . . . . . . . Solenoid OperatorRemote Controlled Latching for Type GHBS, GBHS and GHQRSP Breakers . . . . . . . International Rated Types HQP , BA, QC, GFMB, GFXBC Special Application Breakers, Types HQP , BA, QC Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Factory Modifications and Installed Terminals . . Technical Data and Specifications . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page V4-T1-2 V4-T1-5 V4-T1-8 V4-T1-11 V4-T1-14 V4-T1-17 V4-T1-20 V4-T1-24 V4-T1-28 V4-T1-31 V4-T1-34 V4-T1-37 V4-T1-41 V4-T1-43 V4-T1-46 V4-T1-47 V4-T1-48
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Product Selection
QUICKLAG Type P Switching Neutral
QUICKLAG Type: HQP Switching Neutral Thermal-Magnetic Breakers 10 15 20 25 30 HQP2010B HQP2015B HQP2020B HQP2025B HQP2030B HQP3010B HQP3015B HQP3020B HQP3025B HQP3030B
QUICKLAG Type: BA Switching Neutral Thermal-Magnetic Breakers 10 15 20 25 30 BAB2010C BAB2015C BAB2020C BAB2025C BAB2030C BAB3010C BAB3015C BAB3020C BAB3025C BAB3030C
QUICKLAG Type: QC Switching Neutral Thermal-Magnetic Breakers 10 15 20 25 30 QC2010B QC2015B QC2020B QC2025B QC2030B QC3010B QC3015B QC3020B QC3025B QC3030B
QUICKLAG Type: HQP HID (High Intensity Discharge) Thermal-Magnetic Breakers 15 20 25 30 35 40 50 60 HQP1015D HQP1020D HQP1025D HQP1030D HQP1035D HQP1040D HQP1050D HQP1060D HQP2015D HQP2020D HQP2025D HQP2030D HQP2035D HQP2040D HQP2050D HQP2060D
QUICKLAG Type: BA HID (High Intensity Discharge) Thermal-Magnetic Breakers 15 20 25 30 35 40 50 60 BAB1015D BAB1020D BAB1025D BAB1030D BAB1035D BAB1040D BAB1050D BAB1060D BAB2015D BAB2020D BAB2025D BAB2030D BAB2035D BAB2040D BAB2050D BAB2060D
QUICKLAG Type: QC HID (High Intensity Discharge) Thermal-Magnetic Breakers 15 20 25 30 35 40 50 60 QC1015D QC1020D QC1025D QC1030D QC1035D QC1040D QC1050D QC1060D QC2015D QC2020D QC2025D QC2030D QC2035D QC2040D QC2050D QC2060D
V4-T1-41
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-42
QUICKLAG Type: HQP Non-Automatic Switches 50 60 100 HQP1050N HQP1060N HQP1100N HQP2050N HQP2060N HQP2100N HQP3050N HQP3060N HQP3100N
QUICKLAG Type: BA Non-Automatic Switches 50 60 100 BAB1050N BAB1060N BAB1100N BAB2050N BAB2060N BAB2100N BAB3050N BAB3060N BAB3100N
QUICKLAG Type: QC Non-Automatic Switches 50 60 100 QC1050N QC1060N QC1100N QC2050N QC2060N QC2100N QC3050N QC3060N QC3100N
1.1
1 1 1 1 1 1 1 1 1 1 1 1
Accessories 1
Handle Locks: Non-Padlockable 2
Description QL1NPL QUICKLAG Type P, B, Csingle-pole Order in Multiples of 10 Catalog Number QL1NPL
QL23NPL
10
QL23NPL
1 1 1 1 1
QL123PL
10
QL123PL
1 1 1 1
QC123PL
10
QC123PL
1 1 1 1 1 1 1 1 1
QUICKLAG Type P, Bsingle-, two- and three-pole (off only) QUICKLAG Type Csingle-, two- and three-pole (off only) Notes 1 See Page V4-T1-27 for QCR and QCF accessories. 2 Can lock in ON or OFF position.
10 10
QL123PLOFF QC123PLOFF
V4-T1-43
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-44 QC6BP QCBCLIP QC3FP QC2FP QC1FP QCFCLIP
Mounting Hardware
Description QUICKLAG Type C face mounting clip Order in Multiples of 24 Catalog Number QCFCLIP
10
QC1FP
10
QC2FP
10
QC3FP
QUICKLAG Type C face mounting plate and lock-off (off only)two-pole 1 QUICKLAG Type C face mounting plate and lock-off (off only)three-pole QUICKLAG Type C base mounting clamp
10 10 10
10
QC6BP
1.1
Catalog Number QC6BPS QCDJ2 QCDJ4
1 1 1 1 1
QUICKLAG Type C (QCD) 6-way jumper unit with cover QUICKLAG Type C (QCD) 2-way jumper unit, no cover QUICKLAG Type C (QCD) 4-way jumper unit, no cover QUICKLAG Type C (QCD) 6-way jumper unit, no cover QUICKLAG Type QCD Finger protection attachment QUICKLAG Type QCD 4-prong Quick Connect QCDINADAPT QUICKLAG Type C DIN rail adapter
10 10 10 10 10 10 6
1 1 1 1 1 1
QCDRING
10
QCDRING
1 1 1 1
Dummy Breakers
Description QUICKLAG Type P QUICKLAG Type B QUICKLAG Type C QUICKLAG Type C clear choice breaker Order in Multiples of 1 1 1 4 Catalog Number HQP1000 BAB1000 QC1000 QC30SAMPLE
1 1 1 1 1 1 1 1 1 1
QCRSPACER
Miscellaneous
Description QUICKLAG Type C Spacer Order in Multiples of 1 Catalog Number QCRSPACER
QL1HT
Handle Tie
Description QUICKLAG handle tiesingle-pole Order in Multiples of 100 Catalog Number QL1HT
1 1 1 1 1
V4-T1-45
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-46 Type of Modification
QUICKLAG Types P, B and C QUICKLAG Types P, B and C QUICKLAG Types P, B and C QUICKLAG Types P, B and C QUICKLAG Types P, B, C and ground fault QUICKLAG Types P, B, C QUICKLAG Types P, B, C QUICKLAG Types P, B, C QUICKLAG Types P, B, C
Notes 1 Contact Eaton for factory modifications available for QCR and QCF breakers. 2 Q = 32 Vdc; Q1 = 3240 Vdc; Q2 = 37.5 Vdc; Q3 = 45 Vdc; Q4 = 48 Vdc; Q5 = 50 Vdc; Q6 = 62.5 Vdc; Q7 = 75 Vdc (2P); Q8 = 80 Vdc (2P); Q9 = 125 Vdc (QCR 2P); Q10 = 62.5 Vdc (QCR 1P).
1.1
1
Optional Terminals
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Line N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 6, 7 5, 7 5 N/A N/A 6, 7 5, 7
1 1 1 1 1 1 1 1 1 1 1 1
10
4-Prong Quick Connect Aluminum Box Lug Note 1 Clamp on line side only. Aluminum Box Lug
V4-T1-47
1.1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-48
Dimensions
Approximate Dimensions in Inches (mm) Shipping Data
Miniature Circuit Breaker QUICKLAG Types B, P, Call QUICKLAG Types B, P, Call QUICKLAG Types B, P, Call QUICKLAG ground fault Type Pall Types B and Call Types P and Ball Number of Poles 1 2 3 1 1 2 Standard Carton Quantity 24 12 8 20 20 5 Approximate Carton Weight Lbs (kg) 9.00 (4.1) 9.00 (4.1) 9.00 (4.1) 11.00 (5.0) 11.00 (5.0) 5.00 (2.3) Approximate Standard Carton 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 7.50 x 5.00 (317.5 x 190.5 x 127.0) 12.50 x 6.50 x 5.00 (317.5 x 165.1 x 127.0) 12.50 x 7.00 x 5.50 (317.5 x 177.8 x 139.7) 12.50 x 6.00 x 4.50 (317.5 x 152.4 x 114.3)
1.2
Page V4-T1-50 V4-T1-51 V4-T1-55 V4-T1-57 V4-T1-66
Contents
Description FAZ-NA Circuit Breakers Catalog Number Selection . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 1 1 1 1 1 1 1
1 1 1
Features
Complete range of UL 489 listed DIN rail mounted miniature circuit breakers up to 40A current rating Standard ratings of 10 kAIC up to 277/480 Vac Select amperages available at 14 kAIC up to 277/480 Vac and 10 kAIC up to 125 Vdc per pole Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit Suitable for branch circuit device protection Thermal-magnetic overcurrent protection
SWD (switching duty) suitable for switching fluorescent lighting loads (In 20A) Fulfill UL 489, CSA C22.2 No.5 and also IEC 60947-2 Standard For use in applications for which UL 1077 or CSA C22.2 No.235 are also allowed Field-installable shunt trip and auxiliary switch subsequent mounting Separate version for ringtongue connection (Type FAZ-RT), terminal screws can be removed (on both sides) Module width of only 17 .7 mm (per pole) Contact Position Indicator (red/green) Easy installation on DIN rail Possibility for sealing the toggle in ON or OFF position
1
Device Printing on Front and Side Installation options These branch circuit breakers are available in two terminal configurations: standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to demanding requirements of the semi-conductor industry. All breakers mount on standard 35 mm DIN rail. Bus connectors and feeder terminal facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies. These circuit breakers can also be reverse feed.
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Application Description
Feeder and branch circuit protection for:
Convenience receptacle circuits (internal/external) Motor control circuits Load circuits leaving the equipment (external) HACR internal/external equipment (heating, air conditioning, refrigeration) PLC I/O points Computers Power supplies Control instrumentation Relays UPS Power conditioners
Trip-free designbreaker can not be defeated by holding the handle in the ON position Captive screws cannot be lost
V4-T1-49
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-50 Breaker Family FAZ = FAZ UL circuit breaker
UL 489 Standard for molded case circuit breakers (MCCB) for feeder and branch circuit protection Products meet the requirements of the National Electrical Code (NEC) CSA C22.2 No.5 Standard for molded case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard) Products meet the requirements of the Canadian Electrical Code (CEC)
FAZ C 6 / 1 NA SP
Single Package Trip Characteristics 1 B = 35X In C = 510X In D = 1020X In 0.5 = 1 = 1.5 = 2 = 3 = 4 = 5 = 6 = 7 = 8 = Terminal Ampere Rating 2 0.5A 1A 1.5A 2A 3A 4A 5A 6A 7A 8A 10 = 10A 13 = 13A 15 = 15A 16 = 16A 20 = 20A 25 = 25A 30 = 30A 32 = 32A 35 = 32A 40 = 40A Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole NA = UL 489 branch circuit with screw terminals RT = UL 489 branch circuit with ring tongue terminals DC = UL 489 branch circuit at 125 Vdc per pole SP = Single package for C and D curve single-pole only Blank = Standard packaging
Notes 1 I = Rated current for instantaneous trip characteristics. n 2 B curve starts at 1 ampere.
1.2
1 1 1 1 1 1 1 1
Product Selection
1.13 7200 3600 1200 600 300 120 60 30 10
1
FAZ-NA B Curve UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02) as branch circuit breakers Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2 Current limiting device UL file number E235139
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
2.55 I : N
t [sec]
5 2 1
1
0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
2 3
1 1 1 1 1 1 1 1 1
FAZ-B1/3-RT
I / IN
Single-Pole
Single-Pole
FAZ-RT UL 489 Circuit Breakers with Ring-Tongue Terminals10 kAIC, 14 kAIC B Curve (1525A)
Single-Pole 1 Two-Pole Catalog Amperes Number Catalog Number Three-Pole Catalog Number
FAZ-B1/1-NA
FAZ-B1/2-NA
FAZ-B1/3-NA
FAZ-B1.5/1-NA FAZ-B1.5/2-NA FAZ-B1.5/3-NA FAZ-B2/1-NA FAZ-B3/1-NA FAZ-B4/1-NA FAZ-B5/1-NA FAZ-B6/1-NA FAZ-B7/1-NA FAZ-B8/1-NA FAZ-B2/2-NA FAZ-B3/2-NA FAZ-B4/2-NA FAZ-B5/2-NA FAZ-B6/2-NA FAZ-B7/2-NA FAZ-B8/2-NA FAZ-B2/3-NA FAZ-B3/3-NA FAZ-B4/3-NA FAZ-B5/3-NA FAZ-B6/3-NA FAZ-B7/3-NA FAZ-B8/3-NA Three-Pole Two-Pole
B Curve with Ring-Tongue Terminals (35X In Current Rating) 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 2 40 2 FAZ-B1/1-RT FAZ-B1/2-RT FAZ-B1.5/1-RT FAZ-B1.5/2-RT FAZ-B1.5/3-RT FAZ-B2/1-RT FAZ-B3/1-RT FAZ-B4/1-RT FAZ-B5/1-RT FAZ-B6/1-RT FAZ-B7/1-RT FAZ-B8/1-RT FAZ-B10/1-RT FAZ-B13/1-RT FAZ-B15/1-RT FAZ-B16/1-RT FAZ-B20/1-RT FAZ-B25/1-RT FAZ-B30/1-RT FAZ-B32/1-RT FAZ-B35/1-RT FAZ-B40/1-RT FAZ-B2/2-RT FAZ-B3/2-RT FAZ-B4/2-RT FAZ-B5/2-RT FAZ-B6/2-RT FAZ-B7/2-RT FAZ-B8/2-RT FAZ-B10/2-RT FAZ-B13/2-RT FAZ-B15/2-RT FAZ-B16/2-RT FAZ-B20/2-RT FAZ-B25/2-RT FAZ-B30/2-RT FAZ-B32/2-RT FAZ-B35/2-RT FAZ-B40/2-RT FAZ-B2/3-RT FAZ-B3/3-RT FAZ-B4/3-RT FAZ-B5/3-RT FAZ-B6/3-RT FAZ-B7/3-RT FAZ-B8/3-RT FAZ-B10/3-RT FAZ-B13/3-RT FAZ-B15/3-RT FAZ-B16/3-RT FAZ-B20/3-RT FAZ-B25/3-RT FAZ-B30/3-RT FAZ-B32/3-RT FAZ-B35/3-RT FAZ-B40/3-RT
1 1 1 1 1 1 1 1 1 1 1 1 1
FAZ-B10/1-NA FAZ-B10/2-NA FAZ-B10/3-NA FAZ-B13/1-NA FAZ-B13/2-NA FAZ-B13/3-NA FAZ-B15/1-NA FAZ-B15/2-NA FAZ-B15/3-NA FAZ-B16/1-NA FAZ-B16/2-NA FAZ-B16/3-NA FAZ-B20/1-NA FAZ-B20/2-NA FAZ-B20/3-NA FAZ-B25/1-NA FAZ-B25/2-NA FAZ-B25/3-NA FAZ-B30/1-NA FAZ-B30/2-NA FAZ-B30/3-NA FAZ-B32/1-NA FAZ-B32/2-NA FAZ-B32/3-NA FAZ-B35/1-NA FAZ-B35/2-NA FAZ-B35/3-NA FAZ-B40/1-NA FAZ-B40/2-NA FAZ-B40/3-NA
Notes 1 Two-piece order. Quantities of two per box. 2 240 Vac rated only.
V4-T1-51
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-52 Three-Pole Two-Pole Single-Pole
FAZ-NA C Curve UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02) as branch circuit breakers Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2 Current limiting device UL file number E235139
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
t [sec]
I / IN
Single-Pole
FAZ-RT UL 489 Circuit Breakers with Ring-Tongue Terminals10 kAIC, 14 kAIC C Curve (1525A)
Single-Pole 1 Catalog Amperes Number Two-Pole Catalog Number Three-Pole Catalog Number
C Curve (510X In Current Rating) 0.5 1 1.5 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 2 40 2 FAZ-C0.5/1-NA-SP FAZ-C0.5/2-NA FAZ-C0.5/3-NA FAZ-C1/1-NA-SP FAZ-C1/2-NA FAZ-C1/3-NA Two-Pole
C Curve with Ring-Tongue Terminals (510X In Current Rating) 0.5 1 1.5 2 3 4 5 6 Three-Pole 7 8 10 13 15 16 20 25 30 32 35 2 40 2 FAZ-C0.5/1-RT-SP FAZ-C0.5/2-RT FAZ-C0.5/3-RT FAZ-C1/1-RT-SP FAZ-C1/2-RT FAZ-C1/3-RT
FAZ-C1.5/1-NA-SP FAZ-C1.5/2-NA FAZ-C1.5/3-NA FAZ-C2/1-NA-SP FAZ-C3/1-NA-SP FAZ-C4/1-NA-SP FAZ-C5/1-NA-SP FAZ-C6/1-NA-SP FAZ-C7/1-NA-SP FAZ-C8/1-NA-SP FAZ-C2/2-NA FAZ-C3/2-NA FAZ-C4/2-NA FAZ-C5/2-NA FAZ-C6/2-NA FAZ-C7/2-NA FAZ-C8/2-NA FAZ-C2/3-NA FAZ-C3/3-NA FAZ-C4/3-NA FAZ-C5/3-NA FAZ-C6/3-NA FAZ-C7/3-NA FAZ-C8/3-NA
FAZ-C1.5/1-RT-SP FAZ-C1.5/2-RT FAZ-C1.5/3-RT FAZ-C2/1-RT-SP FAZ-C3/1-RT-SP FAZ-C4/1-RT-SP FAZ-C5/1-RT-SP FAZ-C6/1-RT-SP FAZ-C7/1-RT-SP FAZ-C8/1-RT-SP FAZ-C2/2-RT FAZ-C3/2-RT FAZ-C4/2-RT FAZ-C5/2-RT FAZ-C6/2-RT FAZ-C7/2-RT FAZ-C8/2-RT FAZ-C2/3-RT FAZ-C3/3-RT FAZ-C4/3-RT FAZ-C5/3-RT FAZ-C6/3-RT FAZ-C7/3-RT FAZ-C8/3-RT
FAZ-C10/1-NA-SP FAZ-C10/2-NA FAZ-C10/3-NA FAZ-C13/1-NA-SP FAZ-C13/2-NA FAZ-C13/3-NA FAZ-C15/1-NA-SP FAZ-C15/2-NA FAZ-C15/3-NA FAZ-C16/1-NA-SP FAZ-C16/2-NA FAZ-C16/3-NA FAZ-C20/1-NA-SP FAZ-C20/2-NA FAZ-C20/3-NA FAZ-C25/1-NA-SP FAZ-C25/2-NA FAZ-C25/3-NA FAZ-C30/1-NA-SP FAZ-C30/2-NA FAZ-C30/3-NA FAZ-C32/1-NA-SP FAZ-C32/2-NA FAZ-C32/3-NA FAZ-C35/1-NA-SP FAZ-C35/2-NA FAZ-C35/3-NA FAZ-C40/1-NA-SP FAZ-C40/2-NA FAZ-C40/3-NA
FAZ-C10/1-RT-SP FAZ-C10/2-RT FAZ-C10/3-RT FAZ-C13/1-RT-SP FAZ-C13/2-RT FAZ-C13/3-RT FAZ-C15/1-RT-SP FAZ-C15/2-RT FAZ-C15/3-RT FAZ-C16/1-RT-SP FAZ-C16/2-RT FAZ-C16/3-RT FAZ-C20/1-RT-SP FAZ-C20/2-RT FAZ-C20/3-RT FAZ-C25/1-RT-SP FAZ-C25/2-RT FAZ-C25/3-RT FAZ-C30/1-RT-SP FAZ-C30/2-RT FAZ-C30/3-RT FAZ-C32/1-RT-SP FAZ-C32/2-RT FAZ-C32/3-RT FAZ-C35/1-RT-SP FAZ-C35/2-RT FAZ-C35/3-RT FAZ-C40/1-RT-SP FAZ-C40/2-RT FAZ-C40/3-RT
Notes 1 Option for single packaging on single-pole C and D curves only; add suffix SP when ordering. 2 240 Vac rated only.
1.2
1 1 1 1 1 1
FAZ-NA D Curve UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02) as branch circuit breakers Interrupting capacity: 10 kA UL/CSA; 15 kA IEC 60947-2 Current limiting device UL file number E235139
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
2.55 I : N
t [sec]
5 2 1
1
0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
3 2
1
D
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
I / IN
Single-Pole
Single-Pole
FAZ-RT UL 489 Circuit Breakers with Ring-Tongue Terminals10 kAIC, 14 kAIC D Curve (1320A)
Single-Pole Catalog Amperes Number
1
D Curve (1020X In Current Rating) 0.5 1 Two-Pole 1.5 2 3 4 5 6 7 8 Three-Pole 10 13 15 16 20 25 30 32 35 2 40 2 FAZ-D0.5/1-NA-SP FAZ-D0.5/2-NA FAZ-D0.5/3-NA FAZ-D1/1-NA-SP FAZ-D1/2-NA FAZ-D1/3-NA Two-Pole
D Curve with Ring-Tongue Terminals (1020X In Current Rating) 0.5 1 1.5 2 3 4 5 6 Three-Pole 7 8 10 13 15 16 20 25 30 32 35 2 40 2 FAZ-D0.5/1-RT-SP FAZ-D0.5/2-RT FAZ-D0.5/3-RT FAZ-D1/1-RT-SP FAZ-D1/2-RT FAZ-D1/3-RT
FAZ-D1.5/1-NA-SP FAZ-D1.5/2-NA FAZ-D1.5/3-NA FAZ-D2/1-NA-SP FAZ-D3/1-NA-SP FAZ-D4/1-NA-SP FAZ-D5/1-NA-SP FAZ-D6/1-NA-SP FAZ-D7/1-NA-SP FAZ-D8/1-NA-SP FAZ-D2/2-NA FAZ-D2/3-NA FAZ-D3/2-NA FAZ-D3/3-NA FAZ-D4/2-NA FAZ-D4/3-NA FAZ-D5/2-NA FAZ-D5/3-NA FAZ-D6/2-NA FAZ-D6/3-NA FAZ-D7/2-NA FAZ-D7/3-NA FAZ-D8/2-NA FAZ-D8/3-NA
FAZ-D1.5/1-RT-SP FAZ-D1.5/2-RT FAZ-D1.5/3-RT FAZ-D2/1-RT-SP FAZ-D3/1-RT-SP FAZ-D4/1-RT-SP FAZ-D5/1-RT-SP FAZ-D6/1-RT-SP FAZ-D7/1-RT-SP FAZ-D8/1-RT-SP FAZ-D2/2-RT FAZ-D3/2-RT FAZ-D4/2-RT FAZ-D5/2-RT FAZ-D6/2-RT FAZ-D7/2-RT FAZ-D8/2-RT FAZ-D2/3-RT FAZ-D3/3-RT FAZ-D4/3-RT FAZ-D5/3-RT FAZ-D6/3-RT FAZ-D7/3-RT FAZ-D8/3-RT
FAZ-D10/1-NA-SP FAZ-D10/2-NA FAZ-D10/3-NA FAZ-D13/1-NA-SP FAZ-D13/2-NA FAZ-D13/3-NA FAZ-D15/1-NA-SP FAZ-D15/2-NA FAZ-D15/3-NA FAZ-D16/1-NA-SP FAZ-D16/2-NA FAZ-D16/3-NA FAZ-D20/1-NA-SP FAZ-D20/2-NA FAZ-D20/3-NA FAZ-D25/1-NA-SP FAZ-D25/2-NA FAZ-D25/3-NA FAZ-D30/1-NA-SP FAZ-D30/2-NA FAZ-D30/3-NA FAZ-D32/1-NA-SP FAZ-D32/2-NA FAZ-D32/3-NA FAZ-D35/1-NA-SP FAZ-D35/2-NA FAZ-D35/3-NA FAZ-D40/1-NA-SP FAZ-D40/2-NA FAZ-D40/3-NA
FAZ-D10/1-RT-SP FAZ-D10/2-RT FAZ-D10/3-RT FAZ-D13/1-RT-SP FAZ-D13/2-RT FAZ-D13/3-RT FAZ-D15/1-RT-SP FAZ-D15/2-RT FAZ-D15/3-RT FAZ-D16/1-RT-SP FAZ-D16/2-RT FAZ-D16/3-RT FAZ-D20/1-RT-SP FAZ-D20/2-RT FAZ-D20/3-RT FAZ-D25/1-RT-SP FAZ-D25/2-RT FAZ-D25/3-RT FAZ-D30/1-RT-SP FAZ-D30/2-RT FAZ-D30/3-RT FAZ-D32/1-RT-SP FAZ-D32/2-RT FAZ-D32/3-RT FAZ-D35/1-RT-SP FAZ-D35/2-RT FAZ-D35/3-RT FAZ-D40/1-RT-SP FAZ-C40/2-RT FAZ-D40/3-RT
Notes 1 Option for single packaging on single-pole C and D curves only; add suffix SP when ordering. 2 240 Vac rated only.
V4-T1-53
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-54 Two-Pole Single-Pole
FAZ-NA-DC C Curve
UL approved (UL 489) and CSA Certified (CSA C22.2 No.5-02) as Branch Circuit Breakers Interrupting capacity: 10 kA at 125 Vdc UL/CSA, 10 kA at 250 Vdc 125 Vdc for one-pole, 250 Vdc for two-pole in series Current limiting device Polarity (+/) sensitive and not for use on photovoltaic string application UL file number E235139
C Curve (510X In Current Rating) 2 3 4 5 6 7 8 10 13 15 16 20 25 30 32 35 40 FAZ-C2/1-NA-DC-SP FAZ-C3/1-NA-DC-SP FAZ-C4/1-NA-DC-SP FAZ-C5/1-NA-DC-SP FAZ-C6/1-NA-DC-SP FAZ-C7/1-NA-DC-SP FAZ-C8/1-NA-DC-SP FAZ-C10/1-NA-DC-SP FAZ-C13/1-NA-DC-SP FAZ-C15/1-NA-DC-SP FAZ-C16/1-NA-DC-SP FAZ-C20/1-NA-DC-SP FAZ-C25/1-NA-DC-SP FAZ-C30/1-NA-DC-SP FAZ-C32/1-NA-DC-SP FAZ-C35/1-NA-DC-SP FAZ-C40/1-NA-DC-SP FAZ-C2/2-NA-DC FAZ-C3/2-NA-DC FAZ-C4/2-NA-DC FAZ-C5/2-NA-DC FAZ-C6/2-NA-DC FAZ-C7/2-NA-DC FAZ-C8/2-NA-DC FAZ-C10/2-NA-DC FAZ-C13/2-NA-DC FAZ-C15/2-NA-DC FAZ-C16/2-NA-DC FAZ-C20/2-NA-DC FAZ-C25/2-NA-DC FAZ-C30/2-NA-DC FAZ-C32/2-NA-DC FAZ-C35/2-NA-DC FAZ-C40/2-NA-DC
Note 1 Option for single packaging on single-pole C curves only; add suffix SP when ordering.
1.2
1 1 1 1 1 1 1 1 1 1 1
Accessories
Busbartwo-pole, 18 terminals 2345 Busbarthree-pole, 6 terminals 2345 Auxiliary Contact Auxiliary contact Z-IHK-NA Busbar Shroud
Busbarthree-pole, 12 terminals 2345 Z-SV/UL-16/3P-3TE/12 Busbarthree-pole, 18 terminals 2345 Z-SV/UL-16/3P-3TE/18 Three-pole busbar shroud ZV-BS-UL
Extension Terminal Shunt Trip Shunt trip 110415 Vac Shunt trip 12110 Vac FAZ-XAA-NA110-415VAC FAZ-XAA-NA12-110VAC
Z-EK/35/UL
1 1 1 1
Padlock Hasp
Padlock hasp
1 1 1
Notes 1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed. 2 Do not cut commoning link. 3 A maximum of three commoning links may be used in conjunction. Each breaker connected to the commoning link must have the same number of poles for proper use. 4 Not for use with ring-tongue circuit breakers. 5 Bus may be center fed for high current capacity.
1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-55
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-56
Tripping Signal Switch Z-NHK, Z-IHK-NA Design according to IEC/EN 60947-5-1, IEC/EN 62019 Field installable The specified minimum voltages are per contacttake into account particularly in case of series connection Self-cleaning contacts Contact material and design particularly suitable for extra low voltage Z-NHK: the function of one of the two change-over contacts can be switched from auxiliary switch to tripping signal switch Tripping signal contact transmits message of electric tripping, not mechanical switch-off Test key for contact function electrical tripping Z-IHK-NA: will allow for > 480Y/277 Vac rating
Connection Diagram
Z-NHK 4.14/4.12 4.12/4.14 4.11 21 13 Z-IHK-NA
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-57
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-58 Connection Diagrams
Single-Pole
Two-Pole
Rated voltage FAZ-NA-DC UL/CSA Rated frequency Characteristic Endurance Line voltage connection Mechanical Frame size Device height
45 mm 105 mm 17.7 mm per pole Finger and hand touch safe according to BGV A3, OVE-EN 6 Quick fastening with two lock-in positions on IEC/EN 60715 Open mouth/lift terminals One wire: AWG 186 Two wires: AWG 1810 AWG 1821: 21 lb-in AWG 108: 25 lb-in AWG 6: 36 lb-in Independent of position 40C 30C
Three-Pole
Device width Terminal protection Mounting Upper and lower terminals Terminal capacity Terminal fastening torque
1.2
1
Three-Pole P [W] 4.8 2.3 3.1 3.1 3.6 4.3 4.4 3.5 4.3 3.7 4.5 6.1 4.6 5.2 5.5 7.7 8.1 9.3 11.3 11.6
Power Loss at ln
Characteristic B Single-Pole In [A] 0.5 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0 13.0 15.0 16.0 20.0 25.0 30.0 32.0 35.0 40.0 P [W] Two-Pole P [W] Three-Pole P [W] Characteristic C Single-Pole P [W] 1.6 1.1 1.3 1.4 1.2 1.4 1.9 1.2 1.4 1.4 1.8 2.4 1.9 2.1 2.9 3.1 3.0 3.4 3.7 4.0 Two-Pole P [W] 3.2 2.2 2.6 2.8 2.4 2.9 3.7 2.3 2.8 2.8 3.6 4.7 3.8 4.3 5.8 6.2 6.0 6.8 7.4 8.1 Three-Pole P [W] 4.7 3.4 3.9 4.3 3.6 4.3 5.6 3.5 4.3 4.2 5.3 7.1 5.6 6.4 8.7 9.3 9.0 10.2 11.0 12.1 Characteristic D Single-Pole P [W] 1.6 0.8 1.0 1.0 1.2 1.4 1.5 1.2 1.4 1.2 1.5 2.0 1.5 1.7 1.8 2.6 2.7 3.1 3.8 3.9 Two-Pole P [W] 3.2 1.5 2.1 2.1 2.4 2.9 2.9 2.3 2.8 2.4 3.0 4.1 3.1 3.5 3.7 5.1 5.4 6.2 7.6 7.8
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1.1 2.2 1.4 2.1 1.4 1.8 1.7 2.0 2.0 1.8 2.4 1.9 2.1 2.9 3.1
3.0 3.4 4.0 4.0
2.2 4.4 2.8 4.2 2.9 3.7 3.5 4.0 3.9 3.6 4.7 3.8 4.3 5.8 6.2
6.0 6.8 8.1 8.1
3.4 6.6 4.3 6.4 4.3 5.5 5.2 6.0 5.9 5.3 7.1 5.6 6.4 8.7 9.3
9.0 10.2 12.1 12.1
V4-T1-59
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-60
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-61
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Load Factor KT [I/IN]
Device Market Current Rating In (A) at 40C 0.5 1.0 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10.0 13.0 15.0 16.0 20.0 25.0 30.0 32.0 40.0 15C 0.6 1.1 1.7 2.2 3.3 4.4 5.5 6.6 7.7 8.8 11.0 14.3 16.5 17.6 22.0 27.5 33.0 35.2 44.0
1 1 1 1 1 1 1 1 1 1 1 1 1 1
0.90
0.80
0.70 1 2 3 4 5 6 7 8
V4-T1-62
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Z-NHK
Z-IHK-NA
Utilization category AC13 Rated operational current Ie Utilization category AC15 Rated operational current Ie Utilization category DC12 Rated operational current Ie Rated insulation voltage UI Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50) Conditional short-circuit current Ik with backup fuse 6A Max. backup fuse, overload and short circuit Mechanical Tripping indicator electrical tripping Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws
Blue/white 45 mm 80 mm 8.8 mm (0.5MU) Onto switching device IP40 Finger and hand touch safe According to BGV A3, VE-EN 6 Lift terminals 2014 AWG M3 (Posidrive Z0) 7 lb-in
45 mm 80 mm 8.8 mm (0.5MU) IP40 Finger and hand touch safe According to BGV A3, VE-EN 6 Lift terminals 0.52.5 mm2 M3 (Posidrive Z0) Max. 1.2 Nm
V4-T1-63
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-64
Single-Pole Busbar
Two-Pole Busbar
2
Shunt trip release FAZ-XAA-NA Remote release for subsequent mounting onto FAZ-NA/RT Additional installation of standard auxiliary switch is possible Position indicator redgreen
Connection Diagram
1
Degree of protection, built-in IP40 Terminal protection Terminals Terminal capacity One and two wires
Finger and hand touch safe according to BGV A3, VE-EN 6 Open mouthed/lift 1810 AWG Open mouthed/lift 1810 AWG
Busbar block UL 489 (pin) Tested according to UL 489 Do not cut Extension terminal 35 mm2 Z-EK/35/UL for copper conductors Incoming terminal 50 mm2 Z-EB/50/UL For covering of not used pins, use busbar tag shrouds ZV-BS-UL
Connection Diagrams
Three-Pole Busbar
1.2
1 1 1 1 1 1
External Receptacle
UL 489 Breaker
UL 1077
1 1 1 1
Electronics
UL 489 Branch
External Motor M
1 1 1 1 1 1 1 1 1
HACR
UL 1077
1 1 1 1 1 1 1 1 1 1 1
UL 489 circuit breakers Used for branch circuit protection, internal/external receptacles, external motors and HACR equipment (heating, air conditioning and refrigeration). UL 1077 supplementary protectors Used for overcurrent protection within appliances or electrical equipment, where branch circuit protection is already provided or not required.
Note: UL 489 devices can be used in place of UL 1077; UL 1077 devices cannot be used in place of UL 489.
V4-T1-65
1.2
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-66
4.13 (105.0)
Dimensions
Approximate Dimensions in Inches (mm) Miniature Circuit Breakers
Single-Pole Two-Pole Three-Pole
Lockout AttachmentIS/SPE-ITE
4.13 (105.0)
4.13 (105.0)
.70 (17.7)
Accessories
Z-SV/UL-16/6 Z-SV/UL-18...12 ZV-BS-UL
Z-SV/UL-16.../18
Z-EK/35/UL
Z-EK/35/UL
Description Ue f Uimp Ie UL 489 480 Vac/96 Vdc 50/60 Hz 80A at 40C #214 AWG 60/75C Cu 0.56 in IEC/EN 60947-2 240/415 Vac 50/60 Hz 9.5 kV 80A at 30C 2.535 mm2 Cu 14 mm
Z-EB/50/UL
Description Ue f Uimp Ie UL 489 480 Vac/96 Vdc 50/60 Hz 115A at 40C #114 AWG 60/75C Cu 0.56 in IEC/EN 60947-2 240/415 Vac 50/60 Hz 9.5 kV 160A at 30C 1.550 mm2 Cu 14 mm
1.3
Page V4-T1-67 V4-T1-68 V4-T1-68 V4-T1-69 V4-T1-75 V4-T1-78 V4-T1-85
Contents
Description FAZ Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . . . . . Standards and Certifications. . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications. . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 1 1 1 1 1 1 1 1 1
1
Features
Complete range of UL 1077 recognized DIN rail mounted miniature circuit breakers up to 63A current rating Standard ratings of 10 kAIC up to 277/480 Vac Current limiting design provides fast short-circuit interruption that reduces the let-through energy, which can damage the circuit Suitable for supplementary protection Thermal-magnetic overcurrent protection
Trip-free designbreaker can not be defeated by holding the handle in the ON position Captive screws cannot be lost Fulfill UL 1077 , CSA C22.2 No.235 and also IEC 60947-2 Standard Field-installable shunt trip and auxiliary switch subsequent mounting Module width of only 17 .7 mm (per pole) Contact position indicator (red/green) Easy installation on DIN rail Possibility for sealing the toggle in ON or OFF position
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Application Description
V4-T1-67
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-68 Breaker Family FAZ = Supplementary protector Breakers install on standard DIN rail
Trip-free design; breaker cannot be defeated by holding the handle in the ON position
Breaker information printed on the front of the device for quick identification
UL 1077 , CSA C22.2 No. 235 Apply to supplementary protectors intended for use as overcurrent, or overvoltage or undervoltage protection within an appliance or other electrical equipment where branch circuit protection is already provided, or is not required
RoHS compliant VDE compliant Devices with B, C, and D curves are VDE compliant CCC Devices with B, C, and D curves are CCC compliant ABS compliant
FAZ C 6 / 1 SP
Single Package Trip Characteristics 1 B = 35X In C = 510X In D = 1020X In K = 812X In S = 1317X In Z = 23X In 0.5 = 1 = 2 = 3 = 4 = 5 = 6 = 7 = 8 = 10 = SP Ampere Rating 0.5A 1A 2A 3A 4A 5A 6A 7A 8A 10A 13 = 13A 15 = 15A 16 = 16A 20 = 20A 25 = 25A 30 = 30A 32 = 32A 40 = 40A 50 = 50A 63 = 63A Number of Poles 1 = Single-pole 2 = Two-pole 3 = Three-pole 4 = Single-pole 1N = Single-pole + neutral 3N = Three-pole + neutral = Single packaging of singlepole curve B, C and D for select amperes only Blank = Standard packaging
1.3
1 1 1 1 1 1 1 1
Product Selection
FAZ B curve (35X In current rating) Designed for resistive or slightly inductive loads Response time of instantaneous trip: 35X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) UL file number 177451 Suitable for applications where protection against low-level short-circuit faults in control wiring is desired. Instantaneous trip is 35X continuous rating of device (In). Applications include PLC wiring, business equipment, lighting, appliances and some motors. Low magnetic trip point.
1.13 7200 3600 1200 600 300 120 60 30 10
1
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
2.55 I : N
t [sec]
5 2 1
1
0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
2 3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Single-Pole + Neutral Catalog Number FAZ-B1/1N FAZ-B2/1N FAZ-B3/1N FAZ-B4/1N FAZ-B5/1N FAZ-B6/1N FAZ-B7/1N FAZ-B8/1N FAZ-B10/1N FAZ-B12/1N FAZ-B13/1N FAZ-B15/1N FAZ-B16/1N FAZ-B20/1N FAZ-B25/1N FAZ-B30/1N FAZ-B32/1N FAZ-B40/1N FAZ-B50/1N FAZ-B63/1N Three-Pole + Neutral Catalog Number FAZ-B1/3N FAZ-B2/3N FAZ-B3/3N FAZ-B4/3N FAZ-B5/3N FAZ-B6/3N FAZ-B7/3N FAZ-B8/3N FAZ-B10/3N FAZ-B12/3N FAZ-B13/3N FAZ-B15/3N FAZ-B16/3N FAZ-B20/3N FAZ-B25/3N FAZ-B30/3N FAZ-B32/3N FAZ-B40/3N FAZ-B50/3N FAZ-B63/3N
I / IN
Single-Pole
B Curve (35X In Current Rating) Designed for Resistive or Slightly Inductive Loads 1
Single-Pole 2 Catalog Amperes Number 1 2 3 FAZ-B1/1-SP FAZ-B2/1-SP FAZ-B3/1-SP FAZ-B4/1-SP FAZ-B5/1-SP FAZ-B6/1-SP FAZ-B7/1-SP FAZ-B8/1-SP FAZ-B10/1-SP FAZ-B12/1-SP FAZ-B13/1-SP FAZ-B15/1-SP FAZ-B16/1-SP FAZ-B20/1-SP FAZ-B25/1-SP FAZ-B30/1-SP FAZ-B32/1-SP FAZ-B40/1-SP FAZ-B50/1-SP FAZ-B63/1-SP Two-Pole Catalog Number FAZ-B1/2 FAZ-B2/2 FAZ-B3/2 FAZ-B4/2 FAZ-B5/2 FAZ-B6/2 FAZ-B7/2 FAZ-B8/2 FAZ-B10/2 FAZ-B12/2 FAZ-B13/2 FAZ-B15/2 FAZ-B16/2 FAZ-B20/2 FAZ-B25/2 FAZ-B30/2 FAZ-B32/2 FAZ-B40/2 FAZ-B50/2 FAZ-B63/2 Three-Pole Catalog Number FAZ-B1/3 FAZ-B2/3 FAZ-B3/3 FAZ-B4/3 FAZ-B5/3 FAZ-B6/3 FAZ-B7/3 FAZ-B8/3 FAZ-B10/3 FAZ-B12/3 FAZ-B13/3 FAZ-B15/3 FAZ-B16/3 FAZ-B20/3 FAZ-B25/3 FAZ-B30/3 FAZ-B32/3 FAZ-B40/3 FAZ-B50/3 FAZ-B63/3
Four-Pole
B Curve (35X In Current Rating) Designed for Resistive or Slightly Inductive Loads, continued 1
Four-Pole Catalog Amperes Number 1 2 FAZ-B1/4 FAZ-B2/4 FAZ-B3/4 FAZ-B4/4 FAZ-B5/4 FAZ-B6/4 FAZ-B7/4 FAZ-B8/4 FAZ-B10/4 FAZ-B12/4 FAZ-B13/4 FAZ-B15/4 FAZ-B16/4 FAZ-B20/4 FAZ-B25/4 FAZ-B30/4 FAZ-B32/4 FAZ-B40/4 FAZ-B50/4 FAZ-B63/4
Two-Pole
4 5 6 7 8 10 12
Single-Pole + Neutral
3 4 5 6 7 8 10 12
Three-Pole
13 15 16 20 25 30 32 40 50 63
Three-Pole + Neutral
13 15 16 20 25 30 32 40 50 63
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering. Volume 4Circuit Protection CA08100005EAugust 2013 www.eaton.com V4-T1-69
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-70 Three-Pole Two-Pole Single-Pole
FAZ C curve (510X In current rating) Designed for inductive loads Response time of instantaneous trip: 510X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) UL file number 177451 Suitable for applications where medium levels of inrush current are expected. Instantaneous trip is 510X rating of device (In). Applications include small transformers, lighting, pilot devices, control circuits and coils. Medium magnetic trip point.
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
t [sec]
I / IN
Four-Pole
Single-Pole + Neutral
2 3 4 5 6 7 8
Three-Pole + Neutral
10 13 15 16 20 25 30 32 40 50 63
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering. Volume 4Circuit Protection CA08100005EAugust 2013 www.eaton.com
1.3
1 1 1 1 1 1
FAZ D curve (1020X In current rating) Designed for highly inductive loads Response time of instantaneous trip: 1020X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) UL file number 177451 Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 1020X rating of device (In). The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies.
1.45
Specified non-tripping current INT = 1.13 x IN for t > 1 h Specified tripping current IT = 1.45 x IN for t < 1 h
2.55 I : N
t [sec]
5 2 1
1
0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 4 5 6 7 8 9 10 15 20 30 40 50
3 2
1
D
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
I / IN
Single-Pole
Four-Pole
FAZ-D0.5/1-SP FAZ-D0.5/2 FAZ-D1/1-SP FAZ-D2/1-SP FAZ-D3/1-SP FAZ-D4/1-SP FAZ-D5/1-SP FAZ-D6/1-SP FAZ-D7/1-SP FAZ-D8/1-SP FAZ-D10/1-SP FAZ-D13/1-SP FAZ-D15/1-SP FAZ-D16/1-SP FAZ-D20/1-SP FAZ-D25/1-SP FAZ-D30/1-SP FAZ-D32/1-SP FAZ-D40/1-SP FAZ-D50/1-SP FAZ-D63/1-SP FAZ-D1/2 FAZ-D2/2 FAZ-D3/2 FAZ-D4/2 FAZ-D5/2 FAZ-D6/2 FAZ-D7/2 FAZ-D8/2 FAZ-D10/2 FAZ-D13/2 FAZ-D15/2 FAZ-D16/2 FAZ-D20/2 FAZ-D25/2 FAZ-D30/2 FAZ-D32/2 FAZ-D40/2 FAZ-D50/2 FAZ-D63/2
Two-Pole
3 4 5 6 7 8 10 13
Single-Pole + Neutral
3 4 5 6 7 8 10
Three-Pole
15 16 20 25 30 32 40 50 3 63 3
Three-Pole + Neutral
13 15 16 20 25 30 32 40 50 c 63 c
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 Option for single packaging on single-pole B, C and D curves only; add suffix SP when ordering. 3 IEC 60947-2 only.
V4-T1-71
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-72 Three-Pole Two-Pole Single-Pole
FAZ K curve (812X In current rating) Designed for motors, transformers and upstream electronics Response time of instantaneous trip: 812X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) UL file number 177451 Suitable for applications where medium levels of inrush current are expected. Instantaneous trip is 812X rating of device (In). Applications include small transformers, lighting, pilot devices, control circuits and coils. Medium magnetic trip point.
t (sec)
7200 3600 1200 600 300 120 60 30 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3
1.13 1.45
Specified non-tripping current Int = 1.05 u In for t > 1 h Specified tripping current It = 1.30 u In for t < 1 h
4 5 6 7 8 9 10 15 20 U-rated Current
30 40 50
Four-Pole
Single-Pole + Neutral
2 3 4 6 8 10 13
Three-Pole + Neutral
16 20 25 32 40 50 63
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 These breakers are available by special order and may result in additional delivery time. 3 Two-piece box order, quantities of 2.
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
FAZ S curve (1317X In current rating) Designed for control circuits with high inrush Response time of instantaneous trip: 1317X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) UL file number 177451 Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 1317X rating of device (In). The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies.
7200 3600 1200 600 300 120 60 30 10 5 t (sec) 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3
1.05 1.30
Specified non-tripping current Int = 1.05 u In for t > 1 h Specified tripping current It = 1.30 u In for t < 1 h
4 5 6 7 8 9 10 15 20 U-rated Current
30 40 50
Single-Pole
Two-Pole
4 6 10 16 20 25 32 40
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 These breakers are available by special order and may result in additional delivery time. 3 Two-piece box order, quantities of 2.
V4-T1-73
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-74 Two-Pole Single-Pole
FAZ Z curve (23X In current rating) Designed for protection of electronic devices Response time of instantaneous trip: 23X In current rating UL recognized and CSA Certified as supplementary protectors For international and domestic use (conform to IEC 60947-2) Suitable for applications where low levels of inrush current are expected. Instantaneous trip is 23X rating of device (In). Applications include small transformers, lighting, pilot devices, control circuits and coils. Medium magnetic trip point.
t (sec)
7200 3600 1200 600 300 120 60 30 10 5 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 Z
1.05 1.30
Specified non-tripping current Int = 1.05 u In for t > 1 h Specified tripping current It = 1.30 u In for t < 1 h
4 5 6 7 8 9 10 15 20 U-rated Current
30 40 50
Three-Pole
Four-Pole
2 3 4 6 8 10 13 16 20 25 32 40 50 63
Notes 1 In North America, these switches are UL recognized and CSA Certified as supplementary protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required. 2 These breakers are available by special order and may result in additional delivery time. 3 Two-piece box order, quantities of 2.
1.3
1
Catalog Number
Accessories
FAZ Auxiliary Contacts and Voltage Trips
Circuit Diagram Standard Auxiliary Contacts
Description
1 1 1 1 1
1NO/1NC Installs on left side of FAZ or shunt trip Max. one per FAZ (1077) device Switches when FAZ is tripped electrically or manually
230 Vac
FAZ-XHIN11
12
14
1 changeover contact Installs on left side of FAZ or shunt trip Max. one per FAZ (1077) device Switches when FAZ is tripped electrically or manually
230 Vac
FAZ-XHINW1
1 1 1 1 1 1 1 1 1 1
11
Auxiliary/Trip Indicating Contact
Small selector screw changes mode Two Form C (changeover) contacts Installs on left side of FAZ or shunt trip Auxiliary contacts switch when FAZ is tripped electrically or manually Trip indicating contact switches only when FAZ is tripped electrically
230 Vac
FAZ-XAM002
D1
1 1 1 1 1
voltage is present
Installs on left side of FAZ Includes test button
U
D2
Shunt Trip
C1 C2
FAZ-XAA-C-12-110VAC FAZ-XAA-C-110415VAC
1 1 1 1 1
1
FAZ FAZ
AUX
AUX TRIP
FAZ
AUX
AUX TRIP
1 1 1
V4-T1-75
or
Circuit Breaker
or
Shunt Trip Circuit Breaker UnderV Trip Circuit Breaker
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-76
FAZ FAZ WMZS WMZS WMZS
Busbar System
Description Without Auxiliary Contacts For connecting FAZ supplementary protectors without auxiliary contacts. May be fed from line or load side. 80A 1 57 BB-UL-18/1P-1M/57 Rated Operational Current Number of Poles per Device Number of Terminals Catalog Number 1
56
BB-UL-18/2P-2M/56
57
BB-UL-18/3P-3M/57
100A
57
BB-UL-25/1P-1M/57
56
BB-UL-25/2P-2M/56
57
BB-UL-25/3P-3M/57
Auxiliary/Trip Indicating Contacts For connecting FAZ supplementary protectors with auxiliary contacts. May be fed from line or load side. 80A 1 37 BB-UL-18/1P-1,5M/37
46
BB-UL-18/2P+AS-2,5M/46
48
BB-UL-18/3P+AS-3,5M/48
100A
37
BB-UL-25/1P-1,5M/37
46
BB-UL-25/2P+AS-2,5M/46
48
BB-UL-25/3P+AS-3,5M/48
1.3
Catalog Number BB-UL-TE/50
Incoming Terminal
Incoming Terminal
1 1 1 1 1
Catalog Number BB-UL-EC/3 BB-UL-EC/1
from 635 mm2/#102 AWG 45.5 Nm/3550 lb-in Two- and three-pole
50 mm2 #141 AWG 75 Deg wire 115 A/Y, 480V UL 160 A/Y 690V IEC
Poles 2 and 3 1
1 1 1 1 1
Protective Accessories
Description For covering unused terminals
Prevents reactivation of the device
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
during maintenance
Holds one padlock
Padlock Hasp
V4-T1-77
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-78
7200 3600 1200 600 300 120 60 30 10 5 t (sec) 2 1 0.5 0.2 0.1 0.05 0.02 0.01 0.005 0.002 0.001 0.0005 1 2 3 Z
1.13
Time-current characteristic acc. to UL 1077 Conventional 2.55 I : N non-tripping current t = 160 s (IN < 32A) t = 1120 s (IN < 32A) Int = 1.13 IN: t > 1 h
Conventional tripping
Type B: 3 I : t > 0.1 s N Type B: 5 I : t < 0.1 s N Type C: 5 I : t > 0.1 s N Type C: 10 I : t < 0.1 s N Type D: 10 I : t > 0.1 s N Type D: 20 I : t < 0.1 s N
4 5 6 7 8 9 10 15 20 I/In
30 40 50
1.3
1 1 1
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-79
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-80 Description Electrical Approvals Standards Short-circuit trip response
UR (UL 1077), CSA (CSA 22.2 No. 235), CE IEC/EN 60947-2, E177451, 204453 812 In 0.563A 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 1.35 x In @ 40C 1.45 x In @ 40C 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac 1317 In 0.540A 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 1.35 x In @ 40C 1.45 x In @ 40C 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac 23 In 163A 277 Vac 48 Vdc 480Y/277 Vac 96 Vdc 1.35 x In @ 40C 1.45 x In @ 40C 5 kA @ 277 Vac 5 kA @ 277 Vac 5 kA @ 480Y/277 Vac
Supplementary ProtectorsUL/CSA Current range Maximum voltage ratingsUL/CSA Single-pole, single-pole + neutral Two-, three-, four-pole and three-pole + neutral Two poles in series Thermal tripping characteristics Single-pole Multi-pole Short-circuit ratings (at max. voltage) Single-pole Single-pole + neutral Two-, three-, four-pole Two poles in series Miniature Circuit BreakerIEC Current range Maximum voltage ratingsIEC 60947-2 Single-pole, single-pole + neutral Two-, three-, four-pole, three-pole + neutral Thermal tripping characteristics Single-pole Multi-pole Interrupt ratings (at max. voltage) IEC 60947-2 Operational switching capacity Max. backup fuse [gL/gG] Rated impulse withstandUimp Rated insulation voltageUi Environmental/General Selectivity class Lifespan (operations) Shock (IEC 68-2-22) Operating temperature range Shipment and short-term storage Housing material Mechanical Standard front dimension Device height Terminal protection Mounting width per pole Mounting Degree of protection Terminals top and bottom Supply connection Terminal capacity [mm2] Torque Imperial torque Thickness of busbar material Mounting position 80 mm Finger and back-of-hand proof to IEC 536 17.7 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 (AWG 418) / 2 x 10 (AWG 818) 2.4 Nm 21 lb-in (AWG 1812), 25 lb-in (AWG 108), 36 lb-in (AWG 64) 0.82 mm As required 80 mm Finger and back-of-hand proof to IEC 536 17.7 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 (AWG 418) / 2 x 10 (AWG 818) 2.4 Nm 21 lb-in (AWG 1812), 25 lb-in (AWG 108), 36 lb-in (AWG 64) 0.82 mm As required 80 mm Finger and back-of-hand proof to IEC 536 17.7 mm IEC/EN 60715 top-hat rail IP20 Twin-purpose terminals Line or load side 1 x 25 (AWG 418) / 2 x 10 (AWG 818) 2.4 Nm 21 lb-in (AWG 1812), 25 lb-in (AWG 108), 36 lb-in (AWG 64) 0.82 mm As required 3 > 10,000 (1 operation = ON/OFF) 10g120 ms 40 to +167F (40 to +75C) 40 to +185F (40 to +85C) Nylon 3 > 10,000 (1 operation = ON/OFF) 10g120 ms 40 to +167F (40 to +75C) 40 to +185F (40 to +85C) Nylon 3 > 10,000 (1 operation = ON/OFF) 10g120 ms 40 to +167F (40 to +75C) 40 to +185F (40 to +85C) Nylon 0.563A 240 Vac 240/415 Vac > 1 Hour @ 1.05 x In < 1 Hour @ 1.3 x In 15 kA 7.5 kA 125A 4000 Vac 440 Vac 0.540A 240 Vac 240/415 Vac > 1 Hour @ 1.05 x In < 1 Hour @ 1.3 x In 10 kA 7.5 kA 125A 4000 Vac 440 Vac 163A 240 Vac 240/415 Vac > 1 Hour @ 1.05 x In < 1 Hour @ 1.3 x In 10 kA 7.5 kA 125A 4000 Vac 440 Vac
1.3
1 1
63 A 50 A 40 A 32 A 25 A 16 A20 A 13 A 10 A 6A 4A 3A
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
6A 4A 3A
2 2A 1.5
1A 0.5 A 0.5 A 5
0.5
1.5
5 6 7 8 910
15
Characteristic D
i2dt 10 [A2s] 8
6 4
5
Characteristic D
40 A 32 A 25 A 20 A 16 A 13 A 10 A 6A
lD 104 9 [A] 8
7 6 5 4 3
40 A 32 A 25 A 20 A 16 A 13 A 10 A 6A
1 1 1 1 1 1 1 1 1
1 1 1
0.5
1 1.5 2 3 4 5 6 7 8 910 15
0.5
1.5
5 6 7 8 910
15
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-82
0.5
1
Characteristic S
lD [A]
104
40 A 32 A 25 A 20 A 16 A 10 A
4 6A 4A 3A 2A
2A 1.6 A
1.5 1A
2 1A 1.5
10
5 0.5 A
103
0.5
1.5
7 8 9 10
0.5
1.5
7 8 9 10
Characteristic Z
lD [A]
104 8
63 A 50 A 40 A 32 A 25 A 20 A 16 A 10 A 8A
6A
4A 3A
1.5 2A 103
5 1.6 A 1A 0.5 A
1.5
7 8 9 10
1.3
1
65C 0.14 0.22 0.43 0.65 0.87 1.30 1.40 1.70 2.20 2.60 3.00 3.50 4.30 5.20 6.10 6.90 8.70 10.00 11.00 13.00 14.00 17.00 22.00 28.00 30.00 35.00 43.00 55.00 70C 0.14 0.21 0.42 0.64 0.85 1.30 1.40 1.70 2.10 2.50 3.00 3.40 4.20 5.10 6.00 6.80 8.50 10.00 11.00 13.00 14.00 17.00 21.00 27.00 29.00 34.00 42.00 53.00 75C 0.13 0.21 0.41 0.62 0.83 1.20 1.30 1.70 2.10 2.50 2.90 3.30 4.10 5.00 5.80 6.60 8.30 10.00 11.00 12.00 13.00 17.00 21.00 26.00 29.00 33.00 41.00 52.00
Influence of the Ambient Temperature on the Thermal Tripping Behavior Corrected values of the rated current dependent on the ambient temperature
Ambient Temperature T In (A) 0.16 0.25 0.50 0.75 1.00 1.50 1.60 2.00 2.50 3.00 3.50 4.00 5.00 6.00 7.00 8.00 10.00 12.00 13.00 15.00 16.00 20.00 25.00 32.00 35.00 40.00 50.00 63.00 40C 0.20 0.32 0.64 0.96 1.30 1.90 2.00 2.60 3.20 3.80 4.50 5.10 6.40 7.70 9.00 10.20 13.00 15.00 17.00 19.00 20.00 26.00 32.00 41.00 45.00 51.00 64.00 81.00 30C 0.20 0.31 0.62 0.93 1.20 1.90 2.00 2.50 3.10 3.70 4.40 5.00 6.20 7.50 8.70 9.90 12.00 15.00 16.00 19.00 20.00 25.00 31.00 40.00 43.00 50.00 62.00 78.00 20C 0.19 0.30 0.60 0.90 1.20 1.80 1.90 2.40 3.00 3.60 4.20 4.80 6.00 7.20 8.40 9.60 12.00 14.00 16.00 18.00 19.00 24.00 30.00 38.00 41.00 48.00 60.00 76.00 10C 0.19 0.29 0.58 0.87 1.20 1.70 1.90 2.30 2.90 3.50 4.10 4.70 5.80 7.00 8.20 9.30 12.00 14.00 15.00 17.00 19.00 23.00 29.00 37.00 41.00 47.00 58.00 73.00 0C 0.18 0.28 0.56 0.84 1.10 1.70 1.80 2.20 2.80 3.40 3.90 4.50 5.60 6.70 7.80 9.00 11.00 13.00 15.00 17.00 18.00 22.00 28.00 36.00 38.00 45.00 56.00 71.00 10C 0.17 0.27 0.54 0.81 1.10 1.60 1.70 2.20 2.70 3.30 3.80 4.30 5.40 6.50 7.60 8.70 11.00 13.00 14.00 16.00 17.00 22.00 27.00 35.00 38.00 43.00 54.00 68.00 20C 0.17 0.26 0.52 0.78 1.00 1.60 1.70 2.10 2.60 3.10 3.70 4.20 5.20 6.30 7.40 8.40 10.00 13.00 14.00 16.00 17.00 21.00 26.00 33.00 36.00 42.00 52.00 66.00 30C 0.16 0.25 0.50 0.75 1.00 1.50 1.60 2.00 2.50 3.00 3.50 4.00 5.00 6.00 7.00 8.00 10.00 12.00 13.00 15.00 16.00 20.00 25.00 32.00 35.00 40.00 50.00 63.00 35C 0.16 0.25 0.49 0.74 0.99 1.50 1.60 2.00 2.50 3.00 3.40 3.90 4.90 5.90 6.90 7.90 9.90 12.00 13.00 15.00 16.00 20.00 25.00 32.00 35.00 39.00 49.00 62.00 40C 0.15 0.24 0.48 0.73 0.97 1.50 1.50 1.90 2.40 2.90 3.40 3.90 4.80 5.80 6.80 7.70 9.70 12.00 13.00 15.00 15.00 19.00 24.00 31.00 34.00 39.00 48.00 61.00 45C 0.15 0.24 0.47 0.71 0.95 1.40 1.50 1.90 2.40 2.80 3.30 3.80 4.70 5.70 6.70 7.60 9.50 11.00 12.00 14.00 15.00 19.00 24.00 30.00 33.00 38.00 47.00 60.00 50C 0.15 0.23 0.46 0.69 0.93 1.40 1.50 1.90 2.30 2.80 3.20 3.70 4.60 5.60 6.50 7.40 9.30 11.00 12.00 14.00 15.00 19.00 23.00 30.00 32.00 37.00 46.00 58.00 55C 0.14 0.23 0.45 0.68 0.90 1.40 1.40 1.80 2.30 2.70 3.20 3.60 4.50 5.40 6.30 7.20 9.00 11.00 12.00 14.00 14.00 18.00 23.00 29.00 32.00 36.00 45.00 57.00 60C 0.14 0.22 0.44 0.66 0.89 1.30 1.40 1.80 2.20 2.70 3.10 3.50 4.40 5.30 6.20 7.10 8.90 11.00 12.00 13.00 14.00 18.00 22.00 28.00 32.00 35.00 44.00 56.00
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Influence of the Mains Frequency Influence of the mains frequency on the tripping behavior IMA of the instantaneous release
Mains Frequency f [Hz] 16 2/3 IMA(f)IMA (50 Hz) [%] 91 50 100 60 101 100 106 200 115 300 134 400 141
0.90
0.80
0.70 1 2 3 4 5 6 7 8
1 1
V4-T1-83
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-84 Description Electrical Contact function Rated operational voltage Un
Voltage range Voltage range Closing threshold [x Un] Tripping threshold [x Un] Rated frequency General use (UL/CSA) AC230/240 Vac DC110/120 Vdc Pilot duty Conventional free air thermal current Ith Rated operational current AC-13 Ie AC-15 Ie DC-13 Ie Rated insulation voltage Ui Minimum operating voltage per contract Umin Rated impulse withstand voltage (1.2/50) Uimp Rated conditional short-circuit current with 6A backup fuse ISC Max. admissible backup fuse Mechanical Standard front dimension Device height Mounting width Mounting Degree of protection enclosed
50/60 Hz 2/2A 0.5/0.5A A600/Q600 4A 3A (250 Vac) 2A (250 Vac) 0.5A (110 Vdc) 250 Vac 5 Vdc 2.5 kV 1 kA 4A gL
45 mm 80 mm 17.6 mm IEC/EN 60715 top-hat rail IP40 Protection against electric shock to IEC 536 Twin-purpose terminals 12.5 mm2 12.5 mm2 2.4 Nm (21 lb-in)
45 mm 80 mm 17.8 mm IEC/EN 60715 top-hat rail IP40 Protection against electric shock to IEC 536 Twin-purpose terminals 2 x (12.5) mm2 2 x (12.5) mm2 0.8 Nm (7 lb-in)
Terminal protection Terminals Terminal capacity Solid Flexible Tightening torque of terminal screws
Protection against electric shock to IEC 536 Lift terminals 0.52.5 mm2 0.52.5 mm2 0.81.0 Nm (79 lb-in)
1.3
1 1 1
Dimensions
Approximate Dimensions in Inches (mm) Miniature Circuit Breakers FAZ
0.74 (9.4)
1 1 1 1 1 1 1 1 1 1
3.15 (80.0)
1.77 (45.0)
0.70 (17.8)
1.40 (35.4)
2.09 (53.1)
2.79 (70.8)
0.22 (5.5)
3.15 (80.0)
1.77 (45.0)
3.15 (80.0)
1.77 (45.0)
1 1 1 1
0.35 (8.8)
0.22 (5.5)
1.73 (44.0)
2.36 (60.0)
0.35 (8.8)
0.22 (5.5)
1.73 (44.0)
2.36 (60.0)
1 1 1 1 1 1 1 1
3.15 (80.0)
1.77 (45.0)
3.15 (80.0)
1.77 (45.0)
0.22 (5.5)
0.70 (17.8)
0.22 (5.5)
1.73 (44.0)
2.36 (60.0)
1 1 1 1 1
V4-T1-85
1.3
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-86
L1 L2 L1
L2
L1
L2
L1
L2
L1
L2
L1
L2
1.4
Page V4-T1-88 V4-T1-89 V4-T1-90 V4-T1-91 V4-T1-93
Contents
Description UL 1053 DIN Rail RCCB 480/277 Vac Product Selection . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . UL 1053 DIN Rail RCCB 208Y/120 Vac. . . . . . . . . . . . .
1 1 1 1 1 1 1 1 1 1
1
Standards and Certifications
Features
Application Description
Motor control circuits HVAC internal/external equipment PLCs HMIs Equipment protection European housing
Wide range of compact RCCB types serving as fault-current and additional protection according to UL 1053 and IEC/EN 61008 standards, suitable for worldwide use Type A or Type G/A (with delay) protection available Comprehensive range of accessories Real contact position indicator Fault current tripping indicator Transparent designation plate Trip-free designRCCB can not be defeated by holding the handle in the ON position Captive screws cannot be lost
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-87
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-88 Four-Pole Four-Pole
Product Selection
UL 1053 RCCB 480Y/277V Type A
Two-Pole
Surge CurrentProof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (VE E 8601)
Two-Pole Amperes 25 GF Sensitivity (mA) 30 300 40 30 300 63 30 300 Catalog Number 1 167119 167122 167120 167123 167121 167124 Designation FRCmM-25/2/003-G/A-NA FRCmM-25/2/03-G/A-NA FRCmM-40/2/003-G/A-NA FRCmM-40/2/03-G/A-NA FRCmM-63/2/003-G/A-NA FRCmM-63/2/03-G/A-NA
Surge CurrentProof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (VE E 8601)
Four-Pole Amperes 25 GF Sensitivity (mA) 30 300 40 30 300 63 30 300 Catalog Number 1 167107 167110 167108 167111 167109 167112 Designation FRCmM-25/4/003-G/A-NA FRCmM-25/4/03-G/A-NA FRCmM-40/4/003-G/A-NA FRCmM-40/4/03-G/A-NA FRCmM-63/4/003-G/A-NA FRCmM-63/4/03-G/A-NA
Note 1 Has no thermal element; must be paired with FAZ-NA or FAZ per application.
1.4
1
Catalog Number IS/SPE-1TE
Accessories
UL 1053 DIN Rail RCCB 480/277 Vac
Description Contact Two-pole contact or auxiliary contact / trip indicating contact Catalog Number Z-NHK 1 Padlock Hasp Description Padlock hasp
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Note 1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
V4-T1-89
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity
V4-T1-90
1.4
1
FourPole 63 59 55 50 45 63A FourPole 40 37 34 31 27 TwoPole 63 59 55 50 45
Connection Diagram
1 N
T T
40A TwoPole 40 37 33 30 26
1 1 1 1 1 1 1 1 1 1 1 1
2 N
Two-Pole
2 4 6 N
Four-Pole
Please make sure that these values are not exceeded and that any upstream overload protection switches off in time.
Correct Connection
Three-phase load without N (184254 Vac Phase-Phase) IEC (184277 Vac Phase-Phase) UL
Three-phase load without N (400 Vac Phase-Phase) IEC (480 Vac Phase-Phase) UL
1 1 1 1 1 1 1 1
Dimensions
Approximate Dimensions in Inches (mm) UL 1053 DIN Rail RCCB
0.22 (5.5) 0.18 (4.5)
1.20 (30.5)
3.15 (80.0)
1.77 (45.0)
1 1 1 1 1 1 1 1 1
2.76 (70.0)
0.41 (10.5)
Four-Pole
V4-T1-91
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-92 Description Electrical Contact function Rated voltage Frequency Rated current Rated thermal current Ith Utilization category AC13 Rated operational current Ie Utilization category AC15 Rated operational current Ie Utilization category DC12 Rated operational current Ie Rated insulation voltage UI
2CO 230V 50/60 Hz 2A 2A 3A/250 Vac 2A/250 Vac 0.5A/110 Vdc 250 Vac 5 Vdc 10 mA DC 2.5 kV 1 kA 6A gL Blue/white 45 mm 80 mm 8.8 mm (0.5MU) Onto switching device IP40 Finger and hand touch safe According to BGV A3, VE-EN 6 Lift terminals 2014 AWG M3 (Posidrive Z0) 7 lb-in maximum
Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50) Conditional short-circuit current Ik with backup fuse 6A Maximum backup fuse, overload and short circuit Mechanical Tripping indicator electrical tripping Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws
1.4
Page V4-T1-87 V4-T1-94 V4-T1-95 V4-T1-96 V4-T1-97
Contents
Description UL 1053 DIN Rail RCCB 480/277 Vac . . . . . . . . . . UL 1053 DIN Rail RCCB 208Y/120 Vac Product Selection . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data and Specifications . . . . . . . . . . . . Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 1 1 1 1 1 1 1 1 1
1
Standards and Certifications
Features
Application Description
Motor control circuits HVAC internal/external equipment PLCs HMIs Equipment protection
Wide range of compact RCD type serving as faultcurrent and additional protection according to UL 1053 and IEC/EN 61008 standards, suitable for worldwide use in the 110V range of applications Type A or Type G/A (with delay) protection available Comprehensive range of accessories Real contact position indicator Fault current tripping indicator Transparent designation plate Trip-free designRCCB can not be defeated by holding the handle in the ON position Captive screws cannot be lost
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-93
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-94 Four-Pole
Product Selection
UL 1053 RCCB 208Y/120 Vac Type A
Four-Pole
UL 1053 RCCB 208Y/120 Vac Type G/A Type G/A has a 10 ms delay.
Two-Pole
Surge CurrentProof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (VE E 8601)
Two-Pole Amperes 25 GF Sensitivity (mA) 30 300 40 30 300 63 30 300 Catalog Number 1 167693 167696 167694 167697 167695 167698 Designation FRCmM-25/2/003-G/A-NA-110 FRCmM-25/2/03-G/A-NA-110 FRCmM-40/2/003-G/A-NA-110 FRCmM-40/2/03-G/A-NA-110 FRCmM-63/2/003-G/A-NA-110 FRCmM-63/2/03-G/A-NA-110
Surge CurrentProof 3 kA, Sensitive to Residual Pulsating DC, Type G/A (VE E 8601)
Four-Pole Amperes 25 GF Sensitivity (mA) 30 300 40 30 300 63 30 300 Catalog Number 1 167705 167708 167706 167709 167707 167710 Designation FRCmM-25/4/003-G/A-NA-110 FRCmM-25/4/03-G/A-NA-110 FRCmM-40/4/003-G/A-NA-110 FRCmM-40/4/03-G/A-NA-110 FRCmM-63/4/003-G/A-NA-110 FRCmM-63/4/03-G/A-NA-110
Note 1 Has no thermal element; must be paired with FAZ-NA or FAZ per application.
1.4
1
Catalog Number IS/SPE-1TE
Accessories
UL 1053 DIN Rail RCCB 208Y/120 Vac
Description Contact Two-pole contact or auxiliary contact / trip indicating contact Catalog Number Z-NHK 1 Padlock Hasp Description Padlock hasp
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Note 1 Voltage of FAZ-NA circuit breaker is limited to 300V with this auxiliary contact installed.
V4-T1-95
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Degree of protection, built-in Degree of protection in moisture-proof enclosure Upper and lower terminals Terminal protection Terminal capacity
V4-T1-96
1.4
1
FourPole 63 59 55 50 45 63A FourPole 40 37 34 31 27 TwoPole 63 59 55 50 45
Connection Diagram
1 N
T T
40A TwoPole 40 37 33 30 26
1 1 1 1 1 1 1 1 1 1 1 1
2 N
Two-Pole
2 4 6 N
Four-Pole
Please make sure that these values are not exceeded and that any upstream overload protection switches off in time.
Correct Connection
Three-phase load without N (184254 Vac Phase-Phase) IEC (184277 Vac Phase-Phase) UL
Three-phase load without N (400 Vac Phase-Phase) IEC (480 Vac Phase-Phase) UL
1 1 1 1 1 1 1 1
Dimensions
Approximate Dimensions in Inches (mm) UL 1053 DIN Rail RCCB
0.22 (5.5) 0.18 (4.5)
1.20 (30.5)
3.15 (80.0)
1.77 (45.0)
1 1 1 1 1 1 1 1 1
2.76 (70.0)
0.41 (10.5)
Four-Pole
V4-T1-97
1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V4-T1-98 Description Electrical Contact function Rated voltage Frequency Rated current Rated thermal current Ith Utilization category AC13 Rated operational current Ie Utilization category AC15 Rated operational current Ie Utilization category DC12 Rated operational current Ie Rated insulation voltage UI
2CO 230V 50/60 Hz 2A 2A 3A/250 Vac 2A/250 Vac 0.5A/110 Vdc 250 Vac 5 Vdc 10 mA DC 2.5 kV 1 kA 6A gL Blue/white 45 mm 80 mm 8.8 mm (0.5MU) Onto switching device IP40 Finger and hand touch safe According to BGV A3, VE-EN 6 Lift terminals 2014 AWG M3 (Posidrive Z0) 7 lb-in maximum
1NO + 1NC 250V 50/60 Hz 6A 6A 3A/250 Vac 2A/250 Vac 0.5A/110 Vdc 0.25A/220 Vdc 250 Vac 5 Vdc 10 mA AC/DC 4 kV 1 kA 45 mm 80 mm 8.8 mm (0.5MU) IP40 Finger and hand touch safe According to BGV A3, VE-EN 6 Lift terminals 0.52.5 mm2 M3 (Posidrive Z0) 1.2 Nm
Minimum operational voltage per contact Umin Minimum operational current Imin Rated peak withstand voltage Uimp (1.2/50) Conditional short-circuit current Ik with backup fuse 6A Maximum backup fuse, overload and short circuit Mechanical Tripping indicator electrical tripping Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws