Foam Application Method.............................................................................. F2-F4 FootPrint Methodology............................................................................... F5-F6 Minimum Firewater Requirements for Foam Application Full Surface Protection......................................................................................... F7 Minimum Firewater Requirements for Foam Application 1% Foam Concentrate. ........................................................................................... F8 Minimum Firewater Requirements for Foam Application 3% Foam Concentrate....................................................................................... F9 Big Foot Trailer Mount 4,000 - 14,000 GPM. ........................................ F10-F12 Battler 2 x 10 Monitor / Nozzle.........................................................................F13 Ambassador 1 x 6 Monitor/Nozzle....................................................................F14 Ranger3 ..............................................................................................................F15 Hired Gun Trailer - 2000 GPM. ...........................................................................F16 Hired Gun Layout. .................................................................................................F17 Patriot Ranger3/ Quick Action Deck Gun, 1000-3000 GPM. ..................F18 Gear Operated 6 Monitor..................................................................................F19 Patriot 1- Worm Gear Deck Gun, 1000 GPM.............................................. F20 1.5 HC Ranger 250-1500 Deck Gun................................................................ F21

PRODUCTS 409-745-3232

F1
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


Foam Application Method: High Volume Foam Application

(Design Reference NFPA 11) General High Volume Foam Monitors (fixed or transportable) are effective tools for protecting storage tanks containing flammable or combustible liquids. Foam monitors can be considered as the primary means of fire suppression for full service foam application onto open floating roof storage tanks, or onto fixed roof tanks of up to 60 ft. in diameter. For fixed roof storage tanks greater than 60 ft. diameter, foam monitors can be considered as a viable backup system, to be used in the event that the primary foam fire protection system is rendered inoperable or unavailable.

Cone Roof Tank

Covered Floating Roof Tank

Open Floating Roof Tank

Minimum Foam Application Rates Stated minimum foam application rates are based on the assumption that all foam reaches the interior of the tank, or landing zone. Also, these minimum rates are for tanks 180 ft. in diameter or less. For tanks greater than 180 ft. diameter, consult with your Williams Fire & Hazard Control, Inc representative for current data regarding recommendations for minimum ThunderStorm foam application rates on specific fuels.

PRODUCTS 409-745-3232

F2
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


High Volume Foam Monitors

Design Considerations

Minimum Application Densities


To use the chart, first look up the liquids flash point and its water solubility. Determine their point of intersection and zone on the chart. Then refer to the data below to determine the minimum application density. Examples of common flammable liquids are listed in each category. Flash point and solubility data on additional flammable liquids can be found in the NFPA Hazardous Materials Handbook and in other similar sources.

Type of Fuel Hydrocarbons - Category A Combustible Liquids (flash point <100 F) Flammable Liquids (flash point >100 F) Crude Petroleum Gasohol Water Miscibles - Category B,C,D (Alcohols) Category B Category C Category D

Foam

Minimum Application Density, gpm/ft2

F-601A ATC @ 1% F-601A ATC @ 1% F-601A ATC @ 1% F-601A ATC @ 1%

0.16 0.16 0.16 0.16

F-601A ATC @ 3% F-601A ATC @ 3% F-601A ATC @ 3%

.13 *.13 *.13

* ContactWilliams Fire & Hazard Control, Inc for recommendations regarding application densities for specific fuels Telephone 409-727-2347

PRODUCTS 409-745-3232

F3
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


High Volume Foam Monitors

Design Considerations Determining Water/Foam Requirments


Calculating the area of a circle: r2 = ft2 FT2 x *Application Rate = GPM Water/Foam Solution GPM Water/Foam Sol. x % Concentrate = GPM Foam Concentrate. GPM Foam Concentrate x Recommended Duration (NFPA 11) = Total Gallons of Concentrate required on scene *Application Rate per Square Foot NFPA 11 recommends a minimum 0.16 gpm/ft2 application rate for Type III. Although 0.16 is a minimum much of the industry uses it as a standard. Williams Fire & Hazard Control recognizes as the tank diameter increases, increasing the application rate must be considered.
Williams Recommended Type III Application Rates For Hydrocarbon Storage Tanks

0 151 201 251 300

150 200 250 300

0.16 0.18 0.20 0.22 0.25

GPM/Ft2 GPM/Ft2 GPM/Ft2 GPM/Ft2 GPM/Ft2

Example calculation for a 150 Storage tank:

75 x 75 x 3.14 = 17,662.5 ft2 17,662.5 x .16 = 2,826 gallons per minute required flow (2,826 GPM would practically be rounded up to 3,000 GPM) 3,000 GPM x .01% concentrate = 30.0 gallons concentrate per minute 30.0 Gal/concentrate for 65 minutes = 1,950 total gallons concentrate required (minimum) Add 100% for reserve inventory (if required)

Minimum Foam Application Durations


Combustible Liquids (flash point < 100 F) Flammable Liquids (flash point > 100 F) Crude Oils Alcohols = = = = 50 65 65 65 minutes minutes minutes minutes

Minimum Foam Concentrate Inventories


Calculation for minimum foam inventory is (where D = Tank Diameter): Minimum Foam Inventory = (D x D) x 0.785 x (Min Application Density) x (% Proportioning) x (Application Duration)
Example calculation for an 80 Diameter Tank in Crude Oil Service:

(80 x 80) x 0.785 x 0.16 x .03 x 65 Add for 100% Reserve Inventory (if required) Total Minimum Foam Inventory

1568 gallons + 1568 gallons 3136 gallons

PRODUCTS 409-745-3232

F4
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


FootPrint Methodology

For US and Foreign Patent and Trademark information, please refer to page PI2

PRODUCTS 409-745-3232

F5
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


FootPrint Methodology

US Patents

For use of FootPrint methodology, please contact Williams Fire & Hazard Control, Inc

For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F6
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


Minimum Firewater Requirements for Foam Application Full Surface Protection

Tank Minimum Firewater Flow Rates (gpm)* Diam (Feet) ApplicationDensities***

Minimum Firewater Capacities Required for 65 Minute Application (gallons)** Application Densities***

50 60 70 80 90 100 110 120 130 140

.16 315 453 616 804 1018 1256 1520 1809 2123 2462

.18 354 509 693 905 1145 1413 1710 2035 2389 2770 3180 3618 4084 4579 5101 5652

.20 393 566 770 1005 1272 1570 1900 2261 2654 3078 3533 4020 4538 5089 5668 6280 6924 7599 8306 9044 9813 10614 11446 12309 13204 14130

.22 432 622 847 1106 1399 1727 2090 2487 2919 3385 3886 4422 4992 5596 6235 6908 7617 8359 9136 9948 10794 11675 12590 13540 14525 15543

.25 491 707 962 1256 1590 1963 2375 2826 3317 3847

.16 20475 29445 40040 52260 66170 81640 98800 117585 137995 160030

.18 23010 33085 45045 58825 74425 91845 111150 132275 155285 180050 206700 235170 265460 297635 331565 367380

.20 25545 36790 50050 65325 82680 102050 123500 146965 172510 200070 229645 261300 294970 330785 368420 408200 450060 493935 539890 587860 637845 689910 743990 800085 858260 918450

.22 28080 40430 55055 71890 90935 112255 135850 161655 189735 220025 252590 287430 324480 363740 405275 449020 495105 543335 593840 646620 701610 758875 818350 880100 944125 1010295

.25 31915 45955 62530 81640 103350 127595 154375 183690 215605 250055 287040 326560 368680 413335 460525 510250 562575 617435 674765 734760 797290 862355 929955 1000090 1072825 1148095

150 160 170 180 190 200

4416 5024 5672 6359 7085 7850

210 220 230 240 250 260 270 280 290 300

8655 9499 10381 11304 12266 13267 14307 15386 16505 17663

PRODUCTS 409-745-3232

F7
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


Minimum Requirements for 1% Foam Concentrate Full Surface Protection Using High Volume Monitors*

Tank Diam (Feet)

50 Minutes (Flash Point > 100 F) ApplicationDensities **

65 Minutes (Flash Point < 100 F) Application Densities **

50 60 70 80 90 100 110 120 130 140

.16 160 230 310 405 510 630 760 905 1065 1235

.18 180 255 350 455 575 710 855 1020 1195 1385 1590 1810 2045 2290 2555 2830

.20 200 285 385 505 640 785 950 1135 1330 1540 1770 2010 2270 2545 2835 3140 3465 3800 4155 4525 4910 5310 5725 6155 6605 7065

.22 220 315 425 555 700 865 1045 1245 1460 1695 1945 2215 2500 2800 3120 3455 3810 4180 4570 4975 5400 5840 6295 6770 7265 7775

.25 250 355 485 630 795 985 1190 1415 1660 1925

.16 205 295 405 525 665 820 990 1180 1380 1605

.18 235 335 455 590 745 920 1115 1325 1555 1805 2070 2355 2655 2980 3320 3675

.20 260 370 505 655 830 1025 1235 1470 1730 2005 2300 2615 2950 3310 3685 4082 4505 4940 5400 5880 6380 6900 7440 8055 8585 9185

.22 285 405 555 720 910 1125 1360 1620 1900 2205 2530 2875 3245 3610 4055 4495 4955 5435 5940 6470 7020 7590 8185 8805 9445 10105

.25 320 460 630 820 1035 1280 1545 1840 2160 2505 2875 3270 3690 4135 4610 5105 5630 6175 6750 7350 7975 8625 9300 10005 10760 11485

150 160 170 180 190 200

2210 2515 2840 3180 3545 3925

210 220 230 240 250 260 270 280 290 300

4330 4750 5195 5655 6135 6635 7155 7695 8255 8835

Formula: (Tank Diameter)2 x 0.785 x Application Density x 0.01 x Duration (in minutes) Based on NFPA 11, Hydrocarbon Fuels *Does not include post extinguishment suppression **Application Densities indicated as gpm/ft2

PRODUCTS 409-745-3232

F8
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Storage Tank Protection


Minimum Requirements for 3% Foam Concentrate Full Surface Protection Using High Volume Monitors*

Tank Diam (Feet)

50 Minutes (Flash Point > 100 F) ApplicationDensities **

65 Minutes (Flash Point < 100 F) Application Densities **

.16 480 690 930 1215 1530 1890 2280 2715 3195 3705 .18 540 765 1050 1365 1725 2130 2565 3060 3585 4155 4770 5430 6135 6870 7665 8490 .20 600 855 1155 1515 1920 2355 2850 3405 3990 4620 5310 6030 6810 7635 8505 9420 10395 11400 12465 13575 14730 15930 17175 18465 19815 21195 .22 660 945 1275 1665 2100 2595 3135 3735 4380 5085 5835 6645 7500 8400 9360 10365 11430 12540 13710 14925 16200 17520 18885 20310 21795 23325 .25 750 1065 1455 1890 2385 2955 3570 4245 4980 5775 .16 615 885 1215 1575 1995 2460 2970 3540 4140 4815 .18 705 1005 1365 1770 2235 2760 3345 3975 4665 5415 6210 7065 7965 8940 9960 11025 .20 780 1110 1515 1965 2490 3075 3705 4410 5190 6015 6900 7845 8850 9930 11055 12246 13515 14820 16200 17650 19140 20700 22320 24165 25755 27555 .22 855 1215 1665 2160 2730 3375 4080 4860 5700 6615 7590 8625 9735 10830 12165 13485 14865 16305 17820 19410 21048 22770 24555 26415 28322 30315 .25 960 1380 1830 2460 3105 3840 4635 5520 6480 7515 8675 9810 11070 12405 13830 15315 16890 18525 20250 22050 23925 25875 27900 30015 32184 34455

.16 50 60 70 80 90 100 110 120 130 140

150 160 170 180 190 200

6630 7545 8520 9540 10635 11775

210 220 230 240 250 260 270 280 290 300

12990 14250 15585 16965 18405 19905 21465 23085 24765 26505

Formula: (Tank Diameter)2 x 0.785 x Application Density x 0.03 x Duration (in minutes) Based on NFPA 11, Hydrocarbon Fuels *Does not include post extinguishment suppression **Application Densities indicated as gpm/ft2

PRODUCTS 409-745-3232

F9
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Product Detail: Big Foot Trailer Mount 4,000 - 14,000 GPM
The Williams Big Foot Multi-Flow High-Volume Monitor is designed for the extinguishment of massive petrochemical fires. The nozzle is constructed of all corrosion resistant materials, such as anodized aluminum, stainless steel, and composite plastics, and is capable of flows ranging from 4,000 - 14,000 GPM. The nozzle is available with six separate stems in increments of 2,000 GPM each. The nozzle is the self educting type, incorporating patented Hydro-Foam technology. Foam concentrate is supplied via remote jet ratio controllers, or foam solution can be delivered from an independent proportioning system directly to the water inlets. The nozzle is constant flow, with straight stream to full fog capabilities. The trailer meets all applicable DOT regulations and is constructed of deep channel carbon steel. Ballast tanks are an integral part of the trailer, providing stability and traction to counteract nozzle reaction forces. The internal water inlet manifold is constructed of 10 I.D. stainless steel. Eight (8) ea., 5 storz (6 optional) inlet connections with caps are provided for water-foam solution supply. The full system capacity of 14,000 gpm requires a total of ten (10) 5 storz inlets. Each connection is protected from back flow using a six inch (6) full flow wafer check valve. Two (2) ea., 4 inlets are provided (one each side) for foam concentrate supply. The tandem axle trailer has a gross vehicle weight rating (GVWR) of 14,000 lbs. Mechanical/hydraulic surge brakes are activated via a heavy duty coupler terminating in a pintle hook connection. The tongue is connected rigidly to the trailer using an A-frame arrangement for maximum stability. Non-skid designed upper decking. Stabilizing jacks are provided at four points, providing maximum stability. An operators panel is located aft of the nozzle. The elevated operating position provides a full view of fire ground operations. All controls are manual gear operated and utilize state-of-the-art hydraulic systems to control vertical travel (+15 to +45), horizontal traverse (from 15 right/left of center), and nozzle fog/straight stream pattern.

Standard Trim and Accessories:


2 4 4 1 1 1 1 1 1 1 1 ea.- Concentrate Jumper Hose 4 x 10 ft. coupled storz ea.- Jet Ratio Controllers 2.0 JP60 ea.- Drum Kits for Jet Ratio Controllers ea.- Jet pump selection char t ea.- nozzle flow char t ea.- 4000 GPM stem ea.- 6000 GPM stem ea.- 8000 GPM stem ea.- 10,000 GPM upgrade option ea.-12,000 GPM upgrade option ea.-14,000 GPM upgrade option

Big Foot- Trailer Mount Nominal Flow @ 100 PSI 12,000 gpm Nominal Range @ 100 PSI (straight stream) @ 4,000 GPM @ 6,000 GPM @ 8,000 GPM @ 10,000 GPM @ 12,000 GPM @ 14,000 GPM 330 ft. 350 ft. 360 ft. 390 ft. 400 ft. 430 ft. Eight (8) 5 storz Two (2) 4 storz 1400

Water Inlets (standard) Foam Concentrate Inlet K- Factor, Maximum Flow

For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F10
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Hydro-Foam Technology

Big Foot Trailer Mount 4,000 - 14,000 GPM

5 Storz Inlet (Optional)

*Two Optional inlets required for flows from 10,000 gpm to 14,000 gpm.

For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F11
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Hydro-Foam Technology
Big Foot Hose Lay - For up to 8,000 GPM

For US and Foreign Patent and Trademark information, please refer to page IP2

(8) 5 Water Supply Hoses

(4)

PRODUCTS 409-745-3232

F12
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Product: Battler 2 x 10 Monitor / Nozzle Description:
The Battler Monitor/Nozzle Trailer Unit is capable of large volume discharge to elevations never before attained by conventional equipment to provide fire suppression, cooling, personnel protection, toxic gas dispersion and more. Discharge flow rates from 2000-10,000 USGPM (7571-37854 LPM) can be water or Hydro-Foam for extinguishing liquids. All this and the operator is still afforded the freedom of smooth, rapid horizontal and vertical movement and unsurpassed articulation of 360 that only the Battler can provide, raising this monitor/nozzle above all others.

Advancing the Fire Fighters Ability with Equipment and Knowledge.


This Hybrid nozzle has the unique capability to perform as an automatic pressure or fixed gallonage nozzle. During automatic operation the nozzle will respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a given discharge flow. Once the nozzle reaches the fixed gallonage set point (2000-10,000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable for foam proportioning operations on storage tank fires or other hazards requiring specific application rates. This nozzle is capable of HydroFoam proportioning at rates up to 10,000 GPM @ 1% (8000 GPM @ 3%) using remote jet pump technology. The single 10 stainless steel waterway construction provides minimum friction loss, maximum efficiency, and years of trouble-free service. The user-friendly gear operated controls provide full monitor articulation of 360 rotation and down to +15 and up to +75 vertical travel with a minimal of input effort. Pattern control from straight stream to full fog is accomplished via a full wrap-around handle attached to the outer sleeve.

Standard Features:
Dual Mode Automatic/Fixed Operation Fixed Gallonage plugs: 2K, 4K, 6K, 8K, 10K Hydro-Foam Capable Nozzle Efficient Single 10 SS Monitor Dual Handwheel Controls for Pan & Tilt Wrap-around handle design for pattern control Tandem axle trailer Integral 12 stainless steel manifold Five 5 clappered storz inlets w/caps 2.0 ball fixed height hydraulic surge coupler Large operators deck surface (8 x 11) Anti-skid grip surface Four point trailer jacks plus tongue jack Standard grade Red Finish

Options:
6 clappered storz inlets in lieu of standard (nine) 2.0JP60 Jet Pump w/Metering Valve & Stinger (four) 4-2.5 FNST x 4.0 MNPSH Siamese Jet Pump Manifold 15 x 4 ID Non-collapsible Jet Pump Supply Hose 2.5 FNST x 2-1.5 MNST Gated Wyes for Jet Pump Feed (two) European adjustable tow bar European lighting package Radio remote controlled electric/hydraulic/monitor controls Premium (show grade) paint & finish

For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F13
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Ambassador 1 x 6 Monitor/Nozzle

Advancing the Fire Fighters Ability with Equipment and Knowledge.

Description:
This Hybrid nozzle has the unique capability to perform as an automatic pressure or fixed gallonage nozzle. During automatic operation the nozzle will respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a given discharge flow. Once the nozzle reaches the fixed gallonage set point (1000-6000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable for foam proportioning operations on storage tank fires or other hazards requiring specific application rates. This nozzle is capable of Hydro-Foam proportioning at rates up to 6000 GPM @ 3% (3000 GPM @ 6%) using remote jet pump technology. The extensive Ambassador options list allows this nozzle to be Hydro-Chem capable with PKW flow rates from 25 lbs/s to 100 lbs/s. The single 8 full flow stainless steel waterway construction provides minimum friction loss, maximum efficiency, and years of trouble-free service. The standard tiller-bar control provides full monitor articulation of 360 rotation and down to -15 and up to +75 vertical travel. Pattern control from straight stream to full fog is accomplished via a full wrap-around handle attached to the outer sleeve.

Standard Features:
Dual Mode Automatic/Fixed Operation Fixed Gallonage plugs:1K,2K,3K,4K,5K,6K Hydro-Foam Capable Nozzle Efficient Single 8 SS Monitor Tiller-bar control Wrap-around handle design for pattern control Tandem axle trailer Integral 8 carbon steel manifold Five 5 non-clappered storz inlets w/caps 2.0 ball fixed height hydraulic surge coupler Anti-skid grip surface Four point trailer jacks plus tongue jack Standard grade Red Finish

Options:
Hydro-Chem Tip conversion Choke tubes (25, 50, 75 & 100 lbs./s) Dry chemical manifolds (4,6,7, & 10 inlets) *See Pages J10-J12 1.5JP30 Jet Pump w/stinger (one) 2.0JP60 Jet Pump w/stinger (three) 3-2.5 FNST x 3.0 MNPSH Siamese 1-2.5 FNST x 3-1.5 MNST Wye 10 SS integral manifold w/6-5 Storz inlets Internal 5 clappers European adjustable tow bar European lighting package Gear operated monitor controls (vertical & horizontal) Radio remote controlled electric/hydraulic/gear monitor controls 1-5 x 2-5 Jumbo Siamese (recommended w/std 8 manifold) Premium (show grade) paint & finish 3 x 15 Dry Chemical Hose 3 Valved Siamese w/extra hoses for 100 lbs./s PKW
For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F14
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Product: Ranger3

Description:
The Ranger, featuring Smart Nozzle Technology, was designed for todays Industrial fire fighting and protection needs. Hazards involving flammable liquids in storage and liquids under pressure have met their match with the New Millennium Equipment from Williams Fire & Hazard Control, Inc. The Ranger monitor/nozzle combination is capable of not only selfeducting foam concentrate, but can do so while maintaining a nearly constant pressure (+/- 10%) and a constant foam percentage (1% or 3% selectable) regardless of the flow rate. Discharge flow rates from 1000-3000 USGPM (3800-11356 LPM) can be water only, Hydro-Foam (using jet pumps or automatic constant/selectable metering) or Hydro-Chem for extinguishing liquids and gases under pressure. All this and the operator is still afforded the freedom of smooth, rapid horizontal and vertical movement that only the Ranger can provide, raising this monitor/nozzle above all others. This Hybrid nozzle has the unique capability to perform as an automatic pressure or fixed gallonage nozzle. During automatic operation the nozzle will respond to varying flows to maintain a nearly constant tip pressure, thus maximizing effective range for a given discharge flow. Once the nozzle reaches the fixed gallonage set point (1000-3000 GPM), it performs as a conventional fixed gallonage nozzle. This is desirable for foam proportioning operations on storage tank fires or other hazards requiring specific application rates. This nozzle is capable of Hydro-Foam proportioning at rates up to 3000 GPM @ 3%. It can automatically maintain a nearly constant foam percentage (1% or 3%) throughout the entire flow range while self-educting. It can optionally be configured to proportion foam from remote locations using jet pump technology (thus forfeiting the constant/selectable metering feature). The extensive Ranger options list allows this nozzle to be Hydro-Chem capable (without Hydro-Foam capability) with PKW flow rates from 25 lbs/s to 50 lbs/s. The single 6 full flow stainless steel waterway construction provides minimum friction loss, maximum efficiency, and years of trouble-free service. The standard tiller-bar control provides full monitor articulation of 360 rotation and down to -15 and up to +75 vertical travel. Pattern control from straight stream to full fog is accomplished via a full wrap-around handle attached to the outer sleeve.

Standard Features List:


Dual Mode Automatic/Fixed Operation Fixed Gallonage plugs: 1K, 2K, 3K Hydro-Foam Constant/Selectable 1% or 3% Nozzle Efficient Single 6 SS Monitor Tiller-bar control Wrap-around handle design for pattern control Tandem axle trailer Integral 8 carbon steel manifold Three 5 non-clappered storz inlets w/caps 2.0 ball fixed height hydraulic surge coupler Anti-skid grip surface Four point trailer jacks plus tongue jack Standard grade Red Finish

Options:
Hydro-Chem Tip conversion Choke tubes (25 or 50 lbs/s) Dry chemical manifolds (4 inlet or 7 inlet) *See Pages J10-J12 1.5JP30 Jet Pump w/stinger (one) 2.0JP60 Jet Pump w/stinger (one) 3-2.5 FNST x 3.0 MNPSH Siamese (Jet to Monitor Supply) 1-2.5 FNST x 3-1.5 MNST Wye (Jet Pump Supply) 8 SS integral manifold w/3-5 Storz inlets 8 SS integral manifold w/2-6 Storz inlets Internal 5 or 6clappers European adjustable tow bar European lighting package Gear operated monitor controls (vertical & horizontal) Radio remote controlled electric/hydraulic/gear monitor controls Premium (show grade) paint & finish 2.5 x 10 Dry Chemical Hose

For US and Foreign Patent and Trademark information, please refer to page IP2
120108

PRODUCTS 409-745-3232

F15
WWW.WILLIAMSFIRE.COM

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Product: Hired Gun Trailer - 2000 GPM

Description:
This Trailer Mounted System delivers 2000 gpm of water or foam solution @ 100 psi. Hard anodized nozzle with fog/straight stream adjustment. Foam solution is proportioned through one matched Jet Ratio Controller. Monitor is constructed of 6 stainless steel epoxy coated, gear operated, with pressure gauge. Dual handwheel control, horizontal and vertical positions. Heavy duty trailer includes: diamond plate deck; tool box; and trailer hitch. Water inlet trim includes; 5 storz clappered dual inlet siamese; 5 x 10 ft. hose coupled storz. Trailer is equipped with adjustable jacks for stability.

2 BALL COUPLER STANDARD (ELECTRIC OR SURGE BRAKES OPTIONAL)

Hired Gun Trailer Mount Nominal Flow @ 100 PSI Nominal Range @ 100 PSI (straight stream) Water Inlet Foam Concentrate Inlet Horizontal Rotation Ver tical Travel Propor tioning K-Factor 2000 gpm 235 ft.

5 storz 2.5 NH (F) Swivel 360 0 to 85 1% or 3% 200

For US and Foreign Patent and Trademark information, please refer to page IP2
120108

PRODUCTS 409-745-3232

F16
WWW.WILLIAMSFIRE.COM

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Typical Hired Gun Layout

For US and Foreign Patent and Trademark information, please refer to page IP2

1. USE ONE JET RATIO CONTROLLER (2.0 JP60) FOR 3% @ 2000 GPM. 2. USE TWO JET RATIO CONTROLLERS (2.0 JP60) FOR 6% @ 2000 GPM.

CLAPPERED JUMBO SIAMESE

JET RATIO CONTROLLER (2.0) JP60 1.5 INLET X 2.5 DISCHARGE

NOTE:

PRODUCTS 409-745-3232

F17
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Hydro-Chem Monitor / Nozzle Package


Product: Patriot Ranger3 Quick Action Deck Gun, 1000-3000 GPM

Description:
Hydro-Chem Monitor system includes: fog/straight stream constant pressure/ variable flow nozzle delivering from 1000 to 3000 gpm of foam solution @ 100 psi and 40 lb./sec of dry chemical (nominal flow). Foam solution is proportioned through one matched Jet Ratio Controller. Monitor is constructed of stainless steel with red epoxy finish. Nozzle is constructed of hard anodized aluminum alloy with stainless steel trim. Equipped with quick action handle for fast, positive control. System includes: valved dry chemical six inlet manifold; dry chemical inlet hose.

Patriot Ranger3 Deck Gun Quick Action Nominal Flow @ 100 PSI K-Factors @ 100 psi Nominal Range of dry chemical Foam Concentrate Inlet Dry Chemical Inlet Nozzle Water Inlet Ver tical Travel Horizontal Rotation 1000, 2000 or 3000 gpm Variable 100, 200, 300 100 ft. 2.5 NPT (M) 2 NPT (M) Valved 6 150# flange 0 to +80 360

For US and Foreign Patent and Trademark information, please refer to page IP2

PRODUCTS 409-745-3232

F18
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Monitor / Nozzle Packages


Product: Gear Operated 6 Monitor

Description:
This Fixed Mounted System delivers from 1000 to 3000 gpm of water or foam solution @ 100 psi. Hard anodized constant pressure/variable flow nozzle with fog/straight steam adjustment. For remote application, 1% or 3% foam solution is proportioned through one matched Jet Ratio Controller. Worm gear operated 6 waterway monitor is constructed of stainless steel with stainless steel swivels. Dual handwheels control horizontal and vertical positions.

Patriot Ranger3 Nominal Flow @100 psi Water inlet Foam Concentrate Inlet Horizontal Rotation Ver tical Travel Propor tioning without jet K-Factor (@ 100 psi) 1000, 2000 or 3000 gpm 6 Flange 2.5 NPT(M) 360 0 to +90 1% or 3% 100, 200 or 300

PRODUCTS 409-745-3232

F19
WWW.WILLIAMSFIRE.COM

120108

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Hydro-Chem Monitor / Nozzle Package


Product: Patriot 1- Worm Gear Deck Gun, 1000 GPM

Description:
Hydro-Chem Monitor system, includes fog/straight stream nozzle, delivering 1000 gpm of foam solution @ 100 psi and 20 lb./sec of dry chemical (nominal flow). Foam solution is proportioned through one 1.5 JP30 Jet Ratio Controller. Dual handwheel 4 monitor is fabricated of stainless steel with red epoxy finish. Dual Wafer Nozzle is constructed of hard anodized aluminum alloy with stainless steel trim. System includes: valved dry chemical four inlet manifold; dry chemical inlet hose, 1.5 x 15 ft.

Patriot 1 Deck Gun Worm Gear Nominal flow @ 100 PSI K-Factor Nominal Range of dry chemical Foam Concentrate Inlet Dry Chemical Inlet Nozzle Water Inlet Ver tical Travel Horizontal Rotation 1000 gpm 100 100 ft. 2 NPT (M) 1.5 Valved 4 150# flange -10 to +90 360

For US and Foreign Patent and Trademark information, please refer to page IP2
120108

PRODUCTS 409-745-3232

F20
WWW.WILLIAMSFIRE.COM

EMERGENCY 409-727-2347

MONITOR / NOZZLE PACKAGES

MONITOR / NOZZLE PACKAGES

Hydro-Chem Monitor / Nozzle Package


Product: 1.5 HC Ranger 250-1500 Deck Gun

Description:
Hydro-Chem Monitor System, includes fog/straight stream constant pressure/variable flow nozzle, delivering from 250 gpm to 1500 gpm of foam solution @ 100 psi and 20 lb./sec of dry chemical (nominal flow). Foam solution is proportioned through one matched Jet Ratio Controller. Monitor is constructed of stainless steel with red epoxy finish. Big Body Nozzle is constructed of hard anodized aluminum alloy with stainless steel trim. Equipped with quick action handle for fast, positive control. System includes: valved dry chemical four inlet manifold; dry chemical inlet hose, 1.5 X15 ft.

Patriot Ranger Deck Gun Nominal Flows Nominal Flow @ 100 PSI K-Factor Nominal Range of dry chemical Dry Chemical Inlet Nozzle Water Inlet Ver tical Travel Horizontal Rotation Variable (250-1500 GPM) 1500 gpm 150 100 ft. 1.5 Valved 4 150# flange -25 to +80 360