Professional Documents
Culture Documents
http://www.derby.ac.uk/staff/mahmoud-shafik/
Symmetrical Faults
Protective Equipment: Circuit Breakers & Fuse & Selection Process
Un-Symmetrical Faults
Faults Types
Line to Ground Fault Line to Line Fault Double Line to Ground Fault
Short-circuit currents may be several orders of magnitude than normal operating currents and if allowed to persist, may cause thermal damage to equipments
Protective Equipment
Two factors are of utmost importance for the selection of circuit breakers. These are: 1. The maximum instantaneous current that a breaker must withstand and 2. The total current when the breaker contacts part
This circuit breaker uses both SF6 and air as insulating gases; such devices are sometimes called "hybrid switchgear"
LV Protective Equipment
An air circuit breaker for low voltage (less than 1000 volts) power distribution switchgear
LV Protective Equipment
1. Actuator lever 2. Actuator mechanism - forces the contacts together or apart. 3. Contacts - Allow current when touching and break the current when moved apart. 4. Terminals 5. Bimetallic strip. 6. Calibration screw - allows the manufacturer to precisely adjust the trip current of the device after assembly. 7. Solenoid Photo of inside of a circuit 8. Arc divider/extinguisher breaker
Un-Symmetrical Faults
System Representation:
The three phase power system is represented by its sequence networks. The zero, positive, and negative-sequence networks of system components, generators, motors, transformers and transmission lines. The power system is balanced before the fault occurs such that of the three sequence networks only the positive sequence network is active. Also as the fault occurs, the sequence networks are connected only through the fault location. The fault current is negligible such that the pre-fault positive sequence voltages are same at all nodes and at the fault location. All the network resistances and line charging capacitances are negligible. All loads are passive except the rotating loads which are represented by synchronous machines.
Un-Symmetrical Faults
The sequence circuits and the sequence networks developed will now be used for finding out fault current during unsymmetrical faults. Three Types of Faults:
Line to Ground (LG) Fault Line to Line (LL) Fault Double Line to Ground (DLG) Fault
Un-Symmetrical Faults
System Representation:
Un-Symmetrical Faults
Un-Symmetrical Faults
Line to Ground Fault:
Un-Symmetrical Faults
Line to Line Fault:
Un-Symmetrical Faults
Double Line to Ground Fault:
Symmetrical Faults
Protective Equipment: Circuit Breakers & Fuse & Selection Process
Un-Symmetrical Faults
Faults Types
Line to Ground Fault Line to Line Fault Double Line to Ground Fault
10