MiCOM M211
Non communicating Measurement Centre

MICOM M211 QUICK, SIMPLE MEASUREMENT OF SYSTEM PARAMETERS

> > > >

Fast measurement and monitoring Single or three phase Input current and voltage sampling Wide range of system parameters

INNOVATIVE SOLUTIONS FOR THE MODERN WORLD

In a competitive business environment, it pays to stay ahead of the game. AREVA T&D offers complete solutions for the entire energy chain, from primary equipment to market management software.

THE M2X1 RANGE The MiCOM M2x1 range comprises: > M211 Non communicating Measurement Centre > M231 Communicating Measurement Centre > M241 Communicating Measurement Centre with Data Recorder (See separate documents for M231 and M241)

EASYUSE CASE All models in the range offer the benefits of the new EasyUse case, which uses embedded ring current transformers, allowing cables to be passed through them without the need for a termination connection . The result is simpler installation and increased reliability of the current connection. If the cable needs to be terminated there is a connection block fitted.

M211 NON COMMUNICATING MEASUREMENT CENTRE

Customer Benefits Comprehensive set of measurements Simplified connections Large LCD display Easily programmable settings

The M211 Non communicating Measurement Centre provides quick, reliable measurement and monitoring of electrical quantities in a single or three phase electrical distribution system. It utilises fast microprocessor sampling of the input current and voltage quantities to calculate a wide range of system parameters such as energy, power and frequency.

AREVA T&D

FEATURES
> Large LCD displays up to 3 parameters simultaneously (see fig 1) > Four energy registers for four-quadrant energy measurement > Active energy metering to IEC 61036 class 1.0 > Reactive energy metering to IEC 61268 class 2.0 > Demand values for Current, W, VA, Var: present and since last reset > True rms measurement > Programmable VT and CT ratios > Single phase or three phase connections > For balanced or unbalanced loads > Multilingual selectable menu text > Compact and rugged design > Pulsed outputs

BENEFITS
> Wide range of measurement parameters > Accurate over a wide dynamic range > Replaces separate energy meters and instrumentation in cost sensitive applications > Easily configured to actual system parameters > Industry standard 96mm DIN case

APPLICATION

ENERGY MONITORING The M211 is intended for use on systems where energy monitoring and instrumentation are required, providing Volts, Amps, Watts, Vars, VA, power factor, and frequency, as well as metering for active and reactive energy. Demand values for current, active, reactive and apparent power are also provided.

COST EFFECTIVE SOLUTIONS The M211 is more cost effective than using separate devices, saving on hole punching and wiring costs - as well as device costs and panel space costs.

Fig 1

Typical LCD displays

ELECTRICAL SYSTEMS The M211 can be used on single or three phase systems, with balanced or unbalanced loads.

2>3

M211: Delivers a wide range of measurements at low cost

FUNCTIONS
INSTANTANEOUS MEASUREMENT

DEMAND CALCULATION The M211 is able to calculate Demand values using fixed, thermal and sliding window methods. Both Present Demand and Demand Since Last Reset are available.

Active Power Reactive Power Apparent Power Power Factor Phase Voltage Line Voltage Current Frequency

Pa, Pb, Pc, Pt Qa, Qb, Qc, Qt Sa, Sb, Sc, St Cosa, Cosb, Cosc, Cost Ua, Ub, Uc, Ut Uab, Ubc, Uca, U3 Ia, Ib, Ic, In F

PULSED OUTPUTS The M211 has two pulsed outputs which can be set to correspond to any two of the four energy measurements. These are set via the front menu and can be disabled if not required. (see Fig 2) CONFIGURATION Two password controlled access levels are available. The following settings are password protected: > CT ratio

ENERGY MEASUREMENT

Active Energy Reactive Energy

Wh total, import and export VArh total, leading and lagging.

DEMAND VALUES

> VT Primary > VT secondary

Phase currents Total active power Total reactive power Total apparent power

> System connection > Demand calculation mode > Demand period > Energy meter resetting > Demand resetting > Pulse output configuration

Fig 2

Pulse connections

15

16

R>100R Pulse receptor 24V DC Power Supply OV

100ms pulse output

M211 : Programmable CTs, VTs and pulsed ouputs can be easily configured.

HARDWARE DESCRIPTION
6mm
CASE The M211 is housed in a DIN case with maximum dimensions of 96mm by 96mm by 108mm. (See Fig4 for dimensions)

102mm

DISPLAY The front panel contains an illuminated dot matrix liquid crystal display (LCD) with a large viewable area of 70mm by 38mm. Four pushbuttons provide access to the M211 menu. See Fig 1 for typical screen views.
CT1 CT3

REAR CONNECTIONS The auxiliary supply, pulsed output and measured voltage use plug in M2.5 terminal blocks. The current measuring circuit connections on the rear are by means of individual embedded CTs, see Fig 5. The current cables are passed through these CTs and can be terminated on a separate terminal block. See Fig 3 for rear case view.

15 16 17 18

CT2

11 2 5 8

96mm
19 20 21 13 14

96mm

Panel cutout
Height 92mm (+0.8,-0)

Fig 3

Rear case view

Width 92mm (+0.8,-0)

Fig 4

Case outline

4>5

EasyUse case : simplifies CT wiring connections

TECHNICAL DATA

AC AUXILIARY VOLTAGE

Input voltage
VOLTAGE INPUT

Nominal phase to neutral input voltage (Un):


57.74, 63.5, 120V or 230V (Other voltages in the range 50V to 300V phase to neutral are available on request) Measuring range with separate auxiliary supply: 0 150% Un Burden with separate auxiliary supply: < 0.1VA Rated frequency and range: 50Hz - 60Hz; 45Hz to 65Hz Thermal withstand 1.5 Un continuously 2 Un for 10 seconds

Supply voltage range Burden Frequency range

63.5, 100, 110, 115, 120, 208, 220, 230 and 400 Ux 0.8 1.2 Ux < 5VA 45Hz to 65 Hz

PULSE OUTPUTS

Output relay function2 relays, for active


and/or reactive energy control

Maximum ac switching power


50VA, maxima of 350Vdc or peak ac, 1A

Maximum number of pulses


4,000 per hour

Pulse duration
100mS

CURRENT INPUT

Isolation
4KV rms coil to contacts1.4KV across contacts 1A or 5A 0 160% In < 0.1VA 3 In continuously 25 In for 3 seconds 50 In for 1 second

Rated current (In) Measuring range Burden Thermal withstand

SETTING TRANSFORMER RATIOS

VOLTAGE RATIO Both the primary and secondary values of the VT may be set.

ACCURACY

Active energy Reactive energy Power Phase/phase voltage Phase/Neutral voltage Phase current Neutral current Power Factor Phase angle MD Values Frequency

IEC 61036 class 1.0 IEC 61268 class 2.0 0.5% (*) 1.0% 0.5% (**) 0.5% (*) 1.0% (*) 0.5 degree 0.5 degree 1.0% 10mHz

Primary voltage setting


Voltage range 0.1 to 15,999.9V 1 to 15,999kV 10 to 159.99kV 100 to 1599.9kV Voltage step 0.1V 1V 10V 100V

Secondary voltage setting


Voltage range 10 to 137V 140 to 775V Voltage step 1V 5V

* For these values the accuracy is % of nominal for 0 100% of nominal and % of reading above nominal. ** For these values the accuracy is % of nominal for 10 100% of nominal and % of reading above nominal. For voltage range 0 10% Un the maximum error is 2% of nominal value.

CURRENT RATIO Only the primary value can be altered, the secondary CT value is fixed at either 1A or 5A and must be specified with the order. CT ratio 1 to 63 63 to 315 320 to 630 650 to 3150 4000 CT ratio 1 to 63 63 to 315 320 to 630 650 to 3150 4000 Step 1 5 10 50 1A CT primary rating 1 to 63 63 to 315 320 to 630 650 to 3150 4000 5A CT primary rating 5 to 315 325 to 1575 1600 to 3150 3250 to 15750 20000

Step 5 25 50 250

ELECTRICAL ENVIRONMENT

CASE
PC/ABS uninflammable to UL 94VO Dimensions 96 x 96 x 108mm Enclosure protection IP52 EN60529:1989 Connection terminals IP00 EN60529:1989 Weight 0.6kg

EUROPEAN LEGISLATION

Product safety

73/23/EEC

Compliance with the European Commission Low Voltage Directive. EN 61010-1: 2002 Safety requirements for electrical equipment for measurement, control and laboratory use, Part 1: General requirements.

CONNECTIONS
Permissible cross section of connection leads:

EMC Compliance 89/336/EEC


EN62052-11:2003 Part 11 Metering equipment general requirements, tests and test conditions. Electricity Metering Equipment (ac) EN62053-21:2003 Particular requirements, Part 21: Static meters for active energy (classes 1 and 2) EN62053-23:2003 Particular requirements, Part 23: Static meters for reactive energy (classes 2 and 3)

Measured quantities: 5mm2 single wire Auxiliary supply and outputs: 2.5mm2 single wire

CONNECTION TABLE Function AC current I1 I2 I3 AC voltage UL1 UL2 UL3 N Pulse output OUT 1 OUT 2 Auxiliary Supply +/AC -/AC Terminal CT1 CT2 CT3 2 5 8 11 15/16 17/18 13 14

DESIGN

Protection
Compliance is demonstrated by reference to generic safety standards. Protection class II 600V installation category II 300V installation category III Pollution degree 2

Test voltage
3.7kV rms to EN61010-1:1990

ENVIRONMENTAL WITHSTAND

Climatic rating
EN61036:1996 EN61268: 1995

Reference range of operation


0C to 50C Fig 5

Nominal range of operation


-25C to 55C

Connections when using a pass through CT (per phase)

Transit and storage


-40C to 70C

CT1

Humidity
75% annual mean relative humidity

K
6>7

INFORMATION REQUIRED WITH ORDER

M211

X: Menu Configurable CT Secondary 1: 1A 5: 5A VT Secondary B : 63.5V (57.7 to 69.3V L - N or 100V to 120V L - L) G : 120V (120V L - N or 208V L-L) V : 230V (220 to 250V L -N or 380V to 440V L- L) Auxiliary Voltage B : 63.5V ac D : 100V ac E : 110V ac F : 115V ac G: 120V ac H : 208V ac J : 220V ac V : 230V ac 4 : 400V ac U : 24-276Vac, 24-300Vdc Frequency X : 50 60Hz Output 2: 2 pulsed outputs Rear Port communications 0: No communications Software 0: Basic 00A: Factory Defaults

M211: Used by Industrial or Utility engineers, at low or distribution voltage level

SOUTH EAST ASIA

Tel.: +65 67 49 07 77 - Fax: +65 68 41 95 55


PACIFIC

Tel.: +65 67 49 07 77 - Fax: +65 68 46 17 95


CHINA

Tel.: +86 10 64 10 62 88 - Fax: +86 10 64 10 62 64


INDIA

Tel.: +91 44 2431 7100 - Fax: +91 44 2434 1297


NORTH AMERICA

Tel.: +1 (484) 766-8100 - Fax: +1 (484) 766-8650


CENTRAL AMERICA

Tel.: +52 55 11 01 10 00 - Fax: +52 55 26 24 04 93


SOUTH AMERICA

Tel.: +52 55 11 3491 7469 - Fax: +55 11 3491 7476


FRANCE

Tel.: +33 (0)1 40 89 66 00 - Fax: +33 (0)1 40 89 67 19


BRITISH ISLES

Tel.: +44 (0) 1785 27 41 08 - Fax: +44 (0) 1785 27 45 74


NORTHERN EUROPE

Tel.: +49 69 66 32 11 51 - Fax: +49 69 66 32 21 54


CENTRAL EUROPE & WESTERN ASIA

Tel.: +48 22 850 96 96 - Fax: +48 22 654 55 88


NEAR & MIDDLE EAST

Tel.: +971-6-556 0559 - Fax: +971-6-556 5133


MEDITERRANEAN, NORTH & WEST AFRICA

Tel.: +33 (0)1 41 49 88 38 - Fax: +33 (0)1 41 49 24 23


SOUTHERN & EASTERN AFRICA

Tel.: +27 11 82 05 111 - Fax: +27 11 82 05 220 T&D Worldwide Contact Centre contact.centre@areva-td.com

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

www.areva-td.com

AUTOMATION-L3-M211-BR-08.06-0336c-GB - 2006 AREVA . AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademerk of AREVA. The other names mentioned, registered or not, are the property of their respective companies. - 389191982 RCS PARIS - SONOVISION-ITEP.