IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007

A Distributed Static Series Compensator System for Realizing Active Power Flow Control on Existing Power Lines
Deepak M. Divan, Fellow, IEEE, William E. Brumsickle, Senior Member, IEEE, Robert S. Schneider, Member, IEEE, Bill Kranz, Randal W. Gascoigne, Dale T. Bradshaw, Member, IEEE, Michael R. Ingram, Senior Member, IEEE, and Ian S. Grant, Fellow, IEEE

AbstractFlexible AC transmission systems (FACTS) devices can control power ow in the transmission system to improve asset utilization, relieve congestion, and limit loop ows. High costs and reliability concerns have restricted their use in these applications. The concept of distributed FACTS (D-FACTS) is introduced as a way to remove these barriers. A new device, the distributed static series compensator (DSSC), attaches directly to existing HV or EHV conductors and so does not require HV insulation. It can be manufactured at low cost from conventional industrial-grade components. The DSSC modules are distributed, a few per conductor mile, to achieve the desired power ow control functionality by effectively changing the line reactance. Experimental results from a prototype module are presented, along with examples of the benets deriving from a system of DSSC devices. Index TermsDistributed FACTS, exible AC transmission systems (FACTS), interconnected power systems, power system economics, power system planning, power transmission congestion, power transmission control, power transmission lines.

I. INTRODUCTION HE U.S. transmission system was developed to serve a vertically integrated regulated utility structure. Substantial changes and capital investment are required to modify it for deregulated market needs. Thus it presents a major infrastructural obstacle for the continuing growth of the U.S.$ 224 billion U.S. electricity market [1]. Electricity demand has increased 25% over the last decade and continues to increase. Overall, adequate generation capacity now exists, or is planned, to meet projected needs in the U.S. At the same time, annual investment in transmission facilities has declined over the last decade [1].
Manuscript received December 3, 2004. This work was supported in part by the Tennessee Valley Authority and in part by Soft Switching Technologies Corporation. Paper no. TPWRD-00573-2004. D. M. Divan was with Soft Switching Technologies, Middleton, WI 53562 USA. He is now with the Georgia Institute of Technology, Atlanta, GA 30332 USA (e-mail: deepak.divan@ece.gatech.edu). W. E. Brumsickle, R. S. Schneider, and B. Kranz are with Soft Switching Technologies, Middleton, WI 56562 USA (e-mail: brumsickle@ieee.org). R. Gascoigne was with Soft Switching Technologies, Middleton, WI 53562, USA. He is now a Consultant in Madison, WI 53711 USA. D. T. Bradshaw was with the Tennessee Valley Authority, Chattanooga, TN 37402, USA. He is now with Electrivation, Chattanooga, TN 37416 USA (e-mail: dtbradshaw@electrivation.com). M. R. Ingram and I. S. Grant are with the Tennessee Valley Authority, Chattanooga, TN 37402 USA (e-mail: mringram@tva.gov; isgrant@tva.gov). Color versions of Figs. 211 are available online at http://ieeexplore.ieee.org. Digital Object Identier 10.1109/TPWRD.2006.887103

As a result of load growth, deregulation, and limited investment in new facilities, transmission congestion has rapidly increased. Over 50 transmission corridors in the U.S. are routinely congested, causing high economic impact. According to the New York Independent System Operator (NYISO), T&D system congestion costs over U.S.$ 1 billion per year [2]. Unfortunately, ac power ow follows Ohms Law, not contract law. Uncontrolled loop ow causes congestion and reliability problems, and reduces the ability to fulll energy contracts. Loop ows also impact the ability to fully utilize certain transmission lines, even as other lines suffer congestion, further limiting available transfer capacity under normal and contingency conditions. New transmission lines could relieve congestion, but are expensive to build (U.S.$ 0.52 million/mile typically, but costs can exceed U.S.$ 10 M/mile) and require several years for approval and construction. One solution to the problem of managing power ow on transmission lines has been through the use of Flexible AC Transmission Systems (FACTS). FACTS devices allow control of power ows on ac power systems through the use of large power converters (10300 MW) [3]. While several FACTS installations are operating worldwide, wide scale deployment has not occurred. FACTS typically costs U.S.$ 120U.S.$ 150 per kVAr, compared to U.S.$ 15U.S.$ 20/kVAr for static capacitors. This paper introduces the concept of a distributed static series compensator (DSSC) that uses multiple low-power single-phase inverters that attach to the transmission conductor and dynamically control the impedance of the transmission line, allowing control of active power ow on the line [4]. The DSSC inverters are self-powered by induction from the line itself, oat electrically on the transmission conductors, and are controlled using wireless or power line communication techniques. Implementation of system level control uses a large number of DSSC modules controlled as a group to realize active control of power ow. The DSSC can be used to either increase or decrease the effective line impedance, allowing current to be pushed away from or pulled into a transmission line. The DSSC concept overcomes some of the most serious limitations of FACTS devices, and points the way to a new approach for achieving power ow controlthe use of Distributed FACTS or D-FACTS devices. This paper details the principles of operation of the DSSC, shows operating results from a prototype device, and presents an analysis of its possible impact on typical power systems.

0885-8977/$20.00 2007 IEEE

DIVAN et al.: DSSC SYSTEM FOR REALIZING ACTIVE POWER FLOW CONTROL

643

TABLE I TYPES OF FACTS DEVICE

II. FEATURES AND LIMITATIONS OF FACTS DEVICES FACTS devices are typically high-power high-voltage power converters, operating at 138500 kV and 10300 MVA, that are used to control power ow in the transmission and distribution network. Three basic types of FACTS devices can be identied as shown in Table I [5]. Shunt devices such as the static VAR compensator (SVC) and static synchronous compensator (STATCOM), have been most widely applied, and are typically used for reactive VAR compensation and voltage support. Series devices such as the thyristor controlled series capacitor (TCSC) and the static synchronous series compensator (SSSC) can be used for controlling active power ow on transmission lines. Series-shunt devices such as the universal power ow controller (UPFC) can be used for accomplishing both functions with maximum exibility, and higher cost. For controlling power ow on transmission lines, the series elements clearly have the highest potential and impact. The real and , along a transmission line and reactive power ow, connecting two voltage buses is governed by the two voltage and and the voltage phase angle difference, magnitudes , as

Fig. 1. Variation of transmission line power ow by impedance injection. (a) Passive impedance injection, as p.u. of (TCSC). (b) Quadrature voltage injection to achieve active impedance injection (SSSC, DSSC).

and (1) where is the impedance of the line, assumed to be purely inductive. A series compensator is typically used to increase of the line, or decrease the effective reactive impedance thus allowing control of real power ow between the two buses. The impedance change can be effected by series injection of a passive capacitive or inductive element in the line. Alternatively, a static inverter can be used to realize a controllable active loss-less element such as a negative or positive inductor or a synchronous fundamental voltage that is orthogonal to the line current [6], [7]. In the latter case, the power ow depends on the as injected quadrature voltage

(2)

and the bracketed term is unity if . Fig. 1 shows, for equal bus voltage magnitudes, the variation of power ow along a transmission line that can be achieved by injecting a or an active impedance [7]. passive impedance Signicant barriers remain to the widespread commercial deployment of FACTS. Ratings of FACTS devices are often in the 100 MW range, with system voltages of 138 to 500 kV. Further, series injection devices such as TCSC and SSSC, require platforms or custom transformers for isolation, and need to handle fault voltages and currents. This approach to system implementation has resulted in large and complex converter installations and barriers that have, so far, limited the commercial success of FACTS technology. These include: high-cost resulting from device complexity and component requirements; single point of failure can cause the entire system to shut down; maintenance and on-site repair requirements for a complex custom-engineered system adds signicantly to system operating cost and increases mean time to repair (MTTR); lumped nature of system and initial over-rating of devices to accommodate future growth provides poor return on investment (ROI); custom engineered nature of system results in long design and build cycles, resulting in high system cost that will not easily scale down with volume.

644

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007

Fig. 3. DSSC circuit schematic.

Fig. 2. DSSC concept showing clamp-on capability.

III. DISTRIBUTED STATIC SERIES COMPENSATOR (DSSC) A controlled transmission system can be made up of a large number, e.g., hundreds or thousands of DSSC modules, each module containing a small rated (120 kW) single phase inverter, a communications link and a single turn transformer (STT) that is mechanically clamped on toand suspended fromthe transmission line conductor (or insulator). The STT uses the transmission conductor as a secondary winding, directly injecting the desired voltage into the cable itself. The inverter is self-powered by induction from the line, and can be controlled to inject a voltage that is orthogonal to the line current directly into the conductor. The module can either be suspended from the conductor or congured as a replacement for the conductor support clamp on an insulator. Further, since it does not require supporting phase-ground insulation, the module can easily be applied at any transmission voltage level. Fig. 2 shows an electro-mechanical concept diagram for a typical DSSC module, while Fig. 3 shows the power circuit schematic. The mechanical form of the module may either clip-on to the conductor, as shown in Fig. 2, or may be incorporated into the insulator suspension clamp, avoiding any concern about weight and conductor vibration damage. When the transmission line is not powered up, the STT is bypassed by a normally closed relay contact (R1) that opens once control power is available. A current transformer is used to generate control power, allowing the DSSC module to operate as long as the line current is greater than a minimum level, say 150 A. The line appears to the inverter as an inductive current source. The single phase inverter uses four IGBT devices along with an output LC lter and a dc bus capacitance. The inverter output voltage is controlled using pulse width modulation techniques, and has two components. The rst is in quadrature with the line current, and represents the desired impedance to be injected. The second is in phase with the line current, and allows compensation of power losses in the inverter, and regulation of the dc

bus of the inverter. System commands for gradual changes are received from a central control center using a wireless or power line communication (PLC) technique [8]. In the event of rapid transients or faults the DSSC modules can be programmed to operate autonomously. With the DSSC attached and operating at the conductor potential, conductor temperature measurement capability is easily added and actual temperature readings can be communicated to the central system controller. The STT is a key component of the DSSC module. It is designed such that the module can be clamped onto an existing transmission line. The STT is designed with a high turns ratio, . This implies that under a normal line current of say say 1500 A, the inverter would only handle 20 amperes. Designing the inverter for 500 volts rms output would then allow the DSSC module to inject 7 V rms leading or lagging, corresponding to kVAr in series with the line under normal operating conditions. It is anticipated that such a module could be designed to weigh less than 45 kg (100 lb), making the module suitable for direct clamp-on mounting on the transmission conductor. The STT also allows the inverter to possibly continue operating under fault conditions. For instance, at a fault current of 50 000 A, the inverter current is still only 667 A, well within the capability of commercially used IGBT devices. This raises the interesting possibility that unlike TCSCs, the DSSC could regulate line impedance under normal conditions, switching into a maximum inductance injection mode within microseconds to prevent an increase in the fault current levels. The inverter ratings clearly demonstrate that the semiconductors and components used are commercially available in very high volumes for the motor drives, UPS, and automotive industries, thus validating the potential for realizing low cost. IV. OPERATION OF DSSC IN POWER SYSTEMS A controlled transmission line implemented with multiple DSSC modules can realize signicant benets at a system level. At the highest level, it can: enhance asset utilization; reduce system congestion; increase available transfer capacity (ATC) of the system;

DIVAN et al.: DSSC SYSTEM FOR REALIZING ACTIVE POWER FLOW CONTROL

645

TABLE II CALCULATION OF NUMBER OF DSSC MODULES TO CHANGE LINE IMPEDANCE BY 1%

Fig. 4. Meshed network system DSSC implementation.

enhance system reliability and capacity under contingencies; enhance system stability. and can do so with lower capital and operating cost than most conventional single-point lumped solutions, such as FACTS devices. An overall meshed network system implementation is shown schematically in Fig. 4. DSSC modules can be deployed on select lines, or on all lines. Overall operation of the modules is coordinated using a single (or redundant) communication channel (RF or PLC), with a built-in fail-safe operating mode in case of fast transients (such as system faults) or communication link failure. A typical system level command could be for the DSSC modules to emulate a desired impedance or voltage as a function of line current. For instance, the line impedance could automatically increase above a current set point, causing current to be preferentially steered to other lines that are lightly loaded. Operation of the DSSC modules can be coordinated from the system control center to realize a variety of optimization functions or operating conditions including: system optimization, e.g., loss or VAr minimization; maintaining lines out of congestion or below thermal limit; reconguring current ows to compensate for tripped lines; operating lines above steady-state thermal limit under contingency conditions; forcing power to ow along contract paths; controlling power ow through ow-gates; decreasing susceptibility to sub-synchronous resonance; marginal reduction of fault currents; providing damping of system oscillations. The DSSC modules are insensitive to the cable voltage rating, and are targeted for 138 kV to 500 kV systems. The maximum level of impedance control for specic lines is projected at up % of the actual line impedance under rated current to conditions. At lower current levels, the range of impedance control can be correspondingly increased. For instance, at half the nominal current, the impedance control range can be doubled. The distributed nature of the proposed system also provides ne granularity in the system rating, along with the ability to expand the system with demand. System planners can thus plan on increasing the ATC of a line by 2% every year for 10 years to meet

Fig. 5. DSSC control of power ow over parallel lines connecting voltage buses: uncompensated (top) and with DSSC compensation (bottom).

projected growth needs, without having to invest all the capital at project start. Table II shows the characteristics of typical lines at 138 to 765 kV, and examines the applicability of DSSC technology to realistic applications. Transmission lines are considered to be typical and representative. Taking the 138 kV line as an example, it is seen that the reactive voltage drop is 608 V/mile at rated current (corresponding to 0.79 ohms/mile). A 1% change in the impedance thus requires an injection of 6.08 V/mile, corresponding to a combined DSSC rating of 14 kVA/mile based on three phase injection. A varia% in line impedance would thus need 280 kVA or 28 tion of of the 10 kVA DSSC modules/mile or approximately 9 modules per conductor per mile. A. Examples Fig. 5 shows a simple example of how the DSSC can be controlled so as to relieve transmission congestion. Two lines of unequal lengths are used to transfer power from bus 1 to bus 2. The assumed line parameters are listed in Table III. Setting yields line currents of A, and A, and power transferred along the lines is MW and MW, for a total power transfer of 268 MW between the buses. by 20% and Assuming a DSSC in each line, increasing by 20% allows use of a larger phase angle decreasing , which results in A giving MW, and A and MW, for a total power transfer of 319 MW between the buses. These results are summarized in Table IV. The power transferred through line 2 has increased by almost 50%, while line 1 has been controlled to well within its thermal limit. Approximately 10.9 MVA of control action,

646

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007

TABLE III LINE PARAMETERS FOR EXAMPLE OF FIG. 5

TABLE V COST COMPARISON FOR LUMPED VERSUS DISTRIBUTED SOLUTIONS IN A 138 KV/750 A LINE (U.S. DOLLARS)

TABLE IV POWER TRANSFER BETWEEN TWO BUSES

achieved with 1092 DSSC modules spread over 50 miles of transmission lines7.3 modules per mile per conductor, resulted in 51 MW of additional power ow between buses. This number would be even more advantageous at higher system voltages. This simple example conrms the ability of the DSSC to control loop ows, to manage congestion, and to increase the power handling capacity of transmission lines. V. LUMPED VERSUS DISTRIBUTED SOLUTIONS The distributed nature of the DSSC system provides several benets. A signicant benet accrues from the ability to stage capital investments over a longer time, and being able to match the investment with the actual need or demand. For instance, system planners exploring the addition of a FACTS system such as an SSSC or a phase shifting transformer to increase line ATC would typically plan on a 30 year system operating life, and have to design the system to handle the growth in demand expected over that period. Since only a portion of the system capacity would be usefully deployed in the rst year, this suggests that the return on capital employed (ROCE), a key nancial metric for most organizations, would be low. By way of contrast, a system implemented with DSSC could be expanded every year in tandem with actual load growth, and would maximize the utilization of capital. A simple example is used to show the difference. The 30 mile transmission line shown in Fig. 5 is assumed to operate with an average line current of 340 A (45% of thermal limit), growing at 2.5% per year to 713 A (95% of thermal limit) in 30 years. Lumped and distributed series compensators (or phase shifting transformer) are to be compared as solutions to control power ow on the line. Ratings for the two solutions are: 1) Lumped: a 19.13 MVA SSSC installed beginning of year 1; 2) Distributed: 0.64 MVA of DSSCs installed annually for 30 years. Deployment of either solution allows power ow to increase from 81.2 MW in year one to 170.3 MW by year 30.

Signicant differences are seen to occur in capital cost and operating cost (energy losses) for the two solutions. Table V summarizes the overall impact on cost of ownership. Assumptionsfor the purposes of the example summarized in Table Vinclude U.S.$ 100/kVA rst cost for either solution, a 6% annual cost of capital over 30 years, 2.5% per annum load growth, nominal energy losses of 2.5% (under full voltage and current conditions) and an energy cost of U.S.$ 25/MWh. With todays FACTS capital costs at U.S.$ 120U.S.$ 150/kVA, and DSSC costs expected to be well below U.S.$ 100/kVA, the advantages of the distributed system appear even more compelling. Another important issue relates to the inaccuracy of the estimated growth rates that are the basis of the economic decision. If the achieved rate of demand growth is lower than the projected 2.5%, the distributed solution can be deployed only as required, with minimal impact on the overall cost recovery and return on investment. On the other hand, for lumped solutions, a slower rate of growth would dramatically reduce the return on investment. VI. OPERATIONAL AND ECONOMIC BENEFITS From an operational perspective, the following characteristics may be realized for DSSC systems: ability to increase or decrease steady state line current under system controller command, or autonomously; ability to monitor actual conductor temperature and manually or automatically limit currents as a function of conductor temperature; high system reliability due to massive redundancy, single unit failure has negligible impact on system performance; zero footprint solution; robust and rugged under typical fault conditions; can be used with conventional or advanced conductors; mass produced modules can be stocked on the shelf, and repaired in the factorydoes not require skilled staff on site; easy and rapid installation (may be possible on live line). These operational benets, in turn, lead to signicant economic benets. These include: simple scalable tool for congestion managementincrease ATC and revenues; improves contingency management capabilityreduce TLR calls and meet contingency operating requirements without building new lines; minimize loop ows and wheeling lossesimproved asset utilization and lower operating cost; reduce trapped capital in assets sized for future projected growthimproves return on capital employed (ROCE);

DIVAN et al.: DSSC SYSTEM FOR REALIZING ACTIVE POWER FLOW CONTROL

647

Fig. 6. DSSC prototype with suspension clamps.

TABLE VI PROTOTYPE DSSC MODULE SPECIFICATIONS

Fig. 7. DSSC start-up waveforms at 1500 Arms.

Fig. 8. DSSC steady-state waveforms at 1500 Arms and maximum positive injection. Note: voltage amplitude is scaled by a factor of 100.

Key module specications are summarized in Table VI. The power losses in the DSSC module were measured using a Voltech model PM 3000A power analyzer. A. Module Testing Results Laboratory testing was done at 480 Vrms with a 3000 kVA transformer (5.75% impedance) source and resistive loads. Fig. 7 shows operating waveforms as the module starts up at 1500 Arms. The inverter voltage is in phase with the line current as real power is extracted from the line to charge the inverter DC bus capacitors. Fig. 8 shows steady-state operating waveforms; note that the injected voltage is orthogonal to the line current, and represents a positive inductance injection. In case of overload current levels, e.g., with transmission faults, the DSSC protects itself by quickly shorting the transformer primary winding, rst using the inverter IGBTs, then with a normally closed mechanical relay. Unlike solutions such as the TCSC, the DSSC modules do not contribute to the system fault current, and actually operate to reduce it. The protection features were demonstrated under simulated 15 000 Arms current surge conditions by temporarily switching 1 500 A into a ten-turn coil that was placed in parallel with the single-turn line conductor carrying 350 Arms initially. Fig. 9 shows the resulting voltage and combined effective current waveforms at full negative insertion output. The DSSC inverter voltage can be seen to quickly collapse to zero during the current surge.

improves exibility of locating new generation and allows power ow along the contract pathenables bulk energy trading and reduces overall energy costs; incrementally increase line capacity and defer new line constructionminimize environmental impact, right of way, and NIMBY issues VII. EXPERIMENTAL VERIFICATION A prototype module was designed, built, and tested to validate the DSSC concept. The DSSC module, shown in Fig. 6, is completely enclosed and designed for suspension from a transmission line. It operates in a self-exciting mode, drawing a small real power component from the line for control power and internal losses. This prototype was not designed for extended operation suspended on HV transmission systems, nor for minimization of corona effects.

648

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007

Fig. 9. DSSC operation under 7-cycle 15k Arms fault current. Note: voltage amplitude is scaled by a factor of 10.

Fig. 11. Current steering effect of DSSC quadrature voltage injection as injected voltage is varied from maximum negative injection at time zero, to maximum positive injection at time 10 s, to zero injection at time 25 s.

these losses can be considerably reduced in a nal production version of the DSSC, through optimization of component materials.
Fig. 10. Simulated parallel transmission lines lab setup. Values are per unit on a 480 V, 333 kW base. Line 1 is on top, Line 2 on the bottom.

VIII. CONCLUSION This paper has presented the novel concept of a DSSC that uses multiple low-power single-phase inverters that clip-on to the transmission conductor to dynamically control the impedance of the transmission line allowing control of active power ow on the line. The DSSC inverters are self-powered by induction from the line itself, oat electrically on the transmission conductors, and are controlled using wireless or power line communication techniques. Implementation of system level control uses a large number of DSSC modules that are deployed and controlled as a group to realize active control of power ow. The DSSC can be used to either increase or decrease the line impedance, allowing current to be pushed away from or pulled into a transmission line in a networked system. The DSSC concept overcomes some of the most serious limitations of FACTS devices, and points the way to a new approach for achieving power ow controlthe use of Distributed FACTS or D-FACTS devices. This paper details the principles of operation of the DSSC, shows operating results from a prototype device, and presents a preliminary analysis of its possible impact on typical power systems. Although many aspects of implementation have yet to be explored, this paper has demonstrated the fundamental concept is sound and the economics are compelling. ACKNOWLEDGMENT The authors acknowledge the contributions of Rick Mills in his work on the DSSC prototype packaging. REFERENCES
[1] S. Abraham, National Transmission Grid Study U.S. Dept. Energy, May 2002 [Online]. Available: http://www.eh.doe.gov/ntgs/. [2] W. J. Museler, President and CEO of the New York Independent System Operator (NYISO) May 22, 2003. New York City [Online]. Available: http://www.nyiso.com/topics/articles/news_ releases/2003/pa3_presentation.pdf.

The unit automatically restarted at its previous command point after the fault current condition cleared. B. Current Steering in Parallel Transmission Lines A laboratory simulation of parallel transmission lines between a voltage bus and a load bus was congured as shown in Fig. 10. Identical inductors were placed in series with each of two 500 kcmil cables to provide a representative per unit line impedance. The DSSC is represented as a variable inductance. in Fig. 10, injected quadrature voltage to effectively change the line currents while keeping the DSSC current above the operational minimum of 330 Arms. The resulting rms current proles, as the DSSC output is varied, are shown in Fig. 11. The effects of pushing current away and pulling current into the controlled line are evident. By design, this prototype unit operates with line currents down to 330 A. DSSC designs operational to 100 A or less are possible. C. Extension to Transmission System Usage The module test data allow us to calculate the impact of deploying the DSSC modules in a power system, such as that depicted in Fig. 5. Assuming 10 modules per conductor mile, one sees that the energy losses when the system is in bypass mode total 800 watts/mile at 1 000 A. The insertion inductance in bypass mode is 8 H/mile or 0.003 ohms, as compared with a typical transmission conductor impedance of approximately 0.8 ohms/mile, representing a 0.37% change in line impedance. When the system is operating at full output, the total DSSC system losses are estimated at 14.7 kW/mile (for three phases) to achieve a 5.1% increase in current and MVA, compared with 239 MVA of power owing through the transmission system at the rated operating point (138 kV/1000 A). It is anticipated that

DIVAN et al.: DSSC SYSTEM FOR REALIZING ACTIVE POWER FLOW CONTROL

649

[3] N. Hingorani, Flexible AC transmission, IEEE Spectr., vol. 30, no. 4, pp. 4045, Apr. 1993. [4] D. M. Divan, W. Brumsickle, and R. Schneider, Distributed oating series active impedance for power transmission systems, U.S. Patent 7 105 952, Sep. 2006. [5] D. J. Gotham and G. T. Heydt, Power ow control and power ow studies for systems with FACTS devices, IEEE Trans. Power Syst., vol. 13, no. 1, pp. 6065, Feb. 1998. [6] D. M. Divan, Non-dissipative switched networks for high power applications, Inst. Elect. Eng. Electron. Lett., pp. 277279, Mar. 20, 1984. [7] L. Gyugyi, C. D. Schauder, and K. K. Sen, Static synchronous series compensator: A solid-state approach to the series compensation of transmission lines, IEEE Trans. Power Del., vol. 12, no. 1, pp. 406417, Jan. 1997. [8] D. J. Marihart, Communications technology guidelines for EMS/SCADA systems, IEEE Trans. Power Del., vol. 16, no. 2, pp. 181188, Apr. 2001.

Randal W. Gascoigne received the B.S.E.E. degree from the University of WisconsinMadison in 1982. He was with the University of WisconsinMadison, engineering custom instrumentation and controls for a wide variety of applications. From 1987 to 1995, he was a Lab Manager with the staff of the Wisconsin Electric Machines and Power Electronics Consortium (WEMPEC). From 1995 to 2004, he was a Senior Engineer for Soft Switching Technologies (SST), Middleton, WI, where he continued to apply his expertise in circuit design, component selection/specication, and packaging/system design. He also designs and builds electrical sh barrier controllers for the Wisconsin Department of Natural Resources, and enjoys applying electronics to provide unique solutions to problems in other elds of endeavor.

Deepak M. Divan (S78M78SM91F98) is Professor in the School of Electrical and Computer Engineering and Director of the IPIC Consortium at the Georgia Institute of Technology (Georgia Tech), Atlanta. He is Chairman and Chief Technology Ofcer for Innovolt, Atlanta. From 1995 to 2004, he was Chairman and CEO/CTO of Soft Switching Technologies, a company in the industrial power quality market. His research interests are in the application of power electronics for power quality, power reliability, and utility and industrial applications. He has more than 200 papers and 28 issued and 4 pending patents. Dr. Divan was the recipient of the 2006 IEEE William E. Newell Award for contributions in power electronics. He is a Member at Large of the IEEE Power Electronics Society and is PESC Steering Committee Chair for the society. He is Technical Chair for the 1991 PESC Conference and Chairman and Transactions Editor for the IAS-IPCC committee. William E. Brumsickle (A89S92M98SM05) received the B.S. degree in physics from the University of Washington, Seattle, in 1982, and the M.S. and Ph.D. degrees in electrical engineering (power and energy systems) from the University of Wisconsin-Madison in 1995 and 1998, respectively. He was an Applications Engineer for static power conversion products at Enerpro, Inc., Goleta, CA, from 1985 to 1992. From 1992 to 1998, he participated in Wisconsin Electric Machines and Power Electronics Consortium (WEMPEC) research projects in soft switching converters, active lters, power-electronics building blocks (PEBB), large-scale uninterruptible power supplies (UPS), and traction drive applications of high-voltage insuated-gate bipolar transistors (IGBTs). In 1998, he joined Soft Switching Technologies, Middleton, WI, where he is Director of Engineering. His research interests include power-electronics conversion for utility and industrial applications, soft switching inverter design and control, and the physics, monitoring, and mitigation of power-quality disturbances. Robert S. Schneider (M90) received the B.S. degree in physics from the University of WisconsinEau Claire in 1982 and the M.S. degree in electrical engineering from the University of WisconsinMadison in 1986, where he is currently pursuing a second M.S. degree in controls. Currently, he is a Lead Engineer, Power Electronics, with Soft Switching Technologies (SST), Middleton, WI. He was the Project Leader and Principle Hardware Designer for the rst generation of the DySC line of products that spanned a range of 1.5 kVA through 1.33 MVA. He has more than 18 years of industrial experience in designing and eld testing power-electronic converters and systems, including implementation of photovoltaic, battery storage, motor drive, servo motor, mini-hydroelectric, distributed generation, and powerquality systems. He has been involved in automatic voltage regulators, single-tothree-phase motor drives, and the introduction of demand ow manufacturing technology for DySC products. He is a Co-inventor of three of SSTs patented product technologies. He is a licensed Professional Engineer in the State of Wisconsin. Bill Kranz received the B.S. degree in electrical engineering from the University of WisconsinMadison in 1999. Currently, he is a Lead Engineer, Embedded Controls, with Soft Switching Technologies Corp., Middleton, WI. His research interests include real-time software and analog controls for industrial and utility power protection systems, power quality, and voltage monitoring equipment, and fuecell-based inverters.

Dale T. Bradshaw (M98) is President of Electrivation, Chattanooga, TN. He is External Program Coordinator for National Rural Electric Cooperative Associations (NRECA) Cooperative Research Networks (CRN) Transmission Reliability and Security Advisory Group; Emerging Technology Team Leader for the U.S. DOE NETLs Modern Grid Initiative and University of California, San Diegos Smart Grid; Consultant to the California Institute for Energy and Environment (CIEE) Transmission Research Program; Consultant to Navigant on the assessment of DOEs High Temperature Superconductivity Program; Project Manager for an NRECA Project to identify options for mitigating transmission congestion; Director of Marketing for V&R Energys Physical Operating Margin (POM) suite of transmission system analysis software; Technical Advisor to DOEs Ofce of Electric Transmission and Distribution (OETD); Business Development Consultant for Intelicis; Consultant for a major U.S. ywheel manufacturer; CTO for Advanced Coal Technologies LLC; and a GLG Leader consulting with Gerson Lehrman Groups Council of Advisors. He was with the Tennessee Valley Authority and was Senior Manager of Power Delivery Technology from 1996 until 2004, where he developed projects that improved transmission grid operations with operational planning, transmission asset utilization with the transmission planning group, and transmission performance with transmission operations. He and his staff developed, demonstrated, and/or implemented transmission planning optimization software, improved conductor splice repair, improved transmission oil analysis, improved transmission oil additives, dynamic line rating systems, reduced cost capacitor design, and lower cost dynamic reactive compensation systems.

Michael R. Ingram (M91SM96) received the B.E.E. degree (Hons.) from Auburn University, Auburn University, AL, and the M.S. degree in engineering management from the University of Tennessee, Chattanooga. Currently, he is the Senior Manager of Transmission Technologies with the Tennessee Valley Authority (TVA), Chattanooga, TN. He is responsible for the research, development, and demonstration of new technologies which improve electrical quality and reliability, increase power ow, and reduce operating expense of the TVA transmission system and interconnected distribution network. He provides advice to TVA executives on new technology solutions affecting the T&D networks and sets strategy for research and development in areas of energy storage, power quality, power/transmission markets, exible ac transmission systems (FACTS), and superconductivity. He has been with TVA for 17 years, working in technical project management, protection and control engineering, and substation design. He has authored or coauthored more than 30 technical papers and articles within his area. Mr. Ingram was the Chairman or Committee Member of several users and working groups of IEEE, EPRI, and CIGRE. He was named Outstanding Young Engineer of the Year (2001) by The IEEE Power Engineering Society. He was named Engineer of the Year in 2001 and 2006 by the TVA. Additionally, he was a 2001 and 2006 top-ten nalist for Federal Engineer of the Year. Other professional awards include IEEE Millennium Medal; Outstanding Power Engineer of the Year, 1997; and Chattanooga-Area Young Engineer of the Year, 1996.

Ian S. Grant (F87) received the B.E. degree from the University of New Zealand, Auckland, in 1962 and the M.E. degree from the University of New South Wales, Sydney, Australia, in 1967. After graduation, he joined the Electricity Commission of NSW, Sydney, Austalia, followed by General Electric Co. High Voltage Laboratory, Pittseld, MA; Power Technologies, Inc., Schenectady, NY; Evonyx, Inc., Hawthorn, NY; and the Tennessee Valley Authority (TVA), Chattanooga, TN. Currently, he is Planning Coordinator with TVAs Transmission Reliability Operation. He is the author or coauthor of more than 45 papers and books on transmission design, lightning and transient studies, and insulation coordination.