DAIKIN

SERIES: EWAD~CF (Standard Glycol)

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

R3.6.2

GENERAL CHARACTERISTICS
Cabinet and structure The cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. Colour Ivory White (Munsell code 5Y7.5/1) (RAL7044).The base frame has an eye-hook to lift the unit with ropes for an easy installation. The weight is uniformly distributed along the profiles of the base and this facilitates the arrangement of the unit. Compressor (Asymmetric Single Screw) The compressor is semi-hermetic, single-screw type with gate-rotor made with the latest high-strength fibre reinforced star material. The compressor has an asymmetric slide regulation managed by the unit controller for infinitely modulating capacity from 100% to 25%. An integrated high efficiency oil separator maximizes the oil separation and standard start is Wye-Delta (Y- ) type. Refrigerant The compressors have been with zero ODP (Ozone Depletion Potential) in low TEWI (Total Equivalent Warming Impact). designed to operate and very low GWP with R-134a, ecological refrigerant (Global Warming Potential), resulting shell&tube evaporator with tubes are enhanced for for pure counter-flow heat to the heat exchanger designed for 10 bar of and the evaporator water has 2 circuits, one for

Evaporator (Shell&Tube) The unit is equipped with a direct expansion refrigerant evaporating inside the tubes and water flowing outside. The maximum heat transfer and rolled into steel tube sheet and sealed. The evaporators are single-pass on both the refrigerant and water sides exchange and low refrigerant pressure drops. Both attributes contribute effectiveness and total units outstanding efficiency. The water side is maximum operating pressure and is provided with vents and drain. The external shell is covered with a 20mm closed cell insulation material connections are provided with victaulic kit (as standard). Each evaporator each compressor and is manufactured in accordance to 97/23/EC directive (PED).

Condenser (Air Refrigerant heat exchanger) The condenser is manufactured with internally enhanced seamless copper tubes arranged in a staggered row pattern and mechanically expanded into lanced and rippled aluminum condenser fins with full fin collars. An integral sub-cooler circuit provides sub-cooling to effectively eliminate liquid flashing and increase cooling capacity without increasing the power input. Free Cooling (Air Water heat exchanger) The Free Cooling heat exchanger is with internally enhanced seamless copper tubes arranged in a staggered row mechanically expanded into lanced and rippled aluminum condenser fins with full fin collars. manufactured pattern and

Page 1 of 7

DAIKIN

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

Condenser fans ( 800) The condenser fans are propeller type with high efficiency design blades to maximize performances. The material of the blades is glass reinforced resin and each fan is protected by a guard. Fan motors are protected by circuit breakers (installed inside the electrical panel as a standard) and are IP54. Fan speed regulation is standard available (Option 99). Electronic expansion valve The unit is equipped with the most advanced electronic expansion valves to achieve precise control of refrigerant mass flow. As todays system requires improved energy efficiency, tighter temperature control, wider range of operating conditions and incorporate features like remote monitoring and diagnostics, the application of electronic expansion valves becomes mandatory. Electronic expansion valves possess unique features: short opening and closing time, high resolution, positive shut-off function to eliminate use of additional solenoid valve, continuous modulation of mass flow without stress in the refrigerant circuit and corrosion resistance stainless steel body. Electronic expansion valves are typically working with lower P between high and low pressure side, than a thermostatic expansion valve. The electronic expansion valve allows the system to work with low condenser pressure (winter time) without any refrigerant flow problems and with a perfect chilled water leaving temperature control. Refrigerant circuit Each unit has 2 independent refrigerant circuits and each one includes: Compressor with integrated oil separator Refrigerant Evaporator Air Cooled Condenser Electronic expansion valve Discharge line shut off valve Liquid line shut off valve Sight glass with moisture indicator Filter drier Charging valves High pressure switch High pressure transducers Low pressure transducers Oil pressure transducer Suction temperature sensor Free Cooling Water Circuit
"Standard Glycol" Free Cooling The principal hydraulic circuit is connected directly (through a three way valve) with the free cooling section, creating a circuit with a water-glycol mixture. The free cooling section includes: Air-water heat exchanger Three way valve (as standard)

Electrical control panel Power and control are located in the main panel that is manufactured to ensure protection against all weather conditions. The electrical panel is IP54 and (when opening the doors) internally protected against possible accidental contact with live parts. The main panel is fitted with a main switch interlocked door that shuts off power supply when opening.
Power Section The power section includes compressors and fans protection devices, compressors and fans starters and control circuit power supply.

Page 2 of 7

DAIKIN
MicroTech III controller

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

MicroTech III controller is installed as standard; it can be used to modify unit set-points and check control parameters. A built-in display shows chiller operating status plus temperatures and pressures of water, refrigerant and air, programmable values, set-points. A sophisticated software with predictive logic, selects the most energy efficient combination of compressors, EEXV and condenser fans to keep stable operating conditions to maximise chiller energy efficiency and reliability. MicroTech III is able to protect critical components based on external signals from its system (such as motor temperatures, refrigerant gas and oil pressures, correct phase sequence, pressure switches and evaporator). The input coming from the high pressure switch cuts all digital output from the controller in less than 50ms, this is an additional security for the equipment. Fast program cycle (200ms) for a precise monitoring of the system. Floating point calculations supported for increased accuracy in Pressure / Temperature conversions. Control section - main features Control Section has the following feature. Management of the compressor stepless capacity and fans modulation. Chiller enabled to work in partial failure condition. Full routine operation at condition of: - high ambient temperature value - high thermal load - high evaporator entering water temperature (start-up) Display of evaporator entering/leaving water temperature. Display of Outdoor Ambient Temperature. Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each circuit. Leaving water evaporator temperature regulation (temperature tolerance = 0,1C). Compressor and evaporator pumps hours counter. Display of Status Safety Devices. Number of starts and compressor working hours. Optimized management of compressor load. Fan management according to condensing pressure. Re-start in case of power failure (automatic / manual). Soft Load (optimized management of the compressor load during the start-up). Start at high evaporator water temperature. Return Reset (Set Point Reset based on return water temperature). OAT (Outside Ambient temperature) Reset. Set point Reset (optional). Application and system upgrade with commercial SD cards. Ethernet port for remote or local servicing using standard web browsers. Two different sets of default parameters could be stored for easy restore. Safety device / logic for each refrigerant circuit The following devices / logics are available. High pressure (pressure switch). High pressure (transducer). Low pressure (transducer). Fans circuit breaker. High compressor discharge temperature. High motor winding temperature. Phase Monitor. Low pressure ratio. High oil pressure drop. Low oil pressure. No pressure change at start. System security The following securities are available. Phase monitor. Low Ambient temperature lock-out. Freeze protection. Regulation type Proportional + integral + derivative regulation on the evaporator leaving water output probe.

Page 3 of 7

DAIKIN
MicroTech III

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

MicroTech III built-in terminal has the following features. 164x44 dots liquid crystal display with white back lighting. Supports Unicode fonts for multi-lingual. Key-pad consisting of 3 keys. PushnRoll control for an increased usability. Memory to protect the data. General faults alarm relays. Password access to modify the setting. Application security to prevent application tampering or hardware usability with third party applications. Service report displaying all running hours and general conditions. Alarm history memory to allow an easy fault analysis.

Supervising systems (on request)


MicroTech III remote communication MicroTech III is able to communicate to BMS (Building Management System) based on the most common protocols as: ModbusRTU LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology. BacNet BTP certifief over IP and MS/TP (class 4) (Native). Ethernet TCP/IP.

Page 4 of 7

DAIKIN
TECHNICAL SPECIFICATIONS
MODEL Capacity - Cooling Capacity control - Type Unit power input - Cooling EER ESEER IPLV CASING Colour * Material * DIMENSIONS Height Width Length WEIGHT Unit Weight Operating Weight WATER HEAT EXCHANGER Type * Fluid Fouling factor Water Volume Water temperature (in/out) Nominal water flow rate - Cooling Nominal Water pressure drop - Cooling ** Insulation material * AIR HEAT EXCHANGER Type * FAN Type * Drive * Diameter Nominal air flow Air temperature Altitude Quantity Speed Motor input COMPRESSOR Type Oil charge Quantity SOUND LEVEL Sound Power - Cooling Sound Pressure - Cooling REFRIGERANT CIRCUIT Refrigerant type Refrigerant charge N. of circuits PIPING CONNECTIONS Evaporator water inlet/outlet kg No. dB(A) dB(A) l No. mm l/s C mslm No. rpm kW m C/W l C l/s kPa kg kg mm mm mm kW kW

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

EWADC12CFXS

1118 Stepless 386 2,89 3,88 4,36

IW GPSS

2565 2480 10685

11900 13276

S&T Ethylene Glycol 40% 0,0000176 1372 12,0/6,0 50,4 88 CC

HFP

DPT VFD 800 95253 37,0 0 20 920 29,6

Asymm Single Screw 50 2

102 80

R134a 214 2

DN200 PN16 (219,1)

* IW: Ivory White - GPSS: Galvanized and Painted Steel Sheet - PHE: Plate Heat Exchanger - S&T: Single Pass Shell & Tube * CC: Closed Cell - HFP: High efficiency fin and tube type with integral subcooler - DPT: Direct Propeller Type - VFD: Inverter SPD: Speedtroll ** If value is "Italic-Red Color" please contact factory

Page 5 of 7

DAIKIN
FREE COOLING MODE
MODEL Free Cooling Version Energy Option TECHNICAL DATA Unit capacity - Cooling Free cooling capacity Mechanincal capacity Unit power input - Cooling EER Air Temperature Water temperature - inlet Water flow rate - Cooling Water pressure drop - Cooling FREE COOLING 100% Air Temperature for Free Cooling 100% C kW kW kW kW --C C l/s kPa

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

EWADC12CFXS Standard Glycol Standard Free Cooling

1118 654 464 102 11,00 5,0 12,0 50,4 215

0,0

ELECTRICAL SPECIFICATIONS
MODEL POWER SUPPLY Phases Frequency Voltage Voltage tolerance Minimum Voltage tolerance Maximum UNIT Maximum starting current Nominal running current cooling Mximum running current Maximum current for wires sizing Running current (1) FANS Nominal running current cooling COMPRESSORS Phases Voltage Voltage tolerance Minimum Voltage tolerance Maximum Maximum running current Starting method Nr V % % A --3 400 -10% +10% 333 398 YA 80 A A A A A 1030 636 811 884 198 Nr Hz V % % 3 50 400 -10% +10% EWADC12CFXS

Fluid: + Ethylene Glycol 40% Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%. Nominal current in cooling mode is referred to the following conditions: evaporator 12/7C; ambient 35C; compressors + fans current. Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current Maximum unit current for wires sizing is based on minimum allowed voltage Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1. (1) Running current based on the following conditions: evaporator 12,0/6,0C; ambient 5,0C

Page 6 of 7

DAIKIN
SOUND LEVELS

Chiller selection software


CSS - Rev. 8.2 Printing date: 12/12/2013

Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa) MODEL EWADC12CFXS 63 Hz 75,2 125 Hz 77,3 250 Hz 80,1 500 Hz 79,3 1000 Hz 75,2 2000 Hz 70,7 4000 Hz 61,1 8000 Hz 52,0 dB(A) 80,3

Power dB(A) 102,4

Fluid: + Ethylene Glycol 40% Note: The values are according to ISO 3744 and are referred to: evaporator 12/7 C, air ambient 35 C, full load operation

Page 7 of 7