U-1000 AR2V
Construction:

NF C 32-321
C 32-321/A1
IEC 60502-1

Flame propagation:

NF EN 60332-1-2

Low Voltage Directive: 2006/95/EC


2011/65/EC

www.latrivenetacavi.com

RoHS Directive:

review n 000 date 14/05/12

Description




Installation conditions

Conductor: aluminium, stranded wire, class 2


Insulation: XLPE (cross-linked polyethylene)
Filler: thermoplastic
Sheath: PVC
Colour: black

Functional characteristics


Minimum installation temperature: -10C


Recommended minimum bending radius: 8 times
the cable diameter
Recommended maximum tensile stress: 50 N/mm
of the cross-section of the conductor
Use and installation method

Rated voltage Uo/U: 0,6/1 kV


Max. operating temperature: 90C
Min. operating temperature: -25C
(without mechanical shocks)
Max. short circuit temperature: 250C

For use on industrial sites. Particularly suited in cases of


high operating temperatures and when high resistance
to solar radiation and atmospheric agents is required.
Good resistance to low temperatures and chemical
agents. Can be used without additional mechanical
protection in the open air, fixed to walls or in raceways,
inside gangways or in empty spaces in constructions in
general. Can be laid underground with mechanical protection constructed from slabs, tiles, or bricks. It is not
recommend to lay this cable in ground flooded for more
than two months per year. With appropriate mechanical
protection, it can be used in areas subject to the risk of
explosion, but in this case the permitted current load is
reduced by 15%.

Single-core
Max.
electrical
resistance
at 20C

Formation

Approx.
conductor

Average
insulation
thickness

Min.
sheath
thickness

Max.
external

n x mm2

mm

mm

mm

mm

/km

1 x 10

4,1

0,7

1,09

9,2

1 x 16

4,9

0,7

1,09

1 x 25

6,1

0,9

1 x 35

7,1

1 x 50

Approx.
cable
weight

Current rating
A

kg/km

free air
at 30C

buried
at 20C

3,08

85

62

67

10,5

1,91

115

84

87

1,09

12,5

1,20

150

101

111

0,9

1,09

13,5

0,868

185

126

134

8,2

1,0

1,09

15,0

0,641

230

154

160

1 x 70

9,9

1,1

1,09

17,0

0,443

310

198

197

1 x 95

11,4

1,1

1,18

19,0

0,320

410

241

234

1 x 120

13,1

1,2

1,18

21,0

0,253

505

280

266

1 x 150

14,4

1,4

1,26

23,0

0,206

620

324

300

1 x 185

16,2

1,6

1,26

25,5

0,164

740

371

337

1 x 240

18,4

1,7

1,35

28,5

0,125

950

439

388

1 x 300

20,7

1,8

1,43

31,0

0,100

1190

508

440

Permissible current rating values are according to:


- a three-phase circuit
- a buried cable with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm
If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).

Two-core and three-core


Max.
electrical
resistance
at 20C

Formation

Approx.
conductor

Average
insulation
thickness

Min.
sheath
thickness

Max.
external

n x mm2

mm

mm

mm

mm

/km

2 x 10

4,1

0,7

1,43

16,0

2 x 16

4,9

0,7

1,43

2 x 25

6,1

0,9

2 x 35

7,1

3 x 16

Approx.
cable
weight

Current rating
A

kg/km

free air
at 30C

buried
at 20C

3,08

290

67

80

18,5

1,91

330

91

104

1,43

22,0

1,20

525

108

133

0,9

1,43

24,5

0,868

655

135

160

4,9

0,7

1,43

19,5

1,91

405

77

87

3 x 25

6,1

0,9

1,43

23,5

1,20

590

97

111

3 x 35

7,1

0,9

1,43

26,0

0,868

730

120

134

3 x 50

8,2

1,0

1,43

29,0

0,641

930

146

160

3 x 70

9,9

1,1

1,52

34,0

0,443

1295

187

197

3 x 95

11,4

1,1

1,60

38,5

0,320

1695

227

234

3 x 120

13,1

1,2

1,69

42,5

0,253

2030

263

266

3 x 150

14,4

1,4

1,86

47,5

0,206

2510

304

300

3 x 185

16,2

1,6

1,94

53,0

0,164

3220

347

337

3 x 240

18,4

1,7

2,11

59,5

0,125

4990

409

388

3 x 300

20,7

1,8

2,28

66,0

0,100

6650

471

440

Permissible current rating values are according to:


- a single-phase circuit for two-core cables
- a three-phase circuit for three-core cables
- a buried cable with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm
If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).

Four-core with reduced cross-section


Formation

Approx.
conductor

Average
insulation
thickness

Min.
sheath
thickness

Max.
external

n x mm2

mm

mm

mm

mm

3 x 50 + 35

8,2/7,1

1,0/0,9

1,43

31,1

3 x 70 + 50

9,9/8,2

1,1/1,0

1,60

3 x 95 + 50

11,4/8,2

1,1/1,0

3 x 120 + 70

13,1/9,9

3 x 150 + 70

Max.
electrical
resistance
at 20C

Approx.
cable
weight

Current rating
A

kg/km

free air
at 30C

buried
at 20C

0,641/0,868

1040

146

160

36,2

0,443/0,641

1460

187

197

1,69

40,6

0,320/0,641

1925

227

234

1,2/1,1

1,77

45,4

0,253/0,443

2325

263

266

14,4/9,9

1,4/1,1

1,86

49,5

0,206/0,443

2755

304

300

3 x 185 + 70

16,2/9,9

1,6/1,1

2,03

54,4

0,164/0,443

3265

347

337

3 x 240 + 95

18,4/11,4

1,7/1,1

2,20

61,5

0,125/0,320

4230

409

388

/km

Permissible current rating values are according to:


- a three-phase circuit
- a buried cable with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm
If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).

Four-core and five-core


Max.
electrical
resistance
at 20C

Formation

Approx.
conductor

Average
insulation
thickness

Min.
sheath
thickness

Max.
external

n x mm2

mm

mm

mm

mm

/km

4 x 10

4,1

0,7

1,43

18,5

4 x 16

4,9

0,7

1,43

4 x 25

6,1

0,9

4 x 35

7,1

4 x 50

Approx.
cable
weight

Current rating
A

kg/km

free air
at 30C

buried
at 20C

3,08

370

58

67

21,0

1,91

485

77

87

1,43

25,5

1,20

710

97

111

0,9

1,43

28,5

0,868

890

120

134

8,2

1,0

1,52

32,5

0,641

1115

146

160

4 x 70

9,9

1,1

1,60

37,5

0,443

1575

187

197

4 x 95

11,4

1,1

1,69

42,5

0,320

2050

227

234

4 x 120

13,1

1,2

1,86

47,5

0,253

2408

263

266

4 x 150

14,4

1,4

1,94

52,5

0,206

3010

304

300

4 x 185

16,2

1,6

2,11

59,0

0,164

3930

347

337

4 x 240

18,4

1,7

2,28

66,5

0,125

4900

409

388

4 x 300

20,7

1,8

2,45

73,5

0,100

6120

471

440

5 x 16

4,9

0,7

1,43

23,0

1,91

585

77

87

5 x 25

6,1

0,9

1,43

28,0

1,20

850

97

111

Permissible current rating values are according to:


- a three-phase circuit
- a buried cable with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm
If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).