3HV-I-OUTD-US208/240
Technical Manual
Copyright 2013 Power-One, Inc. All rights reserved. No part of this document may be reproduced in any form without the prior written permission of Power-One. Power-One makes no representations or warranties, express or implied, with respect to the contents of this document. Power-One reserves the right to make changes to this document without notice and shall not be responsible for any damages caused by reliance on the content presented. All trademarks, logos, trade names, service marks and copyrighted materials used in this document are the property of their respective owners. The Power-One name and logo are registered trademarks of Power-One, Inc. in the U.S.A. and other countries. Power-One 3201 E. Harbour Drive Phoenix, AZ 85034 USA 877-261-1374
Page 2 of 62
BCG.00612_AD
Contents
PART 1 1.1 1.2 1.3 PART 2 2.1 2.2 2.3 PART 3 3.1 3.2 3.3 3.4 3.5 PART 4 4.1 4.2 PART 5 5.1 5.2 5.3 5.4 PART 6 6.1 6.2 PART 7 7.1 7.2 7.3 INTRODUCTION AND SAFETY ................................................................................................ 3 INTRODUCTION .................................................................................................................................. 3 SAFETY ............................................................................................................................................ 4 AVAILABLE MODELS .......................................................................................................................... 9 INSTALLATION LOCATION .................................................................................................... 13 TRANSPORTAION AND HANDLING ..................................................................................................... 13 SELECT INSTALLATION LOCATION ..................................................................................................... 14 CHOICE OF AC CABLE ..................................................................................................................... 18 MOUNTING AND WIRING ....................................................................................................... 20 ASSEMBLY DIAGRAM ....................................................................................................................... 20 ASSEMBLY INSTRUCTIONS ............................................................................................................... 21 W IRING DETAILS ............................................................................................................................. 29 CONNECTION TO THE AC DISTRIBUTION GRID (AC SIDE) .................................................................... 30 W IRING OF AC CABLE ..................................................................................................................... 31 OPERATIONS GUIDE .............................................................................................................. 32 DISPLAY AND KEYPAD ..................................................................................................................... 32 COMMISSIONING ............................................................................................................................. 35 TROUBLESHOOTING ............................................................................................................. 38 ALARM MESSAGES GENERATED BY THE MICRO INVERTER ............................................................... 38 VERIFICATION OF GROUND LEAKAGE ............................................................................................... 41 MEASURING THE INSULATION RESISTANCE OF PHOTOVOLTAIC MODULE ............................................ 43 THE POWER-0NE SERVICE CALL ...................................................................................................... 44 MAINTENANCE GUIDE ........................................................................................................... 45 ROUTINE MAINTENANCE .................................................................................................................. 45 STORAGE AND DISMANTLING ........................................................................................................... 46 APPENDIX ................................................................................................................................ 47 TECHNICAL DATA ............................................................................................................................. 47 TEMPLATE FOR MAP OF MICRO INVERTER INSTALLATION ................................................................. 60 INDEX OF TABLES AND FIGURES ....................................................................................................... 61
Page 3 of 62
BCG.00612_AD
1.1.1 PURPOSE
The purpose of this document is to support the qualified technician, who has received training and/or has demonstrated skills and knowledge in construction to install and maintain this MICRO grid tied inverter. This manual does not cover any details concerning equipment connected to the inverter such as the solar modules. Information concerning the connected equipment is available from the respective manufacturer.
1.1.4 WARRANTY
Warranty Conditions can be found on the Power-One Renewable Energy website located in the download section of the AURORA MICRO inverter product page. Any changes or modifications not approved by the responsible party could void the user authority to operate the equipment.
Page 4 of 62 Part 1
BCG.00612_AD
1.2 SAFETY
1.2.1 WARNINGS IN THIS DOCUMENT
This is a list of special safety symbols used in this manual that highlights potential safety risks and/or useful information. The symbol usage is described below: Symbol Usage Indicates a hazardous situation that can result in deadly electric shock hazards, other serious physical injury, and/or fire hazards. DANGER: The reader should stop, use caution, and fully understand the operations explained before proceeding CAUTION: DANGEROUS VOLTAGE The product works with high voltages. All work on the AURORA Inverter must follow the described documentation and must comply with all prevailing codes and regulations associated with high voltages. During inverter operation, parts will be energized at high voltage levels. HOT TEMPERATURE Some surfaces may become hot. Do not touch the product while it is in operation. UL 1741 Standard for Safety for Inverters, Converters, Controllers and Interconnection System Equipment for use with Distributed Energy Resources. CSA CSA-C22.2 No. 107.1-01 - General Use Power Supplies. The enclosed device has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules
WARNING
WARNING
System earth conductor (equipment ground, protective earth) Alternating Current (AC)
Phase
Grounding (earth)
Page 5 of 62 Part 1
BCG.00612_AD
Simulated Utility Source Voltage A V< 50% Vnor (Not Adjustable) B 50%Vnor V< 88% Vnor Adjustable Set Points 55% to 88% C 110%Vnor V< 120% Vnor Adjustable Set Points 110% to 118% D V120% Vnor (Not Adjustable) E Rated F Rated G Rated Rated Rated Rated Rated f > 60.5(Not Adjustable) f < 59.3 (Default)(Adj. Set Points 59.8 Hz to 57.2 Hz) f < 57.0 (Not Adjustable) Frequency
Max.time (sec) at 60Hz before cessation of current to the simulated utility 0.16 sec (Not Adjustable) 2 sec (Default) (Adj. Set Points 0.16 to 5 sec) 1 sec (Default) (Adj. Set Points 0.16 to 5 sec) 0.16 sec (Not Adjustable) 0.16 sec (Not Adjustable) 0.16 sec (Default) (Adj. Set Points 0.16 to 300 sec) 0.16 sec (Not Adjustable)
Page 6 of 62 Part 1
BCG.00612_AD
local power distribution grid company to get appropriate approvals. This connection must be made only by qualified technical personnel Systems with inverters typically require additional control (e.g., switches, disconnects) or protective devices (e.g., fusing circuit breakers) depending upon the local safety regulations. It is the responsibility of the installer to provide external disconnect switches and Overcurrent Protection Devices (OCPD) as required by National Electric Codes and other prevailing regulations. Power-One DOES NOT provide AC output overcurrent protection. To reduce the risk of fire, connect only to a circuit provided with 20A maximum branch circuit overcurrent protection in accordance with the National Electric Code (ANSI/NFPA 70). Make all electrical connections (e.g. conductor termination, fuses, PE connection, etc.) in accordance with the electrical standards prescribed by the applicable National Electric Code, ANSI/NFPA 70 wiring methods and/or by other local regulations and codes. The AC output (neutral) is not bonded to ground. The input and output circuits are isolated from the enclosure and the system grounding shall be installed per the requirements of the National Electric Code, ANSI/NFPA 70, and is the responsibility of the installer.
Do not connect an AURORA MICRO inverter to the electrical distribution grid until after the receipt of a letter of authorization from the authority having jurisdiction. Install the AURORA Inverter in accordance with the electrical standards prescribed by the applicable National Electric Code (NEC), Canadian Electric Code (CEC), and/or by other local codes and regulations. Use personal protective equipment; including gloves and eye protection when working on this unit.
Page 7 of 62 Part 1
BCG.00612_AD
The instructions given in the manual do not replace the information and warnings on the safety labels mounted on the product. They do not replace the safety regulations enforced in the country of installation. It is essential to provide operators with correct information. They must therefore read and comply with the technical information given in the manual and in the attached documentation. Maintenance operations must be carried out according to the Maintenance section in Part 6 of this manual. Do not use the equipment if any operating anomalies are found. Avoid temporary repairs. Liabilities arising from commercial components are delegated to their respective manufacturers.
Warning - Certain parts may be extremely hot immediately following shut down due to normal elevated surface temperatures (e.g. transformers, accumulators, coils etc.). Prior to touching any part of the inverter use care to ensure surfaces and equipment are at touch-safe temperatures and voltage potentials before proceeding. Anytime the inverter has been disconnected from the power network, use extreme caution as some components can retain charge sufficient to create a shock hazard. To minimize occurrence of such conditions, comply with all corresponding safety symbols and markings present on the unit and in this manual.
Page 8 of 62 Part 1
BCG.00612_AD
Page 9 of 62 Part 1
BCG.00612_AD
The inverter can be used only if all the technical characteristics are observed and applied.
This document applies only to the inverter models listed in on the front page of this manual. All model dimensions are 10.5 x 9.7 x 1.37 and weigh 3-1/2 lb (1.65kg
Table 1-2: Inverter models available
Page 10 of 62 Part 1
BCG.00612_AD
01 - Attachment slots 03 - DC connectors 05 - Radio Antenna 02 - Anti-condensation valve 04 - AC cable 06 - Connect/ground clamp For models with an LED on the front, see Part 4, section 4.2, for a description of the LED behavior.
Page 11 of 62 Part 1
BCG.00612_AD
1.3.1 NAMEPLATE
The nameplate shown below is affixed to the inverter and provides the following information:
Certification
Model name
DC Rating
AC Rating
Environmental rating
Serial number
MAC address
Page 12 of 62 Part 1
BCG.00612_AD
Page 13 of 62
BCG.00612_AD
If inspection reveals damage to the inverter, contact the supplier, or authorized distributor for a repair/return determination and instructions regarding the process.
Table 2-1: List of components supplied
Component
AC-TRUNK SPOOL-41 inches-50 plugs
Description
AC cable (4 conductors): 10 AWG Plug (connector) pitch 41 AC cable (4 conductors): 10 AWG Plug (connector) pitch 67 AC cable (4 conductors): 10 AWG Plug (connector) pitch 81 Insulated AC cap for AC Bus connectors (female) End cap for 10 AWG AC cable Tool for releasing connectors
Page 14 of 62 Part 2
BCG.00612_AD
Page 15 of 62 Part 2
BCG.00612_AD
Page 16 of 62 Part 2
BCG.00612_AD
Any maintenance or replacement of the device could require the technician to dismount the photovoltaic module mounted on the top of the MICRO inverter. This condition must be accounted for during the installation ensuring that the safety distances are correct for normal test and maintenance operations. The distance between MICRO inverters installed on the same system array depends on the type of photovoltaic modules and its orientation (horizontal or vertical). Choose the best solution to employ during the project planning stage, bearing in mind that the selected configuration will include the correct type of AC cable.
Page 17 of 62 Part 2
BCG.00612_AD
Page 18 of 62 Part 2
BCG.00612_AD
Power-One Cable Item AC-Trunk Spool 67 inches 32 plugs * Ideal for 60-cell or 96-cell PV modules
Power-One Cable Item AC-Trunk Spool 81 inches 27 plugs * Ideal for 72-cell PV modules
Page 19 of 62 Part 2
BCG.00612_AD
Power-One Cable Item AC-Trunk Spool 41 inches 50 plugs * Ideal for 60-cell, 72-cell, 96-cell PV modules
* Note: The AC-TRUNK SPOOL may contain a number of connectors indicated by the
number of plugs in the part number. The installer may cut the cable to the length needed for the specific installation.
Page 20 of 62
BCG.00612_AD
Page 21 of 62 Part 3
BCG.00612_AD
Page 22 of 62 Part 3
BCG.00612_AD
DC grounding electrode conductor coupling all the MICRO inverters: The conductor must have a minimum cross section of 6 AWG. Tighten with 2Nm (17.7 in-lb) torque.
Page 23 of 62 Part 3
BCG.00612_AD
DC grounding electrode conductors for each MICRO inverter: The conductor linking the assembly to the grounding distribution structure must be at least 6 AWG. Tighten with 2Nm (17.7 in-lb) torque. Ensure that the quality of the bond made between the conductor and the structure is secure. Only a racking system that is certified for use as a grounding structure is permitted to use this method.
Incorrect grounding can cause physical injury, death or equipment malfunction and increase electromagnetic interference. Make sure that grounding conductors are adequately sized as required by safety regulations.
Page 24 of 62 Part 3
BCG.00612_AD
4. Fasten the AC-TRUNK cable to the frame with listed cable ties. Each connector is provided with two guides for ideal fastening. Cable ties are not supplied with the inverter or AC-TRUNK cable. Use listed cable ties rated to 75C.
5. Remove the temporary cap from AC-TRUNK cable connectors and then connect the MICRO inverters. The connectors are coupled correctly when two clicks are heard. Be mindful to keep the connectors in a position accessible to the AC-TRUNK cable coming from the MICRO inverter.
Protect any unused AC-TRUNK cable connectors by fitting the AC-TRUNK PLUG CAP on them to keep them watertight. The temporary caps are only attached for shipping and provide no seal!
Page 25 of 62 Part 3
BCG.00612_AD
6. Fit the appropriate AC-TRUNK END CAP on the unused ends of the ACTRUNK cable.
7. Connect the AC-TRUNK cable/s coming from the MICRO inverters to the junction box or to the AC distribution panel.
8. Draw a map of the system, affixing the extra label that comes attached to each inverter, on the appropriate position on the diagram (found in the Appendix of this manual).
Page 26 of 62 Part 3
BCG.00612_AD
9. Plug the DC cables into the corresponding inputs on the MICRO inverters and install the photovoltaic modules.
The recommended installation entails keeping the MICRO inverters underneath the photovoltaic modules, having them operate in the shade. Direct sunlight could cause elevated temperatures and consequently power limiting. Each module must be connected to the MICRO-Inverter with a DC cable having a length of less than 3m.
10. The inverter will not begin to feed energy into the distribution grid until the association procedure of the CDD (Concentrator Data Device) has been completed. It is required that an AURORA CDD be installed with any AURORA MICRO inverter in compliance with UL1741, for the purpose of indication and resetting of ground faults. See the AURORA CDD Instruction Manual for the procedures.
Page 27 of 62 Part 3
BCG.00612_AD
The following is necessary for properly installing the cap: 1 2 3 4 5 6 Fit the ring nut and gasket around the cross section of the cable to terminate. Strip 18-25 mm/0.7in 1in of the external insulation and separate each conductor. Insert the conductors into the recesses inside the cap to seal them. Insert the gasket into the cap with slight pressure. Screw the ring nut to apply the correct pressure on the gasket (max.2.45Nm/1.81 ft-lbs). Secure the section of the terminated cable to the frame structure with cable ties.
Page 28 of 62 Part 3
BCG.00612_AD
The figures below illustrate the use of the AC-trunk unlock tool.
Page 29 of 62 Part 3
BCG.00612_AD
Protection breaker rating Max number of Inverters @240VAC Max number of inverters @208VAC MICRO-0.25 MICRO-0.3 MICRO-0.3HV MICRO-0.25 MICRO-0.3 MICRO-0.3HV
6A 4 3 4 3
10A 7 6 6 5
16A 12 9 10 8
201 15 12 13 11
The dimensions of the thermal-magnetic circuit breaker should be determined by the number of MICRO inverters connected to a single AC line. A 20A thermal-magnetic circuit breaker represents the maximum value permitted for installation in a single AC line, sized based on the AC cable cross section (10 AWG).
It is the installers responsibility to adequately size the overcurrent protection, based on the number and types of MICRO inverters in the system (see Table 3-1). The maximum thermal-magnetic circuit breaker current rating is 20A for each AC line.
Power-One recommends the use of a switch with type A or AC differential magnetothermal protection with In=30mA sensitivity.
Page 30 of 62 Part 3
BCG.00612_AD
The inverter does not include any electromechanical devices (relays, contactors, etc.) for automatic disconnection from the power grid. The system must therefore be provided with external protection for the physical disconnection of the MICRO inverters from the grid, in compliance with the applicable regulations and with the requirements of the installation countrys power distributor. Such protection is typically composed of an interface protection system that analyzes and controls the grid parameters and, if necessary, sends commands to the interface device, in charge of physically disconnecting the PV installation MICRO inverters line. CAUTION: To reduce the risk of fire, connect only to a circuit provided with 20A maximum branch circuit overcurrent protection in accordance with the National Electric Code (ANSI/NFPA 70)
When connecting to the grid, all the Power-One AC cables coming from MICRO inverters must be joined inside a junction box. A single line cable must then form the connection to the distribution grid. Be particularly mindful of the dimensions of the line cable. The grounding connection from the inverters is obligatory. A 4-wire AC cable must be used and maximum trunk cable allowed beyond the last inverter is limited to 15 feet.
All the external connections to the insulated junction box (caps, adapters, etc.) must be made with securely-sealed Power-One components.
Page 31 of 62 Part 3
BCG.00612_AD
AC-TRUNK SPOOL -41 inches-50 plugs AC cable (4 conductors): 10 AWG, wheelbase 41 40 connectors
AC-TRUNK SPOOL -67 inches-32 plugs AC cable (4 conductors): 10 AWG wheelbase 67 32 connectors
AC-TRUNK SPOOL -81 inches-27 plugs AC cable (4 conductors): 10 AWG wheelbase 81 27 connectors
Do not to reverse the phase with the neutral! The installation technician is responsible for selecting a junction box with the appropriate dimensions and insulation. Close the junction box after the wiring is complete. Confirm that the seal is tight. When connecting the inverter to the distribution grid, the configuration is made with the CDD. It is required that the AURORA CDD be installed with any AURORA MICRO inverter in compliance with UL1741, for the purpose of indication and resetting of ground faults.
Page 32 of 62
BCG.00612_AD
PART 4
OPERATIONS GUIDE
One of the first rules for preventing damage to the equipment and to the operator is to have a thorough knowledge of the operations. It is required that the AURORA CDD be installed with any AURORA MICRO inverter in compliance with UL1741, for the purpose of indication and resetting of ground faults. It is necessary to read the AURORA CDD Instruction Manual before commissioning the MICRO inverter. Power-One CANNOT be held responsible for damage to the equipment or the operator if it is the result of incompetence, insufficient qualifications or lack of training.
The following information can be viewed by navigating in the menu: Operating status of each MICRO inverter and statistics. Operating status of the connection to the internet/local network. Alarm messages and fault indicators.
The display offers user friendly and intuitive use with the option of navigating through the various menus by means of buttons on the side of the CDD.
Page 33 of 62 Part 4
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208-240 Operations
BCG.00612_AD
Page 34 of 62 Part 4
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208-240 Operations
BCG.00612_AD
Page 35 of 62 Part 4
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208-240 Operations
BCG.00612_AD
4.2 COMMISSIONING
Before checking the operation of the equipment, it is necessary to have a thorough knowledge of the instruments described above and the functions that have been enabled in the installation. The MICRO inverter operates automatically without the aid of a controller. The operating state is controlled through the instruments. The interpretation or variation of some data is reserved exclusively for specialized and qualified staff. The incoming voltage must not exceed the maximum values shown in the technical data in order to avoid damaging the equipment. Consult the technical data in the Appendix section of this manual for further details.
Page 36 of 62 Part 4
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208-240 Operations
BCG.00612_AD
Manual. Please refer to the Operations Guide, Part 4, of the AURORA CDD Instruction Manual to complete the commissioning of the MICRO inverter. For MICRO inverters without an LED on the front panel, the ground fault and other indications are reported on the CDD display and monitoring webpage. The following table describes the behavior of the LED during the startup phase and the static phase of the commissioning process.
Table 4-1: LED behavior for inverters with LED on front of MICRO
Phase 1 2 3 4 5 6 7 8 9
System Status
Description
Duration
GREEN
RED
START UP PHASE (first 10 seconds during start up, followed by STATIC PHASE) 50% DUTY MICRO CYCLE, PERIOD OFF Start up ON OFF 10sec. virgin 2SEC MICRO SOLID GREEN OFF Start up ON OFF 10sec. acquired STATIC PHASE No DC OFF OFF Off OFF OFF Continuous present 50% DUTY CYCLE, OFF PERIOD 1SEC Alarm Boot issue ON OFF Continuous (refer to CDD) Ground OFF SOLID RED Alarm ON OFF Continuous Fault Country 50% DUTY CYCLE, OFF Alarm Standard ON OFF Continuous PERIOD 2SEC (CS) issue 50% DUTY 50% DUTY CYCLE, Generic Alarm ON OFF Continuous CYCLE, PERIOD PERIOD 2SEC Alarm 2SEC 50% DUTY DC present, OFF Normal no alarm, no ON OFF Continuous CYCLE, PERIOD 2SEC Grid Conn. 10% DUTY DC present, OFF Normal Grid ON ON Continuous CYCLE, PERIOD 10SEC Connected
1 2 3 4 5 6 7 8 9
= = = = = = =
MICRO not yet acquired by first connection of CDD MICRO acquired by CDD No DC source MICRO doesn't manage to load Firmware Ground Fault Detection Loading Country Standard not compatible with existing firmware MICRO malfunction or grid issue during running (e.g. voltage or frequency exceeding the limits to disconnection) = Grid issue at start up (e.g. voltage or frequency exceeding the limits to connection) =-Normal running, exporting power
Page 37 of 62 Part 4
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208-240 Operations
BCG.00612_AD
Upon completion of the commissioning, mount the CDD to the wall. Complete instructions for wall mounting can be found in Part 3 of the AURORA CDD Instruction Manual.
Page 38 of 62
BCG.00612_AD
PART 5
TROUBLESHOOTING
Table 5-1: Alarm messages and error codes displayed on CDD Alarm Messages Input OC Code displayed E001 Cause The error appears when the inverter input current exceeds the set overcurrent threshold. This may be caused by: a) sudden irradiance changes that may generate input current surges into the MICRO inverter b) PV module incompatible with the MICRO inverter input characteristics c) Faulty MICRO inverter The error is generated when the voltage at the ends of the bulk capacitors exceeds the Over Voltage threshold. This may be caused by: a) Grid voltage too high b) Internal inverter fault Solution a) The error occurs sporadically and no action is required as the MICRO inverter will automatically reset to normal operation b) It is necessary to verify that the photovoltaic module specifications are compatible with the inverter. c) If conditions a) and b) have been verified and the error persists, the malfunction may be caused by an internal inverter fault. a) Check that the grid voltage is compatible with the MICRO inverter specifications. In the event of highly abnormal grid voltage, please contact your grid operator to address the problem. b) If no problems are found when checking the grid voltage, the alarm may be caused by internal inverter faults. a) Check that the grid voltage is stable, mainly upon: - loading with high current peak loads. - maximum power generation of the PV system If the grid voltage is unstable, verify the appropriate sizing of the line cable/s, and, if correct, please contact your grid operator to address the problem. b) If no problems are found when checking the grid voltage, the alarm may be caused by internal inverter faults.
Vbulk OV
E004
Output OC
E006
The error appears when the inverter output current exceeds the internal inverter alarm threshold. This may be caused by: a) High impedance grid with significant voltage variations, even with small loads. b) Internal inverter fault
Page 39 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
Cause High internal temperature recorded by the inverter. This parameter depends in part on the power that the inverter must supply, as the internal inverter temperature is affected by the heat dissipated internally by its components. This may be caused by: a) Failure to observe the installation conditions b) Internal inverter fault
Solution a) Verify the installation conditions (exposure to sunlight) and check that air flow to the MICRO inverter is not obstructed, so as to permit cooling of the device. Check that the ambient temperature measured around the MICRO inverter does not exceed the limits set in the technical data. b) Verify the MICRO inverter temperature readings (see the Internal Web Server section in the CDD manual). If one of the temperatures remains at a value which is not compatible with the environmental conditions (e.g. -40C internal temp. reading with 20C effective ambient temperature), the alarm may be due to internal inverter causes. See the Verification of ground leakage and Measuring the insulation resistance sections for information on how to perform checks and measurements. a) If the measured insulation resistance value is less than 1K, the PV module has a ground leakage that prevents the grid connection of the inverter. In this case the PV module must be replaced. b) If the measured value exceeds 1K, try connecting the MICRO inverter to a different PV module. If the error persists, the alarm may be caused by internal inverter faults. To perform this test, the MICRO inverter Ground Fault condition must be reset via the Web Server. a) Verify the grid parameters and, if the grid voltage is strongly distorted, please contact your grid operator to address the problem If the grid voltage is stable, the error may also be due to sudden irradiance variations. In this case, the inverter will automatically try to reconnect to the grid and no actions are required to solve the problem. b) If the grid voltage is stable, yet the error systematically persists, the malfunction may be caused by an internal inverter fault a) The alarm will automatically reset upon connection of the inverter to the grid, and no actions are required to solve the problem. b) If the error systematically persists, the malfunction may be caused by an internal inverter fault
Ground fault
E018
The error is generated when a ground leakage current is detected in the DC section of the system. This may be caused by: a) PV module ground leakage b) Internal inverter fault
DC Injection
E023
Internal Error
E024
The error is generated if the DC component of the current supplied to the grid exceeds the threshold set by the country of installations applicable regulation. In any case, the inverter will automatically try to reconnect to the grid. This may be caused by: a) Sporadic recurrence of this error is a sign of large grid distortions or sudden changes in irradiance. b) Systematic recurrence of this error may be due to an inverter fault. a) The alarm may occur during inverter initialization and is caused by the initialization of communication between the CDD and the MICRO inverters. b) Systematic occurrence of this error may be due to an inverter fault.
Page 40 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
Cause The alarm is generated when an external shutdown command has been sent to the MICRO inverter.
Country Mismatch
E050
The alarm is generated when the grid standard (selected on the CDD during installation) has not been correctly set on the MICRO inverters. This may be caused by: a) communication problems while setting the grid standard for the MICRO inverter from the CDD: b) poor irradiance while setting the grid standard for the MICRO inverter from the CDD: MICRO inverters are directly supplied by the voltage generated at the panel, and poor irradiance may cause inverter shut downs The set grid standard is not compatible with the firmware installed on the MICRO inverter. This condition may be generated if a MICRO inverter is replaced.
E051
Vpanel Problem
W001
This alarm is displayed when the input voltage generated at the PV generator is outside the allowed range given in the technical data. This may be caused by: a) Poor irradiance b) Possible shadows that may darken the module during part of the day. b) PV module incompatible with the MICRO inverter input parameters d) Internal inverter fault This alarm is generated when one or more grid parameters lie outside the permitted range set by the country of installations grid standard. The error code will be followed by a suffix in brackets indicating the grid parameter out of range: (UV) Grid voltage below the set lower limit (OV) Grid voltage above the set upper limit (UF) Grid frequency below the set lower limit (OF) Grid frequency above the set upper limit Internal fault of the booster circuit inverter
Grid Fail
W003
a) Verify on the Internal Web Server (as described in the CDD manual), the radio communication quality on each MICRO inverter (values above 60% indicate good reception). If the quality of the received signal is good re-configure the installation, otherwise consider installing the CDD device in a different position to ensure better radio signal quality. b) System configuration must be carried out in good irradiance conditions, in order to guarantee the correct operation of the MICRO inverter and to prevent the risk of shut-downs due to insufficient input voltage generated by the PV module. The firmware in the MICRO inverter/s in the installation must be updated to a compatible version. Firmware updates are performed via the Internal Web Server (see the CDD manual), with the software package obtained from Power-One Service a) Wait for appropriate irradiance to guarantee correct operation of the inverter b) Verify that no shadows are present on the PV module when the error is generated c) Verify that the PV module voltage characteristics are compatible with the inverter input specifications. d) If the above checks have yielded positive results, yet the error persists, the malfunction may be caused by the MICRO inverter. If the error is generated only on one of the installation MICRO inverters, this may be due to an inverter fault. If the alarm is generated at multiple inverters in the installation, check the grid voltage for instabilities in any of the 4 parameters monitored by the inverter. If anomalous values are detected, verify the sizing of the AC line conductors. In case of correct sizing, please contact your grid operator to address the problem. Contact Power-One Service.
Vbulk UV
W011
Page 41 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
Cause The alarm is generated when the CDD device does not receive messages from the MICRO inverter for more than 5 minutes. This may be caused by non-optimal positioning of the CDD. The alarm is generated when the CDD device does not receive messages from the MICRO inverter for more than 15 minutes. This may be caused by non-optimal positioning of the CDD.
Solution Consider a new installation position that ensures better communication between the CDD device and the MICRO inverters. Use the CDD Internal Web Server to verify the signal quality (refer to the CDD manual for information on the Internal Web Server) Consider a new installation position that ensures better communication between the CDD device and the MICRO inverters. Use the CDD Internal Web Server to verify the signal quality (refer to the CDD manual for information on the Internal Web Server)
Comm fault
W005
5.2
In the presence of anomalies or report of ground fault, there may be a ground leakage from the photovoltaic module. To check this, measure the voltage between the positive pole and ground and between the negative pole and ground using a voltmeter.
The internal resistance of the voltmeter tends to zero the voltage present on the PV generator due to the capacitive effect
Page 42 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
How to make the measurement: Positive pole Vs Ground Negative pole Vs Ground
Page 43 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
Once the short-circuit has been made, measure the insulation resistance (Riso) using a megohmmeter positioned between the two shorted poles and ground (of the inverter).
If the measured insulation resistance is less than 1Kohm the inverter does not connect to the grid due to a low insulation of photovoltaic module respect to ground. The insulation resistance is affected by the environmental conditions the photovoltaic module is in (E.g.: photovoltaic module wet from dump or rain); therefore, the measurement must be made immediately after the anomaly.
Page 44 of 62 Part 5
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Troubleshooting
BCG.00612_AD
Identify the System structure: Information on the Photovoltaic Field Brand and model of photovoltaic panels Maximum array voltage and current values Number of strings in the array Number of panels for each string
Page 45 of 62
BCG.00612_AD
PART 6
MAINTENANCE GUIDE
Maintenance operations must be carried out with the equipment disconnected from the grid (power switch open) and the photovoltaic modules obscured or isolated, unless otherwise indicated.
Check that there has been no drastic change in the installation conditions that might have a negative influence on radio communication with the MICRO inverter. Conduct an annual visual inspection (where possible) on the various components (DC cables, MICRO inverters, and AC cables) to check for dust, dirt, moisture and water seepage.
Any maintenance or replacement of the device could require dismounting the photovoltaic module mounted on top of the MICRO inverter. This condition must be accounted for during installation, ensuring that the safety distances are correct for normal control and maintenance operations.
Do not attempt to dismantle the equipment or make any internal repairs! With a view to preserving the integrity of their safety and insulation, AURORA MICRO inverters are not designed to allow internal repairs. The AC output wiring harness (AC drop cable on the MICRO inverter) cannot be replaced. If the cord is damaged the equipment should be scrapped.
Page 46 of 62 Part 6
BCG.00612_AD
Dispose of the various types of materials that the parts of the equipment consist of in dumps that are suitable for the purpose.
Page 47 of 62
BCG.00612_AD
PART 7
7.1 TECHNICAL DATA
Values MICRO-0.25-IOUTD-US208/240
250 208 260 240
APPENDIX
MICRO-0.3-IMICRO-0.3HV-IOUTD-US-208/240 OUTD-US-208/240
300 208 310
1
Technical Data
Nominal Output Power Rated Grid AC Voltage Maximum Output Power
W V W
240 310
2652 300
65 25 25-60 12-60 10.5 12.5
3 3
3202 360
65 25 25-60 12-60 10.5 12.5
3 3
3202 360
79 25 30-75 19-75 10.5 12.5
3 3
Amphenol H4 PV connector
Page 48 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Values
Hz A
Technical Data
Adjustable Grid Frequency Range Maximum Current (Iacmax) Power Factor Total Harmonic Distortion At Rated Power Maximum Number of Inverters per String Grid Wiring Termination Type
MICRO-0.25-IOUTD-US208/240
57-60.5 1.20 > 0.95 1.04
MICRO-0.3-IMICRO-0.3HV-IOUTD-US-208/240 OUTD-US-208/240
57-60.5 1.44 > 0.95 1.25 1.44 > 0.95 57-60.5 1.25
% 13
< 2% 15 11
< 2% 12 11
< 2% 12
Output
Anti-Islanding Protection Over-Voltage Protection Type Maximum AC OCPD Rating
Varistor A 20
Varistor 20
Varistor 20
Efficiency
Maximum Efficiency CEC Efficiency % % 96.5 96 96.5 96 96.5 96
Operating Performance
Stand-by Consumption mW < 50 < 50 < 50
Communication
Monitoring System Wireless and Web-Based Monitoring through AURORA CDD
Page 49 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Values
MICRO-0.25-IOUTD-US208/240
MICRO-0.3-IMICRO-0.3HV-IOUTD-US-208/240 OUTD-US-208/240
F
(C)
-40 to 167 (-40 to 75) with derating above 149 (65) -40 to 176 (-40 to +80) 0-100 condensing < 30
F (C)
6560 (2000)
6560 (2000)
6560 (2000)
Mechanical Specifications
Enclosure rating Cooling Dimensions (H x W x in D) (mm) Weight Mounting System lb/ (kg) < 3.5 (1.65) Rack mounting with M8, 1/4" or 5/16" bolt NEMA 4X Natural Convection NEMA 4X Natural Convection NEMA 4X Natural Convection
10.5 x 9.7 x 1.37 (266 x 246 x 35) < 3.5 (1.65) Rack mounting with M8, 1/4" or 5/16" bolt < 3.5 (1.65) Rack mounting with M8, 1/4" or 5/16" bolt
Safety
Isolation Level Safety and EMC Standard Safety Approval HF Transformer HF Transformer HF Transformer
Warranty
Standard Warranty years 10 10 10
Available Models
Standard MICRO-0.25-IOUTD-US-208/240 MICRO-0.3-I-OUTDUS-208/240 MICRO-0.3HV-IOUTD-US-208/240
Page 50 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Values
Technical Data
MICRO-0.25-IOUTD-US208/240
MICRO-0.3-IMICRO-0.3HV-IOUTD-US-208/240 OUTD-US-208/240
1 With derating below 200V for 208VAC operation 2 This is the maximum power that the inverter will utilize. It does not define the maximum power rating for the PV module. 3 Only use PV modules that satisfy these parameters under all operating conditions.
Page 51 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 52 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 53 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 54 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 55 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 56 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 57 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Figure 7-10: Wiring diagram 208Vac three phase * *IMPORTANT: If several Aurora MICRO inverters are installed in a three-phase AC GRID, it is recommended to distribute the inverters between the phases in order to reduce the power unbalances between the phases. Always refer to the local standards.
Page 58 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 59 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 60 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 61 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Page 62 of 62 Part 7
MICRO-0.25/0.3/0.3HV-I-OUTD-US-208/240 Appendix
BCG.00612_AD
Date 12/6/12
2/4/13
7/1/13
AD
New data sheet, new label, modify overcurrent table 3-1 Added requirement of CDD for installation; corrected dimensions, added HV model, added behavior of LED for models with LED Added racking system to assembly instructions in section 3.2;