You are on page 1of 2

DC Power System

Technical Specifications ACTURA Optima 24350 1.6 .... 9.6kW


Typical Applications:
Radio base stations
Smaller telecom exchanges
Private branch exchanges
Nominal system voltage +24V
EMC EN 300 386
System characteristics:
Adjustable output voltage range 23V ... 28.5V
Marking CE
Electrical safety EN 60950
ACTURA Optima 24350
Maximum normal load current 200A
+24V DC, 1.6 ... 9.6kW
ACTURA
General
The ACTURA Optima 24350 is a flexible power system suitable for
communication networks and IT applications requiring small to medium
range power. This system is designed to reliably and cost effectively
provide uninterrupted power to various types of communication and
IT equipment.
The 24350 is a positive 24V system that is suitable for supplying loads
of up to 8kW with N+1 rectifier module redundancy. The system is
supplied in a cabinet which includes provision for distribution and
battery circuit breakers.
The picture shown is a system equipped with an ACTURA DC to DC
sub rack and modules.
The compact size of the ACTURA Optima 24350 power system allows
available space to be used effectively for revenue generating equipment.
Comprehensive supervision and remote access facilities are also
provided which facilitate complete management of your energy
infrastructure. Two ACTURA Optima systems may be paralleled for
higher power requirements.
Of utmost importance to Emerson Energy Systems, is a high standard
of quality. Our ISO9001 certification is an indication of our commitment
to continual quality improvement. Both the system and modules carry
the CE mark of approval.
Data centres
Other data or communication equipment requiring +24V power supply
Rated output power 9.6kW
Rated rectifier output current 360A
Maximum priority load current 200A
Features
Fully pre-wired, including all battery wiring, which allows low installation costs
Comprehensive supervision including self diagnostic features
Remote alarm extension
Alarm log for statistical system data
Repairs possible on live system
Two stage low voltage disconnect - Priority load & normal load
Full battery management maximizes system integrity
System prepared for battery block voltage equalisers
Automatic battery discharge testing
Individual block monitoring for up-to 8 strings
Temperature compensated float voltage
SMS alarm feature
Included in standard system :
AC Distribution
Rectifier circuit breakers 6 x 15A
Mains low voltage detector 185 ... 190V AC per phase to neutral
Rectifier capacity Up to 6 SM2415-1 rectifier modules
Two level disconnect Priority and normal loads
Normal load circuit breakers 3 x 100A + 2 x 10A
Maximum number of load circuit breakers 15 x single pole
Battery backup
Capacity Up to 4 x 200Ah
Battery circuit breakers 4 x 125A
Battery compartment cover plates 4
Control / supervision module 1
Included in standard system:
Mechanical data of the system:
Dimensions 1860mm (H) x 600mm (W) x 600mm (D)
Net weight (Approximately) 90kg (excluding modules & batteries)
Packed weight (Approximately) 120kg (excluding modules & batteries)
Emerson Energy Systems (Pty) Ltd 2 Kikuyu Rd. Sunninghill Ext. 96 Republic of South Africa
Phone: +27 11 257 8500 Fax: +27 11 807 8103 www.emersonenergy.co.za www.emersonenergy.com
Dimensions 96mm (H) x 135mm (W) x 360mm (L)
Safety EN 60 950
EMC, including surge immunity EN 300 386
Weight 3.6kg
Enclosure IP20
Reliability, MTBF (Module) >50 years
Input characteristics:
Input voltage range for start-up 170 ... 275Vac
Non-destructive input voltage range 0 ... 320Vac
Maximum input current, incl. inrush current <12A AC ac
Line frequency 45 ... 65Hz
Output characteristics:
Ouput voltage 27Vdc
Line regulation <0.1%
Load regulation <0.5%%
Psophometric weighted noise <1mV at +27V
Rated output current 60A
Current sharing Within 5% of rated output current
Efficiency at 230V AC 50 ... 100% load >90%
Protection characteristics:
Output short circuit protection
Over and under voltage protection
Overheat protection
Environmental conditions:
Operational temperature range -5 ... 65C
Storage temperature range -25 ... 65C
Cooling Forced convection
non-condensing
with built in low noise
speed control fan
The ACTURA Optima24350 is also available
in different configurations.
The ACTURA Optima DC to DC sub rack &
modules compliment this system.
Preliminary Data Sheet E. & O.E. {Actura24350a7.cdr}
DC Distribution
Priority load circuit breakers 1x 100A + 5 x 10A
Packed dimensions (Approximately) 2040mm (H) x 820mm (W) x 750mm (D)
General:
Technical Specifications rectifier module (SM2415-1)
Active load sharing Yes
Input voltage range (after start-up) 80 ... 275Vac
Input voltage range 175 ... 275Vac for maximum power (1600W)
Power factor, 50 ... 100% load >0.995
Maximum input current THD, 50 ... 100% load 5%
Quality system ISO9001
Operational temperature range -5 ... + 65 C
Normal operation temperature range (up to 9.6kW) 0 ... + 45 C
Nominal input voltage range, 1 (1+N+E) 220 ... 240V AC
Nominal input voltage range, 3 (3+N+E) 380 ... 415V AC
Maximum input current 72A 1 , or 3 x 24A 3
Nominal input frequency range 50 ... 60Hz

System characteristics (contd):


Adjustable output voltage range 23 ... 28.8Vdc
Rated output power 1600W (De-rate below 175Vac)

Relative humidity 0 to 95%


(Expected fan life
>70 000 hours)