General description

The Ch series of fans has been designed to satisfy various needs in many fields of industrial
applications. They are mainly installed in civil and industrial conditioning systems, in drying and dust
removal plants, on spray booths, on boilers, on kilns, etc. Careful design of the casing and of the
two different types of impeller that can be fitted has allowed us to create this extremely versatile
series of fans with the best performance for their field of use. The robust construction is one of its
main features. The bearings are designed for a minimum duration of 40,000 hours; the thickness of
the sheet steel, the position of the strengthening and of the ribs are designed to guarantee an
absence of vibrations and pulsations. The Ch fans are built in 19 sizes with impellers from 400 mm to
2,450 mm in diameter.
The impeller ChA has 12 airfoil type blades welded to a front aerodynamic profile cone and to a rear
disk. This configuration allows a performance of up to 90% to be reached with a consequent very
low noise level. This type of impeller is ideal for fluids without dust and with a relative humidity rate of
less than 80%.

ChA
Impeller with reverse
Blades with a wing profile

The impeller ChA has 12 airfoil type blades welded to a front aerodynamic profile cone and to a rear
disk. This configuration allows a performance of up to 90% to be reached with a consequent very
low noise level. This type of impeller is ideal for fluids without dust and with a relative humidity rate of
less than 80%.

ChB
Impeller with flat
reverse blades

The impeller ChB has 12 flat blades welded to a front aerodynamic profile cone and to a rear disk.
The performance is high because it can reach up to 86%. This type of impeller is ideal for fluids
containing fine, dry and non abrasive powders or those with high moisture rates.
The ChB fans have been tested and approved in France by the CTICM laboratories for continual
operation at 400C for 2 hours. The laboratories of the CTICM are approved by the French Home
Office.

Layout 1

Bare shaft fan ideal for coupling with a motor by means of a transmission unit.

Layout 9

Coupling with transmission unit. The motor is fitted on the seat side. Maximum fluid temperature
100C without cooling fan and 300C with the fan.

Layout 12
BST

Coupling with transmission unit. The motor is fitted on a suitable basement. Maximum fluid
temperature 100C without cooling fan and 300C with the fan.

Layout 12
Basement

The motor is fitted on a suitable basement. Maximum fluid temperature 100C without cooling fan
and 300C with the fan.

Position of the motor

The different positions of the motor are defined by the letters W or Z for Layout 9 and 12, looking at it
from the transmission side, and do not depend on the fans direction. Unless specifically requested,
the motor is fitted opposite the outlet.

Layout 4

Impeller directly coupled on the motor shaft. Maximum fluid temperature 80C without cooling fan
and 200C with the fan.

Layout 8

Impeller and motor are connected directly by a mechanical joint. Maximum fluid temperature 100C
without cooling fan and 300C with the fan.

Accessories

1 Outlet counter flange


2 Outlet anti-vibration joint
3 Gravity gate valve
4 Counterpoised fin gate valve
5 Cooling fan
6 Inlet counter flange
7 Protection mesh
8 Outlet anti-vibration joint
9 Flow rate regulator
10 Inlet section
11 Inspection door (*)
12 Shock absorbers
13 Discharge cap (**)
14 Electric motor
15 Transmission unit
16 Transmission unit guard
(*) always included

(**) always included except directing

Noise level

The LPA noise levels indicated in the selection curves are global sound pressure levels expressed in
dBA referred to 2*10-5 Pa, averages of 7 field measurements on a free field at a distance of 1.5 m
from the fan body in compliance with ISO 37413746 standards with tolerance of +4 dBA (DIN 24
166). The sound measurements are performed with an electric fan positioned on the floor and not
surrounded by reverberant walls, with the inlet free and with piping fitted with a diaphragm on the
outlet to measure the sound pressure level at the different points of operation according to the
diagram reported below and pursuant to the ISO standards mentioned above. The control motor is
extremely quiet so the noise measured only concerns the fan.

In order to have LWA sound levels by octave band it is necessary to sum the corrections reported in
the following tables, which have different values according to the zone of emission and to whether
channels are present or not, to the LPA global sound pressure value:
Noise emitted by an
unchannelled inlet/outlet
ChA
15 18
20 36
40 89

Hz
dB
dB
dB

63
-12
-9
-5

125
+2
+4
+7

250
+7
+7
+9

500
+10
+10
+10

1000
+8
+8
+8

2000
+7
+7
+7

4000
+4
+4
+4

8000
-1
-1
-1

ChB
15 18
20 36
40 89

Hz
dB
dB
dB

63
-13
-9
-5

125
+1
+4
+7

250
+6
+7
+9

500
+10
+10
+10

1000
+8
+8
+8

2000
+7
+7
+7

4000
+4
+4
+4

8000
-1
-1
-1

Noise emitted by an
inlet/outlet in the channel
Ch
15 89

Hz
dB

63
0

125
+7

250
+9

500
+10

1000
+9

2000
+7

4000
+4

8000
-1

Noise emitted by the fan with


both the inlet and outlet
channelled
Ch
Hz
15 89
dB

63
-15

125
-11

250
-10

500
-4

1000
-9

2000
-13

4000
-12

8000
-17

Noise emitted by the flow


regulator
Ch
15 89

63
+9

125
+10

250
+9

500
+8

1000
+10

2000
+8

4000
+6

8000
+3

Hz
dB

If it should be necessary to calculate any soundproofing or insulation, it is always recommended to


express the noise levels in dBA of LWA sound power by octave band. On request, the fans of the K
series may be fitted with the casings insulated with two types of lining.
Type 1 insulation

This insulation is made with a layer of rock wool 100mm thick and with a density of 120 Kg/m.
Externally it is protected with a galvanised steel or aluminium sheet 0.8-1mm thick. The noise
abatement obtained is given by:

Ch
15 89

Hz
dB

Type 2 insulation

This insulation is the same as that of type 1, with the extra addition of a lead sheet 0.8mm thick
positioned 70 mm from the surface of the casing. The noise abatement obtained is given by:

Ch
15 89

Hz
dB

63
0

125
-2

63
-3

125
-6

250
-7

250
-11

500
-8

500
-12

1000
-7

2000
-4

1000
-11

2000
-8

4000
-3

4000
-6

8000
0

8000
-3

The abatement of the noise obtained with the insulation is summed to that produced by the Casing
in the layout with both the inlet and outlet channelled, that is after applying the correction indicated in
the previous page. The different installation and operating conditions may greatly modify the noise
values indicated on the catalogue. There follows some of the most significant and most common
examples.
A
With variations of the distance, there is a reduction of the LPA sound pressure values indicated on
the diagrams. The reduction is different if the fan is installed in a free field (situation AA) or inside a
building considered to be partially reverberant (situation BB). The table below indicates the reduction
values according to the distance expressed in metres in the two different situations:

AA
BB

m
dB
dB

1,5
0
0

3
-6
-1

6
-12
-3

9
-15,5
-5

12
-18
-7

15
-20
-8

Situation BB shows how the environmental conditions may considerably alter the sound pressure
values measured in free field.
B
If the real operating point of the fan does not coincide with the one selected on the catalogue curve,
it is possible to have a noise variation even of 3 dBA.
C
The normal anti-vibrating joints, positioned between the fan and piping, cause an increase in the
noise in the environment that can be quantified at 2 dBA. If necessary particular aphonic joints may
be installed to reduce or cancel the noise increase.
D
In varying the direction of the inlet flow, the flow regulator generates a noise of approximately 9 dBA
which is added to the catalogue LPA global sound pressure.
E
The calibration valve on the delivery side of the fan, by creating a resistance to the fluid, generates a
noise of 3 dBA which is added to the catalogue LPA global sound pressure.

Electric motor

F
Since an electric motor does not increase the overall noise of the unit, it is necessary to foresee a
type whose noise is at least 10 dBA less than that of the fan. Otherwise the total noise R of the
system will be given by the formula:
V

R = 10 log(10 10 + 10 10 )[dBa]

where
V
Noise coming from the fan
M
Noise coming from the motor
The values to be summed must, of course, always be homogeneous, that is both global noises and
both LWA powers or LPA sound pressures.

10

Flow regulation

Flow regulation may be obtained either with counterpoised fin gate valves on the outlet or with flow
regulators on the inlet. Both of these systems have all the external blade fluid passage control
mechanisms and thus may be used with powdery air and with temperatures of up to 300C. The
torsional moment Mt in Nm, at the axis of the control lever, is reported below for the maximum
number of revs of each class.

Finned gate valve


CH
15
16 18 20
Mt2
22
26
32
37
Mt3
35
41
50
58

22 24 27
45
53
63
71
84
100

30
76
120

33
91
143

36 40 44 49
108 129 154 184
170 203 243 289

54 60
220 264
347 416

66
313
493

Flow
CH
Mt2
Mt3

22 24 27
23
31
41
39
52
69

30
57
94

33
76
126

36 40 44 49
107 138 189 253
177 229 314 420

54 60
346 463
573 769

66
73
80 89
616 823 1121 1502
1022 1366 1860 2480

regulator
15
16 18 20
8
11
14
17
13
18
23
29

73
374
590

80 89
423 583
669 840

where
Mt2 is valid for class II
Mt3 is valid for class III

11

Correction of the
performances according to
temperature and altitude

The performances are valid for volume masses 1.20 Kg/m3 t=20C Pb = 101,325 Pa (760 mm Hg)
like air at sea level. For other conditions, it is necessary to correct the pressure requested by
multiplying it by K before selecting the fan on the catalogue. The operating power rating is obtained
by dividing the catalogue one by K.

Correction factor K
Temperature[C]
-40

-20

+20

+40

+60

+80

+100

+150

+200

+250

+300

+350

+400

Altitude [metres]
0
250
500
750
1000
1500
2000

0.86
0.88
0.91
0.93
0.95
1.01
1.07

0.93
0.95
0.98
1
1.03
1.09
1.16

1
1.02
1.05
1.08
1.11
1.17
1.24

1.07
1.09
1.12
1.15
1.18
1.25
1.32

1.14
1.16
1.19
1.22
1.26
1.33
1.41

1.2
1.23
1.27
1.3
1.33
1.41
1.49

1.27
1.3
1.34
1.37
1.41
1.49
1.58

1.44
1.48
1.52
1.56
1.6
1.69
1.79

1.61
1.65
1.7
1.74
1.79
1.89
2

1.78
1.83
1.88
1.92
1.98
2.09
2.21

1.96
2
2.05
2.11
2.17
2.29
2.42

2.13
2.18
2.23
2.3
2.35
2.49
2.64

2.3
2.35
2.41
2.48
2.54
2.69
2.85

0.79
0.81
0.83
0.86
0.88
0.93
0.99

Correction of the rotation


speed according to the
temperature

The max rotation speed for each class must be reduced according to the temperature as per the
diagram below:

100%

90%

Rpm reduction

80%

70%

60%

50%
0

50

100

150

200

250

300

temperature

12

ChB
Fan
Layout 4
Fan
Layout 8

13

0,37-80

0,55-80

0,75-90

1,1-90

1,5-100

2,2-112

3-132

4-132

15

16

16 M

18

20

22

24

27 R

CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA

266
270
0.15
50

V
1400

325
330
0.22
54

251
258
0.15
49

1600

364
370
0.30
55

319
325
0.24
53

232
241
0.16
48

1800

342
350
0.30
55

309
317
0.26
53

209
220
0.16
48

2000

388
395
0.36
56

320
330
0.31
54

295
305
0.27
52

178
192
0.16
48

2240

382
390
0.37
56

287
300
0.32
53

270
282
0.28
51

132
150
0.15
49

2500

485
492
0.61
60

369
380
0.38
55

249
265
0.33
53

239
255
0.27
51

85
107
0.15
50

2800

481
490
0.62
59

352
365
0.39
55

215
235
0.33
53

195
215
0.26
51

3150

477
488
0.64
58

318
335
0.40
54

160
185
0.33
54

125
150
0.22
52

3550

620
630
1.02
63

462
477
0.65
57

.261
283
0.41
55

88
120
0.32
54

48
60
0.18
53

4000

613
625
1.05
62

405
423
0.67
57

193
220
0.42
56

4500

755
765
1.60
66

600
615
1.10
61

362
385
0.70
57

116
150
0.41
57

5000

750
763
1.66
65

563
582
1.12
61

305
333
0.72
58

5600

875
885
2.25
69

740
756
1.75
64

516
540
1.18
60

214
250
0.73
59

6300

868
882
2.33
68

715
735
1.83
64

449
480
1.20
60

7100

842
860
2.43
67

670
695
1.90
63

357
396
1.20
61

8000

797
820
2.51
65

595
630
1.95
63

235
285
1.18
62

9000

740
768
2.57
64

505
545
2.00
63

10000

655
690
2.63
64

380
430
1.97
63

11200

556
600
2.66
65

225
290
1.86
64

12500

14

CBI - CH

433
488
2.64
66

14000

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

kW-motor

Type

1000 Revs/min

5,5-132

7,5-160

11-160

15-180

18,5-200

22-200

30-225

27

30

30 M

33 M

36

40 R

40 M

CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA

V
6300

7100

940
960
2.83
69

8000

920
945
2.97
68

9000

1132
1150
4.45
72

885
910
3.10
67

10000

1237
1260
5.30
73

1117
1140
4.63
71

815
850
3.25
66

11200

1209
1238
S,50
72

1080
1108
4.85
70

720
765
3.33
66

12500

1154
1190
5.70
71

1014
1050
5.08
70

605
660
3.35
66

14000

1730
1760
10.70
78

1053
1100
5.92
70

913
960
5.22
69

420
490
3.28
67

16000

1680
1720
11.00
77

924
983
6.05
70

778
837
5.32
69

18000

1745
1780
12.65
78

1630
1680
11.80
76

782
855
6.10
70

604
677
5.32
69

20000

1705
1750
13.60
77

1515
1580
11.85
75

604
696
6.03
72

383
475
5.22
70

22400

1863
1900
17.15
79

1625
1680
14.05
76

1330
1400
12.15
75

419
533
5.87
73

25000

1835
1880
17.85
78

1495
1560
14.15
76

1080
1180
11.90
75

28000

2340
2400
26.25
81

1740
1800
18.50
77

1315
1400
14.80
76

775
900
11.75
76

31500

2225
2300
27.30
80

1625
1700
19.50
76

1060
1170
14.75
76

430
590
11.65
78

35500

2075
2170
28.00
79

1405
1500
20.10
76

725
860
14.25
77

40000

1770
1890
28.45
79

1110
1230
19.70
76

325
500
13.60
79

45000

1480
1625
28.20
79

805
950
19.40
77

50000

1050
1235
27.80
80

415
600
18.50
79

56000

15

CBI - CH

520
750
26.20
82

63000

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

kW-motor

Type

1000 Revs/min

9-132

7,5-132

5,5-132

4-112

3-100

2,2-100

1,5-90

1,1-90

0,75-80

kW-motor

639
650
0.51
61

V
2000

616
630
0.53
61

2240

768
780
0.76
65

587
605
0.55
60

2500

885
900
0.98
65

744
760
0.79
64

543
565
0.57
59

2800

850
870
1.01
65

710
730
0.85
64

482
510
0.58
59

3150

925
940
1.31
66

800
825
1.05
64

670
695
0.86
63

395
430
0.58
59

3550

905
925
1.37
66

735
765
1.08
64

600
630
0.88
62

275
320
0.57
60

4000

1140
1160
2.22
70

860
890
1.43
65

650
690
1.09
64

520
560
0.88
62

143
200
0.54
61

4500

1290
1315
2.70
70

1125
1150
2.26
69

815
850
1.48
65

545
590
1.10
64

400
450
0.86
62

5000

1270
1300
2.78
69

1100
1130
2.32
68

730
770
1.51
64

397
460
1.09
64

247
310
0.86
63

5600

1420
1445
3.55
74

1238
1273
2.97
69

1045
1080
2.40
68

605
660
1.53
65

220
300
1.06
64

60
140
0.82
64

6300

1400
1430
3.70
73

1165
1210
3.03
69

955
1000
2.46
67

435
500
1.53
66

7100

1735
1760
5.65
76

1340
1380
3.85
72

1033
1093
3.10
69

820
880
2.53
67

225
290
1.51
67

8000

1855
1890
6.70
77

1715
1750
5.90
76

1250
1300
4.00
71

865
940
3.17
69

640
715
2.58
68

9000

1820
1860
7.00
77

1680
1720
6.13
75

1140
1200
4.10
71

680
770
3.22
69

435
525
2.58
69

10000

1770
1820
7.20
76

1610
1660
6.40
75

975
1050
4.18
71

467
580
3.20
70

11200

1685
1750
7.50
75

1495
1560
6.62
74

755
850
4.18
72

12500

1550
1630
7.75
75

1320
1400
6.82
74

470
590
4.10
73

14000

1285
1390
7.90
75

1045
1150
6.90
74

16000

960
1100
8.00
76

700
840
6.80
75

18000

16

CBI - CH

635
800
7.75
76

395
560
6.75
76

20000

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

CHB 15
ps
pt
pv
LpA
CHB 16
ps
pt
pv
LpA
CHB 16 M
ps
pt
pv
LpA
CHB 18
ps
pt
pv
LpA
CHB 20
ps
pt
pv
LpA
CHB 20 M
ps
pt
pv
LpA
CHB 22
ps
pt
pv
LpA
CHB 24
ps
pt
pv
LpA
CHB 24 M
ps
pt
pv
LpA

Type

1500 Revs/min

11-160

15-160

18,5-180

22-180

30-200

37-225

45-225

55-250

75-280

90-280

27 R

27

30

30 M

33

33 M

36 R

36

40 R

40

CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA

1972
2000
7.75
79

V
10000

2165
2200
9.40
80

1935
1970
8.00
78

11200

2135
2180
9.80
79

1870
1915
8.30
77

12500

2095
2150
10.40
78

1765
1820
8.55
76

14000

2565
2610
15.50
83

1960
2030
10.95
77

1560
1630
8.85
75

16000

2795
2850
18.70
84

2495
2550
16.20
82

1760
1850
11.30
77

1350
1440
9.00
76

18000

3120
3170
24.50
87

2695
2765
19.30
83

2380
2450
16.80
81

1540
1650
11.50
77

1110
1220
8.90
76

20000

3440
3500
29.80
88

3070
3135
25.80
86

2555
2640
19.95
82

2215
2300
17 ,40
81

1230
1370
11.45
77

785
925
8.80
77

22400

3320
3400
0.70
86

2990
3070
26.90
85

2340
2450
20.55
82

1990
2100
17.80
80

825
1000
11.20
78

25000

3455
3520
35.50
88

3200
3300
32.10
85

2850
2950
28.00
84

2040
2175
20.90
82

1665
1800
18.00
80

28000

3815
3900
42.60
89

3345
3430
37.00
86

2995
3120
32.90
85

2625
2750
29.00
83

1655
1825
21.00
82

1180
1350
17.90
81

31500

4380
4400
57.10
90

3690
3800
45.00
88

3240
3350
39.80
86

2645
2800
33.70
84

2270
2430
29.50
83

1110
1325
20.65
82

635
850
17.35
83

35500

4805
4900
70.70
91

4255
4350
61.10
89

3465
3600
47.00
87

3005
3140
40.60
85

2160
2360
34.00
84

1770
1970
29.60
84

430
700
19.80
84

40000

4660
4780
73.80
90

4080
4200
64.00
88

3125
3300
48.50
86

2585
2760
41.50
85

1550
1800
33.60
85

1150
1400
29.20
85

45000

4445
4600
77.00
89

3855
4000
65.35
87

2635
2850
50.00
86

2105
2320
41.30
85

810
1120
32.40
87

50000

4165
4350
78.65
88

3525
3720
68.05
87

2035
2300
49.00
87

1485
1750
40.60
86

56000

3700
3930
83.00
88

3195
3280
70.00
87

1210
1550
46.70
88

660
1000
37.20
88

63000

3005
3300
81.35
88

2355
2650
69.70
87

71000

2105
2480
81.05
89

1425
1800
66.70
88

80000

945
1420
75.00
91

90000

17

CBI - CH

100000

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

kW-motor

Type

1500 Revs/min

0,55-71

0,75-80

1,1-80

1,5-90

2,2-90

3-100

4-112

5,5-132

11 R

11

11 M

13 R

13

13 M

15

CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA

942
960
0.35
65

V
900

928
950
0.36
65

1000

882
910
0.37
64

1120

825
860
0.38
63

1250

1066
1085
0.61
69

760
800
0.40
63

1400

1375
1400
0.90
72

1045
1070
0.65
68

605
660
0.46
62

1600

1685
1715
1.22
74

1360
1390
0.96
71

1010
1040
0.67
66

430
500
0.41
64

1800

1660
1700
1.30
73

1320
1360
0.99
69

940
980
0.68
66

255
310
0.40
65

2000

1600
1650
1.34
71

1230
1280
1.00
69

825
875
0.68
65

2240

1672
1700
1.75
75

1500
1560
1.36
71

1120
1180
1.00
68

670
730
0.68
65

2500

2065
2100
2.40
77

1615
1650
1.80
74

1335
1410
1.36
70

885
960
0.99
68

485
560
0.68
66

2800

2485
2530
3.22
79

2005
2050
2.42
76

1535
1580
1.86
73

1065
1160
1.34
70

655
750
0.99
69

265
360
0.67
68

3150

2410
2465
3.32
78

1905
1960
2.57
75

1445
1500
1.92
72

745
865
1.34
71

380
500
0.98
71

3550

2555
2600
4.10
81

2270
2340
3.43
77

1730
1800
2.60
74

1310
1380
1.97
72

380
535
1.33
73

45
200
0.98
72

4000

2490
2550
4.25
81

2100
2190
3.53
76

1620
1710
2.75
74

1125
1215
2.00
72

4500

2350
2420
4.36
79

1910
2020
3.62
76

1390
1500
2.75
74

865
975
1.98
73

5000

2210
2300
4.50
78

1635
1770
3.66
76

1055
1190
2.70
75

495
630
1.93
75

5600

1940
2050
4.65
78

1170
1340
3.60
77

530
700
2.65
77

6300

1560
1700
4.70
79

483
700
3.48
79

7100

1110
1290
4.47
80

8000

18

CBI - CH

570
800
4.40
81

9000

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

kW-motor

Type

3000 Revs/min

7,5-132

9-132

11-160

15-160

16

16 M

18 R

18

CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA
CHB
ps
pt
pv
LpA

22-180

V
3150

3550

4000

4500

3060
3110
6.10
83

5000

3240
3300
7.00
83

2980
3040
6.28
82

5600

3445
3500
9.00
85

3130
3210
7.55
82

2820
2900
6.75
81

6300

4140
4200
11.80
88

3700
3760
10.48
86

3350
3410
9.30
84

3050
3150
7.95
82

2650
2750
6.85
81

7100

4015
4100
12.30
87

3615
3700
11.00
85

3205
3290
9.60
83

2800
2930
8.30
81

2360
2490
6.90
80

8000

3840
3950
12.80
86

3450
3560
11.40
84

3010
3120
9.80
83

2540
2700
8.65
81

1940
2100
7.00
80

9000

4510
4600
18.10
89

3670
3800
13.20
85

3260
3390
11.80
83

2770
2900
9.95
82

2150
2350
8.80
82

1540
1740
7.05
81

10000

4505
4520
18.60
88

3335
3500
13.70
85

2925
3090
12.10
83

2415
2580
10.05
82

1580
1830
8.75
83

960
1210
6.90
82

11200

4200
4340
19.10
87

2995
3200
14.20
85

2455
2660
12.25
83

1895
2100
10.10
82

890
1200
8.50
85

220
530
6.50
84

12500

3870
4050
19.60
86

2290
2550
14.50
86

1820
2080
12.25
84

1240
1500
10.10
83

14000

3275
3510
20.20
86

1360
1700
14.30
87

810
1150
12.10
85

16000

2555
2850
20.60
87

18000

1735
2100
20.60
88

20000

22400

25000

28000

19

CBI - CH

31500

The performances are valid for volume mass: 1.20 Kg/m^3, t=20C, Pb=101.325, Pa (760 mm Hg) like air at sea level

V=flow rate (m^3/h) - ps=static pressure (Pa) - pt=total pressure (Pa) - pv=power rating (kW) - LpA=sound pressure at 1.5 m in free field (dBA)

20

18 M 18,5-160

kW-motor

Type

3000 Revs/min

You might also like