The PCS-921 numerical relay provides the protection
of circuit breakers with breaker failure protection, pole
discrepancy protection, dead zone protection, phase/
neutral overcurrent protection, single and/or three-pole
auto-reclosing and synchronism check functions. The PCS-
921 relay employs the programmable logic, configurable I/
O and definable 3-color LEDs to provide flexibility for the
specifc applications. Frequency tracking is used to minimize
the sampling error caused by system frequency fuctuation.
The PCS-921 relay adopts the advanced multi-processor
platform, providing the interfaces to station bus and process
bus respectively and supporting IEC 61850-8-1 MMS,
GOOSE, IEC 61850-9-2 Sampling Value. In addition, RJ-45
faceplate port for testing and setting to make commissioning
and maintenance easier.
PCS-921
Circuit Breaker Protection
Functions
Protection and Control
Breaker failure protection (50BF)
Re-tripping the own breaker and tripping the adjacent
breakers will be issued if the external tripping command is
received but the overcurrent element does not drop off. To
improve the sensitivity of generator/transformer protection,
the neutral and negative-sequence overcurrent elements are
provided besides phase overcurrent element.
Pole discrepancy protection (62PD)
The pole discrepancy is detected using the breaker auxiliary
contacts, and the asymmetrical current element could be
selected as an additional criteria.
Dead zone protection (50DZ)
The adjacent breakers will be tripped if the fault between CT
and breaker (dead zone) is detected via the initiating binary
input from external protection, breaker auxiliary contacts and
overcurrent element.
Two stages of phase overcurrent protection (50/51P)
Second harmonic element could be selected to block the
overcurrent element to avoid the maloperation due to
transformer inrush current.
Two stages of neutral overcurrent protection (50/51N)
Second harmonic element could be selected to block the
neutral overcurrent element.
Synchronism check (25)
The criteria could be set as frequency difference, voltage
difference, and phase angle difference. And the checking
condition could be selected as live-bus to dead-line, dead-
bus to live-line or dead-bus to dead-line.
Single and/or three-pole auto-reclosing (79)
Up to 4 shots could be selected for the single-/three- pole
auto-reclosing.
Voltage and current drift auto adjustment
The relay continually and automatically traces the voltage
and current drifts and adjusts the zero point.
Frequency tracking
Frequency tracki ng i s provi ded to accommodate the
frequency shift in power system.
Monitoring and Measurement
VT circuit supervision (VTS)
CT circuit supervision (CTS)
Self diagnostic
Auxiliary power supervision
Event recorder including 1024 disturbance records, 1024
binary events, 1024 supervision events and 1024 operating
logs
Disturbance recorder including 64 disturbance records
with waveforms (The file format of disturbance recorder is
compatible with international COMTRADE fle.)
Read more on the web
www.nrelect.com 154
read more on www.nrelect.com
Counter of circuit breaker operation (single-pole tripping,
three-pole tripping and reclosing)
Communication
Two 10Base-T/100Base-TX (RJ45) ports and two optional
100Base-FX ports with IEC 61850-8-1 MMS and GOOSE for
non-time-critical message, IEC 60870-5-103 over TCP/IP or
DNP 3.0
Two RS-485 rear ports with IEC 60870-5-103
Six or Eight 100Base-FX ports with IEC 61850-9-2 Sampling
Value and GOOSE for time-critical message
One RS-485 rear port for clock synchronization
One RS-232 rear port for printer
One faceplate RJ45 port for testing and setting
Clock synchronization via Pulse-Per-Second, IRIG-B and
SNTP
Features
The relay is based on NRs well established and proven
UAPC hardware platform with multi-processor architecture.
The multi CPU technology supports parallel operating
simultaneously.
The two independent data acquisition paths can prevent any
undesired trip caused by component failure. One works as a
fault detector and the other is designed for protection and its
logic. Tripping outputs are supervised by the fault detector to
prevent a mal-operation.
The sensitive DPFC fault detector element is integrated to
target on the quick response to short-circuit fault.
The relay is compatible with IEC 61850-8-1 MMS, GOOSE
and IEC 61850-9-2 Sampling Value and provides the
independent interfaces for station bus and process bus
respectively.
Technical data
Power Supply
Standard IEC 60255-11:2008
Voltage Range 88 to 300 Vdc or 88 to 264 Vac
Permissible AC ripple voltage 15% of the nominal auxiliary voltage
Burden
Quiescent condition
<30W (for conventional substation application)
<35W (for smart substation application)
Operating condition
<35W (for conventional substation application)
<40W (for smart substation application)
Analog Current
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn5Hz
Rated Current (In) 1A 5A
Linear to 0.05I
n
~ 40I
n

Thermal withstand capability
continuously 4I
n
for 10s 30I
n
for 1s 200I
n
for half a cycle 250I
n
Burden <0.2VA/phase < 0.25VA/phase
Analog Voltage
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 50Hz, 60Hz
Nominal range fn5Hz
Rated phase-to-phase voltage (Un) 100~130V 200V (Broken delta for residual voltage)
linear to 1~170V 1~233V
Thermal withstand capability
continuously 200V 220V
10s 260V 380V
1s 300V 420V
Burden < 0.20VA/phase @Un < 0.8VA/phase@Un
Binary Inputs
Standard IEC 60255-1:2009
Rated voltage 24V 30V 48V 110V 125V 220V 250V
Read more on the web
www.nrelect.com
155 read more on www.nrelect.com
Rated current 1.2mA 1.5mA 2.4mA 1.1mA 1.25mA 2.2mA 2.5mA
Pickup voltage 13V~17V 17V~21V 26V~34V 60.5V~77V 60.5V~77V 121V~154V 121V~154V
Dropout voltage 90% of pickup voltage
Maximum permissive voltage 300Vdc
Withstand 2000VAC, 2800VDC(continuously)
Resolving time for logic input <1ms
Binary Outputs
Item Tripping contact Signal contact
Output mode Potential free contact
Continuous carry
5A@250V AC
5A@250V DC
8A@380V AC
8A@250V DC
Pickup time <8ms <10ms
Drop-off time <5ms (not include delay time by software) <8ms
Short duration current
6A@3s
15A@0.5s
30A@0.1s
10A@3s
20A@0.5s
30A@0.2s
Breaking capacity (L/R=40ms)
0.6A@48VDC
0.2A@110VDC
0.1A@220VDC
0.7A@48VDC
0.3A@110VDC
0.2A@220VDC
Maximal working voltage
380V AC
250V DC
380V AC
250V DC
Test voltage across open contact 1000V RMS for 1minute 1200V RMS for 1 minute
Mechanical Specifcations
Enclosure dimensions (WHD) 482.6mm177.0mm291.0mm
Mounting Flush mounted
Trepanning dimensions (WH) 450.0mm179.0mm, M6 screw
Housing color Silver grey
Protection class
Standard IEC 60255-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection terminals IP20
Pollution degree 2
Ambient Temperature and Humidity Range
Standard IEC 60255-1:2009
Operating temperature -40C to +70C Note: The operating temperature of LCD is -20C ~ +70C
Transport and storage temperature range -40C ~ +70C
Permissible humidity 5% ~ 95%, condensation not permissible
Altitude <3000m
Communication Port
- EIA-485 Port
Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable
- Ethernet Port
Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level
- Optical Fiber Port
Characteristic Plastic optical fber Glass optical fber
Terminal BFOC/2.5 (OR F-SMA) BFOC/2.5 (OR F-SMA)
Fibre size Step-index 980/1000 m Graded-index 62.5/125 m
Transmission distance Up to 40m Up to 1000m
Wave length 660nm 820nm~860nm
Transmission power Min. -7dBm Min. -16dBm
Read more on the web
www.nrelect.com 156
read more on www.nrelect.com
Minimum receiving power Min. -20dBm Min. -24dBm
System reserve Min +3dB Min +3dB
- Print Port
Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON 300K printer
Safety level Isolation to ELV level
- Clock Synchronization Port
Type RS-485
Transmission distance <500m
Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level
Type test
- Environmental tests
Dry cold test Per IEC60068-2-1:2007
Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005
- Mechanical tests
Vibration Per IEC 60255-21-1:1988 Class I
Shock and bump Per IEC 60255-21-2:1988 Class I
- Electrical tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category III
Insulation resistance measurements Isolation resistance >100M@500VDC
- Electromagnetic Compatibility
1MHz burst disturbance test
Per IEC 60255-22-1:2007
Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Electrostatic discharge test
Per IEC60255-22-2:2008 class IV
For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=801000MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Fast transient disturbance tests
Per IEC 60255-22-4:2008
Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Surge immunity test
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic Disturbance
Per IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8:2001
class V, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity
Per IEC 61000-4-9:2001
class V, 6.4/16s, 1000A/m for 3s
Damped oscillatory magnetic feld immunity
IEC 61000-4-10:2001
class V, 100kHz & 1MHz100A/m
Auxiliary power supply performance
IEC60255-11: 2008
Voltage dips: Up to 300ms for dips to 40% of rated voltage without reset
Voltage short interruptions: 100ms for interruption without rebooting