MNS with M10x motor management 2 MNS with M10x motor management 3 Content M10x motor management 04 Value 04 Overview 06 Type designation 08 M10x current input 08 M10x functionality 09 Starter types 09 Full motor protection 10 Thermal overload protection: 12 - TOL protection 12 - TOL EEx e protection 12 Start limitation 13 Phase failure protection 13 Unbalance protection 13 Stall protection 13 Underload protection 13 No load protection 13 Earth fault protection 13 Undervoltage protection: (M102 only) 14 Undervoltage and autorestart: (M102 only) 14 PTC protection: (M102 only) 15 RTD protection 15 Monitoring and reporting 16 This guide is intended to be used along with the following brochures: MNS System Guide Publication no. 1TGC902030B0202 containing details on ABB MNS Low Voltage Switchgear design MNS Safety Aspects Publication no. 1TGC900009B0201 containing details on plant and personnel safety assured by MNS design ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without ABBs written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. All rights reserved. COPYRIGHT 2011ABB Operator user interface 17 Communication interface 18 Redundant communication 19 M10x installation 21 MCU setup software 22 M10x interface 23 Terminal wiring diagram 24 Technical data 36 Appendix 38 Type designation 38 MNS with M10x motor management 4 MNS with M10x motor management 5 MNS with M10x motor management: value Inherent safety with MNS Switchgear Intelligent low voltage switchgear solution based on ABBs MNS system which is a fully type tested design according to IEC61439. Reference is made to MNS System Guide and MNS Safety Manual. High functionality for better protection A wide range of protection, monitoring and control functionalities are available as a standard with M10x complying to the most demanding specification. Customer can choose the required functionality anytime based on projects requirement. Lower system design cost M10x device replaces multi functional relays as typically used in MCCs, thus reducing a large amount of internal control wirings, external installation of cabling, inter-panel wiring of control system I/O blocks etc. and contributes to a lower overall cost of system design. Standardized motor starter solutions With protection and control functions combined/embedded in the intelligent M10x device, it becomes possible to standardize solutions for motor starters. This has contributed to a reduced footprint and lesser amount of spare motor starter modules required for the Switchgear and MCC system. Reduced maintenance needs With real time maintenance information available via M10x such as motor operating hours (motor fatigue) and number of operations (contactor fatigue), maintenance staff are able to monitor and arrange necessary maintenance for motors and motor starters if required. Maximize plant availability and efficiency With the information being monitored and transferred via M10x, process control and plant management system could be optimized, hence maximizing plant availability and efficiency. Reduced downtime Plant wide information and need based maintenance together with the standardization of motor starters in the MCC reduce process downtime. A motor starter with M10x can be easily replaced with a spare starter of the same configuration. This eliminates the need for repair at site, thus the motor can be re-started quickly. MNS with M10x motor management 6 MNS with M10x motor management 7 MNS with M10x motor management: overview M10x is an intelligent system based on the low voltage switchgear MNS, offering superior protection, control and monitoring for user-optimized motor management. Relevant information from the process including timely alarms enable plant operators to make smart decisions on process conditions. Plant availability is significantly improved through preventive actions. Data with quality far beyond conventional motor protection or remote control technology, is utilized by the engineering team for detailed system analysis and need-based maintenance. This brochure provides an overview of the M10x system, its components, their functions and benefits as well as relevant technical data. Please refer to our website at www.abb.com/mns for more information. System overview Control system overview showing typical low voltage energy distribution and motor control centre communicating upwards to process control systems and sideways to engineering and maintenance stations. Available in simplex or dual-redundant configuration. MNS with M10x motor management 8 MNS with M10x motor management 9 M10x is an intelligent motor control and protection device based on current and voltage measurement and maintenance data monitoring, which offers superior protection, control and monitoring for user. It is installed as part of ABBs low voltage switchgear system MNS providing an intelligent low voltage switchgear and MCC solution. M10x is available with options for serial communication. MNS with M10x motor management Type designation M10x relays are identified as follows by functions and communication protocols employed. Each type designation is represented by a hardware type. M101 offers basic motor control and protection function based on current measurement. M102 provide advanced functions for motor protection and control based on current, voltage measurement. When selecting a device, user has to know what function and protocol type is required to select the appropriate hardware type. For example a basic device with Modbus RTU is identified as M101-M; an advanced device with Modbus RTU is identified as M102-M. Further details to the M101 and M102 device type designation list is available in Appendix M10x type designation. Note: M10x term is used in this manual if a function applies to M101 and M102. If a function applies to only one type, then the type is specifically mentioned, e.g. M102. M10x current input A current transformer is integrated in M10x with a primary current ranging from 0.5A to max. 63A. M10x devices are available with the following current ranges: 0.5 1A 1 2.5A 2.5 5A 5 12.5A 12.5 30A 30 63A Smaller motor current < 0.5A can be measured by wiring the main circuit multiple times through the integrated with M10x CT (using smallest range: 0.5~1.0A) thus increasing the inlets. For motor current > 63A a secondary current transformer is used. The current transformer to be used as input of M10x shall be of protection type with 8 times of overload capacity. M10x Motor Ie 63A Direct input on device Motor Ie > 63A 1A or 5A input via secondary current transformer M10 x - x Function type 1. Basic Type (Current Based Only) 2. Advanced Type (Current + Voltage Based) Communication type M - Modbus RTU P - PROFIBUS DP Note: 1) M10x-P has options of PROFIBUS DP V0 or PROFIBUS DPV1 2) M10x-P has options of 24VDC DI or 230VAC DI M10x relays provide a full range of functionalities for motor monitoring, control and protection. Starter types M10x offers a variety of motor start modes via parameterization, and supervises the operating state of the contactor through the feedback of the auxiliary contact of the contactor. The control authority of the motor includes local control and remote control. All necessary motor starting control modes are integrated in the device. To select a desired starting control mode, simply click on the setup interface of the M10x motor control unit. Start Modes M101 M102 Non-reversing Direct Online NR-DOL NR-DOL with RCU function Reversing Direct Online REV-DOL REV-DOL with RCU function Actuator (e.g. Valve or Damper control) Start / Delta starter 2 Speed starter Autotransformer NR-Softstarter REV-Softstarter Feeder (motor operated) Remarks: RCU: RCU is an option to control the contactor by bypassing the M10x. Actuator: Starter type is based on Reversing direct on line starters where limit switch inputs are used to stop the motor in some necessary cases like valves, dampers, actuators etc. Feeder: Feeder mode is listed as a specific start mode in M10x to serve for circuit controlling and supervising for motor operated MCCB feeder. M10x functionality MNS with M10x motor management 10 MNS with M10x motor management 11 Full motor protection M10x devices provide full motor protection. Full motor protection means timely and accurate protection by continuously collecting and keeping track of information on all operating states during the course of motor operations, providing fault alarm and protection action (protection trip) and setting action delay times, to safeguard motors and smooth production. Via serial communication, real-time information of process motors is reporting upward to plant control system, hence, providing the basis for process analysis and management optimization. Prior to any possible major fault in the equipment, a limit-exceeding alarm will alert the administrator in a timely manner to take corrective actions to prevent unnecessary shutdown. This provision maximizes the operating efficiency of the equipment. When the preset alarm level is reached, only alarm is generated. A Trip Delay is triggered as soon as the preset trip level is crossed. If the motor is restored before the trip delay time runs out, no trip follows. While it trips when the trip level is remained and the Trip Delay is expired. In any of the above cases, an event message is generated and issued via serial communication. M10x motor protection has the following features: All protection functions are implemented with the microprocessor built in the device and configurable. The desired protection function can be easily selected with the parametering software. The protection function can be set as alarm and trip, alarm only, or trip only. Trip reset modes can be configured as any of the following by preset of trip reset modes. The reset modes are different in various protection functions: Automatic reset Remote reset Local reset Local & remote reset Motor protection functions Description M101 M102 TOL protection It keeps track of and calculates the thermal capacity of the motor in operation to protect the motor against overheating.
TOL EEx e The EEx e protection takes into consideration the stall/nominal current ratio and the maximum motor temperature allowed by the environment class definition.
Start limitation protection Limits the number of starts during a time interval. Number of starts and time interval are parameter settings.
Phase failure protection It uses the minimum/maximum line current ratio as the criterion. To enable the phase failure protection function.
Phase unbalance protection Unbalance can be caused by pitted contacts, faulty motor, loose connections etc. The difference between the minimum and maximum phase currents is compared against the set parameters. Reverse phase protection not supported for the IEEE standard.
Stall protection Protects against stall, the highest measured phase current to compare against the set parameters, activates only after motor start-up time is complete.
Undervoltage protection Protects the motor against undervoltage condition (voltage drop or loss). Undervoltage and autorestart Available in standard and enhanced models. Underload protection Uses the highest measured phase current, to compare against set parameters No load protection Similar to Underload but with different set levels and messages. No load uses the highest measured phase current to compare against the set parameters.
Earth fault protection Protects the motor against the earth fault condition with an additional residual current transformer with adjustable trip level and time delay.
Motor temperature protection (PTC) Protects against too high temperature by using PTC sensors. The resistance values are compared against the set levels.
Motor temperature protection
using PTC relay Monitors motor winding temperatures from PTC sensors against preset values using an additional thermistor relay.
Motor temperature protection using RTD relay Monitors motor winding temperatures from PT 100 sensors against preset values, options are available for single or triple channel monitoring.
Alarm level, trip level and trip delay illustrated Motor start Normal load Normal load Temporary fault Continuous fault Alarm and trip data set according to motor manufacturers specication and process needs Thermal capacity Time MNS with M10x motor management 12 MNS with M10x motor management 13 Thermal overload protection: Thermal overload (TOL) protection keeps track of and calculates the thermal capacity of the motor in operation to protect the motor against overheating, which may shorten the service life of the motor or damage it. In addition, the thermal memory function of the TOL protection is particularly important in the case that frequent starting is required.
The TOL protection has a thermal memory function, which protects the motor from startup in an overheated condition. The M10x unit simulates the thermal conditions in all operating states of the motor to maximize the use of the motor on the premises for safe operation. The TOL protection takes into consideration of the temperature rise of the motor rotors and stators, as well as the impact of the three-phase unbalance on the overheated motor. When the restart command is issued before the temperature drops to the pre- set restart level after a TOL Trip, the M10x device will then suppress the command and consequently the motor will not be restarted. TOL protection The trip level, alarm level and reset level can all be adjusted by setting the parameters or altering constant values. TOL EEx e protection: The EEx e protection takes into consideration the stall/ nominal current ratio and the maximum motor temperature allowed by the environment class definition. Relevant data of EEx e motor is provided by motor manufacturer to direct programming into the M10x device without additional calculation. Start limitation: Start limitation helps to protect the motor and also the process against excess number of starts in a given interval. When the number of starts is reached and the motor is switched off, a new start is prevented. Phase failure protection: The phase failure protection function uses the minimum/ maximum line current ratio as the criterion. To enable the phase failure protection function, relevant parameters must be set, such as the alarm level, the trip level and the trip delay. Protection action can be either delayed trip or alarm only without trip. Unbalance protection: The three phase unbalance protection function uses the minimum/maximum line current ratio as the criterion. To enable the three phase unbalance protection function, relevant parameters must be set, such as the alarm level, the trip level and the trip delay. The protection action can be either delayed trip or alarm only without trip. Stall protection: The stall protection function uses the maximum line current/ motor rated current ratio as the criterion. To enable the stall protection function, relevant parameters must be set, such as the trip level and trip delay. The protection action is delayed trip. Underload protection: The underload protection function uses the maximum line current/rated current ratio as the criterion. To enable the underload protection function, other parameters must also be set, such as the alarm level, the trip level and the trip delay. The protection action is either delayed trip or alarm only without trip. No load protection: The no load protection function uses the maximum line current/rated current ratio as the criterion. To enable the no load protection function, other parameters must also be set, such as the alarm level, the trip level and the trip delay. The protection action is either delayed trip or alarm only without trip. Earth fault protection: The earth fault protection function protects the motor against the earth fault condition with an additional residual current transformer. When the earth fault current exceeds the preset trip level, delayed trip or instantaneous trip is triggered. A torodial current transformer is required for this function. Earth fault protection in M10x can be set to active or inactive during motor start up period. ABB LNG series residual current transformer is employed as earth fault protection input of M10x. ABB LNG is available in three different diameter dimensions 35, 70 and 105. 1A or 5A current can be selected, depending on the setting range of the earth fault current of the protected system. Shielded Twisted Pair should be used between outputs of LNG CT and terminals of M10x. Spec Primary Side Input (A) Secondary Side Output (V) Lead-through Dimensions (mm) LNG35 1A 1 1 35 LNG35 5A 5 1 35 LNG70 1A 1 1 70 LNG70 5A 5 1 70 LNG105 1A 1 1 105 LNG105 5A 5 1 105 LNG CT Thermal overload protaction illustated Thermal capacity Time Thermal capacity must be below Start Inhibit to allow a motor start. MNS with M10x motor management 14 MNS with M10x motor management 15 Undervoltage protection: (M102 only) The undervoltage protection function is enabled when the voltage of the main circuit drops below the set value. To enable the undervoltage protection function, other parameters must be set, such as the alarm level, the trip level and the trip delay. The protection action is delayed trip. Undervoltage and autorestart: (M102 only) Following a sudden voltage dip, M102 can restart the motor in different modes, depending on the specific circumstances in which the voltage is restored. There are three cases of auto restart: The voltage is restored within the autoreclose time (presetting required), the motor will be restarted immediately; If the voltage is restored after the autoreclose time (presetting required) but before the maximum undervoltage time (presetting required), the M102 device will restart the motor in its staggered sequence; in other words, the motor will be restarted after the staggered start delay (adjustable) expires. If the voltage is restored after the maximum undervoltage time (presetting required), M102 will not execute restart; in other words, the auto restart function of the motor will be suspended. Two alternative modes of auto restart function are integrated in M102: standard and enhanced. The standard mode applies to the above 3 cases; the enhanced mode, in addition to the functions available in the standard mode, applies to a fourth case: If the interval between two voltage dips is less than 1 second and neither voltage dip has exceeded 200ms, M102 will restart the motor in the staggered sequence; in other words, the motor will be restarted after the staggered starting delay (adjustable) expires. The auto restart function can effectively protect the motor against the disturbance caused by the instantaneous voltage dip. PTC protection: (M102 only) The PTC protection function (only M102) protects the motor against too high temperature by monitoring the thermal resistance of the PTC-sensor embedded in the stator windings; delayed trip is triggered when the level is exceeded. If the PTC resistance detects an open circuit, M102 will issue an alarm message. PTC Protection with M101 is possible by using an additional PTC protection relay and by connecting the trip signal to a digital input on M101. No PTC alarm is possible through this connection. Direct connect of PTC to M102 L1 L2 L3 M 3 RTD protection: The RTD (or PT100) protection function is possible with M10x and protects the motor against too high temperature by connecting a separate PT100 relay to a digital input on M10x. A PT100 relay type is used to monitor the thermal resistance of the PT100-sensor embedded in the stator windings. Depending on the relay type delayed trip or instantaneous trip is triggered when the level is exceeded. (for details on PT100 monitoring refer to the relay manufacturer manual). PT100 motor temperature protection using external PT100 relay t Staggered start time Restore level Trip level On <1s Contactor open Contactor close Autorestart - fourth case (2x dips < 200ms) MNS with M10x motor management 16 MNS with M10x motor management 17 Monitoring and reporting M10x provides an extensive range of motor operation supervisory functions. Supervisory data are transmitted via the field bus to the upper level system for centralized management and are optionally directly displayed on the operator panel MD2 if installed on the front of the motor starter module. Motor protection functions M101 M102 Description M o t o r
S t a t u s Motor status On/Off, Open/Closed, Tripped Fault info. Overload, phase failure, three phase unbalance, earth fault and PTC protections Three phase current R.M.S value or Relative value Three phase voltage R.M.S value Power factor Power factor Active power Active power KWh*) Energy consumed by the motor Earth fault current Earth fault current Frequency Frequency of the power system M a in t e n a n c e D a t a Number of operations of contactor Maintenance reference Motor running hours Maintenance reference Note: 1) The parameter marked *) cannot be sent by PROFIBUS DPV0. MD2 and MD3 panel can be used for both M101 and M102 device. Function MD2 MD3 Description Control button Start1, Start2, Stop(Reset) Indicator Ready, Start1, Start2, Fault Fault type display Overload, Phase failure, Phase unbalance, Stall, Underload, No load, Earth fault and PTC protections Current Phase Currents: R.M.S value or relative value Voltage Phase voltages: R.M.S value Active power Absolute value Power factor Absolute value kWh Energy Parameterization interface USB plug LCD mode LCD display Operator user interface M10x can optionally be equipped with an operator panel MDx, which is used to display the status of the motor. Motor control is possible through predefined pushbuttons. A USB physical connection port is available on the operator panel for parameterization via service laptop and software. The basic type MD3 provides 4 LED indicators (Ready, Start1, Start2, Fault) and has pushbuttons for operation. The operator panel MD2 integrates the functions of measurement display, LED indicators and pushbuttons as well as fault monitoring functions. MD2 MD3 MNS with M10x motor management 18 MNS with M10x motor management 19 The M10x motor control unit has serial communication interfaces based on EIA-485 (RS-485) standard. M10x is connected to the upper level process control and management system for communication via the communication port on the device, supporting the following protocols: PROFIBUS DP V0 / V1 Communication Modbus RTU Communication Other serial protocols can be achieved by using a protocol converter. Communication interface 1x M10x-P 2x 3x 31x M10x-P 1x M10x-M 2x 3x 31x M10x-M PROFIBUS DP Modbus RTU Modbus Communication PROFIBUS Communication Redundant communication Higher availability in serial communication application is provided with redundant connectivity on M10x. With Modbus RTU direct redundant serial communication is possible as the M10x-M provides two identical RS-485 interfaces on the same device. Two Modbus RTU cables are connected throughout the switchgear assembly to each M10x-M. Both Modbus ports use the same communication parameter (e.g. address, speed etc.). This allows the M10x-M to be connected, for example, to two communication lines to the upper level process control system or alternatively connect one line to the process control and the other line to the management system. 1x M10x-M 2x 3x 31x M10x-M Modbus RTU Modbus Communication (Redundant) MNS with M10x motor management 20 MNS with M10x motor management 21 RLM01 Redundant Link Module With PROFIBUS DP redundant communication to a process control system can be provided utilizing a redundant link module RLM01. Inside the switchgear assembly the PROFIBUS DP cable connection is single while the connection to the upper level process control system through the RLM01 module is provided as a redundant interface. PROFIBUS DP 1x M10x-P 2x 3x 31x M10x-P PROFIBUS Communication M10x installation M10x is installed in withdrawable modules as part of ABBs Low Voltage Switchgear MNS M10x and the operator panel MDx are mounted individually and electrically connected to each other via the connection cable. The compact size makes it possible to installed M10x in the smallest size as 8E/4 module of ABB MNS switchboard. The minimum installation space in MNS is smaller or remains the same as it is required for traditional protection with thermal relays. For further detail on installation size per motor rating refer to the MNS brochure. The operator panel MDx is designed to be flush mounted on the front or door of the MNS module. The following minimum mounting space requirements apply for MNS modules when using the MDx operator panel: Min. Mounting Space MD2 MD3 MNS 8E/2 MNS 8E/4 M10x 6E 8E/4 8E/2 MD2 MD2 M10x MNS with M10x motor management 22 MNS with M10x motor management 23 MCU setup software MCU setup software for the parameterization and configuration of M10x is user friendly and Microsoft Windows based. Parameter setting is carried out via a dedicated parameter cable connecting the M10x to the MDx panel mounted on the front of the motor starter module. Software allows for the parameterization of all functions of the different M10x types
User friendly setup windows make the parameter setting easy to understand and follow. Import and Export setting functions allows users to choose to manage setting files online or offline. For plants that require different access levels for security reasons, up to 3 level user groups can be defined and assigned under the user management menu. M10x interface Digital inputs for various functions, see Connection Diagram for details Digital output Power supply Ground safety and surge Voltage input Thermistor input CT inputs (Lead-through) Interface for operator panel RS485 ports Residual CT input M10x interface X2 X4 X3 X1 T L MNS with M10x motor management 24 MNS with M10x motor management 25 Terminal wiring diagram M101-M terminal diagram M101-M terminal description Terminal No. Name Description X1 Terminal Block X1:1 IN_COM DI common terminal X1:2 NC X1:3 LOC/R Local/remote control select switch input X1:4 NC X1:5 F_Ca Feedback of auxiliary contact of contactor X1:6 NC X1:7 F_Cb Feedback of auxiliary contact of contactor X1:8 NC X1:9 PROG_IN0 Programmable input 0 X1:10 NC X1:11 PROG_IN1 Programmable input 1 X1:12 NC X1:13 PROG_IN2 Programmable input 2 X1:14 NC X1:15 NC X1:16 NC X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 2B RS485 communication port 2 X3:2 2A X3:3 SHIELD Communication port shielding layer X3:4 1B RS485 communication port 1 X3:5 1A X3:6 IoA Residual current input X3:7 IoB X3:8 NC X3:9 NC X3:10 NC X3:11 NC X3:12 NC X3:13 NC Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay output X4:2 GR1_B X4:3 GR1_C X4:4 NC X4:5 NC X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 NC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground
MNS with M10x motor management 26 MNS with M10x motor management 27 M101-P (DC24V power supply for DI) terminal diagram: M101-P (DC24V power supply for DI) terminal description Terminal No. Name Description X1 Terminal Block X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI9 Digital Input 9 X1:11 DI10 Digital Input 10 X1:12 DI11 Digital Input 11 X1:13 DI12 Digital Input 12 X1:14 DI_COM Digital Input common terminal X1:15 NC X1:16 NC X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 5V Power to external terminator X3:2 B RS485B X3:3 A RS485A X3:4 GND Power to external terminator X3:5 SHIELD Communication port shielding layer X3:6 IoA Residual current input X3:7 IoB X3:8 NC X3:9 NC X3:10 NC X3:11 NC X3:12 NC X3:13 NC Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay output X4:2 GR1_B X4:3 GR1_C X4:4 NC X4:5 NC X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 NC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground MNS with M10x motor management 28 MNS with M10x motor management 29 M101-P (AC230V power supply for DI) terminal diagram M101-P (AC230V power supply for DI) terminal diagram Terminal No. Name Description X1 Terminal Block X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI_COM Digital Input common terminal X1:11 NC X1:12 NC X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 5V Power (5V+) to external terminator X3:2 B RS485B X3:3 A RS485A X3:4 GND Power (GND) to external terminator X3:5 SHIELD Communication port shielding layer X3:6 IoA Residual current input X3:7 IoB X3:8 NC X3:9 NC X3:10 NC X3:11 NC X3:12 NC X3:13 NC Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay output X4:2 GR1_B X4:3 GR1_C X4:4 NC X4:5 NC X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 NC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground MNS with M10x motor management 30 MNS with M10x motor management 31 M102-M terminal diagram M102-M terminal description Terminal No. Name Description X1 Terminal Block X1:1 LIMIT1 Limit position switch 1 X1:2 LIMIT2 Limit position switch 2 X1:3 START1 Start button 1 X1:4 START2 Start button 2 X1:5 STOP Stop button X1:6 LOC/R Local/remote control select switch input X1:7 F_Ca Feedback of auxiliary contact of contactor X1:8 F_Cb X1:9 F_Cc X1:10 PROG_ IN0 Programmable input 0 X1:11 PROG_ IN1 Programmable input 1 X1:12 PROG_ IN2 Programmable input 2 X1:13 MCB Main switch auxiliary contact signal input X1:14 PTCA Thermistor Input X1:15 PTCB X1:16 PTCG X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 2B RS485 communication port 2 X3:2 2A X3:3 SHIELD Communication port shielding layer X3:4 1B RS485 communication port 1 X3:5 1A X3:6 IoA Residual current input X3:7 IoB X3:8 N Neutral X3:9 Vc C phase voltage input X3:10 X3:11 Vb B phase voltage input X3:12 X3:13 Va A phase voltage input Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay 1 output X4:2 GR1_B X4:3 GR1_C X4:4 GR2_A Programmable relay 2 output X4:5 GR2_B X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 CCC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground MNS with M10x motor management 32 MNS with M10x motor management 33 M102-P (DC24V power supply for DI) terminal diagram M102-P (DC24V power supply for DI) terminal description Terminal No. Name Description X1 Terminal Block X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI9 Digital Input 9 X1:11 DI10 Digital Input 10 X1:12 DI11 Digital Input 11 X1:13 DI12 Digital Input 12 X1:14 DI_COM Digital Input common terminal X1:15 PTCA Thermistor Input X1:16 PTCB X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 5V Power to external terminator X3:2 B RS485 B X3:3 A RS485 A X3:4 GND Power to external terminator X3:5 SHIELD Communication port shielding layer X3:6 IoA Residual current input X3:7 IoB X3:8 N Neutral X3:9 Vc C phase voltage input X3:10 X3:11 Vb B phase voltage input X3:12 X3:13 Va A phase voltage input Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay 1 output X4:2 GR1_B X4:3 GR1_C X4:4 GR2_A Programmable relay 2 output X4:5 GR2_B X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 CCC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground MNS with M10x motor management 34 MNS with M10x motor management 35 M102-P (AC230V power supply for DI) terminal diagram M102-P (AC230V power supply for DI) terminal description Terminal No. Name Description X1 Terminal Block X1:1 DI0 Digital Input 0 X1:2 DI1 Digital Input 1 X1:3 DI2 Digital Input 2 X1:4 DI3 Digital Input 3 X1:5 DI4 Digital Input 4 X1:6 DI5 Digital Input 5 X1:7 DI6 Digital Input 6 X1:8 DI7 Digital Input 7 X1:9 DI8 Digital Input 8 X1:10 DI_COM Digital Input common terminal X1:11 PTCA Thermistor Input X1:12 PTCB X2 Connector X2 Interface for MDx X3 Terminal Block X3:1 5V Power to external terminator X3:2 B RS485 B X3:3 A RS485 A X3:4 GND Power to external terminator X3:5 SHIELD Communication port shielding layer X3:6 IoA Residual current input X3:7 IoB X3:8 N Neutral X3:9 Vc C phase voltage input X3:10 X3:11 Vb B phase voltage input X3:12 X3:13 Va A phase voltage input Terminal No. Name Description X4 Terminal Block X4:1 GR1_A Programmable relay 1 output X4:2 GR1_B X4:3 GR1_C X4:4 GR2_A Programmable relay 2 output X4:5 GR2_B X4:6 CCL1 Control circuit power supply X4:7 CCA Control relay output X4:8 CCB X4:9 CCC X4:10 GND 24VDC power supply X4:11 24VDC X4:12 GROUND System protection ground MNS with M10x motor management 36 MNS with M10x motor management 37 Technical data Main circuit Rated operation voltage (Ue) 230 / 400V or 400 / 690V Rated insulation voltage (Ui) 690V Rated impulse withstand voltage (Uimp) 6kV Degree of pollution 3 Rated operation current (Ie) 0.5-1A 1-2.5A 2.5-5A 5-12.5A 12.5-30A 30-63A Rated frequency 50 / 60Hz Control circuit Rated operational voltage (Ue) 24VDC or 230VAC Rated insulation voltage (Ui) - or 250V Rated impulse withstand voltage (Uimp) - or 4kV Rated operational current (Ie) Contactor control relay output 2A (DC-13) Programmable relay output 2A (AC-15) 2A (DC-13) Rated frequency 2A (AC-15) 50 / 60Hz DC Power supply Rated operational voltage (Ue) 24VDC Voltage operation range 85%-110% Ue DC Power consumption Typical 4.5W Maximum 8W Maximum starting current 600mA Digital input (24VDC) Number of digital input 6 (M101-M) / 13 (M102-M) 13 (M101-P) / 13 (M102-P) Close contact current (peak) 2.55mA Open contact current (peak) 00.8mA Digital input (230VAC) Number of digital input 9 (M101-P) / 9 (M102-P) , not available for M10x-M Close contact current (peak) 2.13mA Open contact current (peak) 01mA FIELDBUS interface Protocol PROFIBUS-DP V0 & V1 Baud rate 9.6kbps / 19.2kbps / 45.45kbps / 93.75kbps / 187.5kbps / 500kbps / 1.5Mbps Protocol Modbus RTU Baud rate 1.2 / 2.4 / 4.8 / 9.6 / 19.2kbps Environmental conditions Storage temperature -25 - +85C Normal operation temperature -5 - +60C Humidity 15% up to 95% without dew EMC Environment 1) Equipments in the system comply with EMC requirement of CE / CCC certificate. 2) Power supply system complies with IEC61000-2-1, IEC61000-2-2, especially the system in which VSD / Frequency Converters are used. Metering accuracy Phase current Range: 0.1-8 phase CT primary amps Accuracy: 2% Earth fault current Full scale: 1.2 RCT nominal current Accuracy: 2% RCT primary Phase voltage (M102 Only) Voltage metering range: 110V 440V Accuracy: 2% Power (M102 Only) Accuracy: 5% nominal or 5% reading, whichever is greater Thermistor Input (M102 Only) Sensor type: positive temperature coefficient PTC RHOT=100-10,000 Accuracy: 5% or 100 which is greater Standards Low voltage switchgears IEC60947-1 Low voltage switchgear and controlgear Part1: General rules IEC60947-4-1 Low voltage switchgear and controlgear Part4: Contactors and motor- starters, Section one-Electromechanical contactors and motor-starters EMC Electrostatic discharge IEC61000-4-2, Level 3 Electromagnetic field immunity IEC61000-4-3, Level 3 Electrical fast transient/burst immunity IEC61000-4-4, Level 4 Surge immunity IEC61000-4-5, Level 3 Conducted disturbance immunity IEC61000-4-6, Level 2 Radiated disturbance EN55011, Class A MNS with M10x motor management 38 MNS with M10x motor management 39 Appendix Type designation M10x- M 004 - M101-M 24VDC DI (HW1.0) 124 - M102-M 24VDC DI (HW1.2) 0 - Basic Unit 2 - Kit (Basic Unit +MD2) 3 - Kit (Basic Unit +MD3) 82 - M101-M 90 - M102-M 1 - CT range 0.5-1.0A 2 - CT range 1.0-2.5A 3 - CT range 2.5-5.0A 4 - CT range 5.0-12.5A 5 - CT range 12.5.5-30.0A 6 - CT range 30.0-63.0A Note, HW =Hardware Version M101- P 004 - PROFIBUS DPV0, 24VDC DI (*HW1.0) 204 - PROFIBUS DPV1, 24VDC DI (HW2.0) 304 - PROFIBUS DPV0, 230VAC DI (HW3.0) 404 - PROFIBUS DPV1, 230VAC DI (HW4.0) 0 - Basic Unit 2 - Kit (Basic Unit +MD2) 3 - Kit (Basic Unit +MD3) 1 - CT range 0.5-1.0A 2 - CT range 1.0-2.5A 3 - CT range 2.5-5.0A 4 - CT range 5.0-12.5A 5 - CT range 12.5.5-30.0A 6 - CT range 30.0-63.0A Note, HW =Hardware Version 1TNA911 xxx R a bb c 1TNA911 xxx R a 83 c M102- P 214 - PROFIBUS DPV0, 24VDC DI (HW V2.1) 304 - PROFIBUS DPV1, 24VDC DI (HW V3.0) 404 - PROFIBUS DPV0, 230VAC DI (HW V4.0) 504 - PROFIBUS DPV1, 230VAC DI (HW V5.0) 0 - Basic Unit 2 - Kit (Basic Unit +MD2) 3 - Kit (Basic Unit +MD3) 1 - CT range 0.5-1.0A 2 - CT range 1.0-2.5A 3 - CT range 2.5-5.0A 4 - CT range 5.0-12.5A 5 - CT range 12.5.5-30.0A 6 - CT range 30.0-63.0A 1TNA911 xxx R a 91 c MNS with M10x motor management 40 ABB Low Voltage Systems Local contacts on www.abb.com/mns Publication Editor: ABB Malaysia Sdn Bhd (210262-T) Lot 608, Jalan SS13/1K 47500 Subang Jaya Selangor Darul Ehsan, Malaysia Publication No. 1TPMC00201 Copyright 2010 ABB All rights reserved ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts there of must not be reproduced or copied without ABBs written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. The software described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Contact us