You are on page 1of 3

Reference: ADSS LT

Std FADSLT-D-LKO-F-16kN-12(84-96)-1e
2009-11-06

Specifications may be changed at any time without notice. All sizes and values without tolerances are reference values.
Specifications are for product as supplied by Draka: any modification or alteration afterwards of product may give different result
Not to be reproduced or communicated without prior Draka agreement. Page 1 of 2

All dielectric aerial Cable, ADSS long span 16 kN
Tracking resistant

Cable Design
Loose tube structure - filled core - dielectric reinforcement - double sheath


- not to scale -

Central strength member (CSM): glass fibre reinforced plastic material (FRP).
Tube: thermoplastic material, containing 12 single-mode optical fibres and filled
with a suitable water tightness compound.
Stranding: the required number of elements (tubes or fillers) are SZ stranded
around the central strength member.
Longitudinal Water Tightness: filled core.
Inner Sheath: PE. 1 ripcord underneath the sheath.
Armour: High modulus aramid yarns, helically stranded.
Outer Sheath: tracking resistant compound
(1)

(1) the outer sheath is tracking resistant up to 25kV according to specification IEEE P 1222 3.7 Class B, Test requirement
4.1.13, 5.1.13 and Annex A

Configuration
No. of Fibres 84 96
Design 8x12
Loose Tube / Filler - mm 2.8
Cable Diameter mm 16.2
Cable Weight kg/km 222
Thermal elongation coefficient 1E-6/C 6
Effective cross-sectional area mm 25.7
Modulus of elasticity daN/mm 7800
MOT (maximum tension in operation , no
fibre strain)
daN 1600
MAT (maximum allowable tension) daN 2000
RTS (rated tensile strength, no optical
consideration, non-reversible damages)
kN 35.9


Application
Overhead installation on HT Power lines.
Temperature Range Transportation & Storage: - 40 ->+70C Minimum Bending Radius
Installation: -10 ->+60C Dynamic: 20 x cable
Operation: - 40 ->+70C Static: 10 x cable
Aerial installation Nominal span* : 400/ sag : 3 %
Maximum Space Potential recommendation: 12kV**
Maximum span 600 m*
* typical values to be adapted depending on the environmental conditions
** Refer to the document ADSS Cable-Tracking-1e


Optical Characteristics
See the attached cabled optical fibre data sheet.


Reference: ADSS LT

Std FADSLT-D-LKO-F-16kN-12(84-96)-1e
2009-11-06

Specifications may be changed at any time without notice. All sizes and values without tolerances are reference values.
Specifications are for product as supplied by Draka: any modification or alteration afterwards of product may give different result
Not to be reproduced or communicated without prior Draka agreement. Page 2 of 2


Main Mechanical and Environmental Characteristics
Test Standard Specified Value Acceptance Criteria***
MOT : see table above l/l fibre 0.05%, 0.05 dB Maximum Tension IEC 60794-1-2-E1
MAT : see table above l/l fibre 0.2%, 0.1 dB/100m
Crush IEC 60794-1-2-E3 220 daN / 100mm 0.1 dB
Impact IEC 60794-1-2-E4 10 Nm reversible
Torsion IEC 60794-1-2-E6 1m, +-180 0.1 dB
Cable bend IEC 60794-1-2-E11B 20 x Cable- 0.1 dB
Temperature Cycling IEC 60794-1-2-F1 -40C +70C 0.1 dB/km
Water penetration
(optical core)
IEC 60794-1-2-F5B sample=3m, water=1m No water leakage after 24 h
*** values for single-mode fibres, all optical measurements performed at 1550 nm



Identification and Packing

Fibre Colours
No. 1 2 3 4 5 6 7 8 9 10 11 12
Colour blue orange green brown grey white red black yellow violet pink aqua


Buffer Tube Colour
No. 1 2 3 4 5 6 7 8
Colour blue orange green brown grey white red black

Fillers if any are natural.

Sheath Colour:
The outer sheath colour is black.


Sheath Marking:
The state of the outer surface of the cable being determinant for the prevention of the electrical effects that
could be detrimental to the cable over the time, we recommend to not print any legend on the outer sheath.


Packing:
Wooden drums with protection.


Delivery Lengths:
Standard delivery lengths are 2 km, 4 km, 6 km with a tolerance of - 1% / +3%


Reference: ADSS Flextube

Std FADSLT-D-LKO-F-16kN-12(84-96)-600m HTA-G1-1e
2009-11-06

Specifications may be changed at any time without notice. All sizes and values without tolerances are reference values.
Specifications are for product as supplied by Draka: any modification or alteration afterwards of product may give different result
Not to be reproduced or communicated without prior Draka agreement. Page 1 of 1

All dielectric aerial Cable, ADSS long span 16 kN
Tracking resistant

Span: 200-600 m, cable diameter: 16.2mm, 84-96 OF


Installation Sag: 3%

Cable datas Basic Hypothetis (C0)
Cable diameter: mm Temperature: 15 C
Cable Weight: kg/km
Effective cross-sectional area: mm Initial sag: 3.0%
Modulus of Elasticity: kN/mm span range: 200 -> 600 m
Thermal Elongation Coefficient: *10-6/K Denivellation :
MOT: daN (maximum tension in operation, no fibre strain)
MAT: daN (maximum allowable tension)
RTS: kN (tension above which the cable may break, no optical consideration)
Load Conditi ons
(1) Wind applied to diameter without ice
Span (m)
Deniv (m) C0 -30 -20 -10 0 10 20 30 40 50 60 C1 C2
200 Sag(m) 6.00 5.71 5.78 5.84 5.90 5.97 6.03 6.09 6.16 6.22 6.28 8.36 8.96
0.0 Tmax (daN) 183 192 190 188 186 184 182 180 178 176 175 642 810
Angle () 78.1 33.0
240 7.20 6.87 6.94 7.02 7.09 7.16 7.24 7.31 7.38 7.46 7.53 10.38 11.18
0.0 219 230 227 225 223 220 218 216 214 212 210 746 936
78.1 33.0
280 8.40 8.02 8.11 8.19 8.27 8.36 8.44 8.52 8.61 8.69 8.77 12.47 13.49
0.0 256 268 265 262 260 257 255 252 250 248 245 846 1057
78.1 33.0
320 9.60 9.18 9.28 9.37 9.46 9.55 9.65 9.74 9.83 9.92 10.01 14.63 15.89
0.0 292 306 303 300 297 294 291 288 286 283 281 942 1173
78.1 33.0
360 10.80 10.34 10.45 10.55 10.65 10.75 10.85 10.95 11.05 11.15 11.25 16.86 18.37
0.0 329 343 340 337 334 331 328 325 322 319 316 1036 1286
78.1 33.0
400 12.00 11.51 11.62 11.73 11.84 11.95 12.05 12.16 12.27 12.38 12.49 19.15 20.91
0.0 366 381 377 374 371 367 364 361 358 355 351 1127 1396
78.1 33.0
440 13.20 12.67 12.79 12.91 13.02 13.14 13.26 13.37 13.49 13.61 13.72 21.49 23.53
0.0 402 419 415 411 407 404 400 397 394 390 387 1216 1503
78.1 33.0
480 14.40 13.84 13.97 14.09 14.21 14.34 14.46 14.59 14.71 14.83 14.96 23.88 26.20
0.0 439 456 452 448 444 441 437 433 430 426 423 1303 1608
78.1 33.0
520 15.60 15.01 15.14 15.27 15.40 15.53 15.67 15.80 15.93 16.06 16.19 26.32 28.93
0.0 475 494 489 485 481 477 473 469 466 462 458 1388 1710
78.1 33.0
560 16.80 16.18 16.32 16.46 16.59 16.73 16.87 17.01 17.14 17.28 17.42 28.81 31.72
0.0 512 531 527 522 518 514 510 506 502 498 494 1472 1811
78.1 33.0
600 18.00 17.35 17.50 17.64 17.78 17.93 18.07 18.22 18.36 18.50 18.65 31.33 34.55
0.0 548 568 564 559 555 551 546 542 538 534 530 1554 1910
78.1 33.0
16.2
222
25.7
78
Install ation tabl e / Behaviour against temperature (C) Load Conditi ons
6
1600
2000
35.9
C1: NFC 11201-A1 HTA A-ZVF 15 C &wind 640 Pa
C2: NFC 11201-A1 HTA G1 -5 C &wind 480 Pa &ice 1 kg/m (1)