You are on page 1of 2

RADIX Series Unitized Sub Station

Product Overview
Unitized substation (USS) is a compact product comprising of various
substation equipment housed inside a metal enclosure.
The USS comprises of
4HV compartment consisting of a Vacuum Circuit Breaker (VCB) /
Ring Main Unit (RMU) / GIS.
4Transformer (XMER).
4Low Voltage (LV) compartment consisting of LV distribution panel.
Salient Features
4Protection from unauthorized access.
4Protection from environmental hazards.
4Compact design with enhanced safety aspects.
4SCADA compatibility.
4Appealing aesthetics with long Product life.
4Ease of operation & maintenance.
4Ready to charge.
4Fully type tested as per IEC.
Crompton Greaves Ltd.
Technical Data
Degree of Protection IP 23D*
Duty Indoor / Outdoor
Type of Ventilation Natural
Standard Colour CG Blue #
Rated Voltage 12 kV/24kV/36kV
Rated Power Frequency withstand Voltage 28 kV/50kV/70kV
Rated lightening Impulse withstand Voltage 75 kV/95kV/170kV
*
Temperature Class K 10
Earthing system upto 26.3kA
Higher degree of protection shall be provided on request.
# Other color shades shall be provided on request.
MCCB
ACB
LV DIST
X'MER
LV
MV
RMU
Standard Variants
TYPE-1 TYPE-2
TYPE-4
TYPE-3
MCCB
ACB
LV DIST
X' MER
LV
MV
RMU
APFC
ACB
LV DIST
X'MER
LV
MV
RMU
MV METERING
UNIT
MCCB
APFC
MCCB
ACB
LV DIST
X' MER
LV
MV
RMU
MV METERING
UNIT
Vacuum Circuit Breaker Upto 12kV
4CG make horizontal draw out type VCB.
4Complete SCADA Compatible solutions.
4CG make relay & Circuit Breaker Manager.
Gas Insulated Switchgear Upto 36kV
4Sealed for life breaker compartment.
4Virtually maintenance free equipment.
Transformer Compartment
4Choice of Oil cooled or Dry type transformer.
4Rating: Upto 1600kVA with Voltage: 12 kV/22kV/33kV.
4Optional Off Circuit / On Load tap changer arrangement.
4Oil filled transformer - Hermetically sealed / Corrugated tank.
4Primary connection from transformer by XLPE cable & secondary
connections by solid flats with expansion joints ensures proper
joints and avoids stress / impact on transformer bushings.
4Rating upto 2500 A, 440 V.
4LV Switchgear: ACB / MCCB feeder board upto 12 feeders.
4Optional APFC panel with capacitor bank.
LV Compartment
DIMENSIONS (mm)*
COMBINATION L W H
RMU + X'MER + LT 3400 1900 2275
RMU + MU + X'MER + LT 3900 2200 2450
RMU + X'MER + LT + APFC 3550 2200 2575
* The mentioned dimensions are indicative as they are subject to
change based on equipment ratings, layout & total no. of LT
outgoing feeders.
Dimensions
Unitized Sub Station
Handling of a fully assembled unit
RADIX Series
L
W
H
Enclosure
HV Compartment
4All equipments mounted on a common galvanized GI base with
fabricated enclosure.
4Painted with polyurethane rust proof paint.
4Completely detachable side walls, ensuring ease of access to all
equipments.
4Louvers are provided for cross ventilation to allow natural cooling
inside enclosure.
4Enclosure doors are individually pad lockable from outside and are
interlocked to secure all doors by bolting LT Compartment door.
4All busbars inside the cubicle are sleeved using heat shrinkable
sleeves.
4Enclosure lifted directly from base frame by means of specially
designed detachable lifting arrangement ensures no
distortion/damage to the enclosure during lifting/handling.
4Compact layout of Transformer, LT & RMU inside enclosure and
yet without compromising access for maintenance.
SF Gas filled Vacuum RMU Upto 36kV
6
4CG make RMU with side cable entry & rear Tee-off bushings helps
in direct & easy coupling of RMU with Transformer.
4Optional Metering Unit (MU).
4SCADA compatibility.
4Fault passage / Earth Fault indicators.
Crompton Greaves Ltd.,
Power Systems : M. V. Switchgear Division (S2)
A-3, MIDC, Ambad, Nasik - 422 010. India.
Tel. : +91 253 2382271 to 75
Email : mv.switchgear@cgglobal.com
Registered Office
CG House, 6th Floor, Dr. Annie Besant Road, Worli, Mumbai- 400 030.
www.cgglobal.com