You are on page 1of 1

Section 01015 - Page 18

than NPS 2 shall be socket-welded, but welded, or flanged.


3. Piping gaskets shall be of the self-centering or confined type and shall be resistant to LPG.
4. Threaded connections shall be minimized to the extent practicable and shall be between NPS
and NPS 1 , inclusive.
5. Minimum Specifications. The pipe wall thickness shall be equal to or greater than that required
by ASME B31.3.
6. Carbon Steel pipe shall have the following minimum wall thicknesses:
7. Nominal pipe size less than NPS 2-Schedule 80.
8. NPS 2-5-Schedule 40 (except for threaded connections, which shall be schedule 80).
9. NPS 6-wall thickness of 0.25 NPS.
10. NPS 8-12-Schedule 20
11. NPS 14 or larger-Schedule 10.
12. Stainless steel piping shall have the following minimum wall thicknesses:
a. NPS or less-Schedule 80S.
b. NPS 1, 1 , or 2-Schedule 40S
c. NPS larger than 2-Schedule 10S
13. Pressure tubing shall be constructed of steel. If tubing will be exposed to a corrosive atmosphere,
stainless steel shall be used.
14. Butt-Welding Fittings. Butt-welding fittings shall be made from seamless steel or equivalent
material, shall be of at least the same thickness and schedule as the piping, and shall conform to
ASME B16.9.
15. Socket-Welding Fittings. Socket-welding fittings 2 in. or smaller in size, such as elbows, tees,
and couplings, shall be of forged steel and shall have a working pressure of at least 2000 psi.
16. Packed-sleeve and resilient-sealed couplings shall not be used.
17. Weld-neck flanges are preferred. Socket-weld NPS 2 and smaller are acceptable. If slip-on
flanges are used, they shall be welded both inside and outside.
18. Plugs shall be constructed of steel.

5.5 FIRE PROTECTION FOR PROPANE STORAGE AREA
a. Fire Protection shall consist of displacing the propane in the vessels, cooling the vessel exteriors with
water as well as through the use of Dry Chemical Fire Extinguishers where appropriate. All water
piping shall be routed parallel to building lines and concealed in all finished areas. Insulation shall be
provided where required to control sweating of pipes or to provide protection from freezing. Also
Electric Heat Tracing may be utilized on waterlines where insulation alone will not keep pipelines from
freezing.
1. A water Deluge system shall be provided over the Propane Storage Tanks. The water application
rate shall be 0.1 gallons per minute per square foot. The systems shall be manually remotely
activated at a minimum of 50ft away from the tanks.
2. Firewater System for Propane Tanks shall preferably be independent of the domestic water
system. However in places where this is inconvenient or impossible to accomplish tie ins to the
domestic water system shall be connected near the domestic water source i.e. to the discharge
piping between the well pump and water storage tanks. Firewater shall be furnished to the Water
Deluge System on the LPG Storage Vessels.
W912DQ-13-R-4034

You might also like