You are on page 1of 8

RAPI ER RX Ai r Break Swi t ch up t o 52kV

With automation or remote control options


E
N
G
I
N
E
E
R
I
N
G


B
R
I
L
L
I
A
N
T

S
O
L
U
T
I
O
N
S
MV and HV connectors
HV metering units
LV transformer cabinets
Package substations
LV distribution pillars
LV substation fuseboards
Multi service pillars
Multi service distribution boards
Heavy duty cutouts
Domestic service cutouts
Street lighting cutouts
ABC service boxes
Connector boxes
Fuse links
Weatherproof housings
MV and HV disconnectors
Automation solutions
Pole mounting cutouts
A division of W. Lucy & Co Ltd
MV ring main units
RX - t he st at e of t he ar t i n ai r break t echnol ogy
Air break Isolators 400/630/800A
Load-break Switches 400/630A
Fault Make Switches to 31.5kA
Robust and highly reliable contacts capable
of withstanding short time currents of up
to 25kA for 3s (62.5kA peak)
Independent Manual Operation
Single and Double acting
Spring Actuators
Voltage and Current monitoring
Automatic sectionalising capability
Full automation capability
Accessories
REMOTE CONTROL (GEMI NI RTU)
MOTOR ACTUATOR
EARTH BLADES
LOAD-BREAKI NG HEADS
FAULT MAKI NG HEADS
AUTOMATI C SECTI ONALI SI NG
FAULT PASSAGE SENSOR
UNI VERSAL BASE FOR HORI ZONTAL
OR VERTI CAL MOUNTI NG
PADLOCKI NG FACI LI TI ES
Features
RATI NGS UP TO 52k V
ENVI RONMENTALLY FRI ENDLY
AI R BREAK TECHNOLOGY
ROBUST AND RELI ABLE
VERY LOW MAI NTENANCE
EASE OF I NSTALLATI ON
REPLACEABLE UNI VERSAL CONTACTS
ON-SI TE UPGRADES
I NTERLOCKED FOR SAFE OPERATI ON
Our RX air break switch
has been carefully designed
and developed with
flexibility in mind to
meet the most diverse of
customers requirements.
Combining high
performance and high
reliability, our new RX
rocking type switch can be
a key element of your rural
distribution applications.
RX - Robust and Rel i abl e wi t h added f l exi bi l i t y
Robustness and reliability:
Particular attention has been taken to ensure our air break switch is robust
and fully reliable.
A high proportion of RX components are manufactured from stainless steel
for maximum protection against corrosion.
The contacts have been enhanced to enable them to withstand short time
currents of up to 25kA for 3s. Unlike traditional air break switches our RX
range can be supplied with tungsten tipped Fault Make Heads, ensuring
that switches can withstand high fault making currents up to 31.5kA.
Laminated flexible connections, supported by spring steel strips, have a life
span far in excess of the standard 1000 cycle test without showing signs of
stress or fracture.
The Arc Chute design has been improved for rapid arc extinction when
load breaking.
As an additional assurance of reliability, our Load Break Heads are fully
tested to IEC 60265-1 by KEMA laboratory and have passed temperature
rise and ice tests to IEC 60129, which make the RX suitable for the most
extreme climates and conditions (coastal areas, high pollution, humidity).
Flexibility
Based on the concept of modular design, our RX can be configured to suit a variety of applications.
From the standard switch, the RX can be very easily upgraded to meet your highest specifications
and suit the evolving requirements of your network.
Additional parts required for upgrade are easily fitted on locating pins ensuring correct
positioning and accurate alignment without the need for any specific setting.
The standard RX contacts and connector pads have been tested to 800A, 25kA/3secs. This
means by adding extra laminations, the switch can be upgraded to suit specific requirements.
The RX can be fitted with Fault Make Heads, Load Break Heads, or Earth Blades.
The new folded universal base allows the standard switch to be mounted horizontally or
vertically on most structures.
The RX can be manually operated or remotely controlled via an RTU and integrated
motorised actuator.
It can be used as a single point of isolation or configured as an RX-S sectionaliser programmed
to automatically open in the deadtime of an upstream autorecloser.
A wide range of insulators is also available including ceramic or polymeric options including
EPDM, Cyclo-Aliphatic or Silicone Rubber.
RX - a cost ef f ect i ve sol ut i on f or your di st ri but i on net work
Simplicity
Significant cost savings have been achieved through the simplified design
of the Load Break Heads and commonality of main RX components. One
standard contact system is now available across our full range, independent
of the voltage and current ratings. That enables customers to minimise
stock holdings of spares. The retrofit ability of main RX components is
also of prime importance. Both male and female contacts can be easily
replaced on site without affecting the setting of the switch by means
of accurate locating pins. The same applies to the arc chute and fault-
make tips.
Working in partnership with our customers has also provided real benefits.
The result is a simplified and universal steelwork to suit all mounting
configurations for 12, 24 and 36kV switches. This means simpler materials
management, lower stock holding requirements, a greater ease of
installation for the customer and improved delivery times.
Based around flexibility and retrofit ability, considerable
economies in terms of material, engineering and installation
can be offered. All of which makes the RX a cost -effective
solution for your existing network and its future expansion.
RX-RC a f ul l y i nt egrat ed package f or your aut omat i on di st ri but i on needs
By combining our experience in air break
technology and system automation, we can offer
our customers an intelligent switch optimised for
remote control and monitoring.
The integration of sensors (Current, Voltage
and Fault Passage Indicators) provides essential
information to a customers SCADA systems
enabling the operator to localise, determine the
cause and therefore the appropriate action to a
fault on their distribution networks.
Remote control and monitoring for rapid fault
localisation and isolation of the faulty section.
Real time information and remote switching
enables the restoration of electricity supplies
to the healthy parts of the network thereby
improving quality of supply.
Remote controlled RX switch
VT for power
supply to controller
Hook stick
manual override
RTU controller
Secondary automation
scheme for control of
automated air break switches
Primary substation
SCADA control system
Communication via
low power radio, GSM
and Paknet
Protocol - DNP V30
Antenna
Double acting
spring mechanism
Insulating Insert
GEMINI RTU controller features
STAI NLESS STEEL ENCLOSURE FOR LONG TROUBLE FREE LI FE
COMPACTNESS
EASE OF FI ELD SERVI CEABI LI TY: ALL ELECTRONI CS CONTAI NED I N
AN I NNER COVER CAN BE SI MPLY AND RAPI DLY REMOVED FROM
THE CONTROLLER UNI T FOR MAI NTENANCE OR UPGRADE
TOLERANT OF TROPI CAL ENVI RONMENTS
RX General Arrangement
Dimensions and
installation arrangements
600
210 400
GEMINI RTU Features
LOCAL / REMOTE OPERATI ON
FLEXI BLE COMMS I NTERFACE - RADI O, RS232,
PAKNET, GSM, PSTN, OPTI CAL FI BRE
DNP3.0 PROTOCOL AS STANDARD - OTHER
PROTOCOLS ON REQUEST
3 PHASE MONI TORI NG OF I NPUT VOLTAGE
AND CURRENT USI NG ANALOGUE I NPUTS
I SOLATED DI GI TAL I NPUTS
DI GI TAL CONTROL OUTPUTS
24V BATTERY FOR CONTI NUED OPERATI ON
UNDER POWER FAI LURE CONDI TI ONS
BATTERY CONDI TI ON MONI TORI NG
A B C D E F
Rated Impulse Post Post Terminal Isolating Minimum Post Base Mounting Operating
Voltage Withstand Centres Centres Pad Height Distance Phase Centres Fixing Height Mechanism
kV Test Minimum Centres Centres Height
12kV 125kV 310 310 275* 242 500 290 As reqd As reqd 1200
24kV 140kV 355 355 350* 290 600 360 As reqd As reqd 1200
36kV 200kV 415 375 425* 391 700 560 As reqd As reqd 1200
52kV 250kV 500 450 600* 505 800 640 As reqd As reqd 1200
Dim D
Dim A
Dim B
Dim C
Dim F
Dim C
Dim E Dim E
* Nominal values depending on insulator used
Rapi er RX El ect ri cal Per f ormance
All products have been fully certified in accordance with IEC standards: IEC 60694 (1996),
IEC 60265 (1998) to meet and exceed customer specifications.
* With optional Fault Make Head fitted
RX-M Manual Operation Manually operated air break switch disconnector.
Optional accessories include single or double-acting
spring mechanism for independent manual operation.
RX-RC Remote Control Remotely controlled/monitored air break switch
equipped with Gemini RTU controller. Optional
accessories include voltage sensing insulators and
patented fault passage indicator.
RX-FS Fuse Switch Fuse switch consisting of an in-series manually
operated air break switch disconnector with
expulsion type fuses.
RX-S Sectionaliser Automatic air break sectionaliser equipped with
control electronics, low voltage solenoid operated
spring-assisted mechanism with manual reset,
voltage sensing insulator and patented fault
passage indicator. Telemonitoring optional.
Product Designation Mode Description
Product Range
Product Range Rapier RX
Rated Voltage 12kV 24kV 36kV 52kV
Rated Current 400/630A 400/630A 400/630/800A 400/630/800A
Power Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Short Time Current 25kA/3s 25kA/3s 25kA/3s 25kA/3s
Fault make capacity* 31.5kA 25kA 20kA -
Breaking Capacity
Mainly Active Load 400/630A 400/630A 400A 400A
Impulse withstand Voltage 125kV 140kV 250kV 250kV
Insulator Creepage To 560mm To 1000mm To 1320mm To 1440mm
Options
FMH (Fault make Heads)
LBH (Load Break Heads)
EB (Earth Blades)
Environmental
Ambient Temperature -20+50
Humidity 0 -100%
Altitude (max) Up to 1000m
RAPIER RX Electrical Performance
For pole mounted SF6 gas insulated switches, refer to RAPIER GX range.
u ti l i ti e s uk
In the UK, our major customers include:
YORKSH I RE ELECTRI CI TY
EA ST M I DLA N DS ELECTRI CI TY
I N FRA LEC
2 4 SEVEN
M A N WEB
N ORTH ERN ELECTRI CI TY
N ORTH ERN I RELA N D ELECTRI CI TY
SCOTTI SH POWER
SEEBOA RD
SCOTTI SH & SOU TH ERN EN ERG Y
G PU POWER
e xp o r t worldwide
Delivering products worldwide:
CLP H o n g Ko n g
M EW Ku w a i t
M EW Om a n
A DWEA A b u Dh a b i
BEC Ba h a m a s
CEA M a u r i t i u s
G ECOL Li b y a
ECG G h a n a
KPLC Ke n y a
N EPA N i g e r i a
SESCO Sa r a w a k
U EB U g a n d a
TN B M a l a y s i a
POWERG RI D Si n g a p o r e
SCECO Sa u d i
Power Isolators Office
Unit 14 Thorpe Lane
Thorpe Way Industrial Estate
Banbury OX16 4UT United Kingdom
telephone +44 (0)1295 270448
fax +44 (0)1295 270446
email Power.Isolators@wlucy.co.uk
internet http://www.lucyswitchgear.com
A global network
Currently exporting to more than 50 countries.
Over the past three decades LUCY Switchgear
has become a truly international company with
sites in the UK, the Middle East, South Africa,
India and the Mediterranean.
LS 00001 RX 072001

You might also like