Nominal Voltage 24 Volts

Minimum Voltage 21.6 Volts


Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs
S.NO DESCRIPTION LOAD IN
WATTS
INCOMER
FEEDER QTY
Breakers Quantity 1
1 Relays
O\C & E\F Relay 0
Trip Circuit Supervision Relay 3 3
Sensitive E\F Relay 5 5
Master Tripping Relay 5 5
2 Indications
Annunciator 9 window 13.5 6.75
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0.5
Trip Circuit Healthy 0.5 0.5
3
Energising Coils
VCB Tripping Coil 5 5
VCB Closing Coil 5 5
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
DC operrated Motor
Total load in Watts
Load Current
LOAD NAME TIME IN MIN LOAD IN AMPS
A1 1 12.54166667
A2 119 12.41666667
A3 480 4.083333333
1 2 3
Period Load in Amps Change in Load
(Amps)
1 12.54166667 12.54166667
1 12.54166667 12.54166667
2 12.41666667 -0.125
1 12.54166667 12.54166667
2 12.41666667 -0.125
3 4.083333333 -8.333333333
Uncorrected cell size
Corrected cell size
Ah rating for the battery selected asper
catolouge
Charger rating
Section-2 Sub Total
Section-3
Section-3 Sub Total
Section-1
Section-1 Sub total
Section-2
BUS
COUPLER
QTY
OUTGOIN
G FEEDER
QTY
CONTINUOUS
LOAD
MOMENTARY
LOAD
EMERGENCY
LOAD
0 6
0 0 0
0 18 21
0 30 35
0 30 35
27 3
0 3 3.5
3 3.5
0 30 180
0 30
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
EDITABLE DATA
NON EDITABLE DATA
200
98 200 3
4.083333333 8.333333333 0.125
4 5 6 7
Duration of
period(mins)
Time to end
of section
(min)
Capacity at T
minute rate K
factor
Reqd sec size
=3*6 AH
1 1.00 0.79
9.907916667
1 120.00 2.8 35.11666667
119 119.00 2.8 -0.35
34.76666667
1 600.00 10.20 127.925
119 599.00 10.20 -1.275
480 480.00 8.300 -69.16666667
57.48333333
57.48333333
79.03958333
120
8.854166667
Section-2 Sub Total
Section-3
Section-3 Sub Total
Section-1
Section-1 Sub total
Section-2

Nominal Voltage 24 Volts
Minimum Voltage 21.6 Volts
Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs
S.NO DESCRIPTION LOAD IN
WATTS
INCOMER
FEEDER QTY
Breakers Quantity 0
1 Relays
O\C & E\F Relay 0 0
Trip Circuit Supervision Relay 3 0
Sensitive E\F Relay 5 0
Master Tripping Relay 5 0
2 Indications
Annunciator 9 window 13.5 0
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0
Trip Circuit Healthy 0.5 0
3
Energising Coils
VCB Tripping Coil 5 0
VCB Closing Coil 5 0
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
DC operrated Motor
Total load in Watts
Load Current
LOAD NAME TIME IN MIN LOAD IN AMPS
A1 1 9.625
A2 119 9.5
A3 480 1.166666667
1 2 3
Period Load in Amps Change in Load
(Amps)
1 9.625 9.625
1 9.625 9.625
2 9.5 -0.125
1 9.625 9.625
2 9.5 -0.125
3 1.166666667 -8.333333333
Uncorrected cell size
Corrected cell size
Ah rating for the battery selected asper
catolouge
Charger rating
Section-2 Sub Total
Section-3
Section-3 Sub Total
Section-1
Section-1 Sub total
Section-2
BUS
COUPLER
QTY
OUTGOIN
G FEEDER
QTY
CONTINUOUS
LOAD
MOMENTARY
LOAD
EMERGENCY
LOAD
0 2
0 0 0
0 6 6
0 10 10
0 10 10
9 3
0 1 1
1 1
0 10 180
0 10
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
EDITABLE DATA
NON EDITABLE DATA
200
28 200 3
1.166666667 8.333333333 0.125
4 5 6 7
Duration of
period(mins)
Time to end
of section
(min)
Capacity at T
minute rate K
factor
Reqd sec size
=3*6 AH
1 1.00 0.79
7.60375
1 120.00 2.65 25.50625
119 119.00 2.63 -0.32875
25.1775
1 600.00 10.20 98.175
119 599.00 10.20 -1.275
480 480.00 8.300 -69.16666667
27.73333333
27.73333333
38.13333333
120
4.458333333
Section-2 Sub Total
Section-3
Section-3 Sub Total
Section-1
Section-1 Sub total
Section-2
CABLE USED 2Cx35SQMM COPPER XLPE ARMOURED POWER CABLE
From To load current Distance(kM) Resistane/kM Drop %drop
HT ROOM SDB-1 9.17 0.18 0.524 1.72983 7.20762
HT ROOM SDB-2 9.17 0.26 0.524 2.49864 0.104110067
Voltage at terminal
22.2701712
21.5013584 2.5

Nominal Voltage 24 Volts
Minimum Voltage 21.6 Volts
Maximum Voltage 26.4 Volts
End cell Voltage 1.14 Volts
Voltage per cell 1.2 Volts
No of Cells 22 Nos
Minimum Cell Voltage 0.981818182 Volts
Design Margin 1.1
Aging factor 1.25
Temprature correction factor 1
Overload Factor 1
Battery Type Ni-Cd
Back-Up time 8 hrs
S.NO DESCRIPTION LOAD IN
WATTS
INCOMER
FEEDER QTY
Breakers Quantity 0
1 Relays
O\C & E\F Relay 0 0
Trip Circuit Supervision Relay 3 0
Sensitive E\F Relay 5 0
Master Tripping Relay 9 0
2 Indications
Annunciator 9 window 13.5 0
LED Indicating lamp(ON,OFF,TRIP,) 0.5 0
Trip Circuit Healthy 0.5 0
3
Energising Coils
VCB Tripping Coil 5 0
VCB Closing Coil 5 0
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
DC operrated Motor
Total load in Watts
Load Current
LOAD NAME TIME IN MIN LOAD IN AMPS
A1 1 9.177083333
A2 119 9.083333333
A3 480 0.75
BUS
COUPLER
QTY
OUTGOIN
G FEEDER
QTY
CONTINUOUS
LOAD
MOMENTARY
LOAD
EMERGENCY
LOAD
0 1
0 0 0
0 3 3
0 5 5
0 9 9
4.5 2.25
0 0.5 0.5
0.5 0.5
0 5
0 5
Battery Sizing Calculation As per IEEE Std 485-1997
MAIN HT PANEL
EDITABLE DATA
NON EDITABLE DATA
200
18 200 2.25
0.75 8.333333333 0.09375