API 620

DATA SHEET: ATMOSPHERICAL TANK API 620 - FT BY FT METH.


1-Fluid:
Product: Water
Cp (cal/gr C) 0.238
Vapor Pressure @ 200 F, psia 11.53
SG 1
Viscosity @ 130 F (centistokes) 0.55
PM 18
r @ 200 F (lbm/pie3) 60.13
2-Tank Size:
Nominal Diameter 35 ft (10,7 meters)
Nominal Heigth 40 ft (12,2 meters)
Lquido Heigth 39 ft (11,9 meters)
Nominal Capacity 1000 cubic meters
3-Tuberias asociadas al Tanque:
Nozzle Service Cant
N1 Water inlet 1
N2 Service Water Oulet 1
N3 fire fighting Water Oulet 1
N6 Fire Fighting water recirculation inlet 1
N4 Venting 1
N5 Manhole 2
N8 Rebose 1
N7 Drenaje 1
N9 A/B Stand Pipe 2
N10 Low Level Sw 1
TOTALS =
4-Datos de Operacion:
Desgin Temperature, T
1
200F (93 C)
Desging Pressure (ft Water Column) 492
Atmospherical Pressure (Psia) 14.7
Altitude (m.s.n.m.) 350
Inlet Pressure at N1 (Psig)
Inlet Flow at N1 (GPM)
Maximul Allowed Velocity at N1 (m/seg)
5-Nozzles and Conections:
Nozzle Service Cant
N1 Water inlet 1
N2 Service Water Oulet 1
N3 fire fighting Water Oulet 1
N6 Fire Fighting water recirculation inlet 1
N4 Venting 1
N5 Manhole 2
N8 Overflow Nozzle 1
N7 Drainage Nozzle 1
N9 A/B Stand Pipe 2
N10 Low Level Sw 1
TOTAL =
Original File: Archivo: Mdulo 14.xls
NewFile:
Original Date: 7/30/2004
New Date: 4/7/2008
Original Autor: LRRJ
Traslation: afigueredou@gmail.com
Diameter (inch) Schedule Length (m) Weigh (lb) Weigh (kg) Material
8 40
4 40
16 40
8 40
12 40
24
10 40
4 40
2
2
0.00 0.00
Diameter (inch) Weigh (lb) Weigh (kg) Material
8 48.50 31.75 A-105
4 20.00 9.07 A-105
16 173.00 78.47 A-105
8 48.50 22.00 A-105
12 100.00 45.35 A-105
24 662.00 300.27 A-105
10 70.00 31.75 A-105
4 20.00 9.07 A-105
2 15.00 6.80 A-105
2 7.50 3.40 A-105
1164.50 537.93
API 620
Write input Data Only on not colored cells
Module 14
CALCULATIONS
GENERAL DATA
P
d
Design Pressure ftwc= Height of the tank (full of water) + 12 ftwc (ft of
water column)
396.00
T
d
Design Temperature, C 93.00
D Diameter of the Tank, feet 60.00
H Height of the Tank (Calculations Limits = 80 ft), feet 32.00
G specific Gravity of the Stored Fluid (Water=1) 1.00
S
d
Allowable Working stress at Designs conditions, Psi 23,200.00
C.A. Corrosion thickness, inch 0.0625
q
Angle of Inclination of the Roof with regard to the horizontal one, degrees
25.00
CAPt Capacity needed of the Tank, cubic meters
STANDARD SHEET
LENGTH Length of the sheet, feet 20.00
WIDTH Width of the sheet, feet 8.00
AREA STD S:
Area of Standard Sheet, m2
14.86
DENSITY Density of the Sheet of Steel, Kg/m3 7,901.42
THICKNESS WALLS SHEET
Rings= Number of Rings with Standard Sheets 4
Aa= Area of A Ring, m2 140.09
NL
anillo
= Number of Sheets Needed by ring 10
TWALL-A1 = Minimum Thickness of sheet in Ring 1, mm 6.8821
TWALL-A1n = Thickness of Sheet I Ring 1 Nominal, mm 5.00
TWALL-A2 = Minimum Thickness of sheet in Ring 2, mm 5.5157
TWALL-A2n = Thickness of Sheet on Ring 2 Nominal, mm 4.00
TWALL-A3 = Minimum Thickness of sheet in Ring 3, mm 4.1494
TWALL-A3n = Thickness of Sheet on Ring 3 Nominal, mm 4.00
TWALL-A4 = Minimum Thickness of sheet in Ring 4, mm 2.7831
TWALL-A4n = Thickness of Sheet on Ring 4 Nominal, mm 4.00
TWALL-A5 = Minimum Thickness of sheet in Ring 5, mm N/A
TWALL-A5n = Thickness of Sheet on Ring 5 Nominal, mm 0.00
TWALL-A6 = Minimum Thickness of sheet in Ring 6, mm N/A
TWALL-A6n = Thickness of Sheet on Ring 6 Nominal, mm 0.00
TWALL-A7 = Minimum Thickness of sheet in Ring 7, mm N/A
TWALL-A7n = Thickness of Sheet on Ring 7 Nominal, mm 0.00
TWALL-A8 = Minimum Thickness of sheet in Ring 8, mm N/A
TWALL-A8n = Thickness of Sheet on Ring 8 Nominal, mm 0.00
TWALL-A9 = Minimum Thickness of sheet in Ring 9, mm N/A
TWALL-A9n = Thickness of Sheet on Ring 9 Nominal, mm 0.00
TWALL-A10 = Minimum Thickness of sheet in Ring 10, mm N/A
TWALL-A10n = Thickness of Sheet on Ring 10 Nominal, mm 0.00
Vct= Volume of Tanks Body , m
3
2.53
Pct= Weight of Tanks Body, Kg 19,965.94
ATMOSPHERICAL TANK CALCULATOR
ACCORDING WITH API 650 - FT BY FT METHOD
INLETS
OUTPUTS
Thicknesses: Sheets of Conical Roof
NLtecho= Number of Sheets Needed for the Roof 18.00
T
techo
= minimal needed Thickness of Roof's sheet, INCHES 0.35
minimal needed Thickness of Roof's sheet, mm 9.02
T
techo
n = Nominal Thickness of Roof's sheet, mm 6.35
Vtt= Volume of the Roof of the Tank, m3 1.70
Ptt= Weight of the Roof of the Tank, Kg 13,424.16
Thicknesses: Sheets of Floor
NLpiso= Number of Sheets Needed for the Floor 18.00
T
piso
= 0.31
minimal needed Thickness of Floor's sheets, INCHES 7.94
T
piso
n = minimal needed Thickness of Floor's sheets, mm 10.00
Vpt= Nominal Thickness of Floor's sheets, mm 2.68
Ppt= Volume of the Floor of the Tank, m3 21,140.41
Total Weight of the Floor of the Tank, Kg:
Volumen= Total volume of Stored Water, m3 2,562.34
Ft3 90,476.20
gallons 676,970.02
Barrels (U.S. Liquid) 21,491.11
Peso Total= Total Weight of the Empty Tank, Kilograms 54,530.51
Total Weigh of the Tank Full of Water, Kilograms 2,616,869.73
Nominal Tanks Capacity (Barrels): 16,117.17
Nominal Tanks Capacity (Gallons): 676,921.19
Nominal Tanks Capacity (Liters): 2,562,146.71
Nominal Tanks Capacity (Mts3): 2,562.15
Percent of Volume of Air in the Tank(%): 2.50
Net Tanks Capacity (Barrels): 15,714.24
Net Tanks Capacity (Gallons): 659,998.16
Net Tanks Capacity (Liters): 2,498,093.04
Net Tanks Capacity (Mts3): 2,498.09
Archivo: Mdulo 14.xls Fecha 7/30/2004
HOJA DE DATOS PARA TANQUE ATMOSFRICO - API 650 - METODO PIE POR PIE
1-Fluido:
Nombre: Agua
Cp (calora/gramo C) 0.238
Presin de Vapor @ 200 F, psia 11.53
SG 1
Viscosidad @ 130 F (centistokes) 0.55
PM 18
r @ 200 F (lbm/pie3) 60.13
2-Dimensiones del Tanque:
Dimetro Nominal 35 pies (10,7 metros)
Altura Nominal 40 pies (12,2 metros)
Altura del Lquido 39 pies (11,9 metros)
Capacidad Nominal 1000 metros cbicos
3-Tuberias asociadas al Tanque:
Boquilla Servicio Cantidad Dimetro (pulg)
N1 Entrada de Agua 1 8
N2 Salida de Agua de Agua Servicio 1 4
N3 Salida Agua Contra Incendio 1 16
N6 Entrada Recirculacin Agua Contra Incendio1 8
N4 Respiradero 1 12
N5 Manhole 2 24
N8 Rebose 1 10
N7 Drenaje 1 4
N9 A/B Stand Pipe 2 2
N10 Interruptor Bajo Nivel 1 2
TOTALES =
4-Datos de Operacion:
Temperatura de Diseo, T
1
200F (93 C)
Presin de Diseo (Pies de Columna de Agua) 492
Presin Atmosfrica (Psia) 14.7
Altitud (m.s.n.m.) 350
Presin Entrada a N1 (Psig)
Caudal de Entrada a N1 (GPM)
Velocidad de permisible de Aduccin en N1 (m/seg)
5-Boquillas y Conexiones:
Boquilla Servicio Cantidad Dimetro (pulg)
N1 Entrada de Agua 1 8
N2 Salida de Agua de Agua Servicio 1 4
N3 Salida Agua Contra Incendio 1 16
N6 Entrada Recirculacin Agua Contra Incendio1 8
N4 Respiradero 1 12
N5 Manhole 2 24
N8 Rebose 1 10
N7 Drenaje 1 4
N9 A/B Stand Pipe 2 2
N10 Interruptor Bajo Nivel 1 2
TOTALES =
Schedule Longitud (m) Peso (lb) Peso (kg) Material
40
40
40
40
40
40
40
0.00 0.00
Peso (lb) Peso (kg) Material
48.50 31.75 A-105
20.00 9.07 A-105
173.00 78.47 A-105
48.50 22.00 A-105
100.00 45.35 A-105
662.00 300.27 A-105
70.00 31.75 A-105
20.00 9.07 A-105
15.00 6.80 A-105
7.50 3.40 A-105
1164.50 537.93
Solo ingresar datos en las celdas NO sombreadas
Mdulo 14
CLCULO
DATOS GENERALES
P
d
Presin de Diseo en pca=Altura del tanque (lleno de agua) + 12 pca 396.00
T
d
Temperatura de Diseo, C 93.00
D Dimetro del Tanque, pies 60.00
H Altura del Tanque (Lmite de Clculo = 80 ft), pies 32.00
G Gravedad especfica del Fluido Almacenado (Agua=1) 1.00
S
d
Esfuerzo admisible para la Condicin de Diseo, Psi 23,200.00
C.A. Espesor de Corrosin, pulg 0.0625
q Angulo de Inclinacin del Techo respecto a la horizontal, grados 25.00
CAPt Capacidad requerida del Tanque, metros cbicos
LMINAS ESTNDAR
LARGO Largo de la lmina, pies 20.00
ANCHO Ancho de la lmina, pies 8.00
AreaLE
Area de Lmina Estndar, m
2
14.86
DENSIDAD
Densidad de la Lmina de Acero, Kg/m
3
7,901.42
Espesores: Lminas de Pared
Anillos= Nmero de Anillos con Lminas Estndar 4
Aa= rea de Un Anillo, m
2
140.09
NL
anillo
= Nmero de Lminas Requeridas por anillo 10
T
pared-A1
= Espesor mnimo de lmina en Anillo 1, mm 6.8821
T
pared
-A1n = Espesor de Lmina Anillo 1 Nominal, mm 5.00
T
pared-A2
= Espesor mnimo de lmina en Anillo 2, mm 5.5157
T
pared
-A2n = Espesor de Lmina Anillo 2 Nominal, mm 4.00
T
pared-A3
= Espesor mnimo de lmina en Anillo 3, mm 4.1494
T
pared
-A3n = Espesor de Lmina Anillo 3 Nominal, mm 4.00
T
pared-A4
= Espesor mnimo de lmina en Anillo 4, mm 2.7831
T
pared
-A4n = Espesor de Lmina Anillo 4 Nominal, mm 4.00
T
pared-A5
= Espesor mnimo de lmina en Anillo 5, mm N/A
T
pared
-A5n = Espesor de Lmina Anillo 5 Nominal, mm 0.00
T
pared-A6
= Espesor mnimo de lmina en Anillo 6, mm N/A
T
pared
-A6n = Espesor de Lmina Anillo 6 Nominal, mm 0.00
T
pared-A7
= Espesor mnimo de lmina en Anillo 7, mm N/A
T
pared
-A7n = Espesor de Lmina Anillo 7 Nominal, mm 0.00
T
pared-A8
= Espesor mnimo de lmina en Anillo 8, mm N/A
T
pared
-A8n = Espesor de Lmina Anillo 8 Nominal, mm 0.00
T
pared-A9
= Espesor mnimo de lmina en Anillo 9, mm N/A
T
pared
-A9n = Espesor de Lmina Anillo 9 Nominal, mm 0.00
T
pared-A10
= Espesor mnimo de lmina en Anillo 10, mm N/A
T
pared
-A10n = Espesor de Lmina Anillo 10 Nominal, mm 0.00
Vct= Volumen del Cuerpo del Tanque, m
3
2.53
Pct= Peso del Cuerpo del Tanque, Kg 19,965.94
CLCULO DE TANQUES ATMOSFRICOS
SEGN API 650 - METODO PIE POR PIE
ENTRADAS
SALIDAS
Espesores: Lminas de Techo Cnico
NLtecho= Nmero de Lminas Requeridas para el Techo 18.00
T
techo
= Espesor mnimo de lmina de Techo requerido, PULGADAS 0.35
Espesor mnimo de lmina de Techo requerido, mm 9.02
T
techo
n = Espesor de Lmina Techo Nominal, mm 6.35
Vtt=
Volumen del Techo del Tanque, m
3
1.70
Ptt= Peso del Techo del Tanque, Kg 13,424.16
Espesores: Lminas de Piso
NLpiso= Nmero de Lminas Requeridas para el Piso 18.00
T
piso
= Espesor mnimo de lmina de Piso requerido, PULGADAS 0.31
Espesor mnimo de lmina de Piso requerido, mm 7.94
T
piso
n = Espesor de Lmina de Piso Nominal, mm 10.00
Vpt=
Volumen del Piso del Tanque, m
3
2.68
Ppt= Peso del Piso del Tanque, Kg 21,140.41
Totales:
Volumen=
Volumen Total de Agua Almacenada, m
3
2,562.34
En pie
3
90,476.20
En galones 676,970.02
En barriles (U.S. Liquid) 21,491.11
Peso Total= Peso Total del Tanque Vaco, Kilogramos 54,530.51
Peso Total del Tanque Lleno de Agua, Kilogramos 2,616,869.73
Capacidad Nominal del Tanque (Barriles): 16,117.17
Capacidad Nominal del Tanque (Galones): 676,921.19
Capacidad Nominal del Tanque (Litros): 2,562,146.71
Capacidad Nominal del Tanque (Mts
3
): 2,562.15
Volumen de Aire en el Tanque (%): 2.50
Capacidad Neta del Tanque (Barriles): 15,714.24
Capacidad Neta del Tanque (Galones): 659,998.16
Capacidad Neta del Tanque (Litros): 2,498,093.04
Capacidad Neta del Tanque (Mts
3
): 2,498.09