You are on page 1of 91

June 2010

Copyright 2010 ComAp s.r.o.


Written by Vlastimil Vostk
Prague, Czech Republic
ComAp, spol. s r.o.
Kundratka 2359/17, 180 00 Praha 8, Czech Republic
Tel: +420 246 012 111, Fax: +420 246 316 647
E-mail: info@comap.cz, www.comap.cz
Reference Guide



















Automatic Transfer Switch Controller

SW version 2.0, June 2010

InteliATS
NT
IA-NT PWR unit

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 2
IA-NT- PWR-2.0-Reference Guide.pdf
ts
..................... 2
..................... 4
..................... 4
4
..................... 4
..................... 5
..................... 5
..................... 7
..................... 7
..................... 9
..................... 9
................... 10
................... 13
................... 13
................... 14
................... 14
................... 17
................... 17
................... 18
................... 19
................... 19
................... 20
................... 20
................... 21
................... 21
................... 22
................... 23
................... 24
................... 25
................... 26
................... 27
................... 30
................... 30
................... 32
................... 32
................... 33
................... 33
................... 37
................... 39
................... 40
................... 40
................... 42
................... 42
................... 48
................... 48
................... 48
Engine Params.................................................................................................................................. 56
Gener Protect .................................................................................................................................... 59
AMF Settings..................................................................................................................................... 61
Sync Ctrl............................................................................................................................................ 65
Date/Time.......................................................................................................................................... 66
SMS/E-Mail ....................................................................................................................................... 67
Function Description.............................................................................................................................. 69
Operating modes............................................................................................................................... 69
Circuit breakers timing ...................................................................................................................... 72
Table of Conten
Table of Contents ...............................................................................................................
Document information ........................................................................................................
Clarification of notation...................................................................................................
Text .....................................................................................................................................................
Conformity Declaration...................................................................................................
General Guidelines.............................................................................................................
What is in this manual?..................................................................................................
Description..........................................................................................................................
Description of the controller system...............................................................................
Configurability.................................................................................................................
. What is in the package?..... ...........................................................................................
IL-NT RS232 Communication module ...........................................................................
IL-NT RS232-485 Communication module....................................................................
IL-NT S-USB Service USB communication module.......................................................
IL-NT RD Remote display software ...............................................................................
IB-Lite Communication module......................................................................................
IL-NT BIO8 Hybrid binary input/output module..............................................................
Programming of IA-NT controller ...................................................................................
User Interface.....................................................................................................................
Terminals............................................................................................................................
IA-NT PWR terminals and face......................................................................................
Recommended Wiring........................................................................................................
IA-NT PWR Wiring Diagram........................................................................................
. . Applications .................. .............................................................................................. ......
AMF using two separate breakers with feedbacks (MCB and GCB) .............................
AMF using two separate breakers with feedbacks (MCB and GCB) + Test on Load....
AMF using two-position ATS with feedback...................................................................
AMF using three-position ATS with feedbacks ..............................................................
AMF + manual transfer & neutral control using three-position ATS ..............................
. AMF + no battery operation .......................... ................................................................
Controllers in cascade....................................................................................................
Getting Started ...................................................................................................................
How to install ..................................................................................................................
IL-NT BIO8 extension module connection .....................................................................
Current measurement ....................................................................................................
CT location .....................................................................................................................
Voltage measurement and generator connection types ................................................
RS485 connection..........................................................................................................
Inputs and Outputs .............................................................................................................
Binary inputs IA-NT - default ..........................................................................................
Binary inputs list ..........................................................................................................
Binary outputs IA-NT - default........................................................................................
Binary outputs - list.........................................................................................................
Setpoints.............................................................................................................................
Password........................................................................................................................
Basic Settings.................................................................................................................

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 3
IA-NT- PWR-2.0-Reference Guide.pdf
................... 74
................... 74
................... 74
................... 74
................... 75
................... 75
................... 76
................... 77
................... 77
................... 78
................... 79
................... 79
................... 79
................... 79
................... 83
................... 83
................... 83
................... 83
................... 83
................... 84
................... 84
................... 84
................... 84
................... 85
................... 87
................... 87
................... 88
................... 88
................... 89
................... 89
................... 89
................... 89
................... 89
................... 90
Binary inputs and outputs.................................................................................................................. 90
IL-NT RS232 interface (optional card) .............................................................................................. 90
IL-NT RS232-485 interface (optional card) ....................................................................................... 91
IL-NT S-USB interface (optional card) .............................................................................................. 91
IB-Lite interface (optional card) ......................................................................................................... 91
IL-NT BIO8 extension module (optional card)................................................................................... 91

Alarm Management ............................................................................................................
Warning (WRN) ..............................................................................................................
. Trip (TRP)................................................................................................................ ......
Mains failure (MF) ..........................................................................................................
AMF time chart genset OK..........................................................................................
AMF time chart genset not started properly................................................................
Voltage phase sequence detection................................................................................
Gen-set Operation States...................................................................................................
List of possible events....................................................................................................
History file.......................................................................................................................
Remote Control and Data Logging.....................................................................................
Direct connection to the PC ...........................................................................................
PC software LiteEdit....................................................................................................
Modbus protocol.............................................................................................................
Remote Communication.....................................................................................................
Internet connection.........................................................................................................
Recommended ISDN modem........................................................................................
Recommended GSM modem.........................................................................................
Mobile SIM card setting..................................................................................................
IL-NT-RD Remote display software....................................................................................
General description........................................................................................................
Warning! .........................................................................................................................
. IL-NT-RD Software installation................................................................................ ......
IL-NT-RD Wiring.............................................................................................................
Function description.......................................................................................................
SW compatibility.............................................................................................................
Maintenance.......................................................................................................................
Backup battery replacement ..........................................................................................
Technical Data....................................................................................................................
Inputs/Outputs overview.................................................................................................
Power supply..................................................................................................................
Operating conditions ......................................................................................................
Dimensions and weight ..................................................................................................
Mains and generator ......................................................................................................

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 4
IA-NT- PWR-2.0-Reference Guide.pdf
ion
EFERENCE GUIDE
12111, FAX: +420266316647
.COMAP.CZ
Document informat
INTELIATS
NT
PWR

- R
WRITTEN BY: VLASTIMIL VOSTK
2009-2010 COMAP LTD.
KUNDRATKA 17, PRAHA 8, CZECH REPUBLIC
PHONE: +4202460
WEB: HTTP://WWW , -MAIL: IN O@COMAP.CZ
DOCUMENT HISTORY
E F

REVISION NUMBER RELATED SW. VERSION DATE
1 1.0 22.02.2009
2 1.0.1 24.03.2009
3 1.2 09.01.2010
4 2.0 09.06.2010

Clarification of notation

NOTE:
This type of paragraph calls readers attention to a notice or related theme.

CAUTION!
This type of paragraph highlights a procedure, adjustment etc., which can cause a damage or
unproper function of the equipment if not performed correctly and may not be clear at first sight.

WARNING!
This type of paragraph indicates things, procedures, adjustments etc. which need high level of
attent th ause personal injury or death. ion, o erwise can c
Text


PAGE (Capital letters in the frame) buttons on the front panel
Break Return (Italic) set points
Genera
REMO

Conformity Declaration
tor protections (Bold) Set point group
TE START/STOP (Capital letters) binary inputs and outputs


The following escribed m plies with the appropriate basic safety and
health requirement of the EC Low Voltage Directive No: 73/23 / EEC and EC
Electromagnetic Compatibility Directive 89/336 / EEC based on its design and type,
as brought into circulation by us.
d achine com

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 5
IA-NT- PWR-2.0-Reference Guide.pdf
es General Guidelin
What is in this manual?

This manual describes the InteliATS
NT
PWR (IA-NT-PWR) software, which is designed for automatic
s and provides general information on how to install and operate the
Automatic transfer switch panel builders
otely from InteliATS
NT
)
d maintenance of the gen-set
NT
ns of the
T-STD-HW_1.3-
.AIL) form the
higher too, which is
ATS
NT
SW must be
rature ATS controller.
transfer switch application
In li
NT
te ATS controller.

This manual is dedicated for
Operators of remote gen-sets (started rem
For everybody who is concerned with installation, operation an
InteliATS controller SW and HW versions compatibility
Software InteliATS
NT
is compatible with the InteliATS
NT
hardware v. 1.3 and higher.

There are two modifications of the InteliATS HW - STD and PWR and two modificatio
InteliATS
NT
SW STD and HW which together with the appropriate archive file (IA-N
X.X.AIL for STD HW 1.3, IA-NT-STD-X.X.AIL for STD HW > 1.3 and IA-NT-PWR-X.X
InteliATS
NT
PWR or STD controller.

Beside that the InteliATS
NT
software is compatible with IL-NT AMF HW 1.3 and
used when a low temperature ATS application is needed. In this case the Inteli
combined (purchased) with the IL-NT AMF 25 LT HW to obtain the low tempe

NOTE:
Because of large variety of InteliATS
NT
parameters settings, it is not possible to describe any
combination. Some of InteliATS
NT
functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or
characteristic.

CAUTION!
SW and HW must be compatible (e.g. IA-NT firmware and IA-NT HW) otherwise the function will be
disabled. If wrong software is downloaded, message HARDWARE INCOMPATIBLE appears on
controller screen. In this case use Boot load (jumper) programming close Boot jumper and follow
instructions in LiteEdit, download correct software.

NOTE:
C rmation provided herein is correct and reliable and reserves the right to omAp believes that all info
u omAp does not assume any responsibility for its use unless otherwise expressly pdate at any time. C
undertaken.

WARNING!
Remote control - InteliATS
NT
controller can be remotely controlled. In case of the work on the
controlled devices check, that nobody can perform remote operation.To be sure disconnect
- remote control via RS232 line
- input REM TRANSFER
- input REMOTE AUT
- input REMOTE TEST
or disconnect output Rem START/ST tputs GCB CLOSE/OPEN and MCB CLOSE/OPEN

OP and ou

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 6
IA-NT- PWR-2.0-Reference Guide.pdf
WARNING!
E wing InteliATS
NT
controller terminals: very time you want to disconnect follo
d / or - Mains voltage measuring an
- Binary output for MCB control and / or
- MCB Feedback
Switch InteliATS to MAN or OFF Mode or disconnect the Binary outputs Rem Start/Stop and GCB
NT
Close/Open to avoid unexpected automatic start of gen-set and GCB closing.

WARNING!
Dangerous voltage
In no case touch the terminals for voltage and current measurement!
Always connect grounding terminals!
In any case do not disconnect InteliATS current transformer terminals!
NT
The following instructions are for qualified personnel only. To avoid personal injury do not
perform any action not specified in this Reference guide!!!

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 7
IA-NT- PWR-2.0-Reference Guide.pdf
n Descriptio
Description of the controller system

InteliATS
NT
is a comprehensive Automatic Transfer Switch controller designed to mon
AC mains supply (1 or 3 phases) for under & over voltage, under & over frequency an
unbalance. In the case of any mains supply disproportion it will send a remote start co
gen-set and make changeover for both
itor the incoming
d voltage
mmand to the
generator and mains contactors. The gen-set requires a
st a key-start box
al.
ferent types of changeover (transition)
ssive
ze mains and gen-set
it for the both
oltage and frequency
expires.
utes/predicts
the MAINS-MAINS applications and not only for the
en Start/Stop
onfigured/used
tells the controller that the MAINS-GEN application type is to be used. If not
top-fail protection and
ay showing icons, symbols and bar-
ether with high functionality, new standards in Gen-set
The key features are:
Easy-to-use operation and installation. Factory default configuration covers most of
applications
Different customer changes are possible thanks to the configurability
Excellent remote communication capabilities
High reliability
remote start type control unit (e.g. the ComAp InteliLite
NT
MRS 10 controller), at lea
with an external input for the start/stop sign
The controller is capable of providing the following three dif
open delayed transition
open in-pase transition with synch check
closed short-time (100ms) parallel transition with synch check
In order to provide synch check the controller has been enhanced by the feature called pa
synchronization. The passive sync (sync check) offers possibility to synchroni
without the need to use speed regulation or - better to say - it offers possibility to wa
sources to get in phase.
System is evaluated as to be in sync according to the predefined parameters v
difference if the both sources will get in-phase before the synchronization timeout
Parameters defining breaker delay are taken into the account when the system comp
exact moment when the both sources are in phase.

InteliATS
NT
controller can be used also for
MAINS-GEN applications. The system recognizes application type according to the G
and Gen ReadyToLoad logical binary output and input configuration. If the both are c
(default setting) it
c fi on gured, the MAINS-MAINS application type takes place. In this case the s
the generator current protection are not evaluated.
InteliATS
NT
controllers are equipped with a powerful graphic displ
graphs for intuitive o
controls.
peration, which sets, tog

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 8
IA-NT- PWR-2.0-Reference Guide.pdf
Example application


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 9
IA-NT- PWR-2.0-Reference Guide.pdf
Configurability
One of the key features of the controller is high level of adaptability of the system to the needs of
y particular application. The way, how to achieve this, is the configuration. ever
NOTE:
Use LiteEdit PC software to read configuration from the controller or disk, view it, modify it and write
the configuration to controller or disk.

The firmware contains a number of binary inputs and outputs needed for all necessary
available in the
functions
firmware. But not all functions are required at the same time on different gen-sets and
also the controller hardware does not have so many input and output terminals. One of the main tasks
ion is mapping of "logical" firmware inputs and outputs to the "physical" hardware
i
C
1. Mapping of logical binary inputs (functions)
of the configurat
nputs and outputs.
onfiguration parts:
or assigning alarms to physical binary input
terminals
2. Mapping of logical binary outputs (functions) to physical binary output termin
3. Changing language
als
of the controller texts
tandart
eEdit software. See
tion for details.
The controller is delivered with a default configuration, which should fit to most s
applications. This default configuration can be changed only using PC and Lit
LiteEdit documenta
NOTE:
You need one of communication modules to connect the controller to a PC with LiteEdit. There is a
special easy removable service module for cases, where there is no communication module
permanently attached.

ther controller or
is called archive and has file extension ".ail". An archive contains full
image of the controller at the moment of saving (if the controller is online to the PC) except firmware,
are also current adjustment of all setpoints, all measured values, a
ist.
ers aring controllers with
onfigu
in
Once the configuration is modified, it can be stored in a file for later usage with ano
for backup purposes. The file
i.e. besides configuration there
copy of history log and a copy of alarm l
T
identical c
he archive can be simply use cloning of controll
ration and settings.
d for , which means prep
What is the package?

Accessories Description Optional / Obligatory
IA-NT PWR InteliATS
NT
central unit, PWR version Obligatory
IL-NT-RS232 RS232 communication card Optional
IL-NT-RS232-485 RS232 and RS485 communication card Optional
IL-NT-S-USB Service USB communication card Optional
*IL-NT RD Remote display software Optional
IB-Lite Internet commun n idge Optional icatio br
*Remote display for IA-NT controllers uses standard IL-NT controller with Remote display software
NOTE:
For detailed information about extension modules used with IA-NT controllers, please see the IL-NT,
IC-NT, IA-NT, ID-Lite-Accessory Modules manual.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 10
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT RS232 Communication module

NT
IL-NT RS232 is optional plug-in card to enable InteliATS for RS232 communication. This is required
for computer or Modbus connecting. Card inserts into expansion slot back on the contr
To insert the module, you must open the cover first (use screwdriver to open) and then
module into slot. Once you ha
oller.
insert the
ve inserted it, the module will snap under plastic teeth. It is supposed to
be installed permanently. Should you need to remove it, the safest way is to remove whole back cover

and than remove module manually.

How to install RS 232 communication module:
NOTE:
The following procedure is analogic also for other communication modules.

1. Insert a screwdriver into the slot of the cover.




2. Move the screwdriver to set apart the small cover. Be careful!



3. Remove the small cover.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 11
IA-NT- PWR-2.0-Reference Guide.pdf
4. Break apart the small cover into two pieces. Do not throw away the smaller part!






5. Take RS 232 communication module.




InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 12
IA-NT- PWR-2.0-Reference Guide.pdf
unication module into the slot of the controller.
7. Put back the small cover.

6. Plug RS 232 comm


NOTE:
When you insert RS 232 communication module, the boot jumper is hidden. For that reason we
recommend to use RS 232 communication module with the boot jumper placed on it. See pictures
below:



RS 232 communication module with the boot jumper.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 13
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT RS232-485 Communication module

IL-NT RS232-485 is optional plug-in card to enable InteliATS
NT
the RS232 and RS
This is required for computer or Modbus connection. Card inserts into expansio
controller. The IL-NT RS232-485 is a dual port module with RS232 and RS48
485 communication.
n slot back on the
5 interfaces at

s analogous.
slot. Once you
will snap under plastic teeth. It is supposed to be installed permanently.
Should you need to remove it, the safest way is to remove whole back cover and than remove module
manually.
independent COM channels. The RS232 is connected to COM1 and RS485 to COM2.

To insert the module, please follow the instructions for IL-NT RS232 module, procedure i
You must open the cover first (use screwdriver to open) and then insert the module into
have insert it, the module
RS485
RS232
Boot jumper
RS485 Terminator jumper

IL-NT S-USB Service USB communication module

NT
IL-NT S-USB is optional plug-in card to enable InteliATS communication via USB port. This is
required for computer or Modbus connecting. Card inserts into expansion slot back on the controller.
To insert the module, please follow the instructions for IL-NT RS232 module, procedure is analogous.
You must open the cover first (use screwdriver to open) and then insert the module into slot. Once you
have inserted it, part of the module will remain over plastic box. It is supposed to be used as a service
tool. When you need to remove it, grab module in cutouts and pull it up manually.



NOTE:
Use the shielded USB A-B cable with this module! Recommended is ComAp cable Order code:
USB-LINK CABLE 1.8M.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 14
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT RD Remote display software

IL-NT RD is remote display software for a controller. Remote display provides the sam
monitoring functions as controller itself. Remote display for IA-NT controllers uses sta
controller with IL-NT Remote display software. No further programing of the display is
is self configurable from the main controller. It is connected with the c
e control and
ndard IA-NT
required unit
ontroller via IL-NT-RS232
communication modules using RS232 line. Longer distances (up to 1200m) are possible using IL-NT-
2/RS485 converters are used. RS232-485 communication module or when RS23

The IL-NT RD hardware type should fit to the master IA-NT.

NOTE:
Please see the IL-NT-RD Remote display software chapter for more details.
module IB-Lite Communication

IB-Lite is optional plug-in card to enable InteliATS
NT
communication via Ethernet/Intern
into expansion slot back on the controller.
et. Card inserts
ctions for IL-NT RS232 module, procedure is analogous.
river to open) and then insert the module into slot. Once you
have inserted it, part of the module will remain over plastic box. It is supposed to be used as a service
tool. When you need to remove it, grab module in cutouts and pull it up manually.

See IB-Lite-Reference Guide for further details.

To insert the module, please follow the instru
You must open the cover first (use screwd

Web server for IB-Lite
Is an ew secured way of monitoring and controlling the gen-set from any point in world using your web
browser. It ofers clear overview and control of the state of engine, its settings and history. User
friendly.
See IB-Lite-Reference Guide and pictures below for further details.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 15
IA-NT- PWR-2.0-Reference Guide.pdf
Scada window:

Measurement window:


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 16
IA-NT- PWR-2.0-Reference Guide.pdf
Setpoints window:

History window:

HINT:
This feature requires IB-Lite optional plug-in module and visible connection of controller to Ethernet.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 17
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT BIO8 Hybrid binary input/output module
ry
(version 4.4 and higher) it is possible to easily
Installing IL-NT BIO8 module is similar to installing RS 232 module. The difference is that module fits
to Extension module slot and after installing IL-NT BIO8 you do not put back the small cover.
IL-NT BIO8 is optional plug-in card. Through this card controller can accommodate up to 8 bina
inputs or outputs. In LiteEdit PC configuration tool
choose if particular I/O will be binary input or output.

Programming of IA-NT controller

ming is possible only in OFF mode when the engine is not running. Program

NOTE:
For more information on programing, see LiteEdit Reference Guide.

CAUTION!
Check the statistic values after firmware upgrade. Readjust the values if necessary.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 18
IA-NT- PWR-2.0-Reference Guide.pdf
e
s of displaying
only monitor
sire to change the
Changing the mode of User Interface is possible from default measuring screen of controller by
than press again PAGE. On screen will be
displeyed the choice of two different User Interfaces.

Please see latest IA-NT Operator Guide for detailed description.
User Interfac
There is an interchangable User Interface on controller. It allows two different mode
controller menu.
The first mode called USER is dedicated for users who prefer easy function and need
actual values, see alarms or change language settings.
Second mode is called ENGINEER and it is dedicated for advaced users, who de
settings of controller, monitor all values and check the history of events.

simultaneous pressing the ENTER and PAGE button and

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 19
IA-NT- PWR-2.0-Reference Guide.pdf
s
IA-NT PWR terminals and face
Terminal






InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 20
IA-NT- PWR-2.0-Reference Guide.pdf
ing
IA-NT PWR Wiring Diagram
Recommended Wir
L
1
L
2
L
3
N
D
I
E
S
E
L
/
G
A
S
R
S
-
2
3
2
C
I
n
t
e
r
f
a
c
e
M
o
d
e
m
o
r
P
C
E
N
G
I
N
E
G
E
N
E
R
A
T
O
R
G
L
O
A
D
B
.
G
e
n
e
r
a
t
o
r
C
.
.
M
a
in
s
C
.
B
GENREADYTOLOAD
MAINSFAILBLOCK
REMOTEAUT
GCBFEEDBACK
MCBFEEDBACK
REMOTETEST
REMOTETESTONLD
AL START FAIL
GCB CLOSE/OPEN
GEN START/STOP
AL MAINS FAIL
ALARM
READY TO AMF
MCB CLOSE/OPEN
CONTROL
SIGNALS
+
2
4
V
0
V
BINARY
OUTPUTS
BATTERY
- +
GEN-SETCONTROLLER

NOTE:
MCB and GCB is recommended to be mechanically interlocked.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 21
IA-NT- PWR-2.0-Reference Guide.pdf
s
plication, where the
s for the mains power supply fault and then starts a load transfer process.
Next possible application is manually controlled load transfer between two power supply sources
AMF using two separate breakers with feedbacks (MCB and GCB)
Application
The most typical application for the ATS controllers is Auto Mains Failure (AMF) ap
controller watche
(mains x generator).

G
IA-NT
GCB
3x
LOAD
3
x
U
M
3
x
U
G
3
x
I
G
MCB
3x
T
3x
MCB
MCB FEEDBACK
K4
MCB GCB
3x
MCB
K3
GCB
MCB CLOSE/OPEN
GCB CLOSE/OPEN
BO
BI
GCB FEEDBACK
GCB

en-set start when the mains fails (AUT mode)
full control with feedbacks
ak transfer on mains failure
s return (Load reclosing)
running and waiting for mains failure)
Hardware requirements
1x IA-NT PWR
Setpoints
MCB Logic = CLOSE-OFF
Specification
Automatic remote g
GCB & MCB
Bre
Break return on main
Test mode (set

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 22
IA-NT- PWR-2.0-Reference Guide.pdf
two separate breakers with feedbacks (MCB and GCB) +
Test on Load
AMF using

G
GCB
3x
LOAD
3
x
U
M
3
x
U
G
3
x
I
G
MCB
3x
T
3x
K4
MCB GCB
K3
3x
BO
BI
IA- NT
MCB
MCB FEEDBACK
GCB
GCB FEEDBACK
TEST ON LOAD
ON LOAD TEST
REQUIRED
REMOTE TEST
/ CLOSE OPEN GCB
MCB CLOSE/ OPEN

s
s failure
ins return (Load reclosing)
set running and waiting for mains failure)
Load Test - load transfer to gen-set (Island operation) and back to mains in TEST mode on
Test on load activation/deactivation. There are 2 breaks in this operation. Controller may
1x IA-NT PWR
Setpoints
MCB Logic = CLOSE-OFF
RetFromIsland = AUTO automatic return (MCB Close) to mains after TEST
RetFromIsland = MANUAL mual return to mains (MCB Close) after TEST IA-NT goes to MAN
mode.
Specification
Automatic remote gen-set start when the mains fails (AUT mode)
GCB & MCB full kontrol with feedback
Break transfer on main
Break return on ma
Test mode (
On
BI
be forced to TEST mode by BI Remote TEST
Hardware requirements

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 23
IA-NT- PWR-2.0-Reference Guide.pdf
AMF using two-position ATS with feedback

LOAD
G
IA-NT
3x
3
x
U
M
3
x
U
G
3
x
I
G
3x
T
MCB FEEDBACK
GCB FEEDBACK
3x
MCB CLOSE/OPEN
GCB CLOSE/OPEN
BO
BI
K3
3x
ATS
ATS
ATS on "II" position
I II

-set start when the mains fails (AUT mode)
feedback
er on mains failure
ak return on mains return (Load reclosing)
st mode (set running and waiting for mains failure)
Hardware requirements
1x IA-NT PWR
Setpoints
MCB Logic = CLOSE-ON
Specification
Automatic remote gen
Two-position ATS control with
Break transf
Bre
Te

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 24
IA-NT- PWR-2.0-Reference Guide.pdf
AMF using three-position ATS with feedbacks

G
IA-NT
3x
3
x
U
M
3
x
U
G
3
x
I
G
3x
T
MCB FEEDBACK
GCB FEEDBACK
3x
MCB CLOSE/
OPEN
GCB CLOSE/
OPEN
BO
BI
LOAD
3x
ATS
I II 0
ATS
K4
K3
ATS on "II" position
ATS on "I" position

Automatic remote gen-set start when the mains fails (AUT mode)
control with feedbacks, pass through neutral position
er on mains failure
k return on mains return (Load reclosing)
st mode (set running and waiting for mains failure)
Hardware requirements
1x IA-NT PWR
Setpoints
MCB Logic = CLOSE-ON
Specification
Three-position ATS
Break transf
Brea
Te

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 25
IA-NT- PWR-2.0-Reference Guide.pdf
AMF + manual transfer & neutral control using three-position ATS

G
IA-NT
3x
3
x
U
M
3
x
U
G
3
x
I
G
3x
T
REM TRANSFER
NEUTRAL POS
3x
MCB CLOSE/
OPEN
GCB CLOSE/
OPEN
BO
BI
LOAD
3x
ATS
ATS
I II 0
Force Neutral Position
Manual Load Transfer
K3
K4
K5
NEUTRAL
POS

-set start when the mains fails (AUT mode)
control without feedback, pass through neutral position
est for load transfer (AUT mode)
quest for switching to neutral position the highest priority, overrides MCB & GCB state,
ces switch to neutral position. After deactivating return to previous state (MCB or GCB)
Hardware requirements
1x IA-NT PWR
Setpoints
MCB Logic = CLOSE-ON
Specification
Automatic remote gen
Three-position ATS
Manual requ
Re
for

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 26
IA-NT- PWR-2.0-Reference Guide.pdf
AMF + no battery operation

3
x
U
M
3
x
U
G

Specification
It is possible to operate controller without a battery supplying the controller. Fo
following conditions have to be fulfilled:
r such operation the
switched between
ing) according to
m for more details
ontacts have to be used for the gen-set start command. Setpoint
locked when GCB is closed, so the power
e on the mains bus appears protection against
voltage changes arise on Mains.
to Mains when GCB is opened.
/DC power supply source is switched to gen-set
supplying controller disappears
upplied from running gen-set
d, waits for Gen OK conditions
B closed and the 24V AC/DC power supply source is locked in gen-set
If Mains
GCB is opened, 24V AC/DC power supply source is unlocked and switched to Mains
MCB is closed
Gen-set is stopped
Hardware requirements
1x IA-NT PWR
1x 24V/2.5A AC/DC power supply

Controller is supplied from 24V/2.5A AC/DC power supply whose source is
Mains and Gen-set via relay (another contacts of the relay for GCB switch
the Mains state (OK/Fault). See the schematic diagra
Normally closed relay c
GenStart Logic has to be set to CLOSE-OFF
Switching of the 24V AC/DC power supply is b
supply is not switched to Mains if voltag
ng of the power supply when Flip-floppi
It (power supply) will be switched
Then in the case of Mains failure:
24V AC
Voltage
Gen Start relay is deenergized and contacts closed
started Gen-set is
Controller is s
Controller is initialize
MCB is opened, GC
position.
returns:

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 27
IA-NT- PWR-2.0-Reference Guide.pdf
Controllers in cascade
G
e
n

S
t
a
r
t
/
S
t
o
p
G
e
n

S
t
a
r
t
/
S
t
o
p
L
o
a
d
G
e
n
r
e
a
d
y
T
o
L
o
a
d
G
T
o
e
n
r
e
a
d
y
3
x
U
M
3
x
U
G
3
x
I
G
G
e
n

S
t
a
r
t
/
S
t
o
p
G
e
n
r
e
a
d
y
T
o
L
o
a
d

Specification
Controllers are suitable for Cascading applications allowing load to be split into
The followi ave to be fulfilled:
more sections.
Automatic remote gen-set start when the mains fails (AUT mode)
Cascade controlled by Master
Consequent changeover on slave controllers
Simple wiring
Hardw re requirements
1 x IA-NT PWR
(1 to n) x IA-NT PWR or STD
ng conditions h
a

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 28
IA-NT- PWR-2.0-Reference Guide.pdf

Cascade, wiring A, Mains Fail timing diagram with configuration description

Cascade, wiring A, Mains Return timing diagram with configuration description

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 29
IA-NT- PWR-2.0-Reference Guide.pdf

Cascade, wiring B, Mains Fail timing diagram with configuration description

Cascade, wiring B, Mains Return timing diagram with configuration description

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 30
IA-NT- PWR-2.0-Reference Guide.pdf
d
o install
Getting Starte
How t
General
To ensure proper function:
Wiring for binary inputs and analog inputs must not be run with power cables.
en length >3m.
s 36VDC. Maximum allowable power supply voltage
NT
s power supply terminals are protected against large pulse power
itions outside its
Binary inputs should use shielded cables, especially wh
Power supply
To ensure proper function use min. power supply cable of 1.5mm
2

Maximum continuous DC power supply voltage i
is 39VDC. The InteliATS
disturbances. When there is a potential risk of the controller being subjected to cond
capabilities, an outside protection devise should be used.
NOTE:
The InteliATSNT controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controllers negative terminal is 4A (this is dependent on
binary output load).
For the connection
NT
s with 12VDC power supply, the InteliATS includes internal capacitors that allow
the controller to continue operation if the battery voltage dip occurs. If the voltage before dip is 10V,
after 100ms the voltage recovers to 7 V, the controller continues operating. During this voltage dip the
controller screen backlight can turn off and on but the controller keeps operating.
It is possible to further support the controller by connecting the external capacitor and separating
diode or I-LBA module:

The capacitor size depends on required time. It shall be approximately thousands of microFarads.
The capacitor size should be 5 000 microFarad to withstand 150ms voltage dip under following
conditions:
Voltage before dip is 12V, after 150ms the voltage recovers to min. allowed voltage, i.e. 8V
NOTE:
Before the battery is discharged the message "Low BackupBatt" appears.
Or by connecting special I-LBA Low Battery Adaptor module:


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 31
IA-NT- PWR-2.0-Reference Guide.pdf
voltage dip under following conditions:
llowed voltage 5V.
wiring resistance from battery should be up to 0.1 Ohm for I-LBA proper function.
The I-LBA module ensures min. 350ms
RS232 and other plug-in module is connected.
Voltage before dip is 12V and after 350ms the voltage recovers to min. a
The I-LBA enables controller operation from 5VDC (for 10 to 30 sec).
The

NOTE:
I-LBA may not eliminate voltage drop when used with low temperature (-40C) version of controller
and display heating element is on (below 5C). Current drain of heating element exhausts LBA
capacitors very fast
Power supply fusing
A one-amp fuse should be connected in-line with the battery positive terminal t
module
o the controller and
s.
Fuse value and type depends on number of connected devices and wire length.
type - T1A. Not fast due to internal capacitors charging during Recommended fuse (not fast)
power up.

Binary output protections
NOTE:
Do not connect binary outputs directly to DC relays without protection diodes, even if they are not
connected directly to controller outputs.


Grounding
To ensure proper function:
Use as short as possible cable to the grounding point on the switchboard
Use cable min. 2,5mm
2

The - terminal of the battery has to be properly grounded


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 32
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT BIO8 extension module connection


Current measurement
The number of CTs is automaticaly selected based on selected value of setpoint ConnectionType
[3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph].
To ensure proper function:
Use cables of 2,5mm
2
Use transformers to 5A
Connect CT according to following drawings:
Three phase application:



It is necessary to ensure that potencial difference between generator current COM terminal and
battery - terminal is maximally 2V. Therefore is strongly recommended to interconnect
these two terminals together.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 33
IA-NT- PWR-2.0-Reference Guide.pdf
Connect CT according to following drawings. Terminals L2l and L3l are opened.

Single phase application:

CT location
It is possible to set the location of CT s.

There are two options of CT location.
Load
Gen-Set
According to the connection you have to set the setpoint CT location value to Load or Gen-Set
Voltage measurement and generator connection types
There are 4 voltage measurement ConnectionTypes (setpoint ConnectionType [3Ph4Wire /
3Ph3Wire / Split Ph / Mono Ph]) options. Every type matches to corresponding generator connection
type:
1. ConnectionType: 3 Phase 4 Wires

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 34
IA-NT- PWR-2.0-Reference Guide.pdf

Three phase wye measurement 3PY
3 Phase 4 Wires - STAR Connection

2. ConnectionType: 3 Phase 3 Wires

Three phase delta measurement 3PD
3 Phase 3 Wires
DELTA Connection HI-LEG (wild-leg, red-leg) DELTA Connection

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 35
IA-NT- PWR-2.0-Reference Guide.pdf

NOTE:
Only L1, L2 and L3 wires should be connected. In case of HI-LEG DELTA connection the N (neutral)
wire (in the diagram connected between T6 and T9) has to be disconnected.
No separation transformers for three wires voltage connection (without N) are needed.

3. ConnectionType: Split Phase

Single-phase measurement 1PH
Split Phase
DOUBLE DELTA Connection ZIG ZAG (DOG LEG) Connection



InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 36
IA-NT- PWR-2.0-Reference Guide.pdf
4. ConnectionType: Mono Phase

Single-phase measurement 1PH
Mono Phase MONOPHASE Connection

NOTE:
Switchboard lighting strike protection according standard regulation is expected for all 4 connection
types!!!

NOTE:
Phase sequence check is not possible to evaluate under voltage 50V what causes that if measured
voltage 50V is within the allowed range, controller will not allow to close the GCB, even if relevant LED
diod on front panel of IL-NT lits.


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 37
IA-NT- PWR-2.0-Reference Guide.pdf
Binary inputs



Binary outputs

+
Battery
-
iL
4k7
+ -
Power
Supply
iL
LOAD
+ -
Power
Supply
+
-
Battery
RS485 connection
The line has to be terminated by 120 Ohm resistors at both ends.
in any order, but keepi External units can be connected on the RS485 line ng line arrangement (no
star) is necessary.
m.
Shielded cable has to be used, shielding has to be connected to PE on one side (controller side).

A) For s ces (all network components within one room) picture 1
interconnect A and B; shielding connect to PE on controller side
B) For longer distances (connection between rooms within one building) picture 2
interconnect A, B, COM; shielding connect to PE in one point
C) In case of surge hazard (connection out of building in case of storm etc.) picture 3

We recommend to use following protections:
tails, no
Standard maximum link length is 1000
horter distan

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 38
IA-NT- PWR-2.0-Reference Guide.pdf
ntact.com):
2x2-BE (base element)
://www.saltek.cz):
nductors)
/CM (1x2+1 conductors)
TC/CM (1x2+1 conductors)

Picture 1 - shorter distances (all network components within one room)

Picture 2 - longer distances (connection between rooms within one building)
- Phoenix Contact (http://www.phoenixco
PT 5-HF-5DC-ST with PT
85-TTL) (or MT-RS4
- Saltek (http
DM-006/2 R DJ

Recommended data cables: BELDEN (http://www.belden.com)
A) For shorter distances: 3105A Paired - EIA Industrial RS-485 PLTC/CM (1x2 co
B) For longer distances: 3106A Paired - EIA Industrial RS-485 PLTC
C) In case of surge hazard: 3106A Paired - EIA Industrial RS-485 PL

Picture 3 - surge hazard (connection out of building in case of storm etc.)



InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 39
IA-NT- PWR-2.0-Reference Guide.pdf
ts
nputs/Outputs overview table see chapter Technical Data.
Inputs and Outpu
For I

NOTE:
Any Binary input or output can be configured to any IA-NT controller terminal or changed to different
function by LiteEdit software. There is fix 1 sec delay when any binary input is configured as
protection.


Not Used
Binary input has no function. Use this configuration when Binary input is not connected.


Alarm
If the input is closed (or opened) sel d alarm is activated. ecte



Bina nfigu ms

string
ry Alarm co ration ite
Name 14 characters ASCII
NC Normally closed Contact type
NO Normally opened
Warning Alarm type
Trip
All the time Valid if checkbox Engin
on
e running
ly is not checked
Alarm active
Engine running only Valid if checkbox Engine running
only is checked

Control
Use this setting to configure the desired function from the list below.



InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 40
IA-NT- PWR-2.0-Reference Guide.pdf
Binary inputs IA-NT - default
BI1 GCB Feedback

Load
k
ansfer
BI6 Remote TEST
BI7 Remote TEST OnLd
BI2 MCB Feedback
BI3 GenReadyTo
BI4 MainsFailBloc
BI5 Remote Tr
Binary inputs list
Rem Start/Stop
External request for engine run. AUT mode only.



NOTE:
If the binary input Rem Start/Stop is active and mains failure occures, the MCB breaker opens and
after the Trans Del delay the GCB breaker is closed. Once the mains is OK, the MainsReturnDel delay
elaspes and the GCB breaker is opened. Then after the Trans Del delay is MCB breaker closed. Gen-
set remains running as long as Rem Start/Stop is active. See AMF time chart for more details.
without waiting for the AMF
tart Del has elapsed. In the case the transfer not succeeded the system will stay in
rms its work normally.
k
t to the output GCB CLOSE/OPEN
back
ergency Stop
opened. Input
Access Lock
If the input is closed, no setpoints can be adjusted from controller front panel and gen-set mode (OFF-
MAN-AUT-TEST) cannot be changed.

Rem Transfer
External request for an immediate transfer from mains to generator
Settings: EmergS
neutral position. The MainsFailBlock input perfo
GCB Feedbac
Use this input for indication, whether the generator circuit breaker is open or closed.
If the feedback is not used, connect this inpu
MCB Feed
This input indicates whether MCB is closed or opened.
Em
If the input is opened, the stop signal for the gen-set is sent and the MCB and GCB are
is inverted (normally closed) in default configuration.
NOTE:
Access Lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified
changes the selected setpoints can be password protected. Also the button Fault reset, is not blocked
at all and buttons Start and Stop in MAN mode are not blocked.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 41
IA-NT- PWR-2.0-Reference Guide.pdf
ode (there are four modes OFF-MAN-AUT-TEST). When opens
r is switched back to previous mode.
Remote OFF
If closed, IA-NT is switched to OFF m
controlle

NOTE:
This binary input should be connected to schedule timer switch, to avoid start of engine.
te MAN
d to the controller independently on the position of the MODE
tive, AUTO mode is forced to the controller independently on the position of the MODE
st priority.

ST). When opens
Ld
rs load
et to MANUAL.
ally transferred back to the mains when any gen-set shut down protection activates.
active, setpoints writing or command sending from the external terminal is disabled.
esButton
as the same function as Fault Reset button on the InteliATS
NT
front panel.
Remo
If the input is active, MAN mode is force
selector.
Remote AUT
If the input is ac
selector. If another of remote inputs is active, then the REMOTE AUT input has the lowe
Remote TEST
If closed, IA-NT is switched to TEST mode (there are four modes OFF-MAN-AUT-TE
controller is switched back to previous mode.
Rem TEST On
Affects the behavior in TEST mode. When input is closed, the controller automatically transfe
from the mains to the gen-set. Setpoint AMF Settings: ReturnFromTEST must be s
Load is automatic
RemControlLock
If the input is
FaultR
Binary input h
GCB Button
Binary input has the same function as GCB button on the InteliATS
NT
front panel. It is active in MAN
mode only.
MCB Button
Binary input has the same function as MCB button on the InteliATS
NT
front panel. It is active in MAN
mode only.
MainsFailBlock
If the input is closed, the automatic start of the gen-set at Mains failure is blocked. In case of runnin
gen-set the GCB is opened, gen-set goes to Cooling p
g
rocedure and stops.
ns for successful gen-set start and
readiness to undertake load can be depending on the GenerProtect setpoint evaluated from the
voltage and the frequency of the generator or from the state of GenReadyToLoad input. The
conditions have to be fulfilled during time defined by the MaxGenStartDel setpoint (which can be even
unlimited). More info can be found in tp t description.
Neutral Pos
In MAN mode this input switches a three position ATS switch to its neutral position it activates the
binary output NeutralPosition and switches the MCB and GCB off.
GenReadyToLoad
Indicates wether the gen-set is ready to undertake load. Conditio
the se oin

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 42
IA-NT- PWR-2.0-Reference Guide.pdf
ot have usually
power sources.Then this
s is healthy to be able to respond to Mains failure.
has been added.
tive. If the reason
ed, the alarm is activated. If not, the alarm does not
perform filtering of alarms within a specified period of time.
llowing setpoints:
MainsHealthy
This iinput was creted mainly for cascading applications, where slave controllers do n
Mains and Gen-set voltage measuring inputs connected to the repspective
binary input tells the controller if Main
Programmable delay on alarms
Possibility to set programmable delay on alarms configured for binary intput 6 and 7
If set, it blocks alarms of the respective binary input for the whole time the delay is ac
for the alarm persists after the delay time expir
appear. This feature allows the user to
The delay length can be set via the fo
Binary outputs IA-NT - default
BO1 GenStart/Stop
pen
e/Open
AMF
ail
rt Fail
uts - list
BO2 Alarm
BO3 GCB Close/O
BO4 MCB Clos
BO5 Ready To
BO6 AL Mains F
BO7 AL Sta
Binary outp
Not Used
Output has no function.
cked when the
output is inactive and the GCB is blocked too. Output can be inverted (CLOSE-OFF) using Basic
nStart Logic setpoint.
tput closes when the gen-set start is requested and opens after the AMF Settings: Prestart
d. Afterwards the GenStart/Stop output is activated as a start signal for the remote
I the Mains Fail had occurred and the gen-set start is the
result of this event. See the AMF Settings: Prestart Time setpoint for more info.
Alarm
The output closes if :
any alarm comes up or
The output opens if
FAULT RESET is pressed
GenStart/Stop
The closed relay sends remote start signal to the gen-set. Generator protections are blo
Settings: Ge
Prestart
The ou
Time has elapse
gen- t. se
Pre a tr nsfer
s activated during the Prestart phase when
The output closes again if a new fault comes up.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 43
IA-NT- PWR-2.0-Reference Guide.pdf
The output controls the generator circuit breaker.
GCB Close/Open

NOTE:
Supposed time to close (reaction time) of GCB is 0.1 sec.
ates Generator Circuit Breaker coil.
oil
Breaker coil after voltage drop-out.
/Open
aker.
tivates Mains Circuit Breaker coil.
eactivates Mains Circuit Breaker coil.
ntrols Mains Circuit Breaker coil after voltage drop-out.
copy of Fault Reset button on controller and binary input FaultResButton.
opy of generator status LED on IA-NT front panel. The output is closed if gen-set is
On Load
ms OK and (LBI) GCB Feedback OK
R a
ve, if the controller is able to start the engine and simultaneously the controller is in
sed if following conditions are fulfilled:
OFF Mode
Ready To Load
The output is closed if gen-set is running and all electric values are in limits and no alarm is active - it
is possible to close GCB or it is already closed. The output opens during cooling state.
Mains Healthy
The output is copy of mains status LED on IA-NT front panel. The output is closed if mains voltage
and frequency are within limits.
GCB ON Coil
The output activ
GCB OFF C
The output deactivates Generator Circuit Breaker coil.
GCB UV Coil
The output controls Generator Circuit
MCB Close
The output controls the mains circuit bre
MCB ON Coil
The output ac
MCB OFF Coil
The output d
MCB UV Coil
The output co
Fault Reset
The output is a
Gen Healthy
The output is a c
running and all gen-set electric values are in limits.
Gen
(LBO) Gener On Load <= (LBO) Gen Para
e dy To AMF
The output is acti
AUT Mode.
Ready
The output is clo
Gen-set is not running and
Controller is not in

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 44
IA-NT- PWR-2.0-Reference Guide.pdf
On Load <= (LBO) Mains Healthy and (LBI) MCB Feedback OK
r overvoltage shutdown alarm activates.
The out
alarm is not active and
FAULT RESET is pressed
Mains On Load
(LBO) Mains
AL Gen >V
The out t pu closes if the generato
put opens, if
AL Gen <V
The out ervoltage shutdown alarm activates.
The output opens, if
alarm is not active and
put closes if the generator und

FAULT RESET is pressed
AL Gen Volts
The output closes if the generator over/under voltage alarm or voltage asymmetry alarm activates.
ns, if
FAULT RESET is pressed
The output ope
alarm is not active and

AL Ge
the generator over/under frequency alarm activates.
alarm is not active and
pressed
n Freq
Output closes if
The output opens, if

FAULT RESET is
AL Gen >Freq
tivates.
e and
ssed
Output closes if the generator over frequency alarm ac
s, if The output open
alarm is not activ
FAULT RESET is pre
AL Gen <Freq
alarm is not active and
RESET is pressed
Output closes if
The out t
the generator under frequency alarm activates.
pu opens, if
FAULT
AL Mains Volts
The output r/under voltage alarm or voltage asymmetry alarm activates.
if
Output clos ncy alarm activates.
The output opens, if
alarm is ot active
AL Overload Sd
Output closes if the generator overload alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
closes if the mains ove
The output opens,
alarm is not active
AL Mains Freq
es if the mains over/under freque
n

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 45
IA-NT- PWR-2.0-Reference Guide.pdf
ltage or oil pressure
protection goes active 60s after stop command. With start goes this protection
The out
alarm is not active and
FAULT RESET is pressed
AL Stop Fail
Output closes when the engine have to be stopped, but speed or frequency or vo
is detected. This
inactive.
put opens, if


AL Mains Fail
Output c s lo es if the mains ov
rm activates.
er/under voltage alarm, voltage asymmetry alarm or mains over/under
frequency ala
ens, if
AL St t
Output close
, if
ctive and
is pressed
The output op
alarm is not active
ar Fail
s after the gen-set start-up fails.
The output opens
alarm is not a
AULT RESET F
AL Overcurrent
Output closes if the generator
current unbalance or
rm activates.
IDMT over current or
short current ala
The output opens, if
Alarm is not active and
FAULT RESET is pressed
AL Ba
IA-NT performs reset during start procedure (probably due to weak battery) or
rs.
s, if
essed
tteryFail
Output closes when
when battery under/over voltage warning appea
The output open
alarm is not active and
FAULT RESET is pr
AL Common Wrn
Output closes when any warning alarm appears.
The out t
active and
FAULT RESET is pressed
pu opens, if
No warning alarm is
AL Common Trip
Output closes when any trip alarm appears.
No trip alarm is active and
FAULT RESET is pressed
The output opens, if
Mode OFF
The output is closed, if OFF Mode is selected.
Mode MAN
The output is closed, if MAN Mode is selected.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 46
IA-NT- PWR-2.0-Reference Guide.pdf
closed, if AUT Mode is selected.
selected.
tive and
is pressed
Mode AUT
The output is
Mode TEST
The output is closed, if TEST mode is
The output opens, if
Alarm is not ac
FAULT RESET
Exerc Timer 1
in AUT mode.
neously, gen-set is started when it is in AUT mode.
T
MCB and GCB Close/Open
level change
TS three way switch to the position II.
l Pos output switches the ATS three way switch to the position 0 (middle).
behavior of the ATS output differs depending on the priority of the inputs of the particular
overrides the current position of the
witc
Neutral Coil
B ON
Neutral Coil output switches the ATS three way switch to the position 0 (middle).
Power Switch
This switch is assigned to the gen-set active power. The setpoints PowerSwitch ON [kW]
Output activates when Timer 1 is active. Simultaneously, gen-set is started when it is
Exerc Timer 2
Output activates when Timer 2 is active. Simulta
Not In AU
Output activates when the controller is not in AUT mode.
Neutral Pos
Switches ATS switch to its neutral position. It is a complement to the
binary outputs and it switches the ATS switch to its neutral position by applying voltage
(log. 0/ log. 1).
MCB Close/Open output switches the ATS three way switch to the position I.
GCB Close/Open output switches the A
Neutra
The resulting
type of the ATS switch.
If the neutral position input of the switch has the highest priority it
s h and forces the switch to the neutral position.
Activates the neutral position coil of the ATS switch. It is a complement to the MCB and GC
Coil and it switches the ATS switch to its neutral position by applying a voltage pulse.
MCB ON Coil output switches the ATS three way switch to the position I.
GCB ON Coil output switches the ATS three way switch to the position II.
and
PowerSwitch OFF [kW] for on and off level adjustment are located in the setpoint group Engine
Params. Typical usage for this binary output can be switching of dummy load. The output behaves

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 47
IA-NT- PWR-2.0-Reference Guide.pdf
based on the setpoint adjustment as described on picture lower:

Shunt Trip
Activates when the system is running in short time parallel with mains (closed transition) and the time
of the parallel run is longer than 300ms. It is a kind of protection against long time parallel run with
mains when closed transition takes place.


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 48
IA-NT- PWR-2.0-Reference Guide.pdf
s Setpoint
Password
EnterPassword
Password is a four-digit number. Password enables change of relevant protected setpoints.
key to enter the password. Use or keys to set and ENTER

NOTE:
There is only 1 level of a password.
ChangePassword
Use or keys to set and ENTER key to change the password.

NOTE:
At first the password has to be entered before the new password can be changed.
Basic Settings
ControllerName
efine e, used User d d nam for Inteli
NT
identification at remote phone or mobile connection.
llerN 14 characters long and have to be entered using LiteEdit software.
[kW]
rrent [ A ]
rrent and short current protection and means maximal
er Protect: Amps IDMT Del, Short Crct Sd setpoints.
fferent from generator rated current value.
Step: 1 A
nge: 1 - 10000 A
Contro ame is max
Nominal Power
Nominal power of the generator
Step: 1kW
5000 kW Range: 1
Nomin Cu
It is current limit for generator IDMT over cu
con n gen ti uous erator current. See Gen
Nominal Current can be di
Ra
CT Ratio [/5A]
Gen-set phases current transformers ratio.
Step: 1 A
Range: 1 5000 A / 5A

Hint:
For firmware versions < 2.0:
For CT Ratio <= 250 the values of power and current are displayed in a controller with one decimal.
For CT Ratio > 250 the values of power and current are displayed in a controller with integral
numbers. If you change CT Ratio in LiteEdit or directly in the controller, decimal numbers will not be
changed immediately. The change w e uted only by reconfiguring in LiteEdit. The statistics of ill be xec
power will be recounted at this time wi cimal numbers of power. th regards to de
WARNIN When you change the firmware, statistics can be invalid! G!
WARNING! Change of CT ratio over value 250 without reconfiguring in LiteEdit can cause
overflow of current measurement and improper function of controller!


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 49
IA-NT- PWR-2.0-Reference Guide.pdf
For firmware version >= 2.0:
Decimal switching is not done via value of CT ratio setpoint, but in configuration window of LiteEdit
software via icon Units/Formats:

PT Ratio [/1]
rmers ratio.
V / V
[/1]
Mains potential transformers ratio.
Step: 0,1 V / V
Range: 0,1 500,0 V / V
NomVolts Ph-N [V]
Nominal generator voltage (phase to neutral)
Step: 1V
Range: 80 20000 V
Gen-set potential transfo
Step: 0,1
Range: 0,1 500,0 V / V
Vm PT Ratio

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 50
IA-NT- PWR-2.0-Reference Guide.pdf

NOTE:
Phase sequence check is not possible to evaluate under voltage 50V what causes that if measured
voltage 50V is within the allowed range, controller will not allow to close the GCB, even if relevant LED
diod on front panel o NT f IA- lits.
al ge e (phase to phase)
1V
[Hz]
e sually 5

ActivityAtOFF [ENABLE/DISABLE]
trolle avior of OFF mode.
ts and there is Fault reset active all the
time.
, AUT,TEST]
de c es by MODE or MODE buttons.
NomV ts Ph ol -Ph [V]
Nomin nerator voltag
Step:
Range: 000 138 35 V
Nominal Freq
Nominal generator frequ ncy (u 0 or 60 Hz )
Step: 1Hz
Range: 45 65 Hz
ENABLE: Con r at OFF mode stays at standard beh
DISABLE: Controller at OFF mode opens all binary outpu
ControllerMode [OFF, MAN
Equivalent to Controller mo hang

NOTE:
Controller Mode change can be separately password protected.
dress different from the default value
re controllers can be intercon ssed e.g. from Modbus
ControllerAddr (1 .. 32) [-]
Controller identification number. It is possible to set controller ad
(1) so that mo nected (via RS485) and acce
terminal.

NOTE:
When ope ing connection to the controller it's addr n e setting in PC tool. ess has to correspond with th
From LiteEdit it is only possible to connect to controllers with address 1.
COM1 Mode [DIRECT/MODEM/MODBUS]
Communication protocol switch for the COM1 channel.
DIRECT: nication protocol via direc
MODEM: nication protocol via mod
LiteEdit commu t cable.
uide.
LiteEdit commu em.
US: tion in InteliCommunication g MODB Modbus protocol. See detailed descrip

NOTE:
For details on communic. speed and other technical parameters please see chapter Technical Data.
For detail description see chapter Modbus protocol. Register oriented modbus is supported.
COM2 Mode [DIRECT/MODBUS]
Communication protocol switch for the COM2 channel, if dual communication module is pluged in.
DIRECT: LiteEdit communication protocol via direct cable.
MODBUS: Modbus protocol. See detailed description in InteliCommunication guide.

NOTE:
For details on communic. speed and other technical parameters please see chapter Technical Data.
For detail description see chapter Modbus protocol. Register oriented modbus is supported.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 51
IA-NT- PWR-2.0-Reference Guide.pdf
s selected on COM1 or COM2 channels, the Modbus communication speed in
here
-OFF]
i
ld start when the output Gen Start/Stop is closed.
ld start when the output Gen Start/Stop is opened.
nd
Warning threshold for low battery voltage.
0,1 V
Volts)
Ove [V]
hold or hi b ttery voltage.


Connection h3Wire / Split Ph / Mono Ph]
w
l - 4 wires,
t 3PY, 3x CT
3Ph3Wire: DELTA Connection, 3 Phase without neutral - 3 Wires,
Thr ent 3PD, 3x CT


MONOPHAS
rrent measurement) is located next to the load.
t: rement) is located next to the gen-set.
/INPH-OPEN/CLOS-OPEN]
lly enhances controller function and brings
p hase Transition and Closed Transition (short time parallel). Controller
provide urces depending
o
O
I
CLOSED Closed Transition
INPH-OPEN Open In-phase Transition or Open Delayed Transition
CLOS-OPEN Closed Transition or Open Delayed Transition
1. Open Delayed Transition
Open Delayed Transition is standard type of changeover provided by most common AMF or ATS
controllers supplied by other vendors. Controllers perform load transfer between both power
sources with break (blackout). Delayed Transition means there is delay between source breaker
opening and target breaker closing.
ModbusComSpeed [9600,19200, 38400, 57600]
If the Modbus mode i
bps can be adjusted .
GenStart Logic [CLOSE-ON/CLOSE
The set po nt influences the behavior of the output Gen Start/Stop.
CLOSE-ON: Gen-set shou
CLOSE-OFF: Gen-set shou
Batt U ervolt [V]
Step:
Range: 8V 40 (Battery >
Batt rvolt
Warning thres f a
Step: 0,1 V
: 8V 40 (Battery <Volts) Range
Batt Volt Del [s]
Delay for low battery voltage alarm.
Step: 1s
Range: 0 600 s
Type [3Ph4Wire / 3P
Generator inding connection.
nnection, 3 phases and neutra 3Ph4Wire: STAR Co
Three phase wye measuremen
ee phase delta measurem
Split Phase: DOUBLE DELTA Connection, Split Phase,
Single-phase measurement 1PH, 1xCT
Mono Phase: E,
Single-phase measurement 1PH, 1x CT
CT Location [Load / GenSet]
Load: CT (cu
GenSe CT (current measu
Transition [OPEN/INPHASE/CLOSED
Ability to perform passive synchronization dramatica
ossibility to provide Open In-p
s below described types of changeover between Mains and Gen-set power so
n following setpoint value:
PEN Open Delayed Transition
N-PHASE Open In-phase Transition

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 52
IA-NT- PWR-2.0-Reference Guide.pdf
tion ATS switch or two independent breakers/contactors can be used as
A-NT controllers. Our
controllers offer possibility to setup load transfer delay via Transfer Del setpoint.
Two or three posi
switching mechanism.
Bellow you can see how is Open Delay Transition implemented by I

HINT:
This transition can perform fastest possible changeover if Transfer Del is set to zero value.
Overall blackout time then equals to 20 ms + breaker reaction time.

HINT:
Use longer delay time to avoid problems with motor starters. (Motor starts prefer to see break of a
few seconds so they can initialize properly).

HINT:
To avoid issues with contactor mechanical interlocks use delay 0.75s or longer (mech. interlock on
contactors takes some time to clear). If you try to close one contactor before interlock has cleared
it can jam and you end up with out supply to load).

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 53
IA-NT- PWR-2.0-Reference Guide.pdf
here delay during
n both power
setpoint value is ignored (equals to zero). See description of
for such systems where fast changeover (very short blackout) is
ot possible to use
nt breakers/contactors can be used as
ays) affects
switching time << 200 ms). The
faster the better to ensure real in-phase transition > once sync moment is calculated and source
is disconnected from load, electrical parameters of load are changing dynamically and could fall
out of sync rapidly. Real phase difference depends on that switching time.
2. Open In-phase Transition
Open In-phase Transition represents special kind of Open Delayed Transition w
changeover is reduced to minimal possible value and transition initiates only whe
sources are in sync. Transfer Del
passive synchronization for more info.
This kind of transition is suitable
required, huge inductive load (e.g. large electric motor) is involved and it is n
Closed Transition due to some reason.
Two or three position ATS switch or two independe
switching element. Reaction time of whole switching mechanism (including control rel
overall changeover time and in-phase transfer accuracy.
It is recommended to use as fast switches as possible (overall

Picture above shows how is Open In-phase Transition implemented by IA-NT controllers.
In case of system using two separate breakers/contactors controller ensures no overlap between
both switches during changeover however mechanical interlock can still be useful.
Two or three position ATS switches ensure this by its nature.
HINT:

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 54
IA-NT- PWR-2.0-Reference Guide.pdf
It is necessary to use fast breakers with known closing/opening time when Open In-phase
Transition takes place. Breaker switching time is used as parameter (MCB Delay, GCB Delay) for
calculation/prediction of exact in-sync moment.
Overall blackout time equals to 100 ms + one breaker reaction time (incl. control relay delay).

HINT:
In case of source (e.g. mains) failure changeover from source is always performed as open
delayed, not as in-phase.

HINT:
During system tests two separate breakers/contactors with switching time below 50ms were used
along with fast ATS switches (e.g. SOCOMEC ATyS M 3s, switching time 180 ms).
We do not recommend usage of switching elements their reaction time exceeds these values!

HINT:
Breaker delay default value for both breakers (MCB Delay, GCB Delay) is set to 50ms. ATS switch
delay consists of both delays.

3. Closed Transition
Closed Transition presents transition type where both breakers/contactors overlap for 100 ms and
is suitable for
e
on time of whole
switching mechanism (including control relays) affects overall changeover time.
It is required to use as fast switches as possible (breaker opening time < 100 ms including control
relay). If parallel run exceeds 200 ms both breakers are opened and alarm is activated. If parallel
run still continues (breakers are closed for at least 100 additional milliseconds), binary output
Shunt Trip is activated (if configured).

transition initiates only when both power sources are in sync. This kind of transition
such systems where no break (no blackout) changeover is required. Transfer Del setpoint valu
is ignored (equals to zero).
See description of passive synchronization for more info.
Two independent breakers/contactors are required as switching elements. Reacti

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 55
IA-NT- PWR-2.0-Reference Guide.pdf

HINT:
It is necessary to use fast breakers with known closing/opening time when Closed Transition takes
place. Breaker switching time is used as parameter (MCB Delay / GCB Delay) for
calculation/prediction of exact in-sync moment.

HINT:
In case of source (e.g. mains) failure changeover from source is always performed as open
delayed, not as closed.

HINT:
During system tests two separate breakers/contactors with switching time below 50ms were used.
We do not recommend usage of switching elements their reaction time exceeds these values.

HINT:
Breaker delay default value for both breakers (MCB Delay, GCB Delay) is set to 50ms.
ition, Closed + Open Delayed Transition
equals to [INPH-OPEN] or [CLOS-OPEN], system continues with Open
elaye sition after requested synchronized transition failed (sync timeout expired sooner
than both sources reached synchronized state)
GCB Delay [s]
By means of this setpoi system gets m n about breaker/contactor switching time. This value
is needed for exact sync oment/ time predi n.
Step: 0.01 s
Range: 0.01 60.00 s
Default: 0.05 s

4. Closed + Open Delayed Trans
If Setpoint Transition
D d Tran
nt infor atio
m ctio

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 56
IA-NT- PWR-2.0-Reference Guide.pdf
rmation about breaker/contactor switching time. This value
d f oment/ time prediction.

Range: 0.01 60.00 s
MCB Delay [s]
By means of this setpoint system gets info
is nee or exact sync m
.01 s
de
Step: 0
Default: 0.05 s
HINT:
Value of breaker switching time MUST contain all the parts of breaker delay (i.e. breaker switching
time plus switching time of relay used for breaker control).
The more exact value is given, the more exact is the sync result.
Engine Params
Pres Ti tart me [s]
s Prestart and/or Pretransfer output prior to the engine start.
u w nt to ave utput Prestart/Pretransfer open.
[s]
el [s]
u START/STOP. When generator does not reach
defined limits Basic Settings: Nominal Freq) within Max Start Del, Trp Start Fail alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If MaxStartDel is longer then 600 s it means there is NO TIMEOUT.
Step: 1s
Range: 0 600 s, 601 s = NO TIMEOUT
Time of clo ing of the
Set to zero if yo a le the o
Step: 1s
: 0 600 s Range
Cooling Time
Runtime of the lo g un aded en-set to cool the engine before stop.
Step: 1s
Range: 0 3600 s
Max Start D
This timeo t starts after closing binary output GEN

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 57
IA-NT- PWR-2.0-Reference Guide.pdf
Engine start evaluation diagram:

Min Stab Time [s]
Minimum time interval between defined generator voltage is reached to GCB is cl
If BI: GenReadyToLoad is not configured, timer is not used.
Step: 1s
ge: 1 300 s
osed.
Stop Time
of the Stop Time setpoint tells the controller how long should it wait for the
or
pires the Wrn Stop
s Stop command to
(Start/Stop output is deactivated).
Step: 1s
Range: 0 3601 sec Value 3601 mean ntroller doesnt care for the engine is
stopped (Wrn ounced).
Power switch function
This switch is assigned to the gen-set active power. Typical usage for this binary output can be
switching of dummy load. The output behaves based on the setpoint adjustment as described on
picture lower:
Ran
[s]
Period given by the value
engine to change to the stop state (stop state means GenReadyToLoad signal is deactivated
generator voltages disappeared). If the engine is still running after the stop time ex
Fail alarm is announced. Stop Fail starts counting always when the controller send
the engine
s the co
Stop Fail is never ann

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 58
IA-NT- PWR-2.0-Reference Guide.pdf

PowerSwitch ON [kW]
witch on.
1
: 0 kW

PowerSwitchOFF [kW]
Threshold level for switching the binary output Power Switch off.
Step: 1
Range: 0 32000 kW
Threshold level for switching the binary output Power S
Step:
Range 0 3200

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 59
IA-NT- PWR-2.0-Reference Guide.pdf
Gener Protect

NOTE:
All electric protections when activated result in shutdown.
Gener otect [ENABLE/DI Pr SABLE]
Generato ntroller are active.
are inactive.
loa [%]
erload ower)
1% of Nominal power
loa [s]
o d ala

r [%]
o nt reaches Short Crct Sd limit.
nt
:
[s]
10.00 s
IDMT curve shape rotection for 200%
overcurrent I
Step:
ry inverse generator over current protection. Reaction time is not constant but depends on

mal value of all measured phases of generator current.

ENABLE: r protections of the co
DISABLE: en r ctions G erato prote of the controller
Over d
Threshold for generator ov (in % of Nominal p
Step:
Range: 0 200%
Over d Del
Delay for generat r overloa rm.
Step: 0.1s
Range: 0 600.0 s
Short Crct T p
r curre Shutdown occurs when generat
% of Nominal curre Step: 1
Range 100 - 500 %
Short Crct Del
Delay for generator shorcurrent alarm.
1s Step: 0.0
: Range 0.00
Amps IDMT Del [s]
selection. Amps IDMT Del is Reaction time of IDMT p
Current. gen = 2* Nomin
0.1 s
0.1 - 60.0 s Range:
IDMT is ve
generator over current level according following formula.


Igen is maxi
Amps IDMT Del * Nomin Current
Reaction time =
Igen - Nomin Current
NOTE:
Reaction time is limited up to 900 sec = 15 minutes. IDMT protection is not active for Reaction time
values longer than 15 minutes.


EXAMPLE of Reaction time for different over current levels. Values in column 200% are IDMT Curr
Del.


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 60
IA-NT- PWR-2.0-Reference Guide.pdf










Igen
Nominal Current
Short Crct Sd
Amps IDMT Del
Maximal Reaction time
R
e
a
c
t
i
o
n
t
i
m
e

Amps Unbal Trp [%]
old for generator current asymmetry (unbalance).
Step: 1% of Nominal current
1 200% of Nominal current
s U [s]
lance
0.1 s
]
Threshold for generator overvoltage. All three phases are checked. Maximum out of three is used.
Step: 1% of Nominal voltage
Range: 0(Gen <V Sd) 200%
Gen <V Trp [%]
Threshold for generator undervoltage. All three phases are checked. Minimum out of three is used.
Step: 1% of Nominal voltage
Range: 0% 200 (Gen >V Sd)%
rrent Overcu
% =
MT C
Del
100 % 101 % 110 % 200
ID urr

0,2 s o ac 20 2 s N tion s
Thresh
Range:
Amp nbal Del
Delay for generator current unba
Step:
Range: 0.0 600.0 s
Gen >V Trp [%
2 s No 200 s 20 s action Reaction time
20 s No action No action
(time > 900 s)
200 s

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 61
IA-NT- PWR-2.0-Reference Guide.pdf
ervoltage and overvoltage alarm

]
hold f ance alarm.
al voltage
200% f No l voltage
[s]
unbala arm.
>Fr
n ator p ase L rfrequency.

% of Nominal frequency
[%]
: 0 (Gen >Freq Sd ) % of Nominal frequency
[s]
ble del y on alarms
le configured for binary intput 6 and 7 has been added.
spective binary input for the whole time the delay is active. If the reason
the delay time expired, the alarm is activated. If not, the alarm does not
lows the user to perform filtering of alarms within a specified period of time.
l gth can be set via the following setpoints:
[s]
input nr. 6
ct
Step: 0.1s

Range: 0 360.0 s
AMF Settings
Gen V Del [s]
Delay for generator und
Step: 0.1s
Range: 0.0 600.0 s
Volt Unbal Trp [%
Thres or generator voltage unbal
Step: 1% of Nomin
Range: 0 o mina
Volt Unbal Del
Delay for generator voltage nce al
Step: 0.1s
Range: 0.0 600.0 s
Gen eq Trp [%]
Threshold for ge er h 3 ove
Step: 0.1% of Nominal frequency
: 200.0 Range 0 (Gen <Freq Sd)
Gen <Freq Trp
Threshold for generator phase L3 underfrequency.
0.1% of Nominal frequency Step:
Range 0.0 20
Gen Freq Del
Delay for generator underfrequency and overfrequency alarm.
Step: 0.1s
Range: 0.0 600.0 s
Programma a
delay on alarms Possibility to set programmab
the re If set, it blocks alarms of
sists after for the alarm per
appear. This feature al
The delay en
BI6 Delay
Delay for alarm on binary
Setpoint group: Gener Prote
Range: 0 360.0 s
BI7 Delay [s]
Delay for alarm on bin inp r. 7 ary ut n
Setpoint group: Gener Protect
Step: 0.1s
RetFromIsland [MANUAL, AUTO]
MANUAL: After closing GCB, IA-NT goes to MAN Mode automatically.
AUTO: No automatic switching to MAN Mode.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 62
IA-NT- PWR-2.0-Reference Guide.pdf
failure to the start of the gen-set

6000
]
return to the GCB opening.
1s
ng to MCB closing during the return procedure.
Delay after MCB opening to GCB closing if the setpoint MCB Opens On set to GENRUN
Step: 0.1s
Range: 0 600.0 s

EmergStart Del [s]
Delay after the mains
Step: 1s
Range: 0 s
MainsReturnDel [s
Delay after the mains
Step:
Range: s 1 3600
Trans Del fer [s]
Delay after GCB openi

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 63
IA-NT- PWR-2.0-Reference Guide.pdf
The time charts bellow show recommended setting of AMF Settings: Transfer Del setpoint.
shor eedback
of t B Close/Open
s G sfer Del
Close/Open output straight away (100 ms) must be set to sum of MCB opening + del
after the MCB feedback input deactivates. time.
o e D l [s]
-up procedure)
p

[%]
hree is used.
tage
Range: 50 (Mains <V) 150%
[%]
hold for mains undervoltage. All three phases are checked. Maximum out of three is used.
nominal voltage
0 15 (Mai )%
[s]
rvoltage and overvoltage
s
V l [%]
e unbal
1% of Nominal voltage
V [s]
Delay for mains voltage nbalance
Step: 0.1 s
Range: 0- 60.0
Mains >Freq [%]
Threshold for mains overfrequency. All three phases are checked. Maximum out of three is used.
Step: 0.1% of Nominal frequency
Range: 50 (Mains <Freq) 150.0%

If the Transfer Del setpoint is set ter If some delay between MCB f
than the time required for opening he deactivation and closing of GC
output is required, then the Tran circuit breaker, the controller close CB
















MCB
Close/Open
MCB
Feedback
GCB
MCB
Close/Open
MCB
Feedback
GCB
Close/Open
MCB opening del
Transfer Del
MCB Cl s e
Delay after mains returns to MCB closing, if gen-set is not running(e.g. is in start
Ste : 0.1s
Range: 0 60.0 s
Mains >V
Thr s r mains overvoltage e hold fo . All three phases are checked. Maximum out of t
Step: 1% of Nominal vol
Mains <V
Thres
Step: 1% of
Range: 5 % 0 ns >V
Mains Del V
Delay for mains unde
Step: 0.1
Range: 0 s 600.0
Mains Unba
Threshold for mains voltag ance
Step:
Range: 1 150%
Mains Unb Del
u
Close/Open
Transfer
Del
MCB opening

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 64
IA-NT- PWR-2.0-Reference Guide.pdf
hold f All three phases are checked. Maximum out of three is used.
ency
0 15 .0(Ma req)%

rfrequency and overfrequency
0.1s
0 60.0
]
The set point influences the behavior of the output MCB CLOSE/OPEN
CLOSE-ON: When the output MCB CLOSE/OPEN is closed MCB should be closed.
CLOSE-OF the output MCB CLOSE/OPEN is closed MCB should be opened.


Mains <Freq [%]
Thr s or mains underfrequency e .
Step: 0.1% of Nominal frequ
Range: 5 % 0 ins >F
Mains Freq Del [s]
Delay for mains unde
Step:
Range: s
MCB Logic [CLOSE-ON / CLOSE-OFF
F: When
IA OFF

MCB logic = CLOSE-ON

IA ON
Mains O.K. Mains O.K.
Mains Failure
Signal after exter
inverted relay
MCB logic = CLOSE-OFF
nal
+


NOTE:
In the case MCB Logic = CLOSE-OFF it is necessary to change externally the polarity of the output
signal.
ReturnFromTEST [MANUAL / AUTO]
The set point influences the behavior of the TEST mode.

MANUAL:
1) Select TEST, gen-sets starts and running unloaded
Battery
-
iL
DO 4
MCB
AUX.
INVERTING
RELAY

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 65
IA-NT- PWR-2.0-Reference Guide.pdf
CB ON/OFF or wait for power-cut. 2) To transfer load from mains to the gen-set press M
3) When mains recovers, the gen-set remains running loaded.
CB
b) After the Transfer Del delay InteliATS
NT
closes the MCB.
c) The gen-set is cooled and stopped
4) To stop the gen-set select AUTO Mode
5) In AUT Mode:
a teliATS
NT
opens the G ) After the MainsReturnDel In

AUT:
1) Select TEST, gen-sets
2
starts and running unloaded
r the power-cut. the controller does not response ) To transfer load from mains to the gen-set wait fo
for MCB ON/OFF button.
3) When the mains recovers:
ens the GCB
nsfer Del d CB.
ains runnin
Opens On [MAINSFAIL / GENRUN]
a) After the MainsReturnDel the controller op
b) After the Tra elay the controller closes the M
4) The gen-set rem g.
5) To stop the gen-set select a different mode than TEST.
MCB
MAINSFAIL
The command to open the MCB is given immediately after mains fail condition evalu

ated.
RUN GEN
setpoint
EmergStart Del), reaches proper voltage and frequency and Min Stab Time elapses. After that, the
ed and the GCB is closed after the timer elapses.
The command to open the MCB is not given till the Gen-set starts (with respecting the
MCB is opened, Transfer Del timer is start

NOTE:
This option should be used for MCBs using 230V control and not equipped with the undervoltage coil.
this timer starts. After the timer elapses the state of BI:
feedback del setpoint is longer then 60.0 s it means there is NO TIMEOUT.

ackDel [s]
g binary output MCB close/open this timer starts. After the timer elapses the state of BI:
aluated.
NO TIMEOUT.
O TIMEOUT.

GCBFeedbackDel [s]
After closing binary output GCB close/open
GCB feedback is evaluated.
If the setting of the GCB
Step: 0.1s
Rang 0 60.0 s, 60.1 s = NO TIMEOUT. e:
MCBFeedb
After closin
MCB feedback is ev
If the setting of the M fe ck del CB edba setpoint is longer then 60.0 s it means there is
Step: 0.1s
60.0 s, 60.1 s = N Range: 0
Sync Ctrl
Voltage Window [%]
This setpoint adjusts maximum allowed difference between generator and mains/bus voltage in
respective phases for passive synchronizing:
Step: 1 %
Range: 0 30 %
Default: 10 %

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 66
IA-NT- PWR-2.0-Reference Guide.pdf
d difference between generator and mains/bus frequency in
ve
Freq Window [Hz]
This setpoint adjusts maximum allowe
respe phases for passive cti synchronizing:
1 Hz Step: 0.
Range: 0.0 2.0 Hz (0.0 0.3 Hz for CLOSED transition)
Default: 0.2 Hz
HINT:
This setpoint de n trans ion type pe ds on it selected (setpoint Transition). If Closed transition takes
place Frequenc W oint valu y indow setp es above 0.3 Hz are internally limited to value of 0.3 Hz.
mum time interval when system waits for both sources to get synchronized.
hat ti nization timeout alarm is activated and either changeover is interrupted or
ues a n delayed transition. See Transition setpoint description for more details, please.
Step: 1 min
1 60 min
Default: 1 min
Sync Timeout [min]
This setpoint adjusts maxi
After t me synchro
contin s ope
Range:
Date/Time
Time Stamp Per [min]
00m
Time interval for periodic history records.
Step: 1 min
Range: 0 2 in

NOTE:
Time stamps are only recorded into history while gen-set is running. When is engine stopped there are
no time stamps records made.
SummerTimeMod [DISABLED / WINTER / SUMMER, WINTER-
ER-S]
switching between summer and wintertime is disabled.
mer and wintertime is enabled and it is set to
ER-S) : Modification for southern hemisphere.
[DDMMYYYY]
.. Fail Blk /
It is following Timer functions. Binary output Exerc Timer X is always
activated when Timer is active regardless of chosen Timer function. Timer functions require controller
running in AUT mode.
No Func: There is no any other io ut binary output Timer1..2 activation.
TEST: When this option is chosen then the Timer output is also internally connected to the
Remote TEST binary input.
TEST OnLd: When this option is chosen then the Timer output is also internally connected to the
Rem TEST OnLd binary input.
MFail Blk: When this option is chosen then the Timer output is also internally connected to the
MainsFailBlock binary input.
S, SUMM
DISABLED: Automatic
WINTER (SUMMER) : Automatic switching between sum
winter (summer) season.
WINTER-S (SUMM
Time [HHMMSS]
Real time clock adjustment.
Date
Actual date adjustment.
Timer1 2Function [No Func / TEST / TEST OnLd / M
Mode OFF]
possible to choose out of 5
funct n, b

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 67
IA-NT- PWR-2.0-Reference Guide.pdf
Mod ption is chosen then the Timer output is also internally connected to the
binary input.
DNESDAY/FRI
T-SUN]
s TIME is internally linked with Rem Start/Stop binary
MON AY, Y, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
activated on daily basis.
SAT-SUN:
d on selected day interval.
ime
ctivates.
Timer1..2Duration
imer output is active.
1 min
e OFF: When this o
Remote OFF
Timer 1..2 Repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WE
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SA
Define R 1 activation. Binary output TIMER 1
input. Refer to binary inputs for details.

NONE: Timer function is disabled
D TUESDAY, WEDNESDAY, THURSDA
Timer is
MON-FRI, MON-SAT,
Timer is activate
Timer1..2 ON T
Day t en T ime wh imer output a
Duration of T
Step:
Range: 1 1440 s
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet Bridge is connected to the controller, the controller ca
messages and/or emails in the mo
n send SMS
ment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
Msg, which
s shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
il address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm
levels of alarm
e-ma
GSM number or e-mail to both setpoints.
NOTE:
An internet module be ilable for sending of e-mails. S must ava imilarly, a GSM modem is necessary for
sending of SMS.

NOTE:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IA-NT is trying to send an active call type,
incoming calls are blocked.
Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs.
Yel Alarm Msg [DISABLED, ENABLED]
NOTE:
The target address (GSM phone num e ail address) must be set correctly to the setpoint(s) ber or -m
TelNo/Ad r Ch1 resp. TelNo/Addr Ch
Red Alarm Msg [DISABLED, ENABLED]
Set this setpoint to YES if you want to get messages when a red (shutdown) alarm occurs.
d 2.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 68
IA-NT- PWR-2.0-Reference Guide.pdf
NOTE:
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
he alarm messages
e value of this parameter. If it consist @ it is
sup osed to be e-mail address and active e-mail is sent. If the value is number, without @, it is
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where t
shall be sent. Type of active call is considered from th
p
supposed to be the telephone number and active SMS is sent.
NOTE:
For GSM numbers use either national format (i.e. like number you will dial if you want to make a local
call) or full international format with "+" character followed by international prefix in the begining.
This setpoint can be modified from PC only!



InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 69
IA-NT- PWR-2.0-Reference Guide.pdf
on Function Descripti
Operating modes
Selection of the operating mode is done through Mode buttons on the front panel or by changing of the
Controller mode setpoint (from the front panel or remotely).
NOTE:
If this setpoint is configured as password-protected, correct password must be entered prior
attempting to change the mode.

NOTE:
Mode can not be changed, if Access Lock input is active.

T r g binary inputs that can be used to force one respective operating mode
i e the mode setpoint selection:

he e are followin
nd pendently on
Remote OFF
Remote MAN
Remote AUT
Remote TEST
Rem TEST OnLd
If the respective input is active the controller will change mode to the respective position according to
rities of the
he priorities matches the order in the list above. If all inputs are deactivated the mode will
iven by the setpoint.
in OFF mode depends mainly on setting of the ActivityAtOff
the active input. If more inputs are active the mode will be changed according to prio
inputs. T
return to the original position g
OFF
The behavior of the controller setpoint.
No activity
Setpoint ActivityAtOff = DISABLED.
The controller opens all binary outputs and Fault reset is active all the time.
Standard activity
Setpoint ActivityAtOff = ENABLED.
oading The GCB will be opened and the engine will be immediately stopped in this mode without unl
and cooling. The MCB is closed permanently (MCB Opens On = GENRUN) or is open o
according to the mains is present or not (
r closed
MCB Opens On = MAINSFAIL). No AMF (A
- evaluates Mains failure / return) function will be performed. Buttons MCB, GCB, ST
including the appropriate binary inputs for external buttons are not active. Output
uto Mains Failure
ART, STOP
GenStart/Stop is not
d.
nd STOP buttons (or external buttons
wired to appropiate binary inputs) in MAN mode. This will activate/deactivate GenStart/Stop
energize
MAN
The engine can be started and stopped manually using START a
binary
output which polarity depends on GenStart Logic setpoint. When the engine is running, GCB can be
closed to a dead bus. Also MCB can b s nd opened manually using the MCB button,
regardless the mains is present or not. No autostart is performed. No reaction to the input Rem
e clo ed a
Start/Stop.
NOTE:
The engine can run without load unlimited time. The controller does not automatically stop the running
gen-set in MAN Mode and does not start the gen-set when power cut comes.


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 70
IA-NT- PWR-2.0-Reference Guide.pdf
NOTE:
The breakers are internally locked to close two voltages against each. The controller will automatically
recognize if the breaker can be closed, it means it is never possible to close both breakers together

NOTE:
If some voltage arises on generator bus (e.g. gen-set was started externally - not via IA-NT), generator
LED blinks and [Stop], [MCB], [GCB] buttons are inactive. To bring them into operation [Start] button
has to be pressed - it will synchronize IA-NT with gen-set state.

CAUTION!
The MCB can be opened manually in MAN mode. Accidental opening the MCB will cause the object
(load) will remain without power!!!
AUT
The engine is started and stopped either by the binary input Rem Start/Stop or by th
mechani
e AMF
sm or by the manual transfer request via Rem Transfer binary input. Buttons MCB, GCB,
not active. The full start
the moment when the engine is loaded is automatic as well as unloading and stop
re
and no next
Gen-set Start/Stop signal stays active
et parameters are OK (means GenReadyToLoad signal is activated or
generato d limits) and then G reclosed
Fo n Voltage nough to
w e off po l setpoint
s
START, STOP including the appropriate binary inputs for external buttons are
sequence up to
sequence.
The controller behavior when gen-set is stopped and restarted again whilst the mains failu
constantly persists:
If the problem on the gen-set side appears, all faults messages are auto-quit
operation is be blocked
Controller waits for gen-s
r voltages are in allowe CB is

re
r ensuring GCB Open/Close output remains off whilst Ge is OK long e
ind the Circuit breaker to th sition use the Transfer De
AMF equence (simplified)
State Condition of the transition Action Next state
Mains failed
1
or MCB feedback dropout
INSFAIL
MCB CLOSE/OPEN o
EmergStart Del timer started
Mains failure
MCB Opens On = MA
ff Mains
operatio
edback
RUN
Mains failure
n
Mains failed
1
or MCB fe
MCB Opens On = GEN
dropout EmergStart Del timer started
Mains voltage and frequency O
INSFAIL on
Mains operation K After elapsing MCB C
MCB CLOSE/OPEN MCB Opens On = MA
lose Del
Mains voltage and frequency O
MCB Opens On = GENRUN
Mains operation K None
EmergStart Del elapsed
MCB Opens On = MAINSFAIL
nce perf ,
then
o
Island operation Engine start seque ormed
GCB CLOSE/OPEN n
2

Mains
failure
EmergStart Del elapsed
MCB Opens On = GENRUN
ce performed,
EN off, time
lay Transfer Del performed and
2
Island operation Engine start sequen
then MCB CLOSE/OP
de
GCB CLOSE/OPEN on
Island
operation
Mains voltage and frequency OK MainsReturnDel timer started Mains return
Mains failed Island operation Mains
return MainsRetu Del elapsed GCB CLOSE/OPEN off, then after
Transfer Del MCB CLOSE/OPEN
on and then engine stop sequence
performed
3

Mains operation rn

1
Mains failed means mains over/under -voltage, over/under -frequency, voltage assymetry (preset
delay must elapse)

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 71
IA-NT- PWR-2.0-Reference Guide.pdf
lay MCB Close Del
2
If during start-up sequence mains returns, then MCB is reclosed with de (if
opened, depending on MCB Opens On setpoint) and start-up sequence is interrupted.
3
If mains fails during stop procedure (

cooling) again, stop sequence is interrupted, MCB opened and
GCB reclosedclosed with delay Transfer Del.


chapters: Circuit breakers timing See also and AMF time chart.
WARNING!
If an red alarm is present and the gen-set is in AUT mode, it can start by self after all red alarms
becomes inactive and are acknowledged!!!

of the controller in TEST mode depends mainly on setting of the ReturnFromTEST
TEST
The behavior
setpoint.
Automatic return
Setpoint ReturnFromTEST = AUTO.
The gen-set will be started when the controller is put to TEST mode and will remain running unloaded.
If a mains failure occurs, the MCB will be opened and after Transfer Del the GCB will be closed and
After mains is recovered, the delay MainsReturnDel the gen-set will supply the load. will count
ains is still ok, the controller will transfer the load back to the
ged.
down and if elapses and the m
mains and the gen-set will remain running unloaded again until the mode is chan
Manual return
Setpoint ReturnFromTEST = MANUAL.
The d when the controller is put to TEST mode and will remain running unloaded.
sferred to the gen-set also manually:
ansfer Del
gen-set will be starte
If a mains failure occurs, the gen-set will take the load after it has started.
The load can be tran
If the MCB button is pressed, the controller will open the MCB, then wait for Tr and
il the controller is
Test with load
finally close the GCB.
Once the load is supplied by the gen-set, the gen-set remains supplying it unt
switched to other mode.

the gen-
lly make a
, wait for Transfer Del
If the binary input Rem TEST OnLd is activated, the controller is switched to TEST mode (i.e.
set will be started as described above), but once started the controller will automatica
switchover, i.e. open MCB and close GCB.
to previous
controller
will either stay supplying the load if the mains is failed, or will transfer the load back to the mains.
After the binary input Rem TEST OnLd has been deactivated, the controller goes back
operation mode and it's behavior depends on it. In most cases it will be AUT mode and the
Periodic exercises
The output from the Exerc timer 1 is internally connected to the Remote TEST binary input to enable
testing of the gen-set.
The controller must have AUT mode selected by mode buttons and other "mode forcing" binary inputs
must not be active to ensure proper function of the exercise.
periodic
NOTE:
If a shutdown or other red alarm comes while the load is supplied from the gen-set and the mains is
healthy, the load is switched back to the mains.

CAUTION!
The gen-set starts automatically and is always running in TEST mode!

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 72
IA-NT- PWR-2.0-Reference Guide.pdf
Circuit breakers timing
Relation between Mains fail and MCB and start of gen-set

M

etected as Mains <V, Mains >V, Mains V Unbal, Mains <Freq, Mains >Freq. After
CB Opens On = MAINSFAIL:
Mains fail is d
detection MCB is opened.

NOTE:
When MCB feedback drop-out and measured mains electrical limits (voltage, frequency) are still in
limits, the controller switches MCB ON again.

EmergStart Del
Mains fail
MCB
opened
Mains V Del or Mains Freq
Del or Mains VUnb Del
genset start

MCB Opens On = GENRUN:

The MCB is not opened till the engine starts and gets ready to take the load.
Transfer Del
Engine started
MCB opened
MinGenStabTime
GCB closed
MaxGenStartDel

Relation between Mains return and MCB
OFF Mode, GCB and MCB are opened

Mains return
MCB closed (only when genset is
not running and GCB is opened)
M B C Close Del


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 73
IA-NT- PWR-2.0-Reference Guide.pdf
R
en-set loaded.
Mains returns: GCB opens (according 3., MainsReturnDel), MCB closes (Transfer Del)

elation between GCB and MCB
Conditions: AUTO Mode, Mains =off, MCB = opened, GCB = closed, g
GCB opened
MCB closed
Transfer Del


Relation between GCB and MCB (Test mode)

Situation 2: ReturnFromTEST=MANUAL, Mains =OK, MCB is closed, gen-set is running.
Press MCB on/off -> MCB opens, GCB closes (Transfer Del), gen-set is running loaded.
Situation 1: Mains =OK, MCB = closed, GCB = opened, RPM=0.
Change mode to TEST: gen-set starts, GCB = opened.
Mains cut: MCB opens (according 1.), GCB closes (Transfer Del)

MCB opened
GCB closed
Transfer Del


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 74
IA-NT- PWR-2.0-Reference Guide.pdf
nt
F re available:
Trip
re
Alarm Manageme
ollowing alarms a
Warning
Mains failu
Warning (WRN)

When warning comes up, only alarm outputs and common warning output are closed.
warnings:
ossible events
Possible
See List of p
Trip (TRP)

When the trip alarm comes up, InteliATS
NT
opens outputs GCB CLOSE/OPEN, GENSTART/STOP
p the engine immediately. Alarm outputs and common shutdown output are
closed. Active or not reset protection disables start.
s:
and PRESTART to sto
Possible shut-down alarm
See List of possible events
Mains failure (MF)

Mains failure detection depends on Auto mains failure (AMF) setpoints (levels and delays) adjusting.
p, mains circuit breaker is opened.
Possible mains failure reasons:
See List of possible events
When the mains failure comes u


NOTE:
Mains failure is not written to alarm list!

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 75
IA-NT- PWR-2.0-Reference Guide.pdf
AMF time chart genset OK

AMF time chart genset not started properly

NOTE:
For more details please see the:
* AMF Setting: MinStabTime & MaxStartDel setpoint description,
** AMF Setting: MCB Opens On & Transfer Del setpoint description,
*** AMF Setting: MCB Close Del setpoint description

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 76
IA-NT- PWR-2.0-Reference Guide.pdf
Voltage phase sequence detection
InteliATS
NT
controller detects phase sequence on both generator and mains/bus v
These protections are important after c
oltage terminals.
ontroller installation to avoid wrong voltage phases phase
s can be detected:
The
T
controller L1, L2, L3. When the phases are
conn 2, L1, L3) following alarms are detected:
ng generator phase sequence
t CB
tection see following diagrams.

When is BO GCB close/open (MCB Close/Open) in steady state and GCB feedback (MCB feedback)
is changed the GCB fail is detected immediately (no delay).
connection. Following alarm
Wrong phase sequence
re is fix defined phase sequence in InteliATS
N
ected in different order (e.g. L1, L3, L2 or L
Gen CCW Rot = wro
Mains CCW Rot = wrong mains phase sequence
GCB, MCB fail detection
MCB or GCB fail detection is based on binary output CB close/open comparing with binary inpu
feedback.
There are three different time delays for CB fail de

Alarm: GCB fail
BI GCB feedback
BO GCB close/open
Alarm detection:
immediatelly
Alarm: GCB fail
BO GCB close/open
BI GCB feedback
Alarm detection:
immediatelly
closed
opened
active active
opened
closed


When BO GCB close/open (MCB Close/Open) opens there is 5 sec delay for GCB fail (MCB fail)
detection.
Alarm: GCB fail
BO GCB close/open
BI GCB feedback
active
opened
opened
Time delay
5 sec


When BO GCB close/open (MCB Close/Open) closes, there is 5sec delay for GCB fail (MCB fail)
detection:
Alarm: GCB fail
BI GCB feedback
active
closed
closed
BO GCB close/open
Time delay
5 or 2 sec


NOTE:
You can solve state of MCB fail by pressing Fault Reset button.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 77
IA-NT- PWR-2.0-Reference Guide.pdf
tes
ic s
per
Gen-set Operation Sta
Electr tate machine
MainsO Mains is present
MainsFlt off immediate state Mains cut
MainsFlt es EmergStart del Mains cut off tak
IslOper Island operation
MainsRet Mains recover
Brks Off GCB, MCB opened
MinStabTO Minimal Stabilization Timeout
MaxStabTO Maximal Stabilization Timeout
Trans Del Forward return break delay. Delay between GCB opening and MCB closing
L ssib ven ist of po le e ts

Events
specification
Protection
type
Information on binary
output available (See
list of Binary outputs)
Description
Wrn Batt Volt WRN YES its given by Batt
tpoints.
Battery voltage is out of lim
Undervolt/Batt OverVolt se
Binary input Configurable YES Configurable Warning/Shutdown alarms on
ts of IA-NT. the inpu
Trp BatteryFlat TRP YES during starting
n it
nd activates this
If the controller switches off
sequence due to bad battery conditio
doesnt try to start again a
protection.
Trp Start Fail TRP YES Gen-set start failed.
ParamFail NONE NO meters. Happends
new firmware or
r. The controller
all parameters
eter.
Wrong checksum of para
typically after downloading
changing of the paramete
stays in INIT mode. Check
and write at least one new param
Trp Gen Lx >,<V TRP YES is out of limits given
Sd setpoints.
The generator voltage
by Gen <V Sd and Gen >V
Trp Gen V Unbal TRP YES nerator voltage is unbalanced more
nbal Sd setpoint.
The ge
than the value of Volt U
Trp Gen >Freq TRP YES ncy is out of limits
and Gen <Freq Sd
The generator frequ
eq Sd
e
given by Gen >Fr
setpoints.
Wrn Amps Unbal TRP NO unbalanced. The generator current is
Trp Overload TRP YES ter than the value given by The load is grea
Overload setpoint.
EmergencyStop TRP NO p is opened
ctivated.
If the input Emergency Sto
shutdown is immediately a
GCB Fail TRP NO r circuit breaker. Failure of generato
MCB Fail MF NO Failure of mains circuit breaker.
Wrn GeStateNA WRN NO Neither GenerProtect enabled nor BI
GenReadyToLoad defined. At least one
must be enabled / configured.
Trp GenRd Fail TRP NO Signal BI GenReadyToLoad lost
Wrn Stop Fail WRN YES Gen-set stop failed. The alarm appears if
the STOP command fails and the START
command was issued before.
Low BackupBatt WRN NO RTC backup battery is flat

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 78
IA-NT- PWR-2.0-Reference Guide.pdf
History file

InteliATS
NT
stores a record of each important event into the history file. The history file seats 117
rds. When the history file is full, the oldest records are removed. reco

NOTE:
To force history download in LiteEdit (direct, modem or Internet) open History window and select
History | Read history command.
ord s
breviation Historical value
Rec tructure
Ab
Num Number of historical event
Reason Event specification
Date event in format DD/MM/YY Date of historical
Time al event in format HH:MM:SS Time of historic
Mode de Controllers mo
Pwr r Generator active powe
PF Generator PF
LChr e load Character of th
Gfrq uency Generator freq
Vg1 ge L1 Generator volta
Vg2 age L2 Generator volt
Vg3 oltage L3 Generator v
Ig1 urrent L1 Generator c
Ig2 current L2 Generator
Ig3 rrent L3 Generator cu
Vm1 L1 Mains voltage
Vm2 Mains voltage L2
Vm3 Mains voltage L3
Mfrq Mains frequency
UBat Battery voltage
BIN Binary inputs IA-NT
BOUT Binary outputs IA-NT

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 79
IA-NT- PWR-2.0-Reference Guide.pdf
ging Remote Control and Data Log
Direct connection to the PC

InteliATS
NT
can be connected directly with PC via optional IL-NT RS232 interface.
NT
Use the standard serial cable to connect PC with InteliATS .

NOTE:
Make sure the grounding system on controller and PC COM port (negative of the PC DC supply) are
identical before the first direct connection. There must not be any voltage between these two points
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the
PC supply 240/20V is ground free (GND terminal is not connected).

5 - GND
2 - RxD
3 - TxD
PC
5 - GND
2 - RxD
3 - TxD
R
S
2
3
2
R
S
2
3
2
230 VAC
0

V
D
C
CONTROLLER
+
-
Battery
Required the same
voltage potential
between GNDs
RS 232

PC software LiteEdit

On the PC (for direct or modem connection) has to be installed the ComAps software package
dows 95 or newer platform)
r
select software configuration
modify password, commands protections
d on
M
LiteEdit. (based on Win
LiteEdit enables:
read the quantities
adjust all set points
control the engine
configure the controlle
modify alarm inputs and outputs
irect, modem or Internet communicati
odbus protocol

T ion of the function of iL serial port is done via the setpoint COMx Mode in Basic settings
Function 3 (Read Multiply Registers)
Function 6 (Write Single Register)
Function 16 (Write Multiply Regis
The sponse to an incoming messa s nt with minimum 4.096 ms delay after message
reception

The complete description of Modbus communication protocol can be found in Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available from web site at http://www.modicon.com/openmbus/
he select

57600 bps, 8 data bits, 1 stop bit, no parity
Transfer mode RTU
ters)
re ge i se
.


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 80
IA-NT- PWR-2.0-Reference Guide.pdf
Communication object vs. Register
All the data intended for communication has its representation as communication obje
controller. The communication object is represented by the n-byte array in the controll
identified by the unique 16-bit communication object number. The register, according t
communication protocol, represents a two-byte data and in communication functions i
16-bit register address. Further in the description of communication functions the com
object number will always b
cts in the
er memory and
o Modbus
s referenced by
munication
e used as a register address and length of the communication object
will be expressed by number of registers. Just one communication object can be read or written
by one communication function.

NOTE:
To obtain communication object numbers it is possible to download the actual controller description
on-line from controller or from (ail) archive and use export data function from LiteEdit software.
C nica lis d de N arc ommu tion object t (exporte from fault IA- T-PWR hive)

Setpoints of
e re ve r. n
IA-NT PWR:
Nam Firmwa r. Application Date App. ve Ser. um. Filename
IA-NT-PWR
IA-NT-1.2.3
1.2010
12 56

R:7.0
PWR 8.1.201 1,2 34 78
IA-NT-PWR-
1.2.AIL
Group Name ens. Pa Com. o imit Data type Value Dim ssword bj. Lo limit Hi l
Basic Settin lerName PWR No 86 Short string gs Control 37
Basic Settin Power 200 No 8 Unsigned 16 gs Nominal kW 276 1 5000
Basic Settin urrent 350 No 8275 000 Unsigned 16 gs Nomin C A 1 10
Basic Settin o 2000 No 8274 5000 Unsigned 16 gs CT Rati /5A 1
Basic Settin 1,0 No 9579 500,0 Unsigned 16 gs PT Ratio /1 0,1
Basic Settin atio 1,0 No 9580 Unsigned 16 gs Vm PT R /1 0,1 500,0
Basic Settin l Volts 231 No 8277 20000 Unsigned 16 gs Nomina V 80
Basic Settin Freq 50 No 8278 65 Unsigned 16 gs Nominal Hz 45
Basic Settin F BLED No 16 String list gs ActivityAtOF ENA 1 20
Basic Settin lerMode OFF No 83 String list gs Control 15
Basic Settin llerAddr 1 Ye 453 32 Unsigned 8 gs Contro s 2 7 1
Basic Settings COM1 Mode IRECT Yes String list D 24522
Basic Settings COM2 Mode RECT Ye 445 String list DI s 2 1
Basic Settings GenStart Logic ON No 910 String list CLOSE- 0
Basic Settings Batt Undervolt 18,0 No 838 40,0 Integer 16 V 7 8,0
Basic Settings Batt Overvolt 36,0 No 95 40,0 Integer 16 V 87 18,0
Basic Settings Batt Volt Del 5 No 8383 0 600 Unsigned 16 s

Engine Para Time 0 No 83 600 Unsigned 16 ms Prestart s 94 0
Engine Para ime 0 No 82 Unsigned 16 ms Cooling T s 58 0 3600
Engine Para 20 No 091 601 Unsigned 16 ms Max Star tDel s 1 4 0
Engine Para ime 3 No 82 300 Unsigned 16 ms Min Stab T s 59 1
Engine Para ime 60 No 981 Unsigned 16 ms Stop T s 5 1 3601

Gener Prote BLED No 10 String list ct GenerProtect ENA 1 30
Gener Prote ct Trp 250 No 82 500 Unsigned 16 ct Short Cr % 82 100
Gener Prote ct Del 0,00 No 99 0,00 Unsigned 16 ct Short Cr s 91 0,00 1
Gener Prote MT Del 4,0 No 82 60,0 Unsigned 16 ct Amps ID s 83 1,0
Gener Prote nbal Trp 50 No 82 200 Unsigned 16 ct Amps U % 84 1
Gener Protect Amps Unbal Del 5,0 No 8285 0,0 600,0 Unsigned 16 s
Gener Prote rp 110 No 8291 200 Unsigned 16 ct Gen >V T % 70
Gener Protect Gen <V Tr % No 8293 0 110 Unsigned 16 p 70
Gener Protect Gen V Del s No 8292 0,0 600,0 Unsigned 16 3,0
Gener Protect Volt Unbal Trp 10 % No 8288 1 200 Unsigned 16
Gener Protect Volt Unbal Del 3,0 s No 8289 0,0 600,0 Unsigned 16
Gener Protect Gen >Freq Trp 110,0 % No 8296 85,0 200,0 Unsigned 16
Gener Protect Gen <Freq Trp 85,0 % No 8298 0,0 110,0 Unsigned 16
Gener Protect Gen Freq Del 3,0 s No 8297 0,0 600,0 Unsigned 16

AMF Settings RetFromIsland AUTO No 9590 String list

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 81
IA-NT- PWR-2.0-Reference Guide.pdf
ng rt Del 5 No 83 Unsigned 16 AMF Setti s EmergSta s 01 0 6000
AMF Setting eturnDel 20 No 83 Unsigned 16 s MainsR s 02 1 3600
AMF Setting Del 1,0 No 83 00,0 Unsigned 16 s Transfer s 03 0,0 6
AMF Setting Close Del 1,0 No 838 60,0 Unsigned 16 s MCB s 9 0,0
AMF Setting >V 110 No 83 150 Unsigned 16 s Mains % 05 60
AMF Setting 60 No 830 110 Unsigned 16 s Mains <V % 7 50
AMF Setting el 2,0 No 83 00,0 Unsigned 16 s Mains V D s 06 0,0 6
AMF Setting V Unbal 10 No 84 150 Unsigned 16 s Mains % 46 1
AMF Setting Unb Del 2,0 No 84 60,0 Unsigned 16 s Mains V s 47 0,0
AMF Setting req 102,0 No 8310 Unsigned 16 s Mains >F % 98,0 150,0
AMF Setting q 98,0 No 8312 102,0 Unsigned 16 s Mains <Fre % 50,0
AMF Setting q De 0,5 No 8311 60,0 Unsigned 16 s Mains Fre l s 0,0
AMF Setting E-ON No 84 String list s MCB Logic CLOS 44
AMF Setting TEST No 86 String list s ReturnFrom MANUAL 18
AMF Setting On N No 9850 String list s MCB Opens GENRU
AMF Setting ac 3,0 No 983 60,1 Unsigned 16 s GCBFeedb kDel s 6 1,0
AMF Setting 3,0 No 9056 60,1 Unsigned 16 s MCBFeedbackDel s 1,0

Date/Time mp Per 60 No 8979 240 Unsigned 8 Time Sta min 0
Date/Time meMo BLED No 8727 String list SummerTi d DISA
Date/Time :00 No 45 Time Time 0:00 2 54
Date/Time .2006 No Date Date 1.1 24553
Date/Time peat NE No 00 String list Timer1 Re NO 1 45
Date/Time Timer1 ON Time No Time 5:00:00 10042
Date/Time uration 5 No 1440 Unsigned 16 Timer1D min 10044 1
Date/Time epeat NONE No String list Timer2 R 10202
Date/Time Time No Time Timer2 ON 5:00:00 10199
Date/Time ration 5 No 1440 Unsigned 16 Timer2Du min 10201 1

SMS/E-Mail Yel Alarm Ms String list g OFF No 8482
SMS/E-Mail Red Alarm Msg No String list OFF 8484
SMS/E-Mail TelNo/Addr Ch1 No Long string 9597
SMS/E-Mail /Addr Ch2 N 9598 Long string TelNo o

Values o WR:
e mware ver. A on D r. Ser. num. Filename
f IA-NT P
Nam Fir pplicati ate App. ve
IA-NT-PW
IA-NT-1.0
3.01.2009
17.2 12345678 IA-NT-PWR-1.0.AIL R
R:2
PWR .2009 1,0
Group Name Dime j. Data type Value nsion Com. ob
Generato kW 02 Integer 16 r Gen kW 150 82
Generato L1 50 kW 24 Integer 16 r Gen kW 85
Generato L2 50 kW 25 Integer 16 r Gen kW 85
Generato L3 50 kW 26 Integer 16 r Gen kW 85
Generato n kVAr 15 kVAr 03 Integer 16 r Ge 82
Generato L1 5 kVAr 8527 Integer 16 r Gen kVAr
Generato L2 5 kVAr 28 Integer 16 r Gen kVAr 85
Generato L3 5 kVAr Integer 16 r Gen kVAr 8529
Generato 153 kVA Integer 16 r Gen kVA 8565
Generato VA L1 51 kVA 30 Integer 16 r Gen k 85
Generato 2 51 kVA 8531 Integer 16 r Gen kVA L
Generato kVA L3 51 kVA Integer 16 r Gen 8532
Generator F 1,00 Integer 8 Gen P 8204
Generator Gen Load Char R 8395 Char
Generator Gen PF L1 8533 Integer 8 1,00
Generator Gen Ld Char L1 R 8626 Char
Generator Gen PF L2 1,00 8534 Integer 8
Generator Gen Ld Char L2 R 8627 Char
Generator Gen PF L3 1,00 8535 Integer 8
Generator Gen Ld Char L3 R 8628 Char
Generator Gen Freq 50,0 Hz 8210 Unsigned 16
Generator Gen V L1-N 230 V 8192 Unsigned 16





























InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 82
IA-NT- PWR-2.0-Reference Guide.pdf
to L2-N 230 V Unsigned 16 Genera r Gen V 8193
Generato L3-N 230 V Unsigned 16 r Gen V 8194
Generato L1-L2 398 V Unsigned 16 r Gen V 9628
Generato L2-L3 398 V Unsigned 16 r Gen V 9629
Generato V L3-L1 398 V Unsigned 16 r Gen 9630
Generato A L1 41 A Unsigned 16 r Gen 8198
Generator Gen A L2 41 A 8199 Unsigned 16
Generator 3 41 A Unsigned 16 Gen A L 8200

Mains L1-N 231 V Unsigned 16 Mains V 8195
Mains L2-N 230 V Unsigned 16 Mains V 8196
Mains L3-N 230 V Unsigned 16 Mains V 8197
Mains V L1-L2 398 V Unsigned 16 Mains 9631
Mains Mains V L2-L3 398 V 9632 Unsigned 16
Mains Mains V L3-L1 398 V 33 Unsigned 16 96
Mains Mains Freq 50,0 Hz 11 Unsigned 16 82

Controller Volts 24,3 V 13 Integer 16 I/O Battery 82
Controller ts 35 Binary 16 I/O Bin Inpu [1111001] 82
Controller utputs Binary 16 I/O Bin O [1111000] 8239

Statistics Energy kWh 0 Integer 32 8205
Statistics h 0 Integer 32 Energy kVAr 8539
Statistics tarts 0 Unsigned 16 Num S 8207
Statistics adStarts 0 5 Unsigned 32 Num B 1119

IA Info ate ##### 5 Unsigned 16 Breaker St 845
IA Info ##### Unsigned 16 Timer Text 8954
IA Info Timer Value 0 s 8955 Unsigned 16
IA Info FW Version 0,0 8393 Unsigned 8
IA Info Application 19 8480 Unsigned 8
IA Info FW Branch 10 8707 Unsigned 8
IA Info PasswordDecode ##### 9090 Unsigned 32

Date/Time Time ##### 24554 Time
Date/Time Date ##### 24553 Date

































InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 83
IA-NT- PWR-2.0-Reference Guide.pdf
ion Remote Communicat
NOTE:
Refer to InteliCommunication guide for all additional information.
Internet connection

d from InteliMonitor or LiteEdit over the Internet using IB-Lite
DN modem
IA-NT controllers can be monitore
plug-in.
Recommended IS

Develo Microlink ISDN i


R c
Askey TAS-200E
ASUScom TA-220ST
e ommended GSM modem

Siemens M20, TC35, TC35i, ES75, MC39
200/WMOD2
T recommended)
Hz.
GSM Modem setup
P r n following program for GSM proper setup.
Program writes all the necessary AT commands to configure the GSM modem properly for use with
I
_setup.exe.
Select COM port
ress S
Wavecom M1
Wavecom - Maestro 20, dual 900/1800MHz.
Wavecom Fastrack M1306B, dual 900/1800 MHz (Fastrack M1206B is NO
FALCOM A2D, dual 900/1800M
rio to start work with GSM modem ru
A-NT.
This program runs independent on LiteEdit:
Start MS Windows-Start-Program files - LiteEdit Gm

Select iG-CU (=IS-CU) or iG-MU unit


P etup button
Follow command M Modem Setup w

Typical real baud rate for GSM data communication s.

s in GS indow
is 80 to 90 Bp
NOTE:
It is strongly recommended to use the same type of modem on the both sides (IA and PC) of
c

Mobile SIM card setting
onnection.



Analog
modem
Analog GSM
modem
GSM
modem
or
modem

Adjust SIM card in GSM modem following way:
enable data connection (when required)
no PIN code

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 84
IA-NT- PWR-2.0-Reference Guide.pdf
ware
mote signalling
It is the optional
ible to upload into controller instead of standard controllers firmware.
IL-NT-RD Remote display soft
This chapter describes Remote display software IL-NT-RD, which is designed as an re
and control software for InteliATS
NT
, InteliLite
NT
and InteliDrive Lite controllers.
software which is poss
General description

Remote display software works as remote display and control for the master InteliATS
or InteliDrive Lite controller. Genset/Engines can be controlled
NT
, InteliLite
NT

from remote display as well as from
master controller. All remote display screens (Measure, Setpoints and History) displays the same data
controller. Front panel buttons on both controllers work the same way. All remote display
LEDs shows the same state as corresponding LEDs on master controller.
like master
Warning!

It is highly recommended to use the
display. Only in such case is assure
same type and model of controller for master and remote
d the proper function of all buttons, LED diods and display.
Another combinations of HW types and models from Master controller and remote display are
tallation
not supported nor tested!
IL-NT-RD Software ins

The IL-NT-RD remote display firmware is installed in the same way as any other IA-NT firmware using
Reference guide for details about upgrading firmware. IL-NT-RD
c t

H stall back the
origi
Open any type of online connection.
DDE server will try to open the connection, but it will fail and write red error message in the
status bar.
At this moment go to CONTROLLER -> PROGRAMMING AND CLONING -> PROGRAMMING and select
proper! firmware you want program to the controller. Choosing the wrong type of firmware
may result in non-functional controller.
LiteEdit software. Please see LiteEdit
on ains only firmware, not an archive.
owever when there is IL-NT-RD firmware installed in the controller the procedure to in
nal standard firmware is following:

Press "OK" button to programm the firmware to the controller.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 85
IA-NT- PWR-2.0-Reference Guide.pdf
oller, close the boot jumper and switch
r
cess
ns.
tus line and the
controller is blocked showing "Init" state. Use CONTROLLER -> RESET FROM INIT STATE menu
item to put the controller to normal operation. Be sure you have checked all setpoints before.
It may be required to switch off power supply of contr
on controller again. Follow the information windows accordingly.
After programming is finished (it may be required to power off controller, open the boot jumpe
and power it on again) open configuration window and perform the configuration pro
manually. There is no compatibility of the configuration between different firmware versio
In some cases the "wrong setpoints" message can occur in the DDE server sta
CAUTION!
Check the statistic values after firmware upgrade. Readjust the values if necessary.
IL-NT-RD Wiring
IL-NT-RD can be connected to InteliATS
NT
, InteliLite
NT
or InteliDrive Lite controller
RS485 communication line. It is possibl
via RS232 or
e to connect only up to two remote displays to one master
ing different communication COMs. It is not supported to connect two or more
ster
Connection process
onnected. It
ddress 1
to 32. Remote display tries two communication speeds 38400 bps and 56000bps.
Detecting on screen and progress bar below counts from 0 to
prox. 10-15 seconds. Than is 5 seconds pause and process continues
r controller is found.
llers, not supported application, or controllers that are not properly
ing the search.
C n
I e.
T
mote display can not connect with master controller:
o uppo ed type of controller connected (Eg. IGS-NT, ID-DCU, IC-NT, IGS-CU, etc.)
2. Not supported firmware in master controller
tab troller
4. Wrong settings o in master controller
g connectio
Direct RS232 connection
HW module: IL-NT-RS232

Master controller settings: ControllerAddr = 1..32
COM1 Mode = DIRECT

Up to 2 meters: Recommended to use our standard AT-LINK cable.

controller, if they are us
remote displays to one communication line, eg. RS485. It is possible to monitor only one ma
controller from one remote display at the time.
Remote display after power on automaticaly starts to search for any master controller c
starts to search on COM1 from master controllers address 1 to 32 and later on COM2 from a

During this process is displayed text
100%. This process takes ap
again until compatible maste

Not supported types of contro
comunicating are skipped dur
o troller type selection
L-NT-RD automatically detects controller typ
roubles with connection
There are few reasons why re
1. N t s rt
3. Configuration le error in master con
f setpoint COMx Mode
5. Wron n, wiring, communication fail


InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 86
IA-NT- PWR-2.0-Reference Guide.pdf
Up to 10 meters: r local
the three wires
communication:
L-NT/ID-Lite connector (D-SUB9 fem IL-NT-RD connector (D-SUB9 female)
Recommended to use standard Null-modem cable fo
connection between controller and remote display, although
(TxD, RxD, GND) RS 232 connection is enough for direct

IA-NT/I ale)
RxD 2 3 TxD
TxD 3 2 RxD
GND 5 5 GND
Remote RS485 and/or direct RS232 connection
HW module: IL-NT-RS232-485
Up to 1000 meters (only with RS485):



Case 1) RS232 / Master controller settings:
ControllerAddr = 1..32
ECT

COM2 Mode = DIRECT

Case 3) 32 + RS485 / Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
COM2 Mode = DIRECT

It is possible to make a RS232 direct connection with IL-NT-RS232 module on one side and IL-NT-
RS232-485 module on the other side.
COM1 Mode = DIR
Case 2) RS485 / Master controller settings:
ControllerAddr = 1..32
RS2

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 87
IA-NT- PWR-2.0-Reference Guide.pdf
ion using external RS232-RS422/485 converter:
485 bus
0 or 56000 bps.
Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR
.
Alternative connect
Recommend external converter:
ADVANTECH ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS
supervision, no external data flow control signals, galvanic isolated, baud rate 3840

connected) after switch on
Function description
Remote display IL-NT-RD works as remote display and control of the master Inte
InteliDrive Lite controller. It is supposed and highly recommended that both, remote
master are using the same HW type and model of controller. Another types and models of mast
remote display are not supported nor tested. All remote display
liATS
NT
, InteliLite
NT
or
display and
er and
s LEDs show the same state as
ork in the same
ontroller. User can
s, set password, change setpoints and view history records.
All IL-NT-RD screens Init, Measure, Setpoints and History display the same data like in the master
Interruption of the serial line between master device and Remote display has no effect to the master
unication cannot be
Ds are off.
nfiguration table

After the configuration from master is downloaded remote display jump to master controllers Init
and blinking.
en to check its version and serial number of used
essing PAGE button for 3 seconds.
SW compatibility
corresponding LEDs on master controller. Front panel buttons on both controllers w
way. Genset/Engine can be controlled from remote display as well as from master c
switch screen

controller.

Master device is always able to work without connected Remote display.

controller.

If the serial line between master device and remote display is interrupted, or comm
established, remote display shows its Init screen and message Trying and all LE

Once remote display finds compatible master it shows Preparing and downloads co
from master controller.
screen and all LEDs

It is possible to switch to remote displays Init scre
controller and communication status by pr

IL-NT-RD sw. version 1.0 is compatible with masters SW:

All InteliATS
NT
standard software from ver. 1.0
All InteliLite
NT
standard software from ver. 1.1
All ID-Lite standard software from ver. 1.0
Chosen InteliATS
NT
, InteliLite
NT
and ID-Lite customer branches

Some of the future InteliATS
NT
, InteliLite
NT
, ID-Lite versions may require upgrade of the IL-NT-RD
software.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 88
IA-NT- PWR-2.0-Reference Guide.pdf
e Maintenanc
Backup battery replacement

The internal backup battery should be replaced approx. every 5-7 years. Replace the battery, if the
1. Disconnect all terminals from the controller and remove the controller from the switchboard.
2. Release the rear cover using a flat screwdriver or another suitable tool.
alarm Low BackupBatt occurs. Follow these instructions:

3. Remove all plug-in modules.
4. The battery is located in a holder on the circuit board. Remove the old battery with a small
sharp screwdriver and push with a finger the new battery into the holder. Use only CR1225
lithium battery.

5. Put the rear cover back. Use slight pressure to lock the snaps into the housing. Pay attention
that the cover is in correct position and not upside down!
6. Plug the modules back into the slots.
7. Power the controller on, adjust date and time and check all setpoints.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 89
IA-NT- PWR-2.0-Reference Guide.pdf
ta
Inputs/Outputs overview
Technical Da
Model BIN BOUT COM1 COM2
Gen
Voltage
Mains
Voltage
Gen.
Current
.
IA-NT PWR 7 7 Y* Y* Y Y Y

NOTE:
* With optional plug-in module
Y -Available
N -Not available

Power supply

Voltage supply 8-36V DC
Consumption 40-430mA depend on supply voltage and

Consumption depends on supply voltage 0,104A at 8VDC
,051A at 24VDC
0,044A at 30VDC
36VDC
p-out: 100ms from min. 10V, return to min. 8V
ent tolerance 2 % at 24V

temperature
0,080A at 12VDC
0

0,040A at

Allowed supply voltage dro
Battery voltage measurem
NOTE:
For the supply voltage less than 7V the backlight of the display is switched off.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Operating conditions

ing temperature IA-NT
o
C Operat -20.+70
Storage r temperatu e
o
C
Humidity 95% without condensation
EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94, EN 50081-2:96
:99, EN 50082-2:97
- 25 Hz, 1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s
2

Dimensions and weight
-30.+80
Protection front panel IP65
Standard conformity
Low Voltage Directive
EN 50082-1
Vibration 5

Dimensions 180x120x55mm
Weight 450g

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 90
IA-NT- PWR-2.0-Reference Guide.pdf
Mains and generator

Nominal frequency 50-60Hz
urement tolerance 0,2Hz
t current (from CT)
se (In=5A)
A
ent tolerance 2% from the Nominal current
150 A / 1s
ral
phase to phase
ral
ase to phase
0.6 M phase to phase
0.3 M phase to neutral
ent tolerance 2 % from the Nominal voltage
ss III / 2 (EN61010)
Frequency meas
Current inputs
Nominal inpu 5 A
Load (CT output impedanc < 0,1
< 0,2 VA per pha
e)
CT input burden
Max. measured current from CT 10
Current measurem
Max. peak current from CT
Max. continuous cur 12 A rent
Voltage inputs
C phase to neut Measuring voltage range 0 277 VA
0 480 VAC
Maximal measured voltage 340 VAC phase to neut
600 VAC ph
Input resistance

Voltage measurem
Overvoltage cla
Binary inputs and outputs

Binary inputs
Number of inputs 7
4,2 k
36 VDC

Max voltage level for open contact indication 8-36 V
7
A
6 VDC
Input resistance
Input range 0-
Switching voltage level for close contact indication 0-2 V
Binary open collector outputs
Number of outputs
Maximum current 0,5
Maximum switching voltage 3
IL-NT RS232 interface (optional card)

Plugs into IA-NT controller COMMUNICATION MODULE port.
.4kBd Analog
4520: RS232 to RS422/485 converter, DIN rail, automatic RS485 bus
supervision, no external data flow control sign vanic isolated.

Recomm ed internal converter:
ADVANTECH PCL-745B or PCL745S: Dual port RS422/485 Interface card, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated


Maximal distance 10m
Maximum Speed Up to 57.6 kBd (DIRECT), 38
modem, 9.6 kBd digital modem, 57.6 kBd (MODBUS)

Recommend external converter:
ADVANTECH ADAM
als, gal
end
NOTE:
For details on all IA-NT extension and communication modules see IL-NT, IC-NT, IA-NT, ID-Lite-
Accessory Modules manual.

InteliATS
NT
PWR, SW version 2.0, ComAp June 2010 91
IA-NT- PWR-2.0-Reference Guide.pdf
IL-NT RS232-485 interface (optional card)

Plugs into IA-NT controller COMMUNICATION MODULE port.

Maximal distance 10m (RS232), 1200m (RS485)
Maximum Speed Up to 57.6 kBd (DIRECT), 38.4kBd Analog
BUS)
d)
modem, 9.6 kBd digital modem, 57.6 kBd (MOD
IL-NT S-USB interface (optional car

Plugs into IA- o M A MODULE port.

NT c ntroller COM UNIC TION
Up to 57.6 kBd (DIRECT), 38.4kBd Analog
ital modem, 57.6 kBd (MODBUS)
Use only shielded A-B USB cables up to 5m length.
USB-LINK CABLE 1.8M ComAp A-B USB cable.
Maximal distance 5m
Maximum Speed
modem, 9.6 kBd dig


Recommend USB cable:
IB-Lite interface (optional card)

Plugs into IA-NT controller COMMUNICATION MODULE port.
J45 (10baseT)
erature -30..+70
o
C
o
C
IO8 extension module (optional card)

Interface to Ethernet R
Operating temp
Storage temperature -30..+70
IL-NT B
Technical details:
al nfig inary inputs or outputs.
ts 8
4.7 k
0-36 VDC
contact indication (Logical 1) < 0.8 VDC
tage level for open contact indication (Logical 0) > 2 VDC
indication 8-36 VDC
Binary open collector outputs
Number of outputs 8
Maximum current per pin 0.5 A
Maximum switching common current 2 A
Maximum switching voltage 36 VDC
IL-NT BIO8 plugs into the controllers EXTENSION MODULE port.
8 dedicated pins of the plug-in cards r can be co te min ured as b
Binary inputs
Number of inpu
Input resistance
Input range
Voltage level for close
Vol
Max voltage level for open contact
HINT:
Binary inputs are not galvanically isolated.

You might also like