New Zealand/Energy/Electric Utility Cables/MV XLPe/6.

35 - 11kV/Copper Tape/Copper Conductors/3C Cu 11kV CTS SWA





































Conductor Bending Radius
mm
2
No of strands
Nominal
Overall
Diameter

mm
Approximate
Mass


Kg/km
Minimum
Installed

mm
Minimum
During
Installation
mm
16 7 47.7 3100 720 1200
25 7 51.8 4100 780 1300
35 7 53.9 4500 810 1350
50 19 56.7 5100 860 1420
70 19 60.8 6100 920 1520
95 19 64.2 7200 970 1610
120 19 68.2 8200 1030 1710
150 19 71.7 9300 1080 1800
185 37 77.2 11700 1160 1930
240 37 83.1 14000 1250 2080
300 37 88.9 16300 1340 2230

Listed diameter, mass and bending radii are for PVC/HDPE Composite Sheath.
Bending radius based on 25x OD (during installation) and 15x OD (installed) for PVC/HDPE sheath.
Bending radius may be lowered to 18x OD (during installation) and 12x OD (installed) for PVC sheath.

Lengths and packing can be supplied to customers requirements.
For glanding details, contact your local service centre.
NB: Stranding in compacted conductors may be subject to minor variations.
6.35/11kV
COPPER XLPE 3C SWA
COPPER TAPE SCREEN
APPLICATION

Primary supply to urban networks.

PVC/HDPE suitable for installation direct buried or unenclosed
where subject to mechanical damage.

Suitable for glanding.

Copper Tape Screen For use where fault currents less than
light duty screen occur e.g resistance earthed systems

STANDARD IEC 60502.2

VOLTAGE 6350/11000V

CONDUCTOR Compacted Annealed
Copper

INSULATION TR-XLPE
Numbered Cores

SCREEN Copper Tape

BEDDING PVC, ST2

ARMOUR Galvanised Steel Wire

SHEATH PVC, ST2 or
PVC, ST2 / HDPE, ST7

MAX. OPERATING TEMP. 90 C
New Zealand/Energy/Electric Utility Cables/MV XLPe/6.35 - 11kV/Copper Tape/Copper Conductors/3C Cu 11kV CTS SWA
















Diagrams of cables are illustrative only and are not necessarily to scale.

General Cable New Zealand Limited reserves the right to change or vary the construction of any of their products without notice. Whilst every care has been taken in the preparation of this publication, General Cable
New Zealand Limited accepts no liability of any kind and are not responsible for the results of any actions taken on the basis of this information or resulting from errors or omissions. This technical data sheet is
intended as a guide only; any person using it must make reference to the appropriate local standards or authorities. All rights reserved. No part of this work covered by copyright may be reproduced or copied in any
form or by any means without the written permission of General Cable New Zealand Limited.
General Cable New Zealand Ltd
HEAD OFFICE
75-89 Main South Rd
PO Box 8044
Riccarton
Christchurch
Ph: (03) 348 5199
Fax: (03) 348 2009
Website: www.generalcable.co.nz
Auckland Service Centre
14-18 Vestey Drive
PO Box 22-160
Otahuhu
Auckland
Ph: (09) 276 1020
Fax: (09) 276 1028
South Island Customer Services
75-89 Main South Rd
PO Box 8044
Riccarton
Christchurch
Ph: (03) 341 3500
Fax: (03) 341 0844
Free Fax (Orders): 0800 242 267
Wellington Service Centre
22 Barnes St
PO Box 38-271
Petone
Wellington
Ph: 0800 222-537
Ph: 0800 CABLES
Fax: 0800 242-267

CONDUCTOR CURRENT RATING (a) ELECTRICAL CHARACTERISTICS
Nominal Area





mm
Unenclosed
In Air




A
Buried
Direct




A
Buried In
Ducts




A
Max. DC
Resistance
@ 20C



ohm/km
Max. AC
Resistance
@ 90C



ohm/km
Equivalent Star
Reactance




ohm/km
Capacitance





F/km
3 Phase
Voltage
Drop



mV/A.m
16 113 123 105 1.15 1.47 0.137 0.20 2.56
25 141 153 138 0.727 0.927 0.126 0.22 1.62
35 171 185 166 0.524 0.668 0.117 0.24 1.18
50 215 229 200 0.387 0.494 0.112 0.27 0.88
70 263 278 238 0.268 0.342 0.106 0.30 0.62
95 318 324 282 0.193 0.247 0.100 0.34 0.46
120 366 371 321 0.153 0.196 0.0969 0.37 0.38
150 419 414 365 0.124 0.159 0.0943 0.40 0.32
185 478 469 409 0.0991 0.127 0.0914 0.43 0.27
240 556 534 470 0.0754 0.0986 0.0882 0.48 0.23
300 639 608 533 0.0601 0.0798 0.0858 0.53 0.20


CONDUCTOR ELECTRICAL CHARACTERISTICS (CONT.)
1 Sec Fault Rating (b)


Nom. Area


mm
3 Phase
Symmetrical
kA
Screen

kA
Max. Stress


kV/mm

16 2.3 0.8 2.4
25 3.6 1.9 2.2
35 5.0 2.0 2.1
50 7.2 2.1 2.0
70 10.0 2.3 1.9
95 13.6 2.5 1.9
120 17.2 2.7 1.8
150 21.5 2.8 1.8
185 26.5 3.0 1.7
240 34.3 3.3 1.7
300 42.9 3.6 1.6

(a)- Based on 30C ambient air temperature and where applicable,
burial depth of 0.8m, soil temperature of 15C and thermal resistivity
of 1.2Cm/W.

(b)- For fault durations other than one second, divide the appropriate
given value by the square root of the required time (in seconds).

Screen fault ratings are based on an initial temperature of 80C and a
final temperature of 250C.

Conductor fault ratings are based on an initial temperature of 90C
and a final temperature of 250C.

CONDUCTOR SCREEN Armour
Nominal Area


mm
2

Nominal
Diameter

mm
Min.Average
Insulation
Thickness
mm
Nominal Diameter
over
Insulation Screen
mm
Copper Tape
(Helically applied)
Nominal Area
Total 3 Cores

mm
2

Wire Size


mm
16 4.9 3.4 15.7 1 x 0.08mm 11.9 2.0
25 6.0 3.4 16.8 1 x 0.08mm 12.7 2.5
35 7.0 3.4 17.8 1 x 0.08mm 13.4 2.5
50 8.1 3.4 18.9 1 x 0.08mm 14.3 2.5
70 9.8 3.4 20.6 1 x 0.08mm 15.6 2.5
95 11.4 3.4 22.2 1 x 0.08mm 16.8 2.5
120 12.9 3.4 23.7 1 x 0.08mm 17.9 2.5
150 14.3 3.4 25.1 1 x 0.08mm 19.0 2.5
185 16.0 3.4 26.8 1 x 0.08mm 20.2 3.15
240 18.4 3.4 29.2 1 x 0.08mm 22.1 3.15
300 20.8 3.4 31.6 1 x 0.08mm 23.9 3.15