BHAVNAGAR ENERGY COMPANY LIMITED,

GANDHINAGAR

FINAL REPORT
Geotechnical Investigation work for proposed 2 x 250 MW Lignite
Based Thermal Power Plant in Padva Village, Tal: Ghogha,
Dist: Bhavnagar, State: Gujarat,

VOLUME I


















M.K. Soil Testing Laboratory
AHMEDABAD 380 0051.
EMAIL: mkslab@gmail.com, info@mksoil.com
* 0*

M.K. Soil Testing Laboratory

C CO ON NT TE EN NT TS S


S SR R. .
N NO O. .
C CH HA AP PT TE ER R P PA AG GE E
N NO O. .
1. I nt r oduct i on. 1- 2
2. Fi el d I nvest i gat i on 3 11
3. Labor at or y Test 12 14
4. Di scussi on and Recommendat i ons 15 60
4. 1 Cool i ng Tower
4. 2 Reser voi r Ar ea
4. 3 Swi t ch Yar d Ar ea
4. 4 Chi mney Ar ea
4. 5 Tur bi ne Ar ea
4. 6 Boi l er Ar ea
4. 7 ESP Area
4. 8 Admi ni st r at i ve Bui l di ng
4. 9 Coal St or age Ar ea
4. 10 Li gni t e Handl i ng Uni t
15 18
19 23
24 28
29 33
34 39
40 44
45 49
50 53
54 57
58 60
5. Recommendat i ons 61 62
6. Concl usi on 63 66
7. Appendi x
Typi cal Cal cul at i on For Saf e Bear i ng Capaci t y
( Chi mney Ar ea)

67 71
8. Li st of Tabl es: -
1. Obser ved N Val ues
2. Swel l i ng Proper t i es of Soi l
3. Chemi cal Anal ysi s of Soi l
4. Chemi cal Anal ysi s of Wat er
5. Fi el d Per meabi l i t y Test ( Const ant Head Met hod)
6. Cycl i c Pl at e Load Test
7. St at i c Pl at e Load Test
8. Consol i dat i on Test
9. El ect r i cal Resi st i vi t y Test
10. Readi ng For Ground Wat er Tabl e Test
11. Soi l Char act er i st i cs For Borehol es
12. Tr i al Pi t & CBR Test Resul t

72 100
101 103
104
105
106 122
123 128
129 136
137
138 165
166 168
169 334
335 - 335
9. Dr awi ngs: -


* 1*

M.K. Soil Testing Laboratory


[ 1 ] INTRODUCTION :

Bhavnagar Energy Company Limited, Gandhinagar proposes Geotechnical
investigation work for proposed installation of 2 x 250MW Lignite Based Thermal Power Plant at
Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

1.1. Scope of Work :

The purpose of the investigations was to determine the sub soil stratification of the soil,
geotechnical information & safe bearing capacity of the soil, so as to provide information that will
assist the structural engineers in the design of the foundations and the relevant works.

The Job was carried out vide your letter no. BECL/Geotechnical-195 dated 28/02/2008
under the guidance and supervision of Tata Consultancy Engineers Engineers, the soil personels
of M. K. Soil Testing Laboratory and clients engineer. Bhavnagar Energy Company Limited,
Gandhinagar has retained the services of Tata Consulting Engineers Ltd as project
consultant.

The scope of this enquiry covers the work of Geotechnical investigations to be carried out
at proposed plant areas.
The scope of services broadly consists of the following.
1. Mobilisation of necessary equipment and personnel to carry out all the works and
demobilization after completing the work.
2. Drilling of boreholes and carrying out necessary field work such as standard
penetration tests, Field Permeability tests, Electrical resistivity tests, Plate load
tests, Cross-hole seismic tests etc. as per the specification of Tata Consulting
Engineers Ltd.
3. Conducting necessary laboratory tests.
4. Preparation and submission of detailed report including recommendations of
foundations and sketches showing generalized soil sub-soil.

The purpose, in brief of the proposed Geotechnical investigations is to ascertain the type
of sub-strata, their characteristics and their suitability for the type of foundations and sub-
structures to be adopted for the type and magnitude to envisaged loading. All the tests that are
required to be carried out for this purpose are conducted. Any additional tests required or specified
by the Engineer were carried out.

Location of boreholes and other field tests shall be as indicated in the drawing NO.
10/7/LP attached in the Appendix of the report.

* 2*

M.K. Soil Testing Laboratory



This report covers the original work order containing the data of 83 boreholes, 14Nos.
Electrical Resistivity Test, 1 Crosshole test, Cyclic Plate Load Test & Static Plate Load Test and all
the necessary laboratory tests required to furnish the details of specification.

The data of further order containing helipad & colony area will be furnished afterwards in
Vol-II.


1.2 Geology & Geomorphology:

The investigated area is situated at village Padva of Ghogha taluka. The site is about
35 Km. away from Bhavnagar and 13 Km. from Ghogha. The area is connected by road ways with
major cities of Bhavnagar district.

The investigated area is slightly undulating in nature having slope towards sea which is 4
to 5 Km. away from site area The climate of the area is tropical having three main seasons. The
maximum temperature is 44
0
C in the month of May. The average long-term rainfall of Ghogha
taluka is 499 mm. Rainfall is highest in the month of August / September. The Ground water
level of the area is observed at shallow depth, ranges between 6.0 m. to 9.0 m. at the time of
investigation.

Alluvium formation followed by weathered trap formation is observed around the
investigated area. Deccan Trap of Cretaceous to Eocene age is the oldest rock of the area. In
some areas of Ghogha taluka, Ghogha Bed comprising lime stone & conglomerate overlies Gaj
Bed.


SUB-SURFACE GEOLOGY

Geologically the investigated area is covered with alluvial formation, reddish brown, brownish
black clay, lateritic clay, sand, moram, kankar of trap particles.etc. followed by weathered rock.

* 3*

M.K. Soil Testing Laboratory

[ 2 ] FIELD INVESTIGATIONS :

Field work includes the test to be conducted on field as per relevant IS codes alongwith
the specification of Tata Consulting Engineers Ltd. as detailed below :
(1) Exploratory boreholes using suitable accessories with collection of sample as guided by
client.
(2) Conducting Standard Penetration Test (SPT) at desired intervals alongwith collection of
samples.
(3) Collecting undisturbed samples (UDS) and disturbed samples (DS) at desired interval.
(4) Excavation of trialpits
(5) Conducting static & cyclic plate load test
(6) Carrying out field permeability test (FPT) as directed by the client.
(7) Conducting Electric Resistivity tests (ERT)
(8) Conducting Wave Propagation tests / Cross hole seismic test)

2.1. Boreholes :

The field work includes drilling of total 82 nos. of borehole at the locations specified by
client. The location of borehole is indicated in the layout plan given in the Appendix of report.
Rotary calyx type drilling accessories with TC & Diamond bit was used for boring. The diameter of
the borehole was kept 150mm. The use of diamond bit was introduced with occurrence of hard
rocky strata.

Standard penetration tests were conducted as per IS:2131 in the soil strata at 1.5m
intervals upto 1.5m & 2.0m interval below GL and N values noted. The samples from the split
spoon samples were collected and treated as representative samples for laboratory tests. The
standard penetration test was terminated when the blow court is greater than 100 for 5
consecutive intervals. At some locations SPT were also conducted in weathered / soft tock with
Rock Quality Designation (RQD) less than 25%. The observed values are given vide table no. 1 in
the appendix of the report. The undisturbed samples were collected to obtain the engineering
properties of soil. Water table levels in the boreholes were monitored and recorded and the same
is given in the respective borelogs. Details of boring with soil profile, SPT values along with
sampling details are given in the respective borelogs in the appendix of the report.

2.2. Trialpits :

Total 19 nos. of trialpits were proposed as per the specification but the details of this test
will be furnished with final report.

* 4*

M.K. Soil Testing Laboratory


2.3. Plate Load Tests :

2.3.1 Static Plate Load Test :

Seven static plate load tests were conducted in accordance with IS:1888:1982 using test
plate of size 60cm x 60cm x 2.5cm (thick). The test was carried out by the reaction i.e. jacking
against a loaded platform by hydraulic jack with pressure gauge arrangements.

A ball and socket arrangement was inserted between girder and jack so as to allow the
plate to rotate while keeping the direction of load vertical throughout. The loads were applied
usually in increments of 0.5 t and were maintained up to time when the rate of settlement got
appreciably steady or to a value of 0.02 mm/min. The settlement was observed by means of two
dial gauges having least count of 0.01mm and travel of 50 mm. After attaining maximum load,
the unloading was done gradually and the test plate was allowed to rebound. When the rate of
rebound became negligible, the dial gauge readings were recorded. The observations are shown
vide table no. 7/1 to 7/8 in the Appendix of the report.

2.3.2 Cyclic Plate Load Test:-


This report includes six cyclic plate load tests conducted in accordance with IS:1888:1982
using test plate of size 60cm x 60cm x 2.5cm (thick). The test was carried out by the reaction i.e.
jacking against a loaded platform by hydraulic jack with pressure gauge arrangements.

A ball and socket arrangement was inserted between girder and jack so as to allow the
plate to rotate while keeping the direction of load vertical throughout. The loads were applied
usually in increments of 0.5 t and were maintained up to time when the rate of settlement got
appreciably steady or to a value of 0.02 mm/min. The settlement was observed by means of two
dial gauges having least count of 0.01mm and travel of 50 mm. After attaining maximum load, the
unloading was done gradually and the test plate was allowed to rebound. When the rate of
rebound became negligible, the dial gauge readings were recorded. The observations are shown
vide table no. 3/1 to 3/6 in the Appendix of the report.

The results are attached in Appendix of the report vide table no. 6/1 to 6/6







* 5*

M.K. Soil Testing Laboratory


2.4 Field Permeability Test :

Total 19Nos. of field permeability tests were conducted in soil by constant head method as
per IS:5529 (Part-I-1985).

In this method, a hole was drilled or bored up to the level at which the test is to be
performed. The casing is be sunk by drilling and driving or jetting with water and driving, whichever
gives the tightest fir to the casing in the hole. The casing is simultaneously driven as the drilling or
boring of the hole is in progress. After the required level is reached, the hole was cleaned by
means of scooping spoons and bailor. If the hole extends below ground water level, the hole
should be kept full of water while cleaning it (as otherwise, due to water pressure, soil may
squeeze into the bottom of the casing pipe) and should be cleaned by passing air under pressure
by air jetting method.

After the hole is cleaned the test was started by allowing clean water through a metering
system to maintain gravity flow at constant head. The flow was adjusted by the regulating valve in
such a way so as to obtain steady water level in the hole. In the tests above water table, a stable
constant level is rarely obtained and a surging of the level within 20 to 30mm at a constant rate of
flow for about 5 minutes may be considered satisfactory.

For measuring water level or constant water level maintained in the hole during test, the
naked point of the enameled wire of the electric probe was lowered in the hole till it touches the
water level. The observations of the water level at 5 minutes intervals were noted. When three
consecutive readings show constant values, further observations may be stopped and the
constant reading should be taken to the depth of water level. Alternatively, the water reading may
also be taken by means of soundings by masons plumb.

The observations of the test should be recorded suitably. A recommended proforma for
the record of results is given in Appendix of the Report vide table no. 5/1 to 5/17.

The permeability by constant head method (open-end test) should be obtained from the
following relation determined by electrical analogy experiments.

Q
K = -------------
5.5 rH


* 6*

M.K. Soil Testing Laboratory


Where
K = coefficient of permeability
Q = constant rate of flow into the hole,
r = interval radius of casing, and
H = differential head of water = H
1
(gravity head) H
1
(head loss due to friction)

2.5 Electric Resistivity Test :

The resistivity survey is conducted as per the specification an locations are shown in
location plan. In the geophysical resistivity survey wenner configuration method is used. The main
aim of the present survey is to know engineering properties of the formation and its resistivity at
different depth.

In the wenner four pin method, four electrodes are driven into the earth along a straight
line at equal interval. Current I is passed through the two outer electrodes and the voltage
difference V is observed between the two inner electrodes. The current I flowing into the earth
produces an electric proportional to its density and to the resistivity of the soil. The voltage V
measured between the inner electrodes is therefore, proportional to the field condition. Resistivity
thus will be proportional to the ratio of the voltage to the current.
P
=
2 II S V Ohm.m
I

Where P = Resistivity of soil in Ohm.m.

S = Distance between two electrodes in m.

V = Voltage in milli volt.

I = Current in milli Ampere.

At the selected point in the chosen direction i.e. North South, North East South West,
North West South East and East West, four electrodes are driven into the earth up to required
depth along a straight line at equal intervals. The D.C. resistivity meter is placed in the steady and
level base. The current and potential electrodes are connected to the instrument terminals. By
passing current from the battery box, readings are taken and tabulated in the table. The plotting of
resistivity data are plotted on the double log graph paper and the resistivity of different layers with
its thickness is calculated with the help of master curves.

In the investigated area at premark location total 14 vertical electrical sounding (V.E.S.) /
E.R.T. are conducted near boreholes. The resistivity of the sub-surface layers of all the sites is
calculated and data are tabulated in the Table No. 9/1 to 9/14. Plotting of resistivity data is shown
in the drg. No. 10/7/ERT.
* 7*

M.K. Soil Testing Laboratory



2.6 Wave Propogation Test (Cross hole seismic survey) :

The purpose of geophysical investigations cross-hole seismic survey was to measure P
and S wave velocities to determine the dynamic elastic properties of the subsurface strata. The
scope of work includes cross-hole seismic tests at proposed location. Recordings were to be made
at eight (8) levels up to a depth of 14 m using three collinear boreholes spaced at 3.26m and 3.55
m respectively. Recordings were taken at 1m, 3m, 5m, 7m, 9m, 11m, 13m and 14m.

CROSS-HOLE SURVEY


1. Basic Principle of Cross-Hole Seismic method:

There are two borehole seismic techniques in common use which include cross-hole and
down-hole methods. In horizontal or sub-horizontal strata, cross-hole surveying is more sensitive
in response to the change in soil or rock layers than the down-hole surveying. In cross-hole survey
is more effective in detecting an individual higher or lower velocity band and provide information of
the medium between boreholes.

The crosshole seismic test consists of generation of horizontally traveling P and S waves
at a particular level in one borehole (source hole) and recording their arrivals at same level in two
nearby collinear boreholes (receiving holes). Two receiving holes are preferred for timing accuracy
when true zero time could not be measured. The data recording would be started from the bottom
of the borehole at desired interval upward.

The basic data acquisition system consists of the following:

The following recording parameters were used in the present survey.

RECORDING SYSTEM Galileo (BISON Make) 24-CHANNEL SEISMOGRAPH
Main Features 18 bit A/D converter.
IFP amplifier, 126 dB dynamic range.
Selectable sampling rate of 31.25 s to 500 s.
Selectable record length of 16 to 1024 samples.
Frequency range of 3 to 2000 Hz.
Selectable Lowcut, Highcut, Notch filters and automatic
anti-aliasig setting.
Recording Range 64 msec
Sampling Rate 125 s
Filters Off
RECEIVER:
Downhole Sonde
3-component downhole sensor with Pneumatic clamping.
High-pressure pump.
SEISMIC SOURCE Borehole Hammer (BISON)

* 8*

M.K. Soil Testing Laboratory

In present study BISON borehole hammer was used as seismic source in source borehole
at desired depths. Total length of this source is 1.2 m with a clamping and impact device at the
center. It further needs 40 cm (approx.) clearance below it for free fall of the weight attached to the
body for downward polarization of shear wave.

2. Receivers :

The receivers used in this crosshole test have appropriate frequency of 10 Hz and
sensitivity characteristics to determine the seismic wave train arrival. The receiving unit consists of
three geophones combined orthogonally to form a triaxial array that is, one vertical and two
horizontal geophones mounted at right angle. In this triaxial arrangement, the vertical component
will be used for S-wave arrival determination and horizontal will be used for P-wave arrival
determination. All the geophones are housed in a single cylindrical container (probe) having
diameter of 75mm and length 30cm. An inflated rubber bladder attached with the borehole
geophone probe was used to hold the probe in firm contact with the sidewall of the borehole.
Battery operated Motorized compressor was used to inflate the bladder for clamping.

3. Recording System:

General layout plan of source and receiver holes is shown in location plan and a
schematic diagram of cross-hole test procedure is shown in Figure.

Fig. 2 Schematic Diagram of Seismic Crosshole Test Procedure


* 9*

M.K. Soil Testing Laboratory


The recording was made using Galileo (BISON Make) a signal enhancement digital
seismograph. The timing accuracy was made for true zero time by using a Triggering device
attached to the borehole hammer. No filters were applied during data acquisition. The hard copy
prints of the records were taken and saved in hard disc for further processing and interpretation.

Borehole Preparation:

The specifications for borehole preparation are given below:
The preferred method for preparing boreholes for cross hole test incorporates three
collinear boreholes spaced 3 to 5 m apart in a straight line, center-to-center on the ground surface.
In present case source hole to first receiver hole distance was 3.26m and first receiver to second
receiver hole distance was 3.55m. 100 mm boreholes were drilled and 90mm ID PVC casing was
used. The annular space between the casing and the borehole sidewall was filled with grout
mixture using injection grouting. The grout mixture was formulated to approximate closely the
density of surrounding in situ material after consolidation.

A constant center-to-center spacing from top to the bottom of the holes was maintained.
Any minor deviation from verticality of boreholes would result in obtaining ambiguous seismic
velocities and dynamic soil parameters. If the boreholes are not vertical in that case a borehole
deviation survey is to be conducted in all the three-crosshole borings with an instrument capable of
measuring the precise vertical alignment of each hole. Cased and properly grouted boreholes are
essential ensure good quality of data which is to be provided by the client.

4. Data Reduction And Interpretation:

Polarized shear wave trains were added to identify the shear wave arrivals. Fig. 3 shows
the arrival of P & S-waves. Polarised shear waves were stacked for clear identification of S-wave
arrival.

Fig. 3 Polarized Shear Wave for identification of S-wave

* 10*

M.K. Soil Testing Laboratory


The traces recorded on vertical components were used to determine the travel times of S
waves (Shear Wave) and the traces recorded on the horizontal components were used to
determine the travel times of P-Waves (Compressional Wave). The average velocities for P and S
waves were determined by dividing the distance between source and receiver by their
corresponding travel times at each depth.

Precautions were taken during borehole drilling to keep the boreholes vertical and no
borehole deviation survey was required. Therefore, no correction for borehole deviation was
applied on raw data.

As the time taken by P & S waves through the pipe wall (5mm thick) is negligible as
compare to the time taken by P & S waves from source to receivers. Therefore, no correction is
required for PVC casing and same was not applied on raw data.

2.7 Ground Water Observations :

The depth at which ground water is struck during boring is carefully noted and the depth of
water table has to be ascertained subsequently in the completed borehole by daily observing the
depth for the next six to seven days. Depth of ground water should be observed in wells, if wells
exist in the vicinity. The minimum and maximum ground-water levels should be obtained from local
sources and wells in the area.

The fluctuation in ground water table was noted in order to ascertain the directions of the
natural drainage, and to obtain a clue to the design of intercepting drains to prevent the influx of
ground water on to the site from higher ground. The seasonal variation in the level of water table
its to be noted.

The methods adopted for determining the ground water table in bore holes is as per
IS:6935 and as per the instructions of the Engineer.

In case any variation in the ground water level is observed in any specific boreholes, then
the water level in these bore holes it is recorded daily during the course of the field investigation.
Level in nearby wells, streams, etc if any, shall be noted whenever these readings are taken.





* 11*

M.K. Soil Testing Laboratory


2.7.1 Piezometer / Stand pipe Method :

If so called for, observation wells should be drilled for the purpose of long term studies of
the fluctuation in ground water levels and pressure. A stand pipe of PIezometer were installed in
selected previously drilled or specially drilled bore holes covering bore holes covering the
complete site area. These were be at specified depths as per the specifications and instructions of
the Engineer.

Daily water level readings were recorded immediately following the installations upto the
time of leaving the site. At the end of field work, these installations are to be handed over in
satisfactory working condition to the Engineer without disturbing their position so that the owner
can continue further observations. It is important to install some stand pipes and piezometers prior
to the coming monsoon, in order to record the local effects and variations in the ground water level
during the period.

2.7.2 Piezometer :

Piezometer shall be installed to measure the pore pressures in soil with medium to low
permeability. Piezometers consists of a porous filter attached to the bottom of the UPVC tubing.
The filter is 300mm length and is placed in the bore hole and sealed at top and bottom by grouting.
Hydraulic Plezometers with double line to be used to remove the air trapped in the system.
























* 12*

M.K. Soil Testing Laboratory


[ 3 ] LABORATORY TESTS :

Soil samples (disturbed & undisturbed) collected from boreholes were tested for their
physical and engineering properties & shown vide table no. 2 in the appendix of the report..

3.1 Moisture Content :

Natural moisture content of the soil samples was determined from the collected disturbed
samples using oven drying method, as per IS:2720 (Part II)

3.2 Atterberg Limit Tests :

Atterberg limit tests were conducted on the samples collected from the cohesive layer to
determine the liquid and plastic limits, as per IS: 2720 (Part V).

3.3 Grainsize Analysis :

Grain size analysis by sieve was conducted on selected samples to determine the grain
size distribution. Hydrometer tests were conducted to determine the percentage of clay and silt
fractions in cohesive layers, as per IS:2720 (Part IV).

3.4 Specific Gravity Test :

Specific gravity of the soil grains was determined using specific gravity bottles as per IS:2720
(Part III).

3.5 Direct Shear Test :

Direct shear tests were conducted on the undisturbed samples collected from boreholes
as per IS:2720 (Part XIII).

3.6 Triaxial Shear Test :

Unconsolidated and undrained triaxial shear tests were conducted on the undisturbed
samples collected from boreholes, as per IS:2720 (Part XI) to arrive at the C and values.

3.7 Consolidation Test:-

Consolidation tests were conducted on the undisturbed sample collected from boreholes,
as per IS:2720 (Part XV). The e-log P curves along with compression index, various consolidation
parameters like Cv, mv av etc. are given in the Appendix of the report.



* 13*

M.K. Soil Testing Laboratory



3.8 Free Swell Index and Swelling Pressure Test:-

These tests are useful for finding swelling characteristics & are conducted as per IS: 2720
Part: 40 & 41 and are tabulated vide table No. 2 in the Appendix of the Report.


3.9 Laboratory testing on Rock samples:

The laboratory testing of rock samples was started after visually inspecting the rock cores.
Following laboratory tests were carried out for determine the physical properties of rock samples.

(a) Water absorption & Porosity
(b) Density of rock
(c) Crushing / Compressive strength of rock
(d) Point load index

For conducting tests the rock specimens were prepared in accordance with IS:9179 using
heavy rigid machine with clamping devise for holding the sample. Electrical overload breakers
were used to prevent the possible damage due to overload, clean water was used for flushing &
cooling machines.

a. Water absorption & Porosity :


Water absorption (W.A.) test was conducted by saturating the rock specimen in water for
atleast 24 hrs & noting the difference in oven dry weight.

Saturated wt wt of oven dry sample
W.A. = ----------------------------------------------- x 100
Oven dry wt.


b. Density :

Density is calculated taking the physical dimension (viz. length, height & dia) & weight

Weight
Density = --------------- (g/Cc)
Volume







* 14*

M.K. Soil Testing Laboratory


c. Unconfined compressive strength of rock :


Unconfined compressive strength of rock is determined in accordance IS:9143. A loading
machine at sufficient capacity & applying load at required rate was used for this test. The
specimen tested was kept with a moisture content as close to field condition as far as possible.
The length to diameter ratio was kept as 2 & if not possible, correction was applied taking
slenderness standard ratio as 2.

The specimen was kept between two bearing plates wiped clean. The axis was aligned
with the centre of the thrust of the cylindrical seat. A load was applied at a constant rate. The
maximum load was recorded with accuracy causing the failure.

Load at failure
Compressive Strength = -------------------------------- (kg/cm
2
)
Cross sectional area











* 15*

M.K. Soil Testing Laboratory


[ 4 ] DISCUSSION AND RECOMMENDATION :

The whole area under this section is divided as per the field & laboratory data conducted for
different structures like,
Sr.
No.
Description Borehole No.
1. Cooling tower area

BH No. : 50, 51, 52, 47, 48, 49, 64 SPLT : 8 & 9
2. Reservation area BH No. : 74,75,79,80, FPT : 6, 8, 9, 10, 11 ,12
TP No. : 15,16 & TP-17
3. Switchyard area BH No. : 76, 77, 78, 71, 72, 73, 81, 82, 83
SPLT No. : 4, 5, 6, 7 ERT : 6,7,8,9,10,11,12 13 & 14)
4. Chimney area

BH No. : 30, 31, SPLT : 1
5. Turbine area BH No. : 59, 60, 61, 62, 63, 65, 66, 67, 68 69, 70
CPLT : 6, 7, SPLT : 2, 3 ERT : 1 to 5
6. Boiler area

BH No. : 45, 46, 54, 55, 56, 57 CPLT : 3 & 4
7. ESP area BH No. : 33, 34, 37, 38, 39, 40, 41, CPLT : 1 & 2

8. Administrative building BH No. : 35, 36, 27, 28, 42, 43, 58, 59 FPT : 4 to 5

9. Local storage area BH No. : 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19,
20, 21, 22, 23, 24, 25, 26
10. Lignite Handling Unit BH No. : 1 to 5 FPT : 1 to 3


The Discussion of the tests along with its recommendations are discussed in following paras :

4.1 COOLING TOWER:

The location details of the field tests in this zone along with its details is shown as under:

Location

Water table details Termination details Sr.
No.
Northing

Easting
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 734.8 733.42 BH-47 46.7 15.00 31.70 50 -3.3
2 663.66 699.97 BH-48 47.47 13.40 34.07 30 17.47
3 687.54 779.47 BH-49 44.91 13.00 31.91 40 4.91
4 718.9 857.14 BH-50 47.32 8.40 38.92 35 12.32
5 728.07 932.78 BH-51 47.61 8.00 39.61 36.5 11.11
6 657.7 908.42 BH-52 47.05 7.85 39.20 30 17.05
7 628.54 815.74 BH-64 47.1 7.20 39.90 30 17.1
8 694.51 733.42 SPLT-8 46.95 - - - -
9 694.51 894.86 SPLT-9 47.32 - - - -
* 16*

M.K. Soil Testing Laboratory

4.1.1 General :

The sub-soil strata in this location is found to consist mainly of reddish grayish coloured
variegated clay with yellowish colour clay intermittent with blackish coloured compact clay. This
layer is extended upto 35m depth. Below 35m depth greenish black coloured highly weathered,
fractured rock basalt is observed in form of crushed material or small boulder like pieces. Average
water level in this zone is around 6.0m to 7.0m.

4.1.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :

Layer I :

This layer is in stiff to hard consistency with variation in N value as 19 to refusal. The
reddish clayey soil at top shows very high swelling potential. The atterbergs limits & other
laboratory tests along with its variation is shown below :
Properties :
Moisture Content (%) : 15.2 26.5
Dry Density (g/Cc) : 1.37 1.66
Grain size analysis
Gravel (%) : 00 8
Sand (%) : 5 48
Silt & Clay (%) : 52 95
Clay (%) : 25 32
Atterbergs limits
Liquid Limit : 52 78 %
Plasticity Index : 26 52%
Shrinkage Limit : 11 15 %
Shear Properties
Cohesion (kg/cm
2
) : 0.62 1.85
Angle of friction (degree) : 2 5
Consolidation Properties :
Compression Index Cc : 0.020
Co-eff. of vol. change mv : 0.0013
Co-eff. of consolidation Cv : 1.30 x 10
-3

Swelling Properties
Free Swell Index (%) : 31 82
Swelling Pressure (kg/cm
2
) : 0.58 1.66
Type of Soil : CH
* 17*

M.K. Soil Testing Laboratory


Properties :
Moisture Content (%) : 15.7
Dry Density (g/Cc) : 1.66
Grain size analysis
Gravel (%) : 8 51
Sand (%) : 24 70
Silt & Clay (%) : 19 31
Clay (%) : --
Atterbergs limits
Liquid Limit : 38 46 %
Plasticity Index : 14 22%
Shrinkage Limit : --
Shear Properties
Cohesion (kg/cm
2
) : 0.62 0.03
Angle of friction (degree) : 29.5
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SC / SM / GM


Layer II :

The subsequent layer is found to contain Greenish to reddish black coloured completely
weathered to highly weathered fractured hard & compact rock basalt with variation in CR as nil to
26% and RQD nil to 16%.

* 18*

M.K. Soil Testing Laboratory


4.1.3 Static Plate Load Test :
Two static plate load test viz. SPLT-8 and 9 were proposed to be conducted in this area.
Due to heavy rain and other site problems. SPLT-9 was not conducted till today on site.

The analysis for SPLT-8 is given as under :

The max. applied load intensity on 60cm x 60m size plate is 100 t/m
2
with maximum observed
settlement as 5.585mm. No shear or settlement failure was observed at this site.
Hence, the net safe bearing capacity for shear criterion with factor with factor of safety (fs) as 3,

100
qns = ---------- = 33.33 t/m
2
.
3

Considering settlement criterion and footing size of maximum 3m.

Sp Bp
---------- = ---------- for plate load test on clay
Sf Bf

Where,
Sf = Permissible settlement on footing = 0.025m.
Sp = Settlement on plate
Bf = Width of footing = 300cm = 3m
Bp = Width of plate = 60cm = 0.60m.

Substituting all the values
0.6
Sp = 0.025 x [ ------- ] = 0.005mm.
3

= 0.005 = 5mm. Corresponding load intensity = 91 t/m
2

Hence, allowable bearing pressure = > 91 t/m
2
.

Hence, from this test net safe bearing pressure can be considered as not less than 33 t/m
2
.

* 19*

M.K. Soil Testing Laboratory



4.1.4 Recommendation For Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square footing
1.5m x 1.5m
2.5
3.5
4.5
19
19
24
67
69
73
19
19
24
Square footing
2.0m x 2.0m
2.5
3.5
4.5
19
19
24
50
58
62
19
19
24
Square footing
3.0m x 3.0m
2.5
3.5
4.5
19
19
24
32
26
40
19
19
24
Raft foundation
6m dia
2.5
4.5
4.5
19
19
24
26
31
35
19
19
24

Note:- Permissible settlement for footing is considered as 25mm & that for raft is considered as 40mm

























* 20*

M.K. Soil Testing Laboratory


4.2 RESERVOIR AREA :

The general sub-soil profile at this location is found to consist of reddish grayish coloured,
variegated highly compact clay average water level in this section is 6.0m to 7.0m. Water loss
during drilling is observed as very low indicating low permeable stiff to hard strata.

The location details of the field tests in this zone along with its details is shown as under :

Location (m)

Water table details Termination details Sr.
No.
Northing

Easting
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 489.32 699.98 BH-74 48.37 6.80 41.57 33 15.37
2 445.22 781.63 BH-75 46.67 7.10 39.57 30 16.67
3 366.97 713.37 BH-79 48.24 6.60 41.64 30 18.24
4 366.97 829.56 BH-80 46.6 6.00 40.60 30 16.6
5 476.11 696.03 FPT-6 48.41 - - - -
6 487.53 756.86 FPT-7 47.48 - - - -
7 483.83 830.03 FPT-8 46.34 - - - -
8 435.99 764.27 FPT-9 47.04 - - - -
9 389.08 695.73 FPT-10 48.56 - - - -
10 406.05 829.73 FPT-11 46.42 - - - -
11 358.22 757.48 FPT-12 47.72 - - - -
12 482.02 765.62 TP-15 - - - - -
13 414.19 706.5 TP-16 - - - - -
14 375.82 822.6 TP-17 - - - - -













* 21*

M.K. Soil Testing Laboratory

4.2.2 Soil Stratification :

Laboratory tests conducted on soil samples collected from boreholes are discussed as below :

Layer I :

This layer is in stiff to hard consistency with variation in N value as 12 to refusal. The
reddish clayey soil at top shows very high swelling potential. The atterbergs limits & other
laboratory tests along with its variation is shown below :

Properties :
Moisture Content (%) : 14.3 21.3
Dry Density (g/Cc) : 1.32 1.65
Grain size analysis
Gravel (%) : 00 20
Sand (%) : 4 19
Silt & Clay (%) : 62 96
Clay (%) : 21 31
Atterbergs limits
Liquid Limit : 39 61 %
Plasticity Index : 14 37%
Shrinkage Limit : 11 13 %
Shear Properties
Cohesion (kg/cm
2
) : 0.50 1.25
Angle of friction (degree) : 2 9
Consolidation Properties :
Compression Index Cc : 0.017
Co-eff. of vol. change mv : 0.0014
Co-eff. of consolidation Cv : 1.54 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 39 72
Swelling Pressure (kg/cm
2
) : 0.913
Type of Soil : CI / CH






* 22*

M.K. Soil Testing Laboratory

Properties :
Moisture Content (%) : 14.3 21.3
Dry Density (g/Cc) : 1.32 1.65
Grain size analysis
Gravel (%) : 10 70
Sand (%) : 78 18
Silt & Clay (%) : 12 40
Clay (%) : -
Atterbergs limits
Liquid Limit : 40 45 %
Plasticity Index : 17 2%
Shrinkage Limit : -
Shear Properties
Cohesion (kg/cm
2
) : 0.0 0.10
Angle of friction (degree) : 28 30.5
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SM / SC / GM (occasional pocket)

4.2.3 Field Permeability Test :

Field Permeability Tests no. FPT 7,8,9,10 & 11 were conducted by constant head
method in this zone. The value of co-eff of permeability k derived from these tests is as below :
Location
BH No. East North
RL of GL
(m.) Depth K (cm/sec)
FPT-7 756.86 487.53 47.48 6.0 1.44 x 10
-3

FPT-8 830.03 483.83 46.34 4.20 1.19 x 10
-3

FPT-9 761.27 435.99 47.04 7.00 8.27 x 10
-4

FPT-10 695.73 389.08 48.17 5.50 8.42 x 10
-4

FPT-11 829.73 406.05 46.42 5.50 9.26 x 10
-4

This shows k value varies from 1.19 x 10
-3
to 9.6 x 10
-4
cm/sec indicating medium permeability.


* 23*

M.K. Soil Testing Laboratory

4.2.4 Recommendation for Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Wall footing
1.5m wide
2.5
3.5
10
13
51
58
10
13
Wall footing
2.0m wide
2.5
3.0
10
13
39
42
10
13
Wall footing
3.0m wide
2.5
3.5
10
13
26
30
10
13







































* 24*

M.K. Soil Testing Laboratory


4.3 SWITCHYARD AREA :
The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing

Easting
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 446.46 445.81 BH-71 47.07 8.85 38.22 30 17.07
2 446.46 513.81 BH-72 47.57 9.15 38.42 19 28.57
3 446.47 597.65 BH-73 51.46 15.40 36.06 30 21.46
4 387.78 445.81 BH-76 47.62 6.30 41.32 30 17.62
5 387.78 513.81 BH-77 48.12 6.65 41.47 30 18.12
6 387.79 597.65 BH-78 50.16 6.40 43.76 30 20.16
7 321.25 445.81 BH-81 48 5.85 42.15 13.5 34.5
8 321.25 513.81 BH-82 48.36 6.20 42.16 30 18.36
9 321.25 597.65 BH-83 51.25 6.40 44.85 30 21.25
10 427.59 465.33 SPLT-4 47.44 - - - -
11 427.59 580.95 SPLT -5 49.75 - - - -
12 340.62 465.34 SPLT -6 48.1 - - - -
13 340.62 580.95 SPLT -7 49.88 - - - -
14 428.74 455.14 ERT-6 47.5 - - - -
15 428.72 523.14 ERT-7 47.68 - - - -
16 428.74 597.65 ERT-8 50.57 - - - -
17 370.06 455.14 ERT-9 47.8 - - - -
18 370.04 523.14 ERT-10 48.31 - - - -
19 370.06 597.65 ERT-11 50.28 - - - -
20 333.26 455.14 ERT-12 48 - - - -
21 333.26 523.14 ERT-13 48.51 - - - -
22 333.28 597.65 ERT-14 50.9 - - - -

4.3.1 General :

The sub-soil strata in this location is found to consist mainly of reddish grayish coloured
variegated clay with yellowish colour clay intermittent with blackish coloured compact clay. This
layer is extended upto 35m depth. Below 35m depth greenish black coloured highly weathered,
fractured rock basalt is observed in form of crushed material or small boulder like pieces. Average
water level in this zone is around 8.0m to 9.0m.

* 25*

M.K. Soil Testing Laboratory

4.3.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :

Layer I :

This layer is in stiff to hard reddish consistency with variation in N value as 3 to refusal.
The reddish clayey soil at top shows very high swelling potential. The atterbergs limits & other
laboratory tests along with its variation is shown below :
Properties :
Moisture Content (%) : 9.8 23.8
Dry Density (g/Cc) : 1.33 1.71
Grain size analysis
Gravel (%) : 00 4
Sand (%) : 3 13
Silt & Clay (%) : 84 97
Clay (%) : 27 33
Atterbergs limits
Liquid Limit : 53 65 %
Plasticity Index : 25 40%
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.4 1.08
Angle of friction (degree) : 2 6
Consolidation Properties :
Compression Index Cc : 0.017
Co-eff. of vol. change mv : 0.0014 cm
2
/kg
Co-eff. of consolidation Cv : 1.54 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) :
Swelling Pressure (kg/cm
2
) : --
Type of Soil : CH







* 26*

M.K. Soil Testing Laboratory

Properties :
Moisture Content (%) : 14.5 17.7
Dry Density (g/Cc) : 1.47 1.63
Grain size analysis
Gravel (%) : 0 28
Sand (%) : 33 71
Silt & Clay (%) : 18 40
Clay (%) : -
Atterbergs limits
Liquid Limit : 44 52 %
Plasticity Index : 19 27%
Shrinkage Limit : -
Shear Properties
Cohesion (kg/cm
2
) : 0.08 0.06
Angle of friction (degree) : 28 - 29
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SM / SC

Layer II :

The subsequent layer is found to contain Greenish to reddish black coloured completely
weathered to highly weathered fractured hard & compact rock basalt with variation in CR as nil to
32% and RQD nil to 22%, except boreholes BH 71, BH 73 and BH 78 where any soils are
observed upto termination depth of 30.0m.








* 27*

M.K. Soil Testing Laboratory

4.3.3 Static Plate Load Test :

Four static plate load test viz. SPLT-4,5,6 & 7,8 and 9 were proposed to be conducted in
this area. Due to heavy rain and other site problems. SPLT-4 was not conducted till today on site.

The analysis for SPLT-7 is given as under :

The max. applied load intensity on 60cm x 60m size plate is 83.33 t/m
2
with maximum observed
settlement as 9.240mm. No shear or settlement failure was observed at this site.
Hence, the net safe bearing capacity for shear criterion with factor with factor of safety (fs) as 3,

83.33
qns = ---------- = 27.78 t/m
2
. Say 28 t/m
2
.
3

Considering settlement criterion and footing size of max. 3m.

Sp Bp
---------- = ---------- for plate load test on clay
Sf Bf

Where,
Sf = Permissible settlement on footing = 0.025m. (as required by the party)
Sp = Settlement on plate
Bf = Width of footing = 300cm = 3m
Bp = Width of plate = 60cm = 0.60m.

Substituting all the values
0.6
Sp = 0.025 x [ ------- ] = 0.005m.
3

= 0.005m = 5mm. Corresponding load intensity = 42.2 t/m
2

Hence, allowable bearing pressure = > 42 t/m
2
.

Hence, from this test net safe bearing pressure can be considered as not less than 28 t/m
2
.

The analysis of other test is also made is same manner & is listed. The graphs are shown in the
Appendix.




* 28*

M.K. Soil Testing Laboratory


Location (m)

Test No.
Northing
(m)
Easting
(m)
RL of GL
(m)
SBC from Shear
Criterion (t/m
2
)
Safe Bearing
Capacity from
Settlement Criterion
(t/m
2
)
SPLT - 5 427.59 580.95 49.75 22 67
SPLT 6 340.62 465.34 48.1 28 53
SPLT 7 340.62 580.95 49.88 28 42

4.3.4 Electrical Resistivity Test :

LOCATION RESISTIVITY ( Ohm.m. )
/ THICKNESS ( m.)
SR NO ERT
NO.
East (m) North (m) P1 / h1

P2 / h2 P3 / h3

GEOLOGY

1. 6 455.14 428.74 7.2 / 1.07 7.2 / -
2. 7 523.14 428.72 2.4 / 1.05 5.4 / -
3. 8 597.65 428.74 20.0 / 1.06 20 / 3.30 3.0 / -
4. 9 455.14 370.06 39 / 1.07 11.7 / -
5. 10 523.14 370.04 2.0 / 1.09 5.0 / -
6. 11 597.65 370.06 11.3 / 1.07 11.3 / 3.75 2.26 / -
7. 12 455.14 333.26 28 / 1.07 11.2 / -
8. 13 523.14 333.26 1.35 / 1.07 6.75 / -
9. 14 597.65 333.28 11.6 / 1.08 11.6 / 2.38 3.48 / -
Alluvial
formation,
clay, lateritic
clay kankar,
trap
particles.
moram etc.
followed by
weathered
rock.

4.3.5 Recommendation for Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square footing
1.5m x 1.5m
2.5
3.0
11
16
103
110
11
16
Square footing
2.0m x 2.0m
2.5
3.0
11
16
77
86
11
16
Square footing
3.0m x 3.0m
2.5
3.0
11
16
52
58
11
16



* 29*

M.K. Soil Testing Laboratory





4.4 CHIMNEY AREA :

The location details of the field tests in this zone along with its details is shown as under :


Location (m)

Water table details Termination details Sr.
No.
Northing

Easting
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 868.8 521.7 BH-30 44.69 10.00 34.69 30 14.69
2 868.8 578.7 BH-31 44.89 10.50 34.39 35 9.89
3 878.8 550.2 SLPT-1 44.48 - - - -

4.4.1 General :

The sub-soil strata in this location is found to consist grayish white coloured variegated
clay with yellowish coloured clay upto around 20.0m. Below 20.0m depth grayish coloured, highly
fractured weathered rock basalt is observed in form of crushed material or small boulder like
pieces. Average water level is 10m below GL.













* 30*

M.K. Soil Testing Laboratory



4.4.2 Soil Stratification :

Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :


Layer I :

This layer is in stiff to hard reddish consistency with variation in N value as 14 to 92. The
reddish clayey soil at top shows very high swelling potential. The Atterbergs limits & other
laboratory tests along with its variation is shown below :

Properties :
Moisture Content (%) : 18.5 24.3
Dry Density (g/Cc) : 1.42 1.72
Grain size analysis
Gravel (%) : 00
Sand (%) : 3 12
Silt & Clay (%) : 88 97
Clay (%) : 25 32
Atterbergs limits
Liquid Limit : 56 66 %
Plasticity Index : 26 37%
Shrinkage Limit : 11 12%
Shear Properties
Cohesion (kg/cm
2
) : 0.70 1.05
Angle of friction (degree) : 2.56
Consolidation Properties :
Compression Index Cc : 0.020
Co-eff. of vol. change mv : 0.0015 cm
2
/kg
Co-eff. of consolidation Cv : 1.43 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 60 70
Swelling Pressure (kg/cm
2
) : 1.06
Type of Soil : CH


* 31*

M.K. Soil Testing Laboratory



Properties :
Moisture Content (%) : 10.8 16.3
Dry Density (g/Cc) : 1.70 1.74
Grain size analysis
Gravel (%) : 15 28
Sand (%) : 49 63
Silt & Clay (%) : 18 27
Clay (%) :
Atterbergs limits
Liquid Limit : Non plastic
Plasticity Index : Non plastic
Shrinkage Limit : Due to conducted due to sane
Shear Properties
Cohesion (kg/cm
2
) : 0.00
Angle of friction (degree) : 32 33
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -.
Swelling Properties
Free Swell Index (%) :
Swelling Pressure (kg/cm
2
) : --
Type of Soil : SM

Layer II :

The subsequent layer is found to contain Greenish to reddish black coloured completely
weathered to highly weathered fractured hard & compact rock basalt with variation in CR as nil to
32% and RQD nil to 21%. Only in BH 31.







* 32*

M.K. Soil Testing Laboratory


4.4.3 Static Plate Load Test :

One static plate load test viz. SPLT-1 was proposed to be conducted in this area.

The analysis for SPLT-1 is given as under :

The max. applied load intensity on 60cm x 60m size plate is 66.67 t/m
2
with maximum observed
settlement as 23.765mm. No shear or settlement failure was observed at this site. But the large
settlement was observed as load increased from 24t to 30t. Looking to the nature of graph
tangents were drain to find out the failure point i.e. at 18.4t load.
Hence, the net safe bearing capacity for shear criterion with factor with factor of safety (fs) as 3,


18.4
qns = ------------- = 17 t/m
2
. (Considering load corresponding to 12.5mm settlement)
0.6 x 0.6

15.2
= ------------- = 14 t/m
2
. (By tengement method)
0.36 x 3
(Considering load 12.5mm settlement)

Considering settlement criterion and footing size of max. 3m.

Sp Bp
---------- = ---------- for plate load test on clay
Sf Bf

Where,
Sf = Permissible settlement on footing = 0.025m.
Sp = Settlement on plate
Bf = Width of footing = 300cm = 3m
Bp = Width of plate = 60cm = 0.60m.

Substituting all the values
0.6
Sp = 0.025 x [ ------- ] = 0.005m.
3

= 0.005m = 5mm
Corresponding the graph of load v/s settlement, corresponding load against 5mm settlement, is
11.6 giving load intensity 32.2 t/m
2
.
Hence, allowable bearing pressure = 32 t/m
2
.
Hence, from this test net safe bearing pressure can be considered as 17 t/m
2
.
* 33*

M.K. Soil Testing Laboratory





4.4.4 Recommendation for Net Safe Bearing Capacity :


Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
3.0m x 3.0m
3.5
4.0
19
21
46
49
19
21
Square foundation
4.0m x 4.0m
3.5
4.0
19
21
29
37
19
21
Circular raft width
6.0m
3.5
4.0
19
21
20
25
19
21

* 34*

M.K. Soil Testing Laboratory



4.5 TURBINE AREA :

The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1
600.03 444.12 BH-59 46.03 10.50 35.53 40 6.03
2 600.03 493.62 BH-60 45.95 10.70 35.25 40 5.95
3 600.03 545.15 BH-61 46.62 11.20 35.42 40 6.62
4 600.04 592.52 BH-62 48.06 10.30 37.76 30 18.06
5 601.42 644.51 BH-63 48.94 10.15 38.79 30 18.94
6 547.64 478.42 BH-65 46.68 8.10 38.58 30 16.68
7 558.42 532.35 BH-66 46.95 8.00 38.95 30 16.95
8 558.45 589.4 BH-67 48.47 8.70 39.77 40 8.47
9 513.56 485.71 BH-68 47 9.20 37.80 35 12
10 517.18 539.42 BH-69 47.39 8.90 38.49 30 17.39
11 514.54 590.33 BH-70 51.55 9.00 42.55 30 21.55
12 609.56 537.88 CPLT-6 46.65 - - - -
13 582.01 628.63 CPLT-7 49.2 - - - -
14 513.27 505.78 SLPT-2 47.25 - - - -
15 529.13 576.15 SLPT-3 48.3 - - - -
16 584.3 445.36 ERT-1 46.38 - - - -
17 584.3 546.39 ERT-2 47.15 - - - -
18 584.3 605.68 ERT-3 49.65 - - - -
19 516.2 522.71 ERT-4 47.23 - - - -
20 530.27 599.98 ERT-5 51.38 - - - -

4.5.1 General :

In general the sub-soil stratification in this zone is found to contain reddish grayish
coloured, variegated clay with intermittent bluish coloured compact clay upto 20.0m depth. Below
20m. completely weathered, fractured basalt was encountered & is recovered in crushed form.
This layer is extended upto max. 40.m depth of termination crushed form. This layer is extended
upto max. 40.0m depth of termination.


* 35*

M.K. Soil Testing Laboratory


4.5.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :

Layer I :

This layer is in stiff to hard reddish consistency with variation in N value as 5 to refusal.
Borehole No. 65 & 70 shows comparatively loose condition. The reddish soil at top very high
swelling potential. The atterbergs limits & other laboratory tests along with its variation is shown
below :
Properties :
Moisture Content (%) : 18.5 22.5
Dry Density (g/Cc) : 1.14 1.60
Grain size analysis
Gravel (%) : 00
Sand (%) : 3 30
Silt & Clay (%) : 58 98
Clay (%) : 28 34
Atterbergs limits
Liquid Limit : 43 68 %
Plasticity Index : 19 41%
Shrinkage Limit : 13 16%
Shear Properties
Cohesion (kg/cm
2
) : 0.38 0.89
Angle of friction (degree) : 2 8
Consolidation Properties :
Compression Index Cc : 0.08
Co-eff. of vol. change mv : 0.0065 cm
2
/kg
Co-eff. of consolidation Cv : 1.71 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 64 83
Swelling Pressure (kg/cm
2
) : 0.68
Type of Soil : CI/CH





* 36*

M.K. Soil Testing Laboratory


Properties :
Moisture Content (%) :
Dry Density (g/Cc) :
Grain size analysis
Gravel (%) : 00 - 58
Sand (%) : 18 71
Silt & Clay (%) : 2 48
Clay (%) :
Atterbergs limits
Liquid Limit : 40 %
Plasticity Index : 14 17%
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.02 0.06
Angle of friction (degree) : 28
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -.
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SM / SC / GM / GC

Layer II :

The underlying layer is found to contain highly to completely weathered, fractured basalt
having core recovery varying from nil to 46% & RQD as nil to 31%.









* 37*

M.K. Soil Testing Laboratory


4.5.3 Static Plate Load Test :

Four static plate load test viz. SPLT- 2 and 3 were proposed to be conducted in this area.

The analysis for SPLT-2 is given as under :

The max. applied load intensity on 60cm x 60m size plate is 83.33 t/m
2
with maximum observed
settlement as 9.605m. No shear or settlement failure was observed at this site.
Hence, the net safe bearing capacity for shear criterion with factor with factor of safety (fs) as 3,

83.33
qns = ---------- = 27.78 t/m
2
. Say 28 t/m
2
.
3

Considering settlement criterion and footing size of max. 3m.

Sp Bp
---------- = ---------- for plate load test on clay
Sf Bf

Where,
Sf = Permissible settlement on footing = 10.05m.
Sp = Settlement on plate
Bf = Width of footing = 300cm = 3m
Bp = Width of plate = 60cm = 0.60m.

Substituting all the values
0.6
Sp = 0.05 x [ ------- ] = 0.01m.
3

= 0.010m = 10mm which is greater than max. observed settlement
Hence, safe allowable bearing pressure = > 83 t/m
2
.
Hence, from this test net safe bearing pressure can be considered as greater than 28 t/m
2
.
Similarly analysis for SPLT-3 is made & as presented below :

Location

Test No.
Northing
(m)
Easting
(m)
RL of GL Depth
(m.)
SBC from
Shear Criterion
(t/m
2
)
Safe Bearing
Capacity from
Settlement Criterion
(t/m
2
)

SPLT-2 513.27 505.78 47.25 3.5 28 83
SPLT-3 529.13 576.15 48.3 3.5 28 83
* 38*

M.K. Soil Testing Laboratory



4.5.4 Cyclic Plate Load Test:-

Total two nos. of cyclic plate load tests viz. PLT-6 & 7 were conducted to find out dynamic
soil parameters. From graph of elastic settlement V/S load and in accordance with IS 5429, a
dynamic property for CPLT-7 is derived as under:-

CPLT-6 could not be conducted on site due to heavy rain & is pending

From graph of load V/S elastic settlement

*Co.eff of elastic uniform compression Cup = 10 .
0.26 x 0.36

= 106.83 Kg/cm
3


C
u
foundation having area > 10m
2
C
uf
= C
up
Ao/A1

= 106.83 x 0.6 x 0.6
10

= 20.27 Kg/cm
2


* The Elastic modulus E = (1 -
2
). A. Cu.
1.13

Where, = poisons ratio 0.47 = (1 0.47
2
). 100000 x 20.27

1.13

= 4419.4 Kg/cm
2
. Say 4410 kg/cm
2
.


*The shear modulus G = E/2(1+) = 441955___ = 1503.2 Kg/cm
2

2(1+0.47)

* Co.eff of elastic uniform shear C = Cu/2 = 10.135 Kg/cm
3

* Co.eff of elastic uniform shear C = 0.75 Cu = 15.20 Kg/cm
3

* Co.eff of elastic uniform compression C = 1.73cu = 35.06 Kg/cm
3

Hence, the dynamic shear modulus G for this sector is 1503.2 kg/cm
2
.
Elastic modulus is 4410 kg/cm
2
& Cu as 20.27 kg/cm
3
.


* 39*

M.K. Soil Testing Laboratory




4.5.5 Elastic Resistivity Test :
Total five nos. of Electrical resistivity tests viz. ERT 1 to ERT-5 were conducted at this site.
The interpreted resistivity results are tabulated below :
LOCATION RESISTIVITY ( Ohm.m. )
/ THICKNESS ( m.)
SR NO ERT
NO.
East (m.) North (m.) P1 / h1 P2 / h2 P3 / h3
GEOLOGY

1 1 445.36 584.3 10.75 / -
2 2 546.39 584.3 6.0 / -
3 3 605.68 584.3 7.05 / -
4 4 522.71 516.2 7.5 / -
5

5 599.98 530.27 11.2 / -
Alluvial
formation, clay,
lateritic clay
kankar, trap
particles.
moram etc.
followed by
weathered
rock.

4.5.6 Recommendation Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
1.5m x 1.5m
3.5
4.0
5.0
15
17
17
35
37
39
15
17
17
Square foundation
2.0m x 2.0m
3.5
4.0
5.0
15
17
17
25
27.5
30
15
17
17
Square foundation
3.0m x 3.0m
3.5
4.0
5.0
15
17
17
18
19
22
15
17
17
Circular footing
6.0m dia
3.5
4.0
5.0
15
17
17
16
22
27
15
17
17








* 40*

M.K. Soil Testing Laboratory




4.6 BOILER AREA :
The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 725.83 499.97 BH-45 45.08 11.35 33.73 40 5.08
2 725.83 599.97 BH-46 47.34 10.90 36.44 30 17.34
3 685.47 499.97 BH-54 45.76 10.30 35.46 30 15.76
4 685.47 599.97 BH-55 47.72 10.85 36.87 30 17.72
5 651.05 499.97 BH-56 45.93 9.30 36.63 30 15.93
6 651.05 599.97 BH-57 48.63 11.20 37.43 30 18.63
7 669.27 478.88 CPLT-3 45.34 - - - -
8 700.04 618.02 CPLT-4 48.01 - - - -


4.6.1 General :

In general the sub-soil stratification in mainly found to contain reddish grayish coloured
variegated loose clay upto around 10.0m depth. Below 10m, blackish coloured fine to medium
grained gravels upto 20.0m depth. Below 20m depth, grayish black coloured, highly weathered &
fractured basalt is recovered upto 30.0m depth water table is about 1.0m below GL.











* 41*

M.K. Soil Testing Laboratory



4.6.2 Soil Stratification :

Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :

Layer I :

This layer is in stiff to hard reddish consistency with variation in N value as 15 to refusal. In
this zone BH-54 shows very weak zone having silty sand with medium dense consistence. The
reddish soil at top very high swelling potential. The atterbergs limits & other laboratory tests along
with its variation is shown below :


Properties :
Moisture Content (%) : 18.3 27.7
Dry Density (g/Cc) : 1.29 1.57
Grain size analysis
Gravel (%) : 00 10
Sand (%) : 6 42
Silt & Clay (%) : 58 96
Clay (%) : 21 31
Atterbergs limits
Liquid Limit : 44 73 %
Plasticity Index : 19 45%
Shrinkage Limit : 13%
Shear Properties
Cohesion (kg/cm
2
) : 0.65 0.88
Angle of friction (degree) : 4 6
Consolidation Properties :
Compression Index Cc : 0.062
Co-eff. of vol. change mv : 0.0018 cm
2
/kg
Co-eff. of consolidation Cv : 1.62 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 54 77
Swelling Pressure (kg/cm
2
) : 0.80
Type of Soil : CH/CI

* 42*

M.K. Soil Testing Laboratory



Properties :

Moisture Content (%) : 1.47
Dry Density (g/Cc) : 2.12
Grain size analysis
Gravel (%) : 00 - 25
Sand (%) : 28 75
Silt & Clay (%) : 19 60
Clay (%) :
Atterbergs limits
Liquid Limit : Non plastic
Plasticity Index : Non plastic
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.00
Angle of friction (degree) : 28
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -.
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SM / SC / ML


Layer II :

This layer is found to contain greenish black coloured, highly fractured, weathered rock
having core recovery varying from 21 to 61% and Rock quality designation as nil to 52%.






* 43*

M.K. Soil Testing Laboratory

4.6.3 Cyclic Plate Load Test:-

Total two nos. of cyclic plate load tests viz. CPLT-3 & 4 were conducted to find out
dynamic soil parameters. From graph of elastic settlement V/S load and in accordance with IS
5429, a dynamic property for CPLT-4 is derived as under:-

From graph of load V/S elastic settlement

*Co.eff of elastic uniform compression Cup = 10 .
0.43 x 0.36

= 64.6 Kg/cm
3


C
u
foundation having area > 10m
2
C
uf
= C
up
Ao/A1
= 64.6 x 0.36
10

= 12.26 Kg/cm
2


* The Elastic modulus E = (1 -
2
). A. Cu.
1.13

* Where, = poisons ratio 0.44 = (1 0.44
2
). 10000 x 12.26

1.13

= 2573 Kg/cm
2
.


*The shear modulus G = E/2(1+) = 2573___ = 893.40 Kg/cm
2

2(1+0.44)

* Co.eff of elastic uniform shear C = Cu/2 = 6.13 Kg/cm
3

* Co.eff of elastic uniform shear C = 0.75 Cu = 9.2 Kg/cm
3

* Co.eff of elastic uniform compression C = 1.73cu = 21.21 Kg/cm
3


Similarly the all parameters are derived and summarized as under :
Location Location
North
(m.)
East
(m.)
RL
of
GL
Depth
(m)
Cu
(Kg/cm
3
C
(Kg/cm
3
C
(Kg/cm
3
C
(Kg/cm
3
Shear
modulus
G
(kg/cm
3
)
Elastic
Modulus
E (kg/cm
2
)
CPLT-3 669.27 478.88 - 3.5 17.57 8.8 30.4 13.2 1377 3963
CPLT-4 700.04 618.02 - 3.5 12.26 6.1 21.21 9.2 893 2573

From these tests, the recommended values for Boiler area are E as 3200 kg/cm
2
, Cu as 15 kg/cm
3

and G as 1135 kg/cm
2
.

* 44*

M.K. Soil Testing Laboratory

4.6.4 Recommendation for Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
2.0m x 2.0m
3.5
4.0
5.0
17
20
20
42
46
49
17
20
20
Square foundation
3.0m x 3.0m
3.5
4.0
5.0
17
20
20
34
39
44
17
20
20



* 45*

M.K. Soil Testing Laboratory

4.7 ESP AREA :
The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 818.77 513.93 BH-33 44.69 13.10 31.59 30 14.69
2 818.77 600 BH-34 45.73 15.00 30.73 30 15.73
3 805.34 485.64 BH-37 44.23 15.00 29.23 30 14.23
4 753.63 475.2 BH-38 44.61 14.85 29.76 19 25.61
5 777.8 514.01 BH-39 45.45 15.30 30.15 30 15.45
6 777.8 586.4 BH-40 46.8 15.00 31.80 30 16.8
7 777.8 625.2 BH-41 46.37 15.50 30.87 30 16.37
8 777.72 490.6 CPLT-1 44.73 - - - -
9 807.04 600 CPLT-2 45.99 - - - -


4.7.1 General :

In this zone BH-33, 40, 34 & 41 shows reddish to grayish coloured variegated clay with
expansive nature. Whereas remaining boreholes i.e. BH-38,39 & 37 shows top 15m. loose
variegated clay followed by grayish black coloured highly weathered fractured sound rock basalt.
Water table is at 15.0m below GL.











* 46*

M.K. Soil Testing Laboratory


4.7.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :

Layer I :

This layer is in stiff to hard reddish consistency with variation in N value as ---. The reddish
soil at top very high swelling potential. The atterbergs limits & other laboratory tests along with its
variation is shown below :

Properties :
Moisture Content (%) : 17.4 28.3
Dry Density (g/Cc) : 1.38 1.61
Grain size analysis
Gravel (%) : 00 14
Sand (%) : 1 17
Silt & Clay (%) : 58 99
Clay (%) : 24 34
Atterbergs limits
Liquid Limit : 55 76 %
Plasticity Index : 27 42%
Shrinkage Limit : 9 12
Shear Properties
Cohesion (kg/cm
2
) : 0.39 0.96
Angle of friction (degree) : 2 9
Consolidation Properties :
Compression Index Cc : 0.013 0.017
Co-eff. of vol. change mv : 0.0012 cm
2
/kg
Co-eff. of consolidation Cv : 9.85 x 10
-4
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 54 80
Swelling Pressure (kg/cm
2
) : 0.92
Type of Soil : CH





* 47*

M.K. Soil Testing Laboratory




Properties :
Moisture Content (%) : -
Dry Density (g/Cc) : -
Grain size analysis
Gravel (%) : 00 - 21
Sand (%) : 38 66
Silt & Clay (%) : 28 46
Clay (%) : -
Atterbergs limits
Liquid Limit : 36 52
Plasticity Index : 12 28
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : -
Angle of friction (degree) : -
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -.
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : SM / SC


Layer II :

This layer is found to contain greyish black coloured, highly fractured, weathered rock
having core recovery varying from nil to 45% and Rock quality designation as nil to 22%.






* 48*

M.K. Soil Testing Laboratory

4.7.3 Cyclic Plate Load Test:-

Total two nos. of cyclic plate load tests viz. CPLT-1 & 2 were conducted to find out
dynamic soil parameters. From graph of elastic settlement V/S load and in accordance with IS
5249, a dynamic property for CPLT-1 is derived as under:-

CPLT-6 could not be performed on site due to heavy rains.
From graph of load V/S elastic settlement

*Co.eff of elastic uniform compression Cup = 10 .x 1 .
0.36 0.48
= 57.87 Kg/cm
3



C
u
foundation having area > 10m
2
C
uf
= C
up
Ao/A1
= 67.87 x 0.6 x 0.6
10

= 10.98 Kg/cm
2


* The Elastic modulus E = (1 -
2
). A. Cu.
1.13
* Where, = poisons ratio 0.44 = (1 0.44
2
). 60 x 60 x 57.87

1.13

= 2477.86 Kg/cm
2
.


*The shear modulus G = E/2(1+) = 2477.86___ = 860.37 Kg/cm
2

2(1+ 0.44)

* Co.eff of elastic uniform shear C = Cu/2 = 5.5 Kg/cm
3

* Co.eff of elastic uniform shear C = 0.75 Cu = 8.24 Kg/cm
3

* Co.eff of elastic uniform compression C = 1.73cu = 19 Kg/cm
3

Hence, the dynamic properties for this area is recommended as Cu 10.98 kg/cm
3
. E as 2477
kg/cm
2
& G as 860 kg/cm
3
.





* 49*

M.K. Soil Testing Laboratory



4.7.4 Recommendation for Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
1.5m x 1.5m
3.5
4.0
5.0
10
18
20
60
64
68
10
18
20
Square foundation
2.0m x 2.0m
3.5
4.0
5.0
10
18
20
47
49
49
10
18
20
Square foundation
3.0m x 3.0m
3.5
4.0
5.0
10
18
20
34
39
41
10
18
20



* 50*

M.K. Soil Testing Laboratory


4.8 ADMINISTRATIVE BUILDING :
The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 845.02 207.45 BH-27 44.95 11.90 33.05 30 14.95
2 844.98 266.76 BH-28 44.98 13.00 31.98 30 14.98
3 811.97 208.8 BH-35 45.19 15.50 29.69 30 15.19
4 784.29 265.03 BH-36 4.52 14.45 -9.93 30 -25.48
5 711.96 193.85 BH-42 45.93 9.40 36.53 30 15.93
6 697.29 254.69 BH-43 45.93 10.70 35.23 30 15.93
7 632.78 398.16 BH-58 45.03 11.40 33.63 40 5.03
8 600.03 444.12 BH-59 46.03 10.50 35.53 40 6.03



4.8.1 General :

In general overall strata in this area is found to consist of brownish coloured clayey sand.
Underlained by greyish black coloured completely to highly weathered crushed fractured rock
basalt. Water table is observed at around 13m to 15m depth below GL. BH-27 is found very weak
in this zone.










* 51*

M.K. Soil Testing Laboratory

4.8.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :


Layer I :

This layer is in medium dense to dense relative density with variation in N value as 10 to
ref. The top soil in this zone is not having swelling potential. The atterbergs limits & other
laboratory tests along with its variation is shown below :


Properties :
Moisture Content (%) : 12.8 14.5
Dry Density (g/Cc) : 1.45 1.64
Grain size analysis
Gravel (%) : 00 52
Sand (%) : 16 80
Silt & Clay (%) : 19 44
Clay (%) :
Atterbergs limits
Liquid Limit : 35 42 %
Plasticity Index : 11 20%
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.00 0.09
Angle of friction (degree) : 28 29
Consolidation Properties :
Compression Index Cc :
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : --
Swelling Properties
Free Swell Index (%) :
Swelling Pressure (kg/cm
2
) : --
Type of Soil : SM/SC/GM





* 52*

M.K. Soil Testing Laboratory






Properties :
Moisture Content (%) : 17.5 29.8
Dry Density (g/Cc) : 1.41 1.55
Grain size analysis
Gravel (%) : 0.0 2.0
Sand (%) : 2 8
Silt & Clay (%) : 62 97
Clay (%) : 28 36
Atterbergs limits
Liquid Limit : 55 72
Plasticity Index : 27 38
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.52 0.70
Angle of friction (degree) : 2.5
Consolidation Properties :
Compression Index Cc : -
Co-eff. of vol. change mv : -
Co-eff. of consolidation Cv : -.
Swelling Properties
Free Swell Index (%) : -
Swelling Pressure (kg/cm
2
) : -
Type of Soil : CH

Layer II :

This layer is found to contain grayish black coloured, highly fractured, hard basalt rock
having core recovery varying from nil to 45% and Rock quality designation as nil to 36%.







* 53*

M.K. Soil Testing Laboratory


4.8.3 Recommendation for Net Safe Bearing Capacity :
Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
1.5m x 1.5m
2.0
3.0
14
22
12
17
12
17
Square foundation
2.0m x 2.0m
2.0
3.0
15
23
10
14
10
14

Note : This zone contains silty sand and for settlement use of N-value is made as per IS:8009. BH-27 is
very loose through out the drilled depth and hence should be treated carefully.

* 54*

M.K. Soil Testing Laboratory

4.9 COAL STORAGE AREA :
The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 1285.69 369.53 BH-6 42.52 12.00 30.52 30 12.52
2 1324.13 653.43 BH-7 42.25 12.15 30.10 30 12.25
3 1277.15 564.96 BH-8 40.42 11.50 28.92 30 10.42
4 1252.45 462.06 BH-9 40.3 11.75 28.55 30 10.3
5 1179.02 399.1 BH-10 41.66 12.00 29.66 30 11.66
6 1138.52 584.32 BH-11 41.85 11.60 30.25 30 11.85
7 1139.76 663.47 BH-12 45.88 11.20 34.68 30 15.88
8 1160.74 779.11 BH-13 43.26 9.30 33.96 40 3.26
9 1086.2 178.18 BH-14 44.1 14.80 29.30 30 14.1
10 1100.03 399.95 BH-15 42.44 12.20 30.24 30 12.44
11 1079.74 779.11 BH-16 44.26 8.70 35.56 40 4.26
12 1045.22 126.05 BH-17 44.62 12.10 32.52 30 14.62
13 1057.4 534.82 BH-18 43.1 9.45 33.65 30 13.1
14 1057.4 661.65 BH-19 45.83 9.00 36.83 30 15.83
15 1021.07 538.32 BH-20 43.57 9.20 34.37 30 13.57
16 964.28 178.18 BH-21 43.7 15.40 28.30 30 13.7
17 927.07 398.76 BH-22 42.15 12.10 30.05 30 12.15
18 902.48 461.67 BH-23 44.28 11.80 32.48 21 23.28
19 920.71 540.02 BH-24 44.34 10.95 33.39 40 4.34
20 936.36 642.7 BH-25 46.91 11.30 35.61 30 16.91
21 935.67 779.11 BH-26 44.78 8.50 36.28 40 4.78
22 1445.97 57.4 FPT-1 42.12 - - - -
23 1394.85 79.91 FPT-2 41.81 - - - -
24 1362.47 117.04 FPT-3 41.54 - - - -
25 1141.85 189.98 FPT-4 43.9 - - - -
26 1050.81 169.51 FPT-5 44.22 - - - -





* 55*

M.K. Soil Testing Laboratory

4.9.1 General :
The borehole No. BH-6,7,8,9,10,15,17 are found to contain blackish gravelly sand upto
5.0m depth. After 5m to 30m this location contains grayish black coloured highly weathered &
fractured basalt has water table is 11m to 12m depth below GL.
Whereas, in BH-11, 12, 13, 14, 16, 18, 19, 20, 21, 22, 23, 24, 25 & 26 are found to contain
variegated compact clay throughout the explored depth. Water table is about 12m depth below GL.
Whereas, at BH-13, 12m to 28m depth, purple coloured highly compact clay.

4.9.2 Soil Stratification :
Laboratory tests conducted on soil samples collected from boreholes are discussed as below :

Layer I :

This layer is in medium dense to very dense sand and stiff to hard consistency with
variation in N value as 10 to refusal. The reddish soil at top shows very high swelling potential. The
atterbergs limits & other laboratory tests along with its variation is shown below :
Properties :
Moisture Content (%) :
Dry Density (g/Cc) :
Grain size analysis
Gravel (%) : 2 36
Sand (%) : 44 81
Silt & Clay (%) : 12 42
Clay (%) :
Atterbergs limits
Liquid Limit : 40 73 %
Plasticity Index : 16 41%
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) :
Angle of friction (degree) :
Consolidation Properties :
Compression Index Cc :
Co-eff. of vol. change mv : --
Co-eff. of consolidation Cv : --
Swelling Properties
Free Swell Index (%) :
Swelling Pressure (kg/cm
2
) : --
Type of Soil : SM/SC/GM
* 56*

M.K. Soil Testing Laboratory



Properties :
Moisture Content (%) : 16.7 24.8
Dry Density (g/Cc) : 1.40 1.67
Grain size analysis
Gravel (%) : 0.0
Sand (%) : 3 32
Silt & Clay (%) : 66 98
Clay (%) : 22 38
Atterbergs limits
Liquid Limit : 43 114
Plasticity Index : 25 80
Shrinkage Limit : 8 10
Shear Properties
Cohesion (kg/cm
2
) : 0.55 0.99
Angle of friction (degree) : 2 8
Consolidation Properties :
Compression Index Cc : 0.016
Co-eff. of vol. change mv : 0.028 cm
2
/kg
Co-eff. of consolidation Cv : 1.13 x 10
-3
cm
2
/sec.
Swelling Properties
Free Swell Index (%) : 31 125
Swelling Pressure (kg/cm
2
) : 0.8 1.63
Type of Soil : CH / CI

Layer II :

This layer is found to contain as grayish black coloured, completely weathered to highly
weathered fractured hard rock basalt having core recovery varying from nil to 77% and Rock
quality designation as nil to 41%.








* 57*

M.K. Soil Testing Laboratory



4.9.3 Field Permeability Test :

Total five Field permeability test viz. FPT 4 and 5 were done in this zone. The analysis is
given as under :
FPT No. `Depth (m.) K value (cm/sec)
FPT-4 - Cancelled / not conducted
FPT-5 5.0 1.43 x 10
-4


K-value varying from 10
-4
cm/sec shows hard strata with medium permeability.

4.9.4 Recommendation for Net Safe Bearing Capacity :

Borehole No. Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based
on Settlement
(t/m
2
)
Recommended
Net safe bearing
capacity
(t/m
2
)
Square foundation
1.5m x 1.5m
2.0
3.0
22
30
17
22
17
19
Square foundation
2.0m x 2.0m
2.0
3.0
23
32
19
21
19
24
BH-15,6,9,23
Square foundation
3.0m x 3.0m
2.0
3.0
26
34
16
20
16
20
Square foundation
1.5m x 1.5m
2.0
3.0
11
14
48
54
11
14
Square foundation
2.0m x 2.0m
2.0
3.0
11
14
44
50
11
14
BH-7, 8, 10, 11, 12,
13, 14, 16, 17, 18,
19, 20, 21, 22, 24,
25, 26
Square foundation
3.0m x 3.0m
2.0
3.0
11
14
39
48
11
14








* 58*

M.K. Soil Testing Laboratory




4.10 LIGNITE HANDLING UNIT (L.H.U.) :

The location details of the field tests in this zone along with its details is shown as under :

Location

Water table details Termination details Sr.
No.
Northing
(m.)
Easting
(m.)
BH No. RL of GL
(m.)
Depth
(m.)
R.L.
(m.)
Depth
(m.)
R.L.
(m.)
1 1445.61 109.77 BH-1 42.1 16.00 26.10 30 12.1
2 1420.68 82.77 BH-2 42.6 16.65 25.95 30 12.6
3 1366.5 73.03 BH-3 41.08 17.00 24.08 30 11.08
4 1388.81 307.22 BH-4 41.62 12.60 29.02 30 11.62
5 1331.21 271.05 BH-5 42.26 0.00 0.00 0 0


4.10.1 General :

In general this zone is found to contain good quality of strata from 0.0 to 5.0m reddish
black coloured gravels & sand were observed. From 5.0m to 15m depth, is observed to contain
grayish red coloured highly weathered & fractured rock was encountered having core recovery 20
to 30% & rock quality designation as nil. After 15m hard & compact basalt was observed in this
area.











* 59*

M.K. Soil Testing Laboratory


4.10.2 Soil Stratification :

Laboratory tests conducted on soil samples collected from boreholes are discussed as
below :


Layer I :

This layer is in medium dense to very dense consistency with variation in N value as 20 to
refusal. The reddish soil at this location does not show swelling potential. The atterbergs limits &
other laboratory tests along with its variation is shown below :
Properties :
Moisture Content (%) : 16.8 20.3
Dry Density (g/Cc) : 1.34 1.53
Grain size analysis
Gravel (%) : 0 46
Sand (%) : 26 68
Silt & Clay (%) : 17 44
Clay (%) :
Atterbergs limits
Liquid Limit : 39 %
Plasticity Index : 17%
Shrinkage Limit :
Shear Properties
Cohesion (kg/cm
2
) : 0.02 0.05
Angle of friction (degree) : 29.5 32
Consolidation Properties :
Compression Index Cc :
Co-eff. of vol. change mv : --
Co-eff. of consolidation Cv : --
Swelling Properties
Free Swell Index (%) :
Swelling Pressure (kg/cm
2
) : --
Type of Soil : SM/SC/GM

Layer II :

This layer is found to contain grayish black coloured hard rock basalt having CR varying
from 27 to 97% and rock quality designation as nil to 95%.
* 60*

M.K. Soil Testing Laboratory


4.10.3 Field Permeability Test :
Total three Field permeability test viz. FPT 1,2 & 3 were done in this zone. The analysis
is given as under :
Location FPT No.
Northing (m.) Easting (m.)
`Depth
(m.)
K value (cm/sec)
FPT-1 1445.97 57.4 5.50 3.49 x 10
-5

FPT-2 1394.85 79.91 5.50 1.3 x 10
-4

FPT-3 1362.47 117.04 6.00 1.04 x 10
-4

Co-eff. of permeability K varies from 10
-5
to 10
-4
cm/sec indicating very hard type of strata with
medium to low permeability.

4.10.4 Recommendation for Net Safe Bearing Capacity :

Type & Size of
Footing
(m x m)
Depth Below
Ground Level
(m)
Net safe bearing
capacity
Based on Shear
(t/m
2
)
Net safe bearing
capacity based on
Settlement
(t/m
2
)
Recommended Net
safe bearing
capacity
(t/m
2
)
Square foundation
1.5m x 1.5m
1.5
2.0
3.0
18
22
30
23
28
64
18
22
30
Square foundation
2.0m x 2.0m
1.5
2.0
3.0
19
24
32
21
27
33
19
24
32
Square foundation
3.0m x 3.0m
1.5
2.0
3.0
21
26
35
19
25
30
19
25
30













* 61*

M.K. Soil Testing Laboratory




[ 5 ] RECOMMENDATIONS :

5.1.1 General :

Based on location of structures design subsurface profile are prepared for the borehole
and are furnished in Appendix I & II. The bearing capacity recommendations area made for
shallow foundation for this unit.

5.1.2 Shallow Foundation :

The soil profile resembles in a uniform nature for the whole area. The safe bearing
capacity recommendations are calculated for shallow footings for general sub soil profile.
A properly designed foundation on soil has to satisfy two limit states.

1) Limit state of collapse (i.e. Shear strength)
2) Limit state of serviceability (i.e. Settlement)

Shear Criteria :
The first criterion is depending on shear strength. The calculations are based on as TERZAGHI
bearing capacity equation as recommended by IS:6403 (with factor of safety 2.5) which takes care
of L/B ratio (shape) foundation depth etc. along with other parameters.

The intensity of loading at the base of the foundation, which would cause shear failure of the soil
support, is termed as ultimate bearing capacity (UBC).

The following para shows the calculations for ultimate bearing capacity.
UBC = C x NC x SC x dc (for clayey soil)

Safe bearing capacity (SBC) is the maximum intensity of loading that the foundation will safety
carry without the risk of shear failure of soil irrespective of any settlement that may occur. Safe
bearing capacity can be obtained by dividing the UBC with suitable factor of safety (2.5)
SBC = UBC / 2.5





* 62*

M.K. Soil Testing Laboratory

Settlement Criterion :
The intensity of loading that will cause a permissible settlement of specified settlement of the
structure is termed as allowable bearing pressure. These foundation settlements are evaluated
using IS:8009 Part 1 Cl. 9.2.2.2 and 9.2.2.3 Using consolidation data.
The settlement is calculated using the following equation,

Normally to under-consolidated clay
S = H Cc log
10
[ P
0
+ dp ]
1 + e
0
P
0

and
S = mv. dp. H for over consolidated clay


Allowable bearing capacity (ABC) is the intensity of the loading which the foundation will
carry without undergoing settlement in excess of the permissible value for the structure under
consideration but not exceeding the net safe bearing capacity (SBC). The pressure distribution
below the footing is assumed as 2 V : 1 H for estimating the settlement.

Note :
1. Depth of foundation in column (i) will be below NGL / FGL whichever is lower.
2. The above values, given in column (iv) may be increased by 25% under wind / seismic
condition.

Allowable bearing capacity (ABC) is the intensity of the loading which the foundation will
carry without undergoing settlement in excess of the permissible value for the structure under
consideration but not exceeding the net safe bearing capacity (SBC). The pressure distribution
below the footing is assumed as 2 V : 1 H for estimating the settlement.

Based on the above methods the estimated bearing capacities at different foundation
depths are tabulated below. A typical calculation for estimating the bearing capacity of shallow
foundation is given in Appendix.

* 63*

M.K. Soil Testing Laboratory

[ 6 ] CONCLUSIONS :


(6.1) The area falls in seismic earthquake zone III having zone factor 0.20 and basic
horizontal seismic co-eff at 0.04 indicating medium seismic intensity as per IS : 1893
2000.

(6.2) The primary object of this investigation is to study the sub-soil characteristics of different
locations on the site, for the economic & safe design of foundation.

(6.3) The chemical analysis of water shows chlorides and sulphate variation from 1896 mg/l to
2850 mg/l and 184.3 mg/l to 405 mg/l respectively. The ground water is not suitable for use
in plain as well as reinforced concrete, on the basis of chlorides content. On the basis
sulphate content concrete would fall in class 2 (vide table 4 . IS 456-2000), which is
recommended ordinary Portland cement with minimum cement content 330 kg/cm3 and
minimum w/c ration 0.50. Considering severe environmental exposure conditions, the
concrete cover over the reinforcements shell not be less than 50mm.

(6.4) In general the plant area shows top layer of reddish to grayish coloured clay having
bentonitic properties with high swelling potential followed by sand clay & gravels with
some pockets or layers of gravels. The underlying layer is found to contain grayish black
coloured, completely weathered to highly weathered, fractured rock basalt.

Looking to the field investigation & laboratory analysis the are following under Lignite
Handling Unit, coal storage & some portion of administrative building shows rocky area at
shallow depth indicating good bearing strata.

(6.5) Static plate load tests conducted at 3.5m depth shows no shear or settlement failure
except at SPLT-1. Hence it indicates strata having SBC varying from min. 21 to 33 t/m
2
.

(6.6) Cyclic plate load test shows no large settlements or higher elastic settlements. The value
desired for different area is as under :

Area Cu
(kg/cm
3
)
E
(kg/cm
2
)
G
(kgcm
2
)
Turbine 20.27 4410 1503
Boiler 15 3200 1135
ESP 10.98 2477 860

* 64*

M.K. Soil Testing Laboratory

(6.7) Field permeability tests conducted at depths varying from 3.0m to 7.5m depths at different
locations shows low to medium permeable strata. The k-values for different area is as
under :
Area Recommended K value
(cm/sec)
Remarks
LHU 10
-5
Low
Administrative building 10
-4
Medium to low
Reservoir 10
-3
to 10
-4
Medium

(6.8) Interpreted resistivity results of the formation varies from 1.50 ohm.m to 56 ohm.m.

(6.9) Cross hole test shows recommended values for different depths as under :
Parameters

Depth
below
ground
level (m)
Density
(gm/cc)
V
p

m/sec)
V
s

(m/sec)
Poison's Ratio Shear Modulus
(GPa)
Youngs Modulus
(GPa)
1 1.76 591 234 0.41 0.0964 0.2712
3 1.76 529 282 0.30 0.1400 0.3643
5 1.81 507 286 0.27 0.1481 0.3751
7 1.86 959 306 0.44 0.1742 0.5027
9 1.80 866 348 0.40 0.2180 0.6120
11 1.80 1267 311 0.47 0.1741 0.5111
13 1.80 1384 385 0.46 0.2668 0.7780
14 1.80 1420 382 0.46 0.2627 0.7675

The general observation from the cross hole seismic investigation indicates that the
velocities of P and S waves vary from 507 - 1420 m/sec and 234 - 385 m/sec respectively.
The value of Poisson ratio varies from 0.27 to 0.47. The value of shear modulus varies
from 0.0964 GPa to 0.2668 GPa. Youngs modulus also varies from 0.2712 GPa to 0.778
GPa.

(6.10) In general most of locations, clayey soil was prevailing and foundations should rest on
swelling type of stiff to hard clay. It is strictly recommended to provide atleast 30cm to
50cm thick layer of compacted sand rubble layer around all the embedded walls &
footings. Or otherwise CNS material as per requirements of IS code are to be used below
foundations. The specification for CNS material is as under :

* 65*

M.K. Soil Testing Laboratory




Very Broad Specifications for soil to be considered as CNS Material

Sr.
No.
Property Very Broad
Specification
Range
Grain size analysis
(i) Clay 15-25%
(II) Silt 35-50%
(iii) Sand 30-40%

1
(Iv) Gravel <10%

Consistency Limits
(i) Liquid Limit 30-50%
(II) Plastic Limit 20-25%
(iii) Plasticity Index 10-25%

2.
(Iv) Shrinkage Limit 15% and above

(a) Swelling pressure when compacted to maximum dry
density corresponding to standard Proctor compaction and
initial compaction moisture corresponding to optimum
moisture content for no volume change condition.

Less than 0.1 Kg/cm
2

(10 kN/m
2

)

3.
(b) Swelling pressure when compacted to maximum dry
density corresponding to standard Proctor compaction and
initial compaction moisture corresponding to optimum
moisture content for no volume change condition.

Less than 0.05 Kg/cm
2
( 5 kN/m
2

)
4 Clay minerals Preferable Kaolinite and illite.
5. Shear strength of compacted sample compacted to maximum
dry density correspond to standard Proctor compaction and
initial moisture content corresponding to optimum moisture
content but sample tested on saturation.
(a) From unconfined compression

(b) From consolidated undrained direct shear test.




0.15-0.35 kg/cm
2
( 15 to 35 kN/m
2

)

0.1-0.3 kg/cm
2
( 10 to 30 kN/m
2

)

8 -15






* 66*

M.K. Soil Testing Laboratory



Thickness of CNS layer Needed to Nullify the effect of Swelling Pressure of Expansive Soils

Sr. No. Swelling Pressure
of Expansive Soil Kg/cm
2
( kN/m
2

)
Thickness of CNS Soil Layer Required
cm*
1 1.0 to 1.5 (100 to 150) 75 85
2 2.0 to 3.0 (200 to 300) 90 100
3 3.5 to 5.00 (350 to 500) 105 115


It is necessary to conduct large scale tests to arrive at optimum thickness of CNS soil
layer with available soil material.

Whenever CNS layer is used, it is desirable to compact it to density of Proctor compaction
test and optimum moisture content.

It is also advisable to prevent the seepage of water and to avoid any plantation.


(6.11) The results of the laboratory tests are incorporated in the form of table at the later part of
the report.






Prepared by Checked by Approved by





For, M. K. SOIL TESTING LABORATORY







* 67*

M.K. Soil Testing Laboratory

APPENDIX

[ 1 ] TYPICAL CALCULATIONS FOR SAFE BEARING CAPACITY (CHIMNEY AREA)

[ 1.1] ASSUMPTION / DATA :

i. Type of foundation considered : Square foundation

ii. Total Permissible settlement : 25mm (as per client)

iii. Depth of foundation below G.L. : 3.50m.

iv. Width of foundation : 3.0m x 3.0m

v. Water Table : around 10.0m below GL

[ 1.2 ] BEARING PRESSURE BASED ON C & VALUES :- (SHEAR CRITERION)
For computing bearing capacity at 3.50m depth below GL.
Following shear parameters are adopted at 3.50m depth for calculation of safe bearing capacity
from triaxial shear test on undisturbed soil samples.
C = 0.70 Kg/cm
2

= 2 (Neglected being very small)
The ultimate net bearing capacity (Qnd) for footing on clay is mixed shear failure is given by
equation.,
Qnd = C Nc Sc dc ic
Where,
Qnd = Net ultimate bearing capacity of foundation.
C = Cohesion = 0.70 Kg/cm
2

Considering shape factor for square foundation.
Sc = 1.30
Dc is a depth factor,
(Assuming that overburden soil is not compacted properly)
dc = 1.0,
ic is inclination factor,
Considering ic = 1.0 (Since load is vertical)

* 68*

M.K. Soil Testing Laboratory


Adopting Nc factors as per IS : 6403 as below :
For = 0
Nc = 5.14
Qnd = [0.70 x 5.14 x 1.30 x 1.0 x 1.0]
= 4.6774 Kg/cm
2

Where,
Qnd is net ultimate bearing capacity
Applying factor of safety as 2.5,
Qnd 4.6774
qs = ------------ = ------------
FS 2.50

= 1.871 Kg/cm
2

= 18.71 t/m
2
. Say 19 t/m
2
.
* 69*

M.K. Soil Testing Laboratory



[ 2 ] TYPICAL CALCULATIONS FOR SAFE BEARING CAPACITY OF OPEN FOUNDATION:

[2.1] SAFE BEARING PRESSURE BASED ON SETTLEMENT CRITERION :
(CONSOLIDATION SETTLEMENT)

Pressure bulb shall be taken as,
2 x B = 2 x 3.0 = 6.0m below foundation level,























Assuming pressure distribution as 2(vertical) : 1(Horizontal)
Now,

* 70*

M.K. Soil Testing Laboratory


As the soil is over consolidated use of mv is made for settlement analysis
Co-eff. of vol. change (mv) at mid depth of compressible layer = 0.015 cm
2
/kg.
Height of compressible layer H = 600cm
Initial void ratio (e
0
) at mid depth of compressible layer = 0.89
dp = Increase in pressure at mid depth.
P X 3.0 x 3.0
dp = --------------------- = 0.25 P
6.0 X 6.0


Now,
Settlement (S) in cm at depth of over consolidated compressible stratum is given by equation.
S = mv. dp. H.
Sc = 0.0015 x 0.25p x 600
= 0.225P
Settlement of clay layer resting on rock consists of
S = Si + Sc
Where,
Si = Immediate settlement
P. B (1 -
2
). I
S = ---------------------
E

Where,

= Poissons ratio = 0.44
I = Influence factor = 0.85
E = Youngs Modulus = 0.3751 Say 375 kg/cm
2
.
P = Load intensity on foundation
And Sc = Consolidation settlement
= mv. dp. H


* 71*

M.K. Soil Testing Laboratory


Where,
mv = Co-eff. of col. Change
dp = Change in pressure at mid-depth of compressible layer
H = Ht of layer = 2 x B
P x (1 0.44
2
) x 0.85 x 300
Si = ---------------------------------------
375

= 0.55p.

Hence, S = Si + Sc
= 0.55P + 0.225P at gr. Surface
Apply depth factor corrections Df = 0.7
For permissible settlement of 25mm,
2.5 = (0.5 + 0.225) P x 0.7
P = 2.5______ = 4.608 kg/cm
2
= 46 t/m
2

0.7 x 0.775
Hence, recommended net SBC is 19 t/m
2
.

* 72*

M.K. Soil Testing Laboratory



Table No. 1

Observed N-Val ues

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based
Thermal Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

Client: Bhavnagar Energy Company Limited, Gandhinagar







Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-1 3.00 9 13 21 34
BH 2 1.50
4.50
7.50
9.00
10.50
7
20
30
35
21
9
28
35
42
28
13
31
41
45
31
22
59
Refusal
Refusal
Refusal
BH 3 1.50
4.50
7.50
10.50
13.50
6
5
7
8
10
9
8
9
11
12
11
14
12
15
15
20
22
21
26
27
BH 4 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
10
11
13
13
15
18
19
20
19
20
21
22
12
13
17
14
28
18
24
23
24
25
26
29
17
12
12
11
22
28
27
27
28
29
30
30
29
25
29
25
50
46
51
50
52
54
56
59
* 73*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-6 1.50
4.50
3
6
5
8
7
11
12
19
BH 7 3.00
6.00
9.00
10.50
12.00
13.50
15.00
17.00
4
10
15
17
17
40
30
38
6
15
20
22
18
58
25
60
9
20
22
25
24
-
30
-
15
35
42
47
42
Refusal
55
Refusal
BH 8 1.50
4.50
7.50
9.00
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
3
8
7
7
8
10
12
13
15
12
100
30
40
4
10
12
13
10
14
16
20
24
26
-
52
51
6
12
17
20
16
18
20
27
30
37
-
-
-
10
22
29
33
26
32
36
42
54
63
Refusal
Refusal
Refusal
BH 9 1.50 100 - - Refusal
BH 10 1.50
3.00
4.50
3
6
100
4
8
-
5
12
-
9
20
Refusal






* 74*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 11 1.50
4.50
7.50
10.50
13.50
15.00
9
10
12
10
12
30
11
12
10
12
15
40
12
14
18
15
18
50
23
26
28
27
33
Refusal
BH 12 1.50
4.50
7.50
9.00
10.50
13.50
17.50
19.00
21.00
3
6
7
100
4
8
11
7
7
4
8
15
-
10
17
20
18
19
6
10
20
-
16
22
26
24
32
10
18
35
Refusal
26
39
46
42
51
BH 13 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
32.50
35.00
37.50
8
10
7
9
8
11
12
9
10
9
8
9
10
10
40
30
10
12
9
11
11
14
15
11
12
10
11
11
13
21
50
40
12
14
11
15
13
17
20
14
14
12
14
15
16
40
58
55
22
26
20
26
24
37
35
25
26
22
25
26
29
61
Refusal
Refusal

* 75*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 14 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
15
20
10
10
100
100
100
100
100
100
100
100
100
27
29
13
15
-
-
-
-
-
-
-
-
-
38
40
17
16
-
-
-
-
-
-
-
-
-
65
69
30
31
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
BH 15 1.50
3.00
4.50
6.00
7.50
4
100
100
100
100
5
-
-
-
-
8
-
-
-
-
13
Refusal
Refusal
Refusal
Refusal
BH 16 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.00
30.00
32.50
35.00
37.5
40.0
8
10
10
9
10
11
13
15
15
15
14
15
17
40
35
42
9
12
13
14
13
15
17
21
19
18
29
100
100
46
42
100
11
14
15
18
14
17
21
28
20
22
23
-
-
50
50
-
20
26
28
32
27
32
38
49
39
40
42
Refusal
Refusal
Refusal
Refusal
Refusal

* 76*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 17 1.50
4.50
7.50
9.00
10.50
12.00
13.50
15.00
17.00
21.00
23.00
25.00
27.00
30.00
7
10
14
15
13
15
27
100
100
100
100
100
100
100
9
12
17
19
17
20
100
-
-
-
-
-
-
-
11
15
19
21
20
21
-
-
-
-
-
-
-
-
20
27
36
40
37
41
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
BH 18 1.50
4.50
7.50
10.50
3
5
6
8
6
11
13
15
8
15
17
20
14
26
30
35
BH 19 1.50
4.50
7.50
10.50
13.50
17.00
21.00
25.00
27.50
4
5
7
100
100
100
100
100
100
7
7
10
-
-
-
-
-
-
9
12
13
-
-
-
-
-
-
16
19
23
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal










* 77*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 20 3.00
6.00
9.00
9.00
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
30.00
4
5
7
100
100
100
100
100
100
100
100
100
40
7
7
10
-
-
-
-
-
-
-
-
-
100
9
12
13
-
-
-
-
-
-
-
-
-
-
16
19
23
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
BH 21 1.50
4.50
7.50
9.00
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
9
10
15
17
100
100
100
17
10
17
15
17
19
40
17
12
13
17
19
-
-
-
21
15
21
27
21
25
35
40
15
16
21
22
-
-
-
27
28
33
23
29
50
50
70
27
29
38
41
Refusal
Refusal
Refusal
48
43
54
40
50
Refusal
Refusal
Refusal





* 78*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 22 1.50
4.50
7.50
10.50
13.50
17.00
21.00
23.00
25.00
27.50
30.00
3
5
8
7
9
11
42
50
58
100
100
5
7
10
9
10
13
80
65
60
-
-
5
8
11
13
15
17
-
-
-
-
-
10
15
21
22
25
30
Refusal
Refusal
Refusal
Refusal
Refusal
BH 23 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
7
8
6
9
9
10
10
10
40
9
10
8
12
15
15
-
-
47
11
12
11
14
17
17
-
-
-
20
22
19
16
32
32
Refusal
Refusal
Refusal
BH 24 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
32.50
9
8
7
11
15
18
20
19
18
20
21
100
100
11
10
9
15
17
20
22
21
21
23
23
-
-
13
12
13
21
20
28
26
24
23
26
27
-
-
24
22
21
36
37
48
48
45
44
49
50
Refusal
Refusal

* 79*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 24 35.00
37.50
40.00
40
36
100
68
68
-
-
-
-
Refusal
Refusal
Refusal
BH 25 3.00
6.00
9..00
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
4
6
8
8
8
9
10
10
12
12
6
7
25
36
6
11
15
16
17
17
18
19
22
21
12
13
32
42
8
15
18
18
18
20
21
24
25
25
15
15
36
22
14
26
33
34
35
37
39
43
47
46
27
28
68
Refusal
BH 26 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
3
6
6
7
7
7
8
9
12
13
15
18
20
21
4
8
9
11
14
15
15
15
17
18
20
24
26
32
6
11
18
20
21
22
24
28
29
30
31
40
42
50
10
19
27
31
35
39
43
46
48
51
64
68
82
Refusal




* 80*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 26 32.50
35.00
37.00
40.00
24
46
48
55
40
54
52
-
36
-
-
-
Refusal
Refusal
Refusal
Refusal
BH 27 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
4
3
4
100
2
4
5
6
3
5
4
6
6
6
6
7
-
3
5
7
8
3
4
5
8
8
8
9
8
-
7
6
8
9
13
9
9
10
11
14
15
15
Refusal
10
11
15
17
16
13
14
18
19
BH 28 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
5
6
100
100
100
100
100
20
21
100
100
30
29
30
7
8
-
-
-
-
-
30
35
-
-
32
31
33
9
11
-
-
-
-
-
100
38
-
-
40
44
41
16
19
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
73
Refusal
Refusal
72
65
74




* 81*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 29 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
5
4
5
6
5
7
100
100
100
100
100
100
100
100
7
6
7
9
8
9
-
-
-
-
-
-
-
-
9
11
12
11
10
11
-
-
-
-
-
-
-
-
16
17
19
20
18
20
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
BH 30 1.50
4.50
7.50
10.50
13.50
17.00
21.00
25.00
30.00
3
10
18
12
13
18
12
15
16
6
12
22
17
15
27
15
22
32
8
18
27
21
22
32
23
27
60
14
30
49
38
37
59
38
49
92

* 82*

M.K. Soil Testing Laboratory



Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 31 1.50
4.50
7.50
10.50
13.50
17.00
19.00
8
10
11
13
15
100
100
10
12
13
15
17
-
-
12
13
15
17
20
-
-
22
25
28
32
37
Refusal
Refusal
BH 32 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
5
6
10
12
14
15
19
20
40
48
55
100
100
100
7
6
11
15
17
16
21
25
100
100
80
-
-
-
8
9
12
16
20
22
22
27
-
-
-
-
-
-
15
15
23
31
37
38
43
52
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
















* 83*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 33 3.00
6.00
9.00
12.00
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
10
13
15
17
19
21
23
25
27
30
66
100
12
17
20
22
24
26
29
35
38
41
-
-
23
21
24
27
29
32
35
39
43
45
-
-
35
38
44
49
53
58
64
74
81
86
Refusal
Refusal
BH 34 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
6
8
10
11
14
18
20
25
22
100
8
8
12
12
18
20
24
25
27
-
10
12
15
17
22
25
26
28
30
-
18
20
27
29
40
45
50
53
57
Refusal
BH 35 1.50
4.50
7.50
9.00
10.50
13.50
15.00
17.00
19.00
21.00
3
22
15
100
100
100
100
80
82
100
4
27
20
-
-
-
-
20
20
-
5
32
28
-
-
-
-
-
-
-
9
59
48
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal



* 84*

M.K. Soil Testing Laboratory



Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 36 1.50
4.50
7.50
9.00
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
8
9
100
100
100
17
100
100
100
18
17
19
21
22
25
11
12
-
-
-
20
-
-
-
21
20
22
23
25
30
15
17
-
-
-
23
-
-
-
24
24
24
25
28
32
26
29
Refusal
Refusal
Refusal
43
Refusal
Refusal
Refusal
45
44
46
48
53
62
BH 37 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
5
10
12
15
17
20
24
27
100
8
14
16
20
22
26
30
33
-
11
17
19
23
25
29
34
38
-
19
31
35
43
47
55
64
71
Refusal
BH 38 1.50
4.50
7.50
9.00
10.50
3
19
21
23
15
5
26
28
30
20
7
29
31
32
22
12
55
59
62
24





* 85*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 39 1.50
4.50
7.50
9.00
10.50
3
19
21
23
15
5
26
28
30
20
7
29
31
32
22
12
55
59
62
24
BH 39 3.00
6.00
9.00
12.00
15.00
17.00
4
6
10
12
24
100
8
11
13
16
39
-
12
16
19
21
41
-
20
27
32
37
80
Refusal
BH 40 1.50
4.50
7.50
9.00
13.50
17.00
21.00
25.00
30.00
4
7
9
11
4
7
13.00
100
100
6
15
17
13
11
15
19
-
-
8
20
22
16
24
22
28
-
-
14
35
39
29
35
37
47
Refusal
Refusal
BH 41 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
2
3
5
7
10
21
23
25
28
30
32
35
3
4
6
9
12
24
25
27
30
32
33
37
5
7
8
10
13
26
28
30
31
35
36
40
8
11
14
19
25
50
53
57
61
67
69
77


* 86*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 42 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
15
11
14
24
100
100
100
100
100
100
100
100
17
13
18
28
-
-
-
-
-
-
-
-
18
16
20
32
-
-
-
-
-
-
-
-
35
29
38
60
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
BH 43 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
6
5
4
6
100
100
6
4
100
100
100
100
8
7
7
7
-
-
8
6
-
-
-
-
10
9
10
15
-
-
10
11
-
-
-
-
18
16
17
22
Refusal
Refusal
18
17
Refusal
Refusal
Refusal
Refusal
BH 44 1.50
4.50
7.50
4
5
8
6
11
100
8
17
-
14
28
Refusal









* 87*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 45 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
5
8
10
21
23
25
30
100
100
8
11
12
25
28
30
34
-
-
10
13
17
32
23
35
41
-
-
18
24
31
57
61
65
75
Refusal
Refusal
BH 46 1.50
4.50
7.50
10.50
13.50
17.00
21.00
25.00
4
6
9
11
11
15
19
19
8
9
11
15
21
27
40
40
9
11
13
24
32
100
100
100
17
20
24
39
53
Refusal
Refusal
Refusal
BH 47 1.50
4.50
9.00
10.50
12.00
15.00
19.00
21.00
23.00
25.00
9
11
11
100
100
11
12
19
9
10
11
13
13
-
-
19
15
23
11
12
18
19
19
-
-
27
19
43
18
19
39
32
32
Refusal
Refusal
46
34
66
29
31









* 88*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 48 1.50
4.50
7.50
9.00
12.00
13.50
17.00
19.00
21.00
25.00
30.00
10
2
30
9
11
14
15
18
19
11
50
15
5
45
18
25
27
28
29
29
19
100
20
14
100
23
28
30
35
37
38
27
-
35
19
Refusal
41
53
57
63
66
67
46
Refusal
BH -49 3.00
6.00
9.00
12.00
15.00
17.00
21.00
23.00
25.00
30.00
35.00
40.00
4
19
35
25
25
10
19
47
50
12
100
100
9
35
50
50
50
12
23
50
50
29
-
-
11
50
100
100
100
19
43
100
100
29
-
-
20
85
Refusal
Refusal
Refusal
31
46
Refusal
Refusal
58
Refusal
Refusal
BH - 50 1.50
4.50
9.00
12.00
15.00
19.00
23.00
27.50
30.00
35.00
6
14
12
11
6
5
12
15
21
100
9
24
20
17
17
14
23
25
45
-
11
28
24
20
22
20
25
30
-
-
11
28
24
20
22
20
25
30
-
-
* 89*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 51 1.50 3.00
3.00 4.5
6.00 7.50
9.00 10.50
12.00 13.50
15.00 19.00
19.00 21.00
23.00 - 25.00
27.0 30.00
8
12
22
37
40
14
24
37
56
13
13
31
41
45
24
30
64
35
15
18
39
50
54
41
35
-
-
28
31
70
91
99
65
65
Refusal
Refusal
BH -52 1.50 3.00
4.50 6.00
7.50 9.00
10.50 12.00
13.50 15.00
17.00 19.00
21.00 23.00
25.00 - 27.50
9
22
25
28
15
16
35
37
11
36
33
40
29
28
45
48
16
46
48
50
32
33
50
52
27
82
81
9
61
61
95
100
BH 53 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
5
6
8
10
12
15
20
21
25
30
50
100
100
7
8
9
12
15
20
21
25
28
31
48
-
-
9
10
12
15
17
22
25
26
3
33
-
-
-
16
18
21
27
32
42
46
51
58
64
Refusal
Refusal
Refusal





* 90*

M.K. Soil Testing Laboratory



Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 54 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
6
6
8
4
7
7
8
8
7
9
8
9
8
7
9
8
11
11
12
13
11
12
11
14
9
8
11
9
13
11
13
15
14
17
18
17
17
15
20
17
24
22
25
28
25
29
29
31
BH - 55 3.00 4.50
6.00 7.50
9.00 10.50
12.00 13.50
15.00 17.00
19.00 21.00
23.00 -
7
11
7
8
82
19
20
7
13
11
14
-
32
31
15
27
13
16
-
-
-
22
40
24
30
Refusal
Refusal
Refusal
BH 56 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.00
30.00
6
8
10
-
-
-
-
-
-
-
-
-
-
-
9
10
13
-
-
-
-
-
-
-
-
-
-
-
10
12
15
-
-
-
-
-
-
-
-
-
-
-
19
22
28
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
* 91*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 57 0.00 1.50
3.00 4.5
6.00 7.50
9.00 10.50
12.00 13.50
15.00 17.00
19.00 21.00
23.00 -
25.00
6
8
11
10
12
8
11
23
45
8
10
13
14
21
15
15
37
-
11
12
15
17
33
20
17
-
-
19
22
28
31
54
35
32
Refusal
Refusal
BH 58 3.00
4.50
6.00
7.50
9.00
10.50
12.00
13.50
15.00
17.00
7
10
12
14
15
20
21
23
25
100
13
14
13
17
19
23
25
27
28
-
17
21
25
27
28
30
32
37
39
-
30
35
38
44
47
53
57
64
67
Refusal
BH 59 1.50
4.50
27.50
30.00
6
100
12
15
8
-
18
21
11
-
20
25
19
Refusal
38
46
BH 62 1.50
4.50
7.50
10.50
13.50
17.50
19.00
21.00
23.00
25.00
27.50
30.00
6
8
6
8
10
100
-
-
-
-
-
8
9
10
11
14
-
-
-
-
-
-
9
11
12
12
17
-
-
-
-
-
-
17
20
22
23
31
Refusal
Refusal
Refusal
Refusal
Refusal
Refusal
* 92*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 60 3.0
6.00
9.00
12.00
13.50
21.00
23.00
25.00
27.50
30.00
5
7
8
10
35
100
100
10
20
100
7
10
11
15
65
-
-
18
32
-
12
13
15
4
-
-
-
31
40
-
19
23
26
39
Refusal
Refusal
Refusal
49
72
Refusal
BH 61 3.00
6.00
9.00
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
32.50
35.00
37.50
40.00
4
6
14
15
18
20
20
18
15
19
20
21
23
25
100
100
100
6
9
22
21
25
28
27
25
25
27
29
32
34
36
-
-
-
7
11
25
28
30
35
34
34
34
35
36
37
39
42
-
-
-
13
20
47
49
55
63
61
59
59
62
65
69
73
78
Refusal
Refusal
Refusal






* 93*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 63 1.50
3.00
6.00
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
8
8
10
8
9
11
7
9
7
9
10
15
10
30
10
11
13
12
20
18
12
11
9
15
22
45
35
40
15
17
20
14
22
25
14
17
17
17
100
55
45
-
25
28
33
26
42
43
26
28
26
32
Refusal
Refusal
Refusal
Refusal
BH 64 0.00 1.50
3.00 4.50
6.00 7.50
9.00
10.50
12.00
13.50
15.00
17.00
7
40
4
6
8
29
15
18
10
50
5
11
15
16
30
27
41
14
40
8
13
28
20
33
29
-
24
Refusal
13
24
43
36
63
56
Refusal
BH 65 3.00
6.00
9.00
10.50
12.00
13.50
15.00
17.00
21.00
3
6
14
15
22
24
-
-
-
4
8
24
26
45
46
-
-
-
6
12
32
35
43
50
-
-
-
10
20
56
61
88
96
Refusal
Refusal
Refusal



* 94*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 66 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
6
7
7
10
12
15
20
21
20
100
7
9
11
15
15
19
21
26
25
-
8
10
12
15
18
20
25
30
32
-
16
19
23
30
33
37
46
56
59
Refusal
BH 67 1.50
4.50
7.50
10.50
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
32.50
35.00
37.50
40.00
6
8
7
9
10
11
12
12
15
13
13
100
10
9
100
100
100
9
10
9
11
15
19
14
14
17
14
42
-
21
23
-
-
-
10
11
11
13
20
15
16
20
18
16
5
-
23
20
-
-
-
19
21
20
24
35
34
30
34
35
30
Refusal
Refusal
44
43
Refusal
Refusal
Refusal










* 95*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 68 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
32.50
35.00
7
8
9
8
11
12
15
17
15
17
6
6
8
7
9
9
11
10
15
18
20
-
36
28
9
8
9
9
12
11
14
11
17
19
21
-
60
63
11
12
13
11
21
20
25
21
32
37
41
Refusal
96
Refusal
20
20
22
20
BH 69 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
5
7
9
12
13
15
18
20
22
25
26
28
45
5
6
8
11
16
18
20
22
25
26
28
30
32
60
50
8
10
15
21
22
25
27
30
32
35
34
36
-
-
14
18
26
37
40
45
49
55
58
63
64
68
Refusal
Refusal







* 96*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH 70 1.50
4.50
7.50
10.50
13.50
17.00
21.00
23.00
25.00
1
4
3
8
8
3
100
100
100
2
7
10
10
10
3
-
-
-
3
10
13
15
18
5
-
-
-
5
17
23
25
28
8
Refusal
Refusal
Refusal
BH 71 1.50
4.50
7.50
10.50
12.00
13.50
15.00
17.00
19.00
21.00
23.00
25.00
27.50
30.00
6
8
5
6
36
12
27
31
11
22
23
14
62
100
8
15
25
21
-
15
-
-
21
32
33
16
47
-
10
19
32
28
-
17
-
-
33
-
-
30
-
-
18
34
57
49
Refusal
32
Refusal
Refusal
54
Refusal
Refusal
46
Refusal
Refusal
BH-72 3.00
6.00
9.00
12.00
13.5
15.0
4
5
6
100
100
100
10
9
10
-
-
-
14
16
17
-
-
-
24
25
27
Refusal
Refusal
Refusal







* 97*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-73 1.50
4.50
7.50
10.5
12.0
15.0
17.0
19.0
23.0
25.0
27.5
30.0
1
2
4
9
5
8
3
7
7
10
15
17
2
2
6
10
14
15
9
16
10
13
18
22
3
1
8
15
22
23
9
25
27
25
30
35
5
3
14
25
36
38
15
41
37
38
48
57
BH-74 0.0 to 1.5
3.0 to 4.5
6.0 to 7.5
9.0 to 10.5
10.5 to 12.0
13.5 to 15.0
17.0 to 19.0
21.0 to 23.0
25.0 to 27.5
27.5 to 30.0
32.0 to 33.0
3
3
4
6
3
4
8
9
9
100
100
7
12
11
14
5
6
10
10
10
-
-
9
18
13
19
7
7
12
13
18
-
-
16
30
24
33
12
13
22
23
28
Refusal
Refusal
BH-75 1.5 to 3.0
4.5 to 6.0
7.5 to 9.0
10.5 to 12.0
13.5 to 15.0
17.0 to 19.0
21.0 to 23.0
23.0 to 25.0
3
7
12
10
14
8
100
100
4
10
14
13
16
16
-
-
7
12
17
17
18
21
-
-
11
22
31
30
34
37
Refusal
Refusal




* 98*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-76 1.50
4.50
7.50
10.5
13.5
17.0
19.0
21.0
23.0
25.0
27.5
30.0
7
7
8
8
6
8
21
11
14
13
100
100
9
8
11
10
11
11
33
30
28
25
-
-
11
10
12
11
13
12
40
38
38
30
-
-
20
18
23
21
24
23
13
68
66
55
Refusal
Refusal
BH-77 1.50
4.50
7.50
10.5
13.5
15.0
17.0
19.0
21.0
2
4
5
7
100
100
100
100
100
3
6
10
12
-
-
-
-
-
4
9
21
23
-
-
-
-
-
7
15
31
32
Refusal
Refusal
Refusal
Refusal
Refusal
BH-78 1.50
4.50
7.50
10.5
13.5
17.0
21.0
25.0
30.0
4
4
12
3
10
13
100
12
15
6
6
15
4
13
15
-
16
21
8
10
18
8
15
18
-
21
28
14
16
33
12
28
33
Refusal
37
49





* 99*

M.K. Soil Testing Laboratory

Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-79 1.5 to 3.0
4.5 to 6.0
7.5 to 9.0
10.5 to 12.0
13.5 to 15.0
17.0 to 19.0
21.0 to 23.0
25.0 to 27.5
10
4
4
6
7
8
6
12
15
7
6
8
13
12
12
45
20
10
10
12
15
12
17
-
35
17
16
20
28
24
29
Refusal
BH-80 0.5 to 1.5
3.0 to 4.5
6.0 to 7.5
9.0 to 10.5
12.0 to 13.5
15.0 to 17.0
19.0 to 21.0
23.0 to 25.0
27.0 to 30.0
8
4
8
14
15
15
13
4
12
11
7
12
17
18
18
22
12
45
18
9
18
19
23
23
26
15
-
29
16
30
36
41
41
48
27
Refusal
BH-81 1.50
4.50
7.50
10.50
13.50
17.00
19.00
21.00
23.00
25.00
27.50
30.00
8
8
9
6
6
6
11
5
100
100
100
100
21
12
11
9
8
9
25
8
-
-
-
-
22
17
17
11
10
10
45
11
-
-
-
-
43
29
28
20
18
19
Refusal
19
Refusal
Refusal
Refusal
Refusal







* 100*

M.K. Soil Testing Laboratory


Bore
Hole
No.
Depth
In
(m)
Nos. of blow to drive
Sampler for penetration of
0150 150-300 300-450
(mm) (mm) (mm)
N-value
for last
300
(mm)
BH-82 1.50
4.50
7.50
10.5
13.5
15.0
17.0
19.0
21.0
23.0
25.0
27.5
30.0
6
45
21
9
10
21
24
20
17
14
29
100
100
8
56
43
12
12
56
29
37
21
19
-
-
-
10
-
100
15
14
63
50
42
40
-
-
-
-
18
Refusal
143
27
26
119
79
79
61
Refusal
Refusal
Refusal
Refusal
BH-83 1.50
4.50
7.50
10.50
13.5
17.0
19.0
21.0
23.0
25.0
27.5
30.0
7
8
10
8
9
8
9
25
25
100
100
100
9
10
11
11
11
10
11
100
100
-
-
-
11
12
13
12
13
13
15
-
-
-
-
-
20
22
24
23
24
23
26
Refusal
Refusal
Refusal
Refusal
Refusal












* 101*

M.K. Soil Testing Laboratory


Table No. 2

Swelling Properties of Soil

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based
Thermal Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

Client : Bhavnagar Energy Company Limited, Gandhinagar

Bore
Hole
No.
Depth
In
(m)
Differential Free
swell
(%)
Shrinkage Limit
(%)
Swelling
Pressure
(kg/cm
2
)
BH-8 4.50 to 6.00
6.0 to 7.5
9.0 to 10.5
17.0 to 19.0
150.00
125.00
100.00
90.00
-
7.85
8
8.10
-
1.63
-
0.92
BH-13 0.0 to 1.50
9.0 to 10.5
17.0 to 18.5
19.0 to 21.0
31.0 to 32.5
36.0 to 37.5
60.00
50.00
66.67
91.67
81.81
60.00
12
13.65
-
-
12.90
-
0.86
-
0.70
-
-
-
BH-16 4.50 to 6.00
10.5 to 12.0
13.5 to 15.0
22.5 to 23.0
75.00
66.67
72.72
64.28
-
10
-
12
-
0.923
-
0.86
BH-20 1.50 to 3.00
6.00 to 7.50
7.50 to 9.0
12.5 to 13.00
31.25
57.14
60.00
63.63
14
-
12
12
-
-
0.802
-
BH-23 3.00 to 4.50
6.00 to 7.50
9.00 to 10.5
12.0 to 13.5
18.5 to 19.0
81.81
76.92
69.23
100.00
90.00
12
-
9.80
-
12
0.84
-
0.94
-
0.574





* 102*

M.K. Soil Testing Laboratory



Bore
Hole
No.
Depth
In
(m)
Differential Free
swell
(%)
Shrinkage Limit
(%)
Swelling
Pressure
(kg/cm
2
)
BH-29 1.50 to 3.00
3.00 to 4.50
6.0 to 7.50
17.50 to 19.0
76.92
42.85
-
66.66
-
10
-
11
0.657
0.75
-
0.80
BH-31 24.5 to 25.0
29.5 to 30.0
1.50 to 3.00
15.0 to 17.0
64.28
70.00
69.23
60.00
-
-
10.79
12.00
-
-
1.06
1.00
BH-38 0.00 to 1.50
3.00 to 4.50
80.00
58.33
9
12
0.92
-
BH-49 1.50 to 3.00
4.50 to 6.00
29.5 to 30.0
75.00
76.92
72.72
-
11
12
-
0.85
0.79
BH-51 1.50 to 3.00
3.00 to 4.50
7.50 to 9.00
9.00 to 10.5
19.0 to 21.0
30.0 to 32.5
57.14
53.84
54.00
31.25
46.67
-
-
-
12.20
10.91
13.59
-
-
1.055
0.96
-
-
-
BH-52 1.50 to 3.00
7.5 to 9.00
13.50 to 15.0
19.0 to 21.0
27.0 to 30.0
23.0 to 25.0
46.15
81.81
40.00
50.00
53.84
62.00
-
15.06
13.17
14.00
-
12.70
-
0.577
-
0.62
-
0.872
BH-55 3.00 to 4.50
6.00 to 7.50
9.00 to 10.50
10.5 to 12.0
50.00
50.00
58.33
70.00
14.00
15.63
-
13.32
0.65
-
0.474
-
BH-57 7.50 to 9.00
10.5 to 12.00
21.0 to 23.0
66.67
76.92
53.84
12.00
10.00
13.09
0.80
0.86
-
* 103*

M.K. Soil Testing Laboratory



Bore
Hole
No.
Depth
In
(m)
Differential Free
swell
(%)
Shrinkage Limit
(%)
Swelling
Pressure
(kg/cm
2
)
BH-64 10.5 to 12.0
15.0 to 17.0
21.0 to 23.0
53.84
43.85
42.85
12.84
-
15.10
0.821
0.70
0.80
BH-67 6.0 to 7.50
7.50 to 9.00
10.5 to 12.0
18.5 to 19.0
24.0 to 25.0
69.23
64.28
66.67
72.72
83.33
15.58
12.00
12.53
12.00
15.25
-
0.76
0.675
0.80
0.65
BH-80 3.00 to 4.50
6.0 to 7.50
9.00 to 10.5
19.0 to 21.0
27.0 to 30.0
66.67
38.89
66.67
72.72
57.14
12.60
14.00
13.33
12.10
10.63
0.58
0.39
0.72
0.913
-






























* 104*

M.K. Soil Testing Laboratory



Table No. 3

Chemi cal Anal ysi s of Soi l

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based
Thermal Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

Client : Bhavnagar Energy Company Limited, Gandhinagar


Borehole
No.
Depth
(m.)
pH Chlorides
(%)
Sulphate
(%)
TDS
(%)
BH1 3.00 7.52 0.0096 0.0021 0.062
BH2 6.00 7.40 0.013 0.0023 0.074
BH-4 7.50 7.54 0.0075 Nil 0.045
BH-8 19.0 6.98 0.021 0.0013 0.051
BH-10 1.50 7.81 0.012 0.0020 0.060
BH-11 9.00 7.19 0.014 0.0023 0.058
BH-12 13.50 7.36 0.0069 Nil 0.043
BH-13 25.0 7.34 0.010 0.0028 0.062
BH-16 35.0 6.70 0.023 0.0072 0.16
BH-19 12.0 7.20 0.076 Nil 0.044
BH-20 12.0 7.53 0.013 0.0034 0.083
BH-23 27.50 7.59 0.0071 0.0027 0.052
BH-26 3.00 7.74 0.025 0.0069 0.17
BH-29 15.0 7.62 0.0087 Nil 0.039
BH-38 9.00 7.98 0.015 0.0027 0.098
BH-44 6.00 8.26 0.026 0.0052 0.14
BH-46 10.50 7.34 0.0073 0.0013 0.045
BH-53 10.50 7.39 0.0026 Nil 0.017
BH-58 1.50 8.18 0.16 0.031 0.47
BH-63 25.0 7.24 0.0091 0.0046 0.075
BH-68 9.00 7.06 0.018 0.0065 0.11





* 105*

M.K. Soil Testing Laboratory



Table No. 4

Chemi cal Anal ysi s of Water

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based
Thermal Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar


Borehole
No.
pH Chlorides
(mg/l)
Sulphate
(mg/l)
TDS
(mg/l)
Carbonates
(mg/l)
Organic
Matter
(mg/l)
Nitrates
(mg/l)
BH-1 7.85 1896 360.5 3655
Nil Nil Nil
BH-8 7.9 2075 290.2 2894
Nil Nil Nil
BH-15 7.82 2122 200.9 2890
Nil Nil Nil
BH-18 7.66 2108 184.3 3935
Nil Nil Nil
BH-46 7.59 1904 214.6 3050
Nil Nil Nil
BH-55 7.85 2220 298 2906
Nil Nil Nil
BH-62 7.66 2208 215.8 2950
Nil Nil Nil
BH-74 8.02 2850 405 2887
Nil Nil Nil
BH-80 7.82 2436 200 2860
Nil Nil Nil
BH-84 7.86 2194 326 2795
Nil Nil Nil
















* 106*

M.K. Soil Testing Laboratory


Tabl e No. 5/ 1

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 1

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based
Thermal Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar


1) Date of Test : 24/5/2008
2) Test No. : FPLT 1
3) Co-Ordinate : E. 1445.97m, N. 57.40m
4) Ground RL : 42.12m
5) Depth of Test : 5.50
6) Dia of Hole : 7
7) Radius of Hole : 100mm = 1cm = 0.1m


Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m) K = Q
5.5. r. H
(cm/sec)
600 0.6 0.6 x 10
3

600
5.50 3.31 X 10
-5

900 0.8 0.8 x 10
3

900
5.50 2.94 X 10
-5

1200 1.3 1.3 x 10
3

1200
5.50 3.58 X 10
-5

1500 1.8 1.8 x 10
3

1500
5.50 3.97 X 10
-5

1800 2.0 2.0 x 10
3

1800
5.50 3.67 X 10
-5

K Average (cm/sec) 3.49 X 10
-5








* 107*

M.K. Soil Testing Laboratory



Tabl e No. 5/ 2

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 2


1) Date of Test : 24/5/2008
2) Test No. : FPLT 2
3) Co-Ordinate : E. 67.4m, N. 1445.97m
4) Ground RL : 41.81m
5) Depth of Test : 5.50
6) Dia of Hole : 7
7) Radius of Hole : 100mm = 1cm = 0.1m


Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m) K = Q
5.5. r. H
(cm/sec)
300 2.1 2.1 x 10
3

300
5.50 2.31 X 10
-4

600 2.1 2.1 x 10
3

600
5.50 1.16 X 10
-4

900 2.5 2.5 x 10
3

900
5.50 1.0 X 10
-4

1200 3.3 3.3 x 10
3

1200
5.50 1.0 X 10
-4

1500 4.6 4.6 x 10
3

1500
5.50 1.01 X 10
-4

1800 5.0 5.0 x 10
3

1800
5.50 9.18 X 10
-4

K Average (cm/sec) 1.03 X 10
-4









* 108*

M.K. Soil Testing Laboratory

Tabl e No. 5/ 3

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 3


1) Date of Test : 24/5/2008
2) Test No. : FPLT 3
3) Co-Ordinate : E. 117.04m, N. 1362.47m
4) Ground RL : 41.54m
5) Depth of Test : 6.0m
6) Dia of Hole : 6
7) Radius of Hole : 75mm = 7.5cm


Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m) K = Q
5.5. r. H
(cm/sec)
300 0.8 0.8 x 10
3

300
6.0 1.08 X 10
-4

600 1.5 1.5 x 10
3

600
6.0 1.01 X 10
-4

900 2.4 2.4 x 10
3

900
6.0 1.08 X 10
-4

1200 3.1 3.1 x 10
3

1200
6.0 1.04 X 10
-4

1500 3.8 3.8 x 10
3

1500
6.0 1.02 X 10
-4

1800 4.21 4.4 x 10
3

1800
6.0 1.0 X 10
-4

K Average (cm/sec) 1.04 X 10
-4











* 109*

M.K. Soil Testing Laboratory

Tabl e No. 5/ 4

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 5

Sub: Geotechnical Investigation work for proposed 2 x 250 MW Lignite Based
Thermal Power Plant in Padva Village, Tal: Ghogha, Dist: Bhavnagar, State:
Gujarat,

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar


1) Date of Test : 24/5/2008
2) Test No. : FPLT 5
3) Co-Ordinate : E. 1659.51m, N. 1050.81m
4) Ground RL : 44.22m
5) Depth of Test : 5.0m
6) Dia of Hole : 6
7) Radius of Hole : 75mm = 7.5cm


Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m) K = Q
5.5. r. H
(cm/sec)
300 0.7 0.7 x 10
3

300
5.0 1.13 X 10
-4

600 1.9 1.9 x 10
3

600
5.0 1.54 X 10
-4

900 2.8 2.8 x 10
3

900
5.0 1.51 X 10
-4

1200 3.6 3.6 x 10
3

1200
5.0 1.45 X 10
-4

1500 4.5 4.5 x 10
3

1500
5.0 1.45 X 10
-4

1800 5.5 5.5 x 10
3

1800
5.0 1.48 X 10
-4

K Average (cm/sec) 1.43 X 10
-4




* 110*

M.K. Soil Testing Laboratory


Tabl e No. 5/ 5

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 6


1)
Date of Test : 20/5/2008
2) Test No. : FPLT 6
3) Co-Ordinate : E. 696.03m, N. 476.11m
4) Ground RL : 48.49m
5) Depth of Test : 5.0m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 5.6 5.6 x 10
-3

300
5.0 6.79 X 10
-4

600 12.8 12.8 x 10
3

600
5.0 7.76 X 10
-4

900 16.2 16.2 x 10
3

900
5.0 6.55 X 10
-4

1200 18.4 18.4 x 10
3

1200
5.0 5.58 X 10
-4

1500 22.4 22.4 x 10
3

1500
5.0 5.43 X 10
-4

1800 26.3 26.3 x 10
3

1800
5.0 5.31 X 10
-4

2100 30.5 30.5 x 10
3

1800
5.0 5.28 X 10
-4

2400 34.7 34.7 x 10
3

1800
5.0 5.26 X 10
-4

2700 38.7 38.7 x 10
3

1800
5.0 5.21 X 10
-4

3000 42.6 42.6 x 10
3

1800
5.0 5.16 X 10
-4

K Average (cm/sec) 5.83 X 10
-4

* 111*

M.K. Soil Testing Laboratory


Tabl e No. 5/ 6

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 7


1) Date of Test : 21/5/2008
2) Test No. : FPLT 7
3) Co-Ordinate : E. 756.86m, N. 487.53m
4) Ground RL : 47.48m
5) Depth of Test : 6.0m
6) Dia of Hole : 6
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 13.9 13.9 x 10
3

300
6.0 1.87 X 10
-3

600 25.4 25.4 x 10
3

600
6.0 1.71 X 10
-3

900 31.4 31.4 x 10
3

900
6.0 1.41 X 10
-3

1200 39.8 39.8 x 10
3

1200
6.0 1.34 X 10
-3

1500 48.8 48.8 x 10
3

1500
6.0 1.31 X 10
-3

1800 55.3 55.3 x 10
3

1800
6.0 1.24 X 10
-3

2100 62.9 62.9 x 10
3

1800
6.0 1.21 X 10
-3

K Average (cm/sec) 1.44 X 10
-3









* 112*

M.K. Soil Testing Laboratory




Tabl e No. 5/ 7

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 8


1) Date of Test : 21/5/2008
2) Test No. : FPLT 8
3) Co-Ordinate : E. 830.03m, N. 483.83m
4) Ground RL : 46.34m
5) Depth of Test : 4.20m
6) Dia of Hole : 6
7) Radius of Hole : 7.5cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 5.2 5.2 x 10
3

300
4.20 1.0 X 10
-3

600 12 12 x 10
3

600
4.20 1.15 X 10
-3

900 19 19 x 10
3

900
4.20 1.22 X 10
-3

1200 26 26 x 10
3

1200
4.20 1.25 X 10
-3

1500 32.8 32.8 x 10
3

1500
4.20 1.26 X 10
-3

1800 39.6 39.6 x 10
3

1800
4.20 1.27 X 10
-3

K Average (cm/sec) 1.19 X 10
-3










* 113*

M.K. Soil Testing Laboratory





Tabl e No. 5/ 8

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 9

1) Date of Test : 21/5/2008
2) Test No. : FPLT 9
3) Co-Ordinate : E. 764.27m, N. 435.99m
4) Ground RL : 47.04m
5) Depth of Test : 7.0m
6) Dia of Hole : 6
7) Radius of Hole : 7.5cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 10.9 10.9 x 10
3

300
7.0 1.26 X 10
-3

600 17.8 17.8 x 10
3

600
7.0 1.03 X 10
-3

900 22.2 22.2 x 10
3

900
7.0 0.85 X 10
-3

1200 27.0 27 x 10
3

1200
7.0 0.80 X 10
-3

1500 29.4 29.4 x 10
3

1500
7.0 0.68 X 10
-3

1800 31.7 31.7 x 10
3

1800
7.0 0.61 X 10
-3

2100 33.9 33.9 x 10
3

2100
7.0 0.56 X 10
-3

K Average (cm/sec) 8.27 X 10
-4








* 114*

M.K. Soil Testing Laboratory





Tabl e No. 5/ 9

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 10


1) Date of Test : 20/5/2008
2) Test No. : FPLT 10
3) Co-Ordinate : E. 695.73m, N. 389.08m
4) Ground RL : 48.17m
5) Depth of Test : 5.50m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 8.4 8.4 x 10
3

300
5.50 9.26 X 10
-4

600 16 16 x 10
3

600
5.50 8.82 X 10
-4

900 23.3 23.3 x 10
3

900
5.50 8.56 X 10
-4

1200 30.5 30.5 x 10
3

1200
5.50 8.40 X 10
-4

1500 37.7 37.7 x 10
3

1500
5.50 8.31 X 10
-4

1800 44.2 44.2 x 10
3

1800
5.50 8.12 X 10
-4

2100 50.7 50.7 x 10
3

2100
5.50 7.98 X 10
-4

2400 57.1 57.1 x 10
3

2400
5.50 7.87 X 10
-4

K Average (cm/sec) 8.42 X 10
-4




* 115*

M.K. Soil Testing Laboratory





Tabl e No. 5/ 10

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 11

1) Date of Test : 21/5/2008
2) Test No. : FPLT 11
3) Co-Ordinate : E. 829.73m, N. 406.05m
4) Ground RL : 46.42m
5) Depth of Test : 5.50m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 9.2 9.2 x 10
3

300
5.50 1.01 X 10
-3

600 19.9 19.9 x 10
3

600
5.50 1.10 X 10
-3

900 29.5 29.5 x 10
3

900
5.50 1.08 X 10
-3

1200 36.4 36.4 x 10
3

1200
5.50 1.0 X 10
-3

1500 41.5 41.5 x 10
3

1500
5.50 0.91 X 10
-3

1800 46.4 46.4 x 10
3

1800
5.50 0.85 X 10
-3

2100 50.4 50.4 x 10
3

2100
5.50 0.80 X 10
-3

K Average (cm/sec) 9.6 X 10
-4








* 116*

M.K. Soil Testing Laboratory





Tabl e No. 5/ 11

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 12

1) Date of Test : 21/5/2008
2) Test No. : FPLT 12
3) Co-Ordinate : E. 757.48m, N. 358.22m
4) Ground RL : 47.72m
5) Depth of Test : 7.50m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 12.5 12.5 x 10
3

300
7.50 1.01 X 10
-3

600 20.2 20.2 x 10
3

600
7.50 0.82 X 10
-3

900 27.6 27.6 x 10
3

900
7.50 0.74 X 10
-3

1200 31.3 31.3 x 10
3

1200
7.50 0.63 X 10
-3

1500 34.9 34.9 x 10
3

1500
7.50 0.56 X 10
-3

1800 37.8 37.8 x 10
3

1800
7.50 0.51 X 10
-3

K Average (cm/sec) 7.12 X 10
-4











* 117*

M.K. Soil Testing Laboratory






Tabl e No. 5/ 12

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 14

1) Date of Test : 23/6/2008
2) Test No. : FPLT 14
3) Co-Ordinate : E. 413.47m, N. 1488.04m
4) Ground RL : 41.200m
5) Depth of Test : 5.0m
6) Dia of Hole : 5
7) Radius of Hole :

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 3.1 3.1 x 10
3

300
5.0 6.83 X 10
-4

600 4.5 4.5 x 10
3

600
5.0 4.96 X 10
-4

900 6.0 6.0 x 10
3

900
5.0 4.41 X 10
-4

1200 7.5 7.5 x 10
3

1200
5.0 4.13 X 10
-4

1500 9.2 9.2 x 10
3

1500
5.0 4.06 X 10
-4

1800 10.6 10.6 x 10
3

1800
5.0 3.89 X 10
-4

K Average (cm/sec) 4.62 X 10
-4










* 118*

M.K. Soil Testing Laboratory








Tabl e No. 5/ 13

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 15

1) Date of Test : 23/6/2008
2) Test No. : FPLT 15
3) Co-Ordinate : E. 643.77m, N. 1514.56m
4) Ground RL :
5) Depth of Test : 6.0m
6) Dia of Hole : 5
7) Radius of Hole : 6.3cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 3.2 3.2 x 10
3

300
6.0 5.13 X 10
-4

600 5.4 5.4 x 10
3

600
6.0 4.33 X 10
4

900 7.8 7.8 x 10
3

900
6.0 4.17 X 10
4

1200 10.9 10.9 x 10
3

1200
6.0 4.37 X 10
4

1500 13.4 13.4 x 10
3

1500
6.0 4.30 X 10
4

1800 15.6 15.6 x 10
3

1800
6.0 4.17 X 10
4

K Average (cm/sec) 4.41 X 10
4








* 119*

M.K. Soil Testing Laboratory







Tabl e No. 5/ 14

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 16


1) Date of Test : 23/6/2008
2) Test No. : FPLT 16
3) Co-Ordinate : E. 1045.10, N. 1413.84m
4) Ground RL : 45.105m
5) Depth of Test : 4.0m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 8.0 8 x 10
3

300
4.0 1.21 X 10
-3

600 12.5 12.5 x 10
3

600
4.0 0.95 X 10
-3

900 17.5 17.5 x 10
3

900
4.0 0.84 X 10
-4

1200 22.7 22.7 x 10
3

1200
4.0 8.6 X 10
-4

1500 28.3 28.3 x 10
3

1500
4.0 8.58 X 10
-4

1800 33 33 x 10
3

1800
4.0 8.33 X 10
-4

K Average (cm/sec) 9.33 X 10
-4








* 120*

M.K. Soil Testing Laboratory




Tabl e No. 5/ 15

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 17


1) Date of Test : 23/6/2008
2) Test No. : FPLT 17
3) Co-Ordinate : E. 886.70, N. 1615.18m
4) Ground RL : 42.62m
5) Depth of Test : 3.0m
6) Dia of Hole : 5
7) Radius of Hole : 7.5cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 3 3 x 10
3

300
3.0 8.08 X 10
-4

600 4.4 4.4 x 10
3

600
3.0 5.93 X 10
-4

900 6.0 6.0 x 10
3

900
3.0 5.39 X 10
-4

1200 7.1 7.1 x 10
3

1200
3.0 4.78 X 10
-4

1500 8.1 8.1 x 10
3

1500
3.0 4.36 X 10
-4

1800 9.2 9.2 x 10
3

1800
3.0 4.13 X 10
-4

K Average (cm/sec) 5.44 X 10
-4











* 121*

M.K. Soil Testing Laboratory



Tabl e No. 5/ 16

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 18


1) Date of Test : 23/6/2008
2) Test No. : FPLT 17
3) Co-Ordinate : E. 752.59, N. 1314.14m
4) Ground RL : 44.70m
5) Depth of Test : 4.5m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 5.3 5.3 x 10
3

300
4.5 7.14 X 10
-4

600 8.3 8.3 x 10
3

600
4.5 5.59 X 10
-4

900 11.4 11.4 x 10
3

900
4.5 5.12 X 10
-4

1200 14.6 14.6 x 10
3

1200
4.5 4.92 X 10
-4

1500 17.9 17.9 x 10
3

1500
4.5 4.82 X 10
-4

1800 21.5 21.5 x 10
3

1800
4.5 4.83 X 10
-4

K Average (cm/sec) 5.40 X 10
-4







.

* 122*

M.K. Soil Testing Laboratory


Tabl e No. 5/ 17

FI ELD PERMEABI LI TY TEST BY CONSTANT HEAD METHOD

FPLT - 19

1) Date of Test : 23/6/2008
2) Test No. : FPLT 17
3) Co-Ordinate : E. 986.14, N. 1486.31m
4) Ground RL : 42.30m
5) Depth of Test : 5.5m
6) Dia of Hole : 8
7) Radius of Hole : 10cm

Time
(sec)
Discharge
in lit
Q
(m
3
/sec)
H (m)
K = Q
5.5. r. H
(cm/sec)
300 5.7 5.7 x 10
3

300
5.5 6.28 X 10
-4

600 10.7 10.7 x 10
3

600
5.5 5.90 X 10
-4

900 14.9 14.9 x 10
3

900
5.5 5.47 X 10
-4

1200 19 19 x 10
3

1200
5.5 5.23 X 10
-4

1500 22.2 22.2 x 10
3

1500
5.5 4.90 X 10
-4

1800 26.1 26.1 x 10
3

1800
5.5 4.79 X 10
-4

2100 29.8 29.8 x 10
3

2100
5.5 4.69 X 10
-4

2400 33.5 33.5 x 10
3

2400
5.5 4.61 X 10
-4

K Average (cm/sec) 5.23 X 10
-4






.

* 123*

M.K. Soil Testing Laboratory


Tabl e No. 6/ 1

CYCLI C PLATE LOAD TEST
CPLT - 1

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based Thermal
Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar

TESTNO. CPLT 1
CO-ORDINATES(m) E.490.60, E. 777.72
RL of GL (m) 44.73m
Depth of Test(m) 3.50 (RL 41.23m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 22/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 0.205
0.0 0.0 0.045
0.16
2. 6.0 16.67 1.485
0.0 0.0 1.11
0.375
3. 9.0 25.0 2.35
0.0 0.0 1.72
0.63
4. 12.0 33.33 3.015
0.0 0.00 2.47
0.545
5. 18.0 50.0 3.82
0.0 0.0 2.935
0.885
6. 24.0 66.67 4.985
0.0 0.00 4.045
0.94
7. 30.0 83.33 6.055
0.0 0.00 5.11
0.00 0.00 8.065
0.945


.

* 124*

M.K. Soil Testing Laboratory

Tabl e No. 6/ 2

CYCLI C PLATE LOAD TEST
CPLT - 2

TESTNO. CPLT 2
CO-ORDINATES(m) E.600.0, E. 807.04
RL of GL (m) 45.99m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 21/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 0.45
0.0 0.0 0.45
0.00
2. 6.0 16.67 1.780
0.0 0.0 1.715
0.065
3. 9.0 25.0 2.950
0.0 0.0 2.790
0.160
4. 12.0 33.33 3.805
0.0 0.00 3.595
0.210
5. 18.0 50.0 6.175
0.0 0.0 6.030
0.145
6. 24.0 66.67 7.950
0.0 0.00 7.48
0.470
7. 30.0 83.33 9.025
0.0 0.00 8.050
0.00 0.00 8.065
0.975


.

* 125*

M.K. Soil Testing Laboratory

Tabl e No. 6/ 3

CYCLI C PLATE LOAD TEST
CPLT - 3

TESTNO. CPLT 3
CO-ORDINATES(m) E.477.88, E. 669.27
RL of GL (m) 45.34m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 21/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 0.355
0.0 0.0 0.285
0.07
2. 6.0 16.67 1.320
0.0 0.0 1.080
0.240
3. 9.0 25.0 1.920
0.0 0.0 1.65
0.270
4. 12.0 33.33 2.580
0.0 0.00 2.085
0.495
5. 18.0 50.0 5.375
0.0 0.0 4.715
0.660
6. 24.0 66.67 6.250
0.0 0.00 5.530
0.720
7. 30.0 83.33 8.190
0.0 0.00 7.585
0.605


.

* 126*

M.K. Soil Testing Laboratory

Tabl e No. 6/ 4

CYCLI C PLATE LOAD TEST
CPLT - 4

TESTNO. CPLT 4
CO-ORDINATES(m) E.618.02, E. 700.04
RL of GL (m) 48.010m
Depth of Test(m) 3.50 (RL 44.51m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 19/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 0.58
0.0 0.0 0.495
0.82
2. 6.0 16.67 2.065
0.0 0.0 1.905
0.16
3. 9.0 25.0 3.05
0.0 0.0 2.71
0.34
4. 12.0 33.33 3.895
0.0 0.00 3.505
0.39
5. 18.0 50.0 5.305
0.0 0.0 4.710
0.595
6. 24.0 66.67 6.46
0.0 0.00 5.26
1.20
7. 30.0 83.33 7.955
0.0 0.00 6.535
1.42
8. 36.0 100.00 9.41
0.00 0.00 8.065
1.345

.

* 127*

M.K. Soil Testing Laboratory




Tabl e No. 6/ 5

CYCLI C PLATE LOAD TEST
CPLT - 5

TESTNO. CPLT 5
CO-ORDINATES(m) E.451.81, E. 609.56
RL of GL (m) 46.48m
Depth of Test(m) 3.50 (RL 42.98m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 2/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 1.495
0.0 0.0 1.205
0.29
2. 6.0 16.67 2.855
0.0 0.0 2.455
0.40
3. 9.0 25.0 4.025
0.0 0.0 3.315
0.071
4. 12.0 33.33 4.740
0.0 0.00 3.915
0.825
5. 18.0 50.0 5.665
0.0 0.0 4.625
1.04
6. 24.0 66.67 6.410
0.0 0.00 5.685
0.725
7. 30.0 83.33 7.210
0.0 0.00 5.485
1.725
8. 36.0 100.00 - -
0.00 0.00 - -

.

* 128*

M.K. Soil Testing Laboratory

Tabl e No. 6/ 6

CYCLI C PLATE LOAD TEST
CPLT - 7

TESTNO. CPLT 7
CO-ORDINATES(m) E.628.63, E. 582.01
RL of GL (m) 49.02m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 23/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
Elastic
Settlement (mm)
1. 3.0 8.33 0.350
0.0 0.0 0.320
0.030

2. 6.0 16.67 1.245
0.0 0.0 1.220
0.025
3. 9.0 25.0 1.760
0.0 0.0 1.675
0.085
4. 12.0 33.33 2.690
0.0 0.00 2.615
0.075
5. 18.0 50.0 4.375
0.0 0.0 3.875
0.50
6. 24.0 66.67 6.190
0.0 0.00 5.330
0.860
7. 30.0 83.33 8.820
0.0 0.00 7.350
1.470















.

* 129*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 1
STATI C PLATE LOAD TEST
SPLT - 1

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based Thermal
Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar


TESTNO. SPLT 1
CO-ORDINATES(m) E.550.2, N. 878.8
RL of GL (m) 44.480m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 4/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 1.035
2. 4.50 12.5 -
3. 6.00 16.67 2.165
4. 9.00 25.0 3.99
5. 12.00 33.33 5.345
6. 18.00 50.0 11.54
7. 24.00 66.67 22.765
8. 30.00 83.33 -
9. 36.00 100.00 -


.

* 130*

M.K. Soil Testing Laboratory
Tabl e No. 7/ 2
STATI C PLATE LOAD TEST
SPLT - 2

TESTNO. SPLT 2
CO-ORDINATES(m) E.550.78, N. 513.28
RL of GL (m) 47.25m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 27/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 0.205
2. 4.50 12.5 -
3. 6.00 16.67 0.820
4. 9.00 25.0 1.710
5. 12.00 33.33 2.625
6. 18.00 50.0 5.310
7. 24.00 66.67 7.950
8. 30.00 83.33 9.605
9. 36.00 100.00 -


.

* 131*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 3
STATI C PLATE LOAD TEST
SPLT - 3

TESTNO. SPLT 3
CO-ORDINATES(m) E.576.15, N. 529.13
RL of GL (m) 48.300m
Depth of Test(m) 3.50 (RL = 44.8m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 25/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 1.735
2. 4.50 12.5 -
3. 6.00 16.67 2.60
4. 9.00 25.0 -
5. 12.00 33.33 4.215
6. 18.00 50.0 5.145
7. 24.00 66.67 6.185
8. 30.00 83.33 7.035
9. 36.00 100.00 -

.

* 132*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 4
STATI C PLATE LOAD TEST
SPLT - 5

TESTNO. SPLT 5
CO-ORDINATES(m) E.580.95, N. 427.59
RL of GL (m) 49.75m
Depth of Test(m) 3.50 (RL = 46.25m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 29/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 0.320
2. 4.50 12.5 -
3. 6.00 16.67 0.780
4. 9.00 25.0 1.785
5. 12.00 33.33 2.435
6. 18.00 50.0 3.71
7. 24.00 66.67 4.615
8. 30.00 83.33 8.525
9. 36.00 100.00 -



















.

* 133*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 5
STATI C PLATE LOAD TEST
SPLT - 6

TESTNO. SPLT 6
CO-ORDINATES(m) E.465.34, N. 340.62
RL of GL (m) 48.10m
Depth of Test(m) 3.50 (RL = 44.6m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 28/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 2.27
2. 4.50 12.5 -
3. 6.00 16.67 3.10
4. 9.00 25.0 4.06
5. 12.00 33.33 5.125
6. 18.00 50.0 6.435
7. 24.00 66.67 7.45
8. 30.00 83.33 9.555
9. 36.00 100.00 -

.

* 134*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 6
STATI C PLATE LOAD TEST
SPLT - 7

TESTNO. SPLT 7
CO-ORDINATES(m) E.580.95, N. 340.62
RL of GL (m) 49.88m
Depth of Test(m) 3.50
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 25/6/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 0.475
2. 4.50 12.5 -
3. 6.00 16.67 1.085
4. 9.00 25.0 1.605
5. 12.00 33.33 2.435
6. 18.00 50.0 5.035
7. 24.00 66.67 7.015
8. 30.00 83.33 9.240
9. 36.00 100.00 -

.

* 135*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 7
STATI C PLATE LOAD TEST
SPLT - 8

TESTNO. SPLT 8
CO-ORDINATES(m) E.733.42, N. 694.51
RL of GL (m) 46.95m
Depth of Test(m) 3.50 (RL = 43.45m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 12/5/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 0.015
2. 4.50 12.5 -
3. 6.00 16.67 0.65
4. 9.00 25.0 1.35
5. 12.00 33.33 1.88
6. 18.00 50.0 2.825
7. 24.00 66.67 3.69
8. 30.00 83.33 4.74
9. 36.00 100.00 5.585







.

* 136*

M.K. Soil Testing Laboratory

Tabl e No. 7/ 8
STATI C PLATE LOAD TEST
SPLT - 9

TESTNO. SPLT 9
CO-ORDINATES(m) E.894.86, N. 694.51
RL of GL (m) 47.32m
Depth of Test(m) 3.50 (RL = 43.82m)
Size of Plate 60cm x 60cm x 2.5cm (thick)
Date of Test 30/4/2008

Sr. No. Load (t) Load Intensity
(t/m
2
)
Average
Settlement (mm)
1. 3.0 8.33 0.71
2. 4.50 12.5 1.505
3. 6.00 16.67 2.465
4. 9.00 25.0 2.790
5. 12.00 33.33 4.205
6. 18.00 50.0 5.115
7. 24.00 66.67 6.15
8. 30.00 83.33 6.91
9. 36.00 100.00 8.875
















.

* 137*

M.K. Soil Testing Laboratory
Tabl e No. 8
CONSOLI DATI ON TEST

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based Thermal
Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar

Pressure 1 to 2 kg/cm
2
Range (kg/cm
2
) BH No. Depth (m)
Cv (cm
2
/sec) Mv Cv (cm
2
/sec) Mv
Cc
BH - 13 6.0 1.55 x10
3
0.0026 1.13 x10
3
0.0028 0.016
BH 19 15.0 8.06 x10
4
0.023 1.09 x10
3
0.012 0.13
BH 30 6.0 6.54 x10
4
0.0026 3.43 x10
3
0.0015 0.020
BH 33 1.50 2.75 x10
3
0.0030 9.85 x10
4
0.0012 0.013
BH 37 9.0 1.14 x10
3
0.001 1.45 x10
3
0.0013 0.017
BH 51 12.0 1.65 x10
3
0.0035 9.79 x10
4
0.0018 0.020
BH 52 1.50 1.65 x10
3
0.0031 1.30 x10
3
0.0013 0.020
BH 65 1.50 1.13 x10
3
0.014 1.71 x10
3
0.0065 0.08
BH 80 15.0 1.49 x10
3
0.0029 1.54 x10
3
0.0014 0.017
BH 45 6.0 9.93 x10
4
0.0026 1.62 x10
3
0.0018 0.062

.

* 138*

M.K. Soil Testing Laboratory

Tabl e No. 9/ 1
ELECTRI CAL RESI STI VI TY TEST

Sub: Geotechnical investigation work for proposed to installation of 2 x 250MW Lignite Based Thermal
Power Plant at Padva Village, Tal : Ghogha, Dist : Bhavnagar, Gujarat State.

CLIENT: Bhavnagar Energy Company Limited, Gandhinagar


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 1. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 4.856 5.233 5.563 5.705 5.339
2 3.0 4.50 1.50 5.940 6.223 6.506 6.600 6.317
3 6.0 9.00 3.00 6.977 8.486 8.109 8.486 8.014
4 8.0 12.00 4.00 7.794 9.303 10.057 9.554 9.177
5 10.0 15.00 5.00 8.800 9.743 11.000 10.057 9.900
6 12.0 18.00 6.00 10.560 10.937 10.183 11.314 10.749



APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 1. SPREADING : NORTH - SOUTH
VILLAGE : PADVA,
GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.)
3S/2
(m.)
S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY
R = K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.53 0.50 0.515 4.856
2 3.0 4.50 1.50 18.857 0.31 0.32 0.315 5.940
3 6.0 9.00 3.00 37.714 0.19 0.18 0.185 6.977
4 8.0 12.00 4.00 50.286 0.16 0.15 0.155 7.794
5 10.0 15.00 5.00 62.857 0.14 0.14 0.140 8.800
6 12.0 18.00 6.00 75.429 0.13 0.15 0.140 10.560
.

* 139*

M.K. Soil Testing Laboratory

APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 1. SPREADING : NORTH - SOUTH
VILLAGE : PADVA,
GHOGHA
LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.)
3S/2
(m.)
S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY
R = K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.55 0.56 0.555 5.233
2 3.0 4.50 1.50 18.857 0.32 0.34 0.330 6.223
3 6.0 9.00 3.00 37.714 0.22 0.23 0.225 8.486
4 8.0 12.00 4.00 50.286 0.19 0.18 0.185 9.303
5 10.0 15.00 5.00 62.857 0.16 0.15 0.155 9.743
6 12.0 18.00 6.00 75.429 0.13 0.16 0.145 10.937



APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 1. SPREADING : EAST - WEST.
VILLAGE : PADVA,
GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.)
3S/2
(m.)
S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY
R = K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.59 0.59 0.590 5.563
2 3.0 4.50 1.50 18.857 0.34 0.35 0.345 6.506
3 6.0 9.00 3.00 37.714 0.21 0.22 0.215 8.109
4 8.0 12.00 4.00 50.286 0.20 0.20 0.200 10.057
5 10.0 15.00 5.00 62.857 0.17 0.18 0.175 11.000
6 12.0 18.00 6.00 75.429 0.13 0.14 0.135 10.183


ERT - 1. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R = K *
V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.60 0.61 0.605 5.705
2 3.0 4.50 1.50 18.857 0.35 0.35 0.350 6.600
3 6.0 9.00 3.00 37.714 0.22 0.23 0.225 8.486
4 8.0 12.00 4.00 50.286 0.19 0.19 0.190 9.554
5 10.0 15.00 5.00 62.857 0.16 0.16 0.160 10.057
6 12.0 18.00 6.00 75.429 0.15 0.15 0.150 11.314


.

* 140*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 2
ELECTRI CAL RESI STI VI TY TEST



APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 2. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 9.523 10.042 9.146 10.183 9.724
2 3.0 4.50 1.50 5.214 9.806 8.297 9.523 8.210
3 6.0 9.00 3.00 8.297 8.486 6.789 8.297 7.967
4 8.0 12.00 4.00 6.537 6.537 5.280 3.344 5.425
5 10.0 15.00 5.00 5.469 5.594 4.966 5.689 5.429
6 12.0 18.00 6.00 5.355 5.318 5.054 5.355 5.271


ERT NO. - 2. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.000 1.020 1.010 9.523
2 3.0 4.50 1.50 18.857 0.500 0.053 0.277 5.214
3 6.0 9.00 3.00 37.714 0.220 0.220 0.220 8.297
4 8.0 12.00 4.00 50.286 0.130 0.130 0.130 6.537
5 10.0 15.00 5.00 62.857 0.087 0.087 0.087 5.469
6 12.0 18.00 6.00 75.429 0.071 0.071 0.071 5.355


ERT NO. - 2. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.050 1.080 1.065 10.042
2 3.0 4.50 1.50 18.857 0.510 0.530 0.520 9.806
3 6.0 9.00 3.00 37.714 0.230 0.220 0.225 8.486
4 8.0 12.00 4.00 50.286 0.130 0.130 0.130 6.537
5 10.0 15.00 5.00 62.857 0.091 0.087 0.089 5.594
6 12.0 18.00 6.00 75.429 0.070 0.071 0.071 5.318

.

* 141*

M.K. Soil Testing Laboratory
ERT NO. - 2. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY
R = K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.970 0.970 0.970 9.146
2 3.0 4.50 1.50 18.857 0.430 0.450 0.440 8.297
3 6.0 9.00 3.00 37.714 0.180 0.180 0.180 6.789
4 8.0 12.00 4.00 50.286 0.110 0.100 0.105 5.280
5 10.0 15.00 5.00 62.857 0.082 0.076 0.079 4.966
6 12.0 18.00 6.00 75.429 0.066 0.068 0.067 5.054


ERT NO. - 2. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY
R = K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.090 1.070 1.080 10.183
2 3.0 4.50 1.50 18.857 0.500 0.510 0.505 9.523
3 6.0 9.00 3.00 37.714 0.220 0.220 0.220 8.297
4 8.0 12.00 4.00 50.286 0.120 0.013 0.067 3.344
5 10.0 15.00 5.00 62.857 0.090 0.091 0.091 5.689
6 12.0 18.00 6.00 75.429 0.071 0.071 0.071 5.355
.

* 142*

M.K. Soil Testing Laboratory

Tabl e No. 10/ 3
ELECTRI CAL RESI STI VI TY TEST



APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 3. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 16.171 17.208 16.595 18.009 16.996
2 3.0 4.50 1.50 10.277 10.937 11.220 11.503 10.984
3 6.0 9.00 3.00 7.731 8.486 8.109 8.674 8.250
4 8.0 12.00 4.00 8.297 9.303 9.806 10.057 9.366
5 10.0 15.00 5.00 6.286 8.171 7.229 9.429 7.779
6 12.0 18.00 6.00 5.619 6.185 6.072 6.298 6.044


ERT NO. - 3. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.710 1.720 1.715 16.171
2 3.0 4.50 1.50 18.857 0.550 0.540 0.545 10.277
3 6.0 9.00 3.00 37.714 0.200 0.210 0.205 7.731
4 8.0 12.00 4.00 50.286 0.170 0.160 0.165 8.297
5 10.0 15.00 5.00 62.857 0.100 0.100 0.100 6.286
6 12.0 18.00 6.00 75.429 0.077 0.072 0.075 5.619
ERT NO. - 3. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.820 1.830 1.825 17.208
2 3.0 4.50 1.50 18.857 0.560 0.600 0.580 10.937
3 6.0 9.00 3.00 37.714 0.220 0.230 0.225 8.486
4 8.0 12.00 4.00 50.286 0.180 0.190 0.185 9.303
5 10.0 15.00 5.00 62.857 0.130 0.130 0.130 8.171
6 12.0 18.00 6.00 75.429 0.082 0.082 0.082 6.185


.

* 143*

M.K. Soil Testing Laboratory


ERT/SEHMS NO. - 3. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.750 1.770 1.760 16.595
2 3.0 4.50 1.50 18.857 0.590 0.600 0.595 11.220
3 6.0 9.00 3.00 37.714 0.220 0.210 0.215 8.109
4 8.0 12.00 4.00 50.286 0.200 0.190 0.195 9.806
5 10.0 15.00 5.00 62.857 0.110 0.120 0.115 7.229
6 12.0 18.00 6.00 75.429 0.080 0.081 0.081 6.072


ERT.-3. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.920 1.900 1.910 18.009
2 3.0 4.50 1.50 18.857 0.600 0.620 0.610 11.503
3 6.0 9.00 3.00 37.714 0.230 0.230 0.230 8.674
4 8.0 12.00 4.00 50.286 0.200 0.200 0.200 10.057
5 10.0 15.00 5.00 62.857 0.150 0.150 0.150 9.429
6 12.0 18.00 6.00 75.429 0.084 0.083 0.084 6.298









.

* 144*

M.K. Soil Testing Laboratory

Tabl e No. 10/ 4
ELECTRI CAL RESI STI VI TY TEST



APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 4. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 7.355 7.732 7.025 7.779 7.472
2 3.0 4.50 1.50 6.506 7.354 5.846 7.826 6.883
3 6.0 9.00 3.00 8.297 8.674 7.166 7.920 8.014
4 8.0 12.00 4.00 9.554 9.051 7.040 7.794 8.360
5 10.0 15.00 5.00 9.429 10.057 7.543 7.543 8.643
6 12.0 18.00 6.00 9.806 10.560 8.297 4.563 8.307


ERT NO. - 4. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.780 0.780 0.780 7.355
2 3.0 4.50 1.50 18.857 0.340 0.350 0.345 6.506
3 6.0 9.00 3.00 37.714 0.220 0.220 0.220 8.297
4 8.0 12.00 4.00 50.286 0.190 0.190 0.190 9.554
5 10.0 15.00 5.00 62.857 0.150 0.150 0.150 9.429
6 12.0 18.00 6.00 75.429 0.130 0.130 0.130 9.806


ERT NO. - 4. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.820 0.820 0.820 7.732
2 3.0 4.50 1.50 18.857 0.390 0.390 0.390 7.354
3 6.0 9.00 3.00 37.714 0.230 0.230 0.230 8.674
4 8.0 12.00 4.00 50.286 0.180 0.180 0.180 9.051
5 10.0 15.00 5.00 62.857 0.160 0.160 0.160 10.057
6 12.0 18.00 6.00 75.429 0.140 0.140 0.140 10.560
.

* 145*

M.K. Soil Testing Laboratory


ERT. - 4. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.740 0.750 0.745 7.025
2 3.0 4.50 1.50 18.857 0.310 0.310 0.310 5.846
3 6.0 9.00 3.00 37.714 0.190 0.190 0.190 7.166
4 8.0 12.00 4.00 50.286 0.140 0.140 0.140 7.040
5 10.0 15.00 5.00 62.857 0.120 0.120 0.120 7.543
6 12.0 18.00 6.00 75.429 0.110 0.110 0.110 8.297


ERT.- 4. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.820 0.830 0.825 7.779
2 3.0 4.50 1.50 18.857 0.410 0.420 0.415 7.826
3 6.0 9.00 3.00 37.714 0.200 0.220 0.210 7.920
4 8.0 12.00 4.00 50.286 0.150 0.160 0.155 7.794
5 10.0 15.00 5.00 62.857 0.120 0.120 0.120 7.543
6 12.0 18.00 6.00 75.429 0.110 0.011 0.061 4.563























.

* 146*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 5
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 5. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 39.177 42.619 40.875 40.545 40.804
2 3.0 4.50 1.50 29.700 30.737 31.020 30.360 30.454
3 6.0 9.00 3.00 16.217 17.537 21.308 17.726 18.197
4 8.0 12.00 4.00 11.063 13.074 14.583 13.577 13.074
5 10.0 15.00 5.00 8.171 11.314 10.057 11.629 10.293
6 12.0 18.00 6.00 6.713 9.429 8.297 9.051 8.373


ERT NO. - 5. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 4.140 4.170 4.155 39.177
2 3.0 4.50 1.50 18.857 1.580 1.570 1.575 29.700
3 6.0 9.00 3.00 37.714 0.440 0.420 0.430 16.217
4 8.0 12.00 4.00 50.286 0.230 0.210 0.220 11.063
5 10.0 15.00 5.00 62.857 0.130 0.130 0.130 8.171
6 12.0 18.00 6.00 75.429 0.090 0.088 0.089 6.713


ERT NO. - 5. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 4.540 4.500 4.520 42.619
2 3.0 4.50 1.50 18.857 1.660 1.600 1.630 30.737
3 6.0 9.00 3.00 37.714 0.450 0.480 0.465 17.537
4 8.0 12.00 4.00 50.286 0.260 0.260 0.260 13.074
5 10.0 15.00 5.00 62.857 0.180 0.180 0.180 11.314
6 12.0 18.00 6.00 75.429 0.130 0.120 0.125 9.429


.

* 147*

M.K. Soil Testing Laboratory


ERT. - 5. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 4.340 4.330 4.335 40.875
2 3.0 4.50 1.50 18.857 1.640 1.650 1.645 31.020
3 6.0 9.00 3.00 37.714 0.570 0.560 0.565 21.308
4 8.0 12.00 4.00 50.286 0.290 0.290 0.290 14.583
5 10.0 15.00 5.00 62.857 0.150 0.170 0.160 10.057
6 12.0 18.00 6.00 75.429 0.110 0.110 0.110 8.297








ERT.-5. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 4.320 4.280 4.300 40.545
2 3.0 4.50 1.50 18.857 1.600 1.620 1.610 30.360
3 6.0 9.00 3.00 37.714 0.460 0.480 0.470 17.726
4 8.0 12.00 4.00 50.286 0.270 0.270 0.270 13.577
5 10.0 15.00 5.00 62.857 0.190 0.180 0.185 11.629
6 12.0 18.00 6.00 75.429 0.120 0.120 0.120 9.051
















.

* 148*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 6
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 6. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 7.402 7.779 7.166 8.109 7.614
2 3.0 4.50 1.50 6.223 6.789 6.223 8.014 6.812
3 6.0 9.00 3.00 6.600 7.920 6.600 8.863 7.496
4 8.0 12.00 4.00 6.286 8.046 6.286 9.303 7.480
5 10.0 15.00 5.00 5.154 8.800 6.286 8.171 7.103
6 12.0 18.00 6.00 6.072 6.977 6.034 7.317 6.600


ERT NO. - 6. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.800 0.770 0.785 7.402
2 3.0 4.50 1.50 18.857 0.330 0.330 0.330 6.223
3 6.0 9.00 3.00 37.714 0.180 0.170 0.175 6.600
4 8.0 12.00 4.00 50.286 0.120 0.130 0.125 6.286
5 10.0 15.00 5.00 62.857 0.082 0.082 0.082 5.154
6 12.0 18.00 6.00 75.429 0.080 0.081 0.081 6.072

ERT NO. - 6. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.820 0.830 0.825 7.779
2 3.0 4.50 1.50 18.857 0.360 0.360 0.360 6.789
3 6.0 9.00 3.00 37.714 0.200 0.220 0.210 7.920
4 8.0 12.00 4.00 50.286 0.160 0.160 0.160 8.046
5 10.0 15.00 5.00 62.857 0.140 0.140 0.140 8.800
6 12.0 18.00 6.00 75.429 0.092 0.093 0.093 6.977



.

* 149*

M.K. Soil Testing Laboratory

ERT. - 6. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.780 0.740 0.760 7.166
2 3.0 4.50 1.50 18.857 0.330 0.330 0.330 6.223
3 6.0 9.00 3.00 37.714 0.180 0.170 0.175 6.600
4 8.0 12.00 4.00 50.286 0.120 0.130 0.125 6.286
5 10.0 15.00 5.00 62.857 0.100 0.100 0.100 6.286
6 12.0 18.00 6.00 75.429 0.082 0.078 0.080 6.034


ERT.-6. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 0.840 0.880 0.860 8.109
2 3.0 4.50 1.50 18.857 0.420 0.430 0.425 8.014
3 6.0 9.00 3.00 37.714 0.230 0.240 0.235 8.863
4 8.0 12.00 4.00 50.286 0.180 0.190 0.185 9.303
5 10.0 15.00 5.00 62.857 0.130 0.130 0.130 8.171
6 12.0 18.00 6.00 75.429 0.094 0.100 0.097 7.317























.

* 150*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 7
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 7. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 2.876 3.253 3.112 3.300 3.135
2 3.0 4.50 1.50 2.734 3.300 3.677 3.394 3.276
3 6.0 9.00 3.00 3.489 3.413 3.507 3.451 3.465
4 8.0 12.00 4.00 4.299 4.450 4.475 4.501 4.431
5 10.0 15.00 5.00 5.186 5.469 5.060 5.406 5.280
6 12.0 18.00 6.00 5.657 6.336 5.883 5.959 5.959


ERT NO. - 7. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.300 0.310 0.305 2.876
2 3.0 4.50 1.50 18.857 0.150 0.140 0.145 2.734
3 6.0 9.00 3.00 37.714 0.089 0.096 0.093 3.489
4 8.0 12.00 4.00 50.286 0.086 0.085 0.086 4.299
5 10.0 15.00 5.00 62.857 0.083 0.082 0.083 5.186
6 12.0 18.00 6.00 75.429 0.076 0.074 0.075 5.657


ERT NO. - 7. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.340 0.350 0.345 3.253
2 3.0 4.50 1.50 18.857 0.170 0.180 0.175 3.300
3 6.0 9.00 3.00 37.714 0.090 0.091 0.091 3.413
4 8.0 12.00 4.00 50.286 0.088 0.089 0.089 4.450
5 10.0 15.00 5.00 62.857 0.087 0.087 0.087 5.469
6 12.0 18.00 6.00 75.429 0.088 0.080 0.084 6.336


.

* 151*

M.K. Soil Testing Laboratory

ERT. - 7. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.320 0.340 0.330 3.112
2 3.0 4.50 1.50 18.857 0.190 0.200 0.195 3.677
3 6.0 9.00 3.00 37.714 0.092 0.094 0.093 3.507
4 8.0 12.00 4.00 50.286 0.089 0.089 0.089 4.475
5 10.0 15.00 5.00 62.857 0.080 0.081 0.081 5.060
6 12.0 18.00 6.00 75.429 0.079 0.077 0.078 5.883



ERT.-7. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.350 0.350 0.350 3.300
2 3.0 4.50 1.50 18.857 0.180 0.180 0.180 3.394
3 6.0 9.00 3.00 37.714 0.091 0.092 0.092 3.451
4 8.0 12.00 4.00 50.286 0.089 0.090 0.090 4.501
5 10.0 15.00 5.00 62.857 0.086 0.086 0.086 5.406
6 12.0 18.00 6.00 75.429 0.079 0.079 0.079 5.959






















.

* 152*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 8
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 8. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.300 2.320 2.310 21.781
2 3.0 4.50 1.50 18.857 1.180 1.170 1.175 22.157
3 6.0 9.00 3.00 37.714 0.520 0.530 0.525 19.800
4 8.0 12.00 4.00 50.286 0.260 0.270 0.265 13.326
5 10.0 15.00 5.00 62.857 0.160 0.160 0.160 10.057
6 12.0 18.00 6.00 75.429 0.100 0.100 0.100 7.543


ERT NO. - 8. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 2.330 2.340 2.335 22.017
2 3.0 4.50 1.50 18.857 1.160 1.170 1.165 21.968
3 6.0 9.00 3.00 37.714 0.490 0.490 0.490 18.480
4 8.0 12.00 4.00 50.286 0.280 0.290 0.285 14.332
5 10.0 15.00 5.00 62.857 0.150 0.160 0.155 9.743
6 12.0 18.00 6.00 75.429 0.110 0.110 0.110 8.297


ERT. - 8. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 2.230 2.260 2.245 21.168
2 3.0 4.50 1.50 18.857 1.140 1.110 1.125 21.214
3 6.0 9.00 3.00 37.714 0.470 0.490 0.480 18.103
4 8.0 12.00 4.00 50.286 0.230 0.240 0.235 11.817
5 10.0 15.00 5.00 62.857 0.130 0.140 0.135 8.486
6 12.0 18.00 6.00 75.429 0.090 0.089 0.090 6.751


.

* 153*

M.K. Soil Testing Laboratory

ERT.-8. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 2.340 2.360 2.350 22.158
2 3.0 4.50 1.50 18.857 1.190 1.190 1.190 22.440
3 6.0 9.00 3.00 37.714 0.490 0.490 0.490 18.480
4 8.0 12.00 4.00 50.286 0.280 0.290 0.285 14.332
5 10.0 15.00 5.00 62.857 0.170 0.170 0.170 10.686
6 12.0 18.00 6.00 75.429 0.110 0.100 0.105 7.920








































.

* 154*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 9
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT - 9. LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 19.188 19.754 20.131 19.377 19.612
2 3.0 4.50 1.50 32.905 35.168 35.451 36.017 34.885
3 6.0 9.00 3.00 13.388 20.554 15.274 16.028 16.311
4 8.0 12.00 4.00 8.800 11.314 10.057 9.806 9.994
5 10.0 15.00 5.00 8.486 10.371 9.429 9.743 9.507


ERT NO. - 9. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.040 2.030 2.035 19.188
2 3.0 4.50 1.50 18.857 1.760 1.730 1.745 32.905
3 6.0 9.00 3.00 37.714 0.360 0.350 0.355 13.388
4 8.0 12.00 4.00 50.286 0.170 0.180 0.175 8.800
5 10.0 15.00 5.00 62.857 0.130 0.140 0.135 8.486
6 12.0 18.00 6.00 75.429 0.100 0.100 0.100 7.543
ERT NO. - 9 SPREADING : NORTH EAST- SOUTH WEST.

VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.090 2.100 2.095 19.754
2 3.0 4.50 1.50 18.857 1.870 1.860 1.865 35.168
3 6.0 9.00 3.00 37.714 0.690 0.400 0.545 20.554
4 8.0 12.00 4.00 50.286 0.220 0.230 0.225 11.314
5 10.0 15.00 5.00 62.857 0.170 0.160 0.165 10.371
6 12.0 18.00 6.00 75.429 0.120 0.130 0.125 9.429




.

* 155*

M.K. Soil Testing Laboratory
ERT. - 9. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.140 2.130 2.135 20.131
2 3.0 4.50 1.50 18.857 1.880 1.880 1.880 35.451
3 6.0 9.00 3.00 37.714 0.410 0.400 0.405 15.274
4 8.0 12.00 4.00 50.286 0.200 0.200 0.200 10.057
5 10.0 15.00 5.00 62.857 0.150 0.150 0.150 9.429
6 12.0 18.00 6.00 75.429 0.110 0.120 0.115 8.674


ERT.-9. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.050 2.060 2.055 19.377
2 3.0 4.50 1.50 18.857 1.920 1.900 1.910 36.017
3 6.0 9.00 3.00 37.714 0.430 0.420 0.425 16.028
4 8.0 12.00 4.00 50.286 0.190 0.200 0.195 9.806
5 10.0 15.00 5.00 62.857 0.150 0.160 0.155 9.743
6 12.0 18.00 6.00 75.429 0.120 0.120 0.120 9.051
























.

* 156*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 10
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT 10 LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 2.216 2.782 2.687 2.876 2.640
2 3.0 4.50 1.50 2.169 2.923 2.829 3.111 2.758
3 6.0 9.00 3.00 3.168 3.489 3.507 3.262 3.357
4 8.0 12.00 4.00 3.947 3.998 3.646 4.123 3.929
5 10.0 15.00 5.00 4.746 4.777 4.400 4.809 4.683


ERT NO. - 10. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.230 0.240 0.235 2.216
2 3.0 4.50 1.50 18.857 0.120 0.110 0.115 2.169
3 6.0 9.00 3.00 37.714 0.084 0.084 0.084 3.168
4 8.0 12.00 4.00 50.286 0.079 0.078 0.079 3.947
5 10.0 15.00 5.00 62.857 0.075 0.076 0.076 4.746
6 12.0 18.00 6.00 75.429 0.068 0.065 0.067 5.016

ERT NO. - 10. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.300 0.290 0.295 2.782
2 3.0 4.50 1.50 18.857 0.160 0.150 0.155 2.923
3 6.0 9.00 3.00 37.714 0.093 0.092 0.093 3.489
4 8.0 12.00 4.00 50.286 0.080 0.079 0.080 3.998
5 10.0 15.00 5.00 62.857 0.076 0.076 0.076 4.777
6 12.0 18.00 6.00 75.429 0.067 0.068 0.068 5.091




.

* 157*

M.K. Soil Testing Laboratory
ERT/SEHMS NO. - 10. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.280 0.290 0.285 2.687
2 3.0 4.50 1.50 18.857 0.150 0.150 0.150 2.829
3 6.0 9.00 3.00 37.714 0.092 0.094 0.093 3.507
4 8.0 12.00 4.00 50.286 0.071 0.074 0.073 3.646
5 10.0 15.00 5.00 62.857 0.070 0.070 0.070 4.400
6 12.0 18.00 6.00 75.429 0.065 0.067 0.066 4.978



ERT.-10. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.310 0.300 0.305 2.876
2 3.0 4.50 1.50 18.857 0.170 0.160 0.165 3.111
3 6.0 9.00 3.00 37.714 0.087 0.086 0.087 3.262
4 8.0 12.00 4.00 50.286 0.082 0.082 0.082 4.123
5 10.0 15.00 5.00 62.857 0.077 0.076 0.077 4.809
6 12.0 18.00 6.00 75.429 0.068 0.069 0.069 5.167























.

* 158*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 11
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT 11 LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 12.163 12.399 12.022 12.163 12.187
2 3.0 4.50 1.50 12.068 11.974 11.880 12.351 12.068
3 6.0 9.00 3.00 9.994 10.183 9.429 10.937 10.136
4 8.0 12.00 4.00 7.291 8.549 7.543 8.549 7.983
5 10.0 15.00 5.00 6.066 6.191 5.877 6.160 6.074


ERT NO. - 11. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.290 1.290 1.290 12.163
2 3.0 4.50 1.50 18.857 0.640 0.640 0.640 12.068
3 6.0 9.00 3.00 37.714 0.260 0.270 0.265 9.994
4 8.0 12.00 4.00 50.286 0.140 0.150 0.145 7.291
5 10.0 15.00 5.00 62.857 0.097 0.096 0.097 6.066
6 12.0 18.00 6.00 75.429 0.072 0.073 0.073 5.469

ERT NO. - 11. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.310 1.320 1.315 12.399
2 3.0 4.50 1.50 18.857 0.640 0.630 0.635 11.974
3 6.0 9.00 3.00 37.714 0.270 0.270 0.270 10.183
4 8.0 12.00 4.00 50.286 0.170 0.170 0.170 8.549
5 10.0 15.00 5.00 62.857 0.098 0.099 0.099 6.191
6 12.0 18.00 6.00 75.429 0.072 0.073 0.073 5.469




.

* 159*

M.K. Soil Testing Laboratory
ERT. NO. - 11. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.270 1.280 1.275 12.022
2 3.0 4.50 1.50 18.857 0.630 0.630 0.630 11.880
3 6.0 9.00 3.00 37.714 0.250 0.250 0.250 9.429
4 8.0 12.00 4.00 50.286 0.150 0.150 0.150 7.543
5 10.0 15.00 5.00 62.857 0.092 0.095 0.094 5.877
6 12.0 18.00 6.00 75.429 0.068 0.069 0.069 5.167


ERT.NO. -11. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 1.290 1.290 1.290 12.163
2 3.0 4.50 1.50 18.857 0.650 0.660 0.655 12.351
3 6.0 9.00 3.00 37.714 0.290 0.290 0.290 10.937
4 8.0 12.00 4.00 50.286 0.170 0.170 0.170 8.549
5 10.0 15.00 5.00 62.857 0.098 0.098 0.098 6.160
6 12.0 18.00 6.00 75.429 0.071 0.071 0.071 5.355
























.

* 160*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 12
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT 12 LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 22.724 22.535 22.111 22.865 22.559
2 3.0 4.50 1.50 18.668 19.328 17.348 20.366 18.928
3 6.0 9.00 3.00 13.388 15.651 12.634 16.406 14.520
4 8.0 12.00 4.00 12.069 12.069 10.811 13.829 12.194
5 10.0 15.00 5.00 11.943 11.000 9.429 11.629 11.000


ERT NO. - 12. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.400 2.420 2.410 22.724
2 3.0 4.50 1.50 18.857 1.000 0.980 0.990 18.668
3 6.0 9.00 3.00 37.714 0.350 0.360 0.355 13.388
4 8.0 12.00 4.00 50.286 0.230 0.250 0.240 12.069
5 10.0 15.00 5.00 62.857 0.190 0.190 0.190 11.943
6 12.0 18.00 6.00 75.429 0.120 0.120 0.120 9.051


ERT NO. - 12. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.400 2.380 2.390 22.535
2 3.0 4.50 1.50 18.857 1.030 1.020 1.025 19.328
3 6.0 9.00 3.00 37.714 0.420 0.410 0.415 15.651
4 8.0 12.00 4.00 50.286 0.250 0.230 0.240 12.069
5 10.0 15.00 5.00 62.857 0.170 0.180 0.175 11.000
6 12.0 18.00 6.00 75.429 0.120 0.130 0.125 9.429



.

* 161*

M.K. Soil Testing Laboratory

ERT. NO. - 12. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.330 2.360 2.345 22.111
2 3.0 4.50 1.50 18.857 0.930 0.910 0.920 17.348
3 6.0 9.00 3.00 37.714 0.340 0.330 0.335 12.634
4 8.0 12.00 4.00 50.286 0.220 0.210 0.215 10.811
5 10.0 15.00 5.00 62.857 0.150 0.150 0.150 9.429
6 12.0 18.00 6.00 75.429 0.110 0.120 0.115 8.674



ERT. NO. -12. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R
= K * V/I
(Ohm.m.)
1 1.5 2.25 0.75 9.429 2.430 2.420 2.425 22.865
2 3.0 4.50 1.50 18.857 1.090 1.070 1.080 20.366
3 6.0 9.00 3.00 37.714 0.430 0.440 0.435 16.406
4 8.0 12.00 4.00 50.286 0.270 0.280 0.275 13.829
5 10.0 15.00 5.00 62.857 0.190 0.180 0.185 11.629
6 12.0 18.00 6.00 75.429 0.130 0.140 0.135 10.183






















.

* 162*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 13
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT 13 LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 2.169 2.216 1.697 2.027 2.027
2 3.0 4.50 1.50 2.546 2.263 1.980 2.829 2.404
3 6.0 9.00 3.00 3.545 3.375 3.375 3.677 3.493
4 8.0 12.00 4.00 4.174 4.023 4.299 4.199 4.174
5 10.0 15.00 5.00 4.714 4.934 4.683 4.997 4.832


ERT NO. - 13. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.230 0.230 0.230 2.169
2 3.0 4.50 1.50 18.857 0.140 0.130 0.135 2.546
3 6.0 9.00 3.00 37.714 0.095 0.093 0.094 3.545
4 8.0 12.00 4.00 50.286 0.087 0.079 0.083 4.174
5 10.0 15.00 5.00 62.857 0.073 0.077 0.075 4.714
6 12.0 18.00 6.00 75.429 0.072 0.070 0.071 5.355

ERT NO. - 13. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.240 0.230 0.235 2.216
2 3.0 4.50 1.50 18.857 0.120 0.120 0.120 2.263
3 6.0 9.00 3.00 37.714 0.090 0.089 0.090 3.375
4 8.0 12.00 4.00 50.286 0.080 0.080 0.080 4.023
5 10.0 15.00 5.00 62.857 0.079 0.078 0.079 4.934
6 12.0 18.00 6.00 75.429 0.069 0.070 0.070 5.242




.

* 163*

M.K. Soil Testing Laboratory
ERT. NO. - 13. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.190 0.170 0.180 1.697
2 3.0 4.50 1.50 18.857 0.110 0.100 0.105 1.980
3 6.0 9.00 3.00 37.714 0.090 0.089 0.090 3.375
4 8.0 12.00 4.00 50.286 0.085 0.086 0.086 4.299
5 10.0 15.00 5.00 62.857 0.071 0.078 0.075 4.683
6 12.0 18.00 6.00 75.429 0.069 0.065 0.067 5.054



ERT.-13. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 0.220 0.210 0.215 2.027
2 3.0 4.50 1.50 18.857 0.150 0.150 0.150 2.829
3 6.0 9.00 3.00 37.714 0.097 0.098 0.098 3.677
4 8.0 12.00 4.00 50.286 0.084 0.083 0.084 4.199
5 10.0 15.00 5.00 62.857 0.079 0.080 0.080 4.997
6 12.0 18.00 6.00 75.429 0.072 0.072 0.072 5.431























.

* 164*

M.K. Soil Testing Laboratory
Tabl e No. 10/ 14
ELECTRI CAL RESI STI VI TY TEST


APPARENT RESISTIVITY OF ALL DIRECTION.
WENNER FOUR PIN METHOD.
ERT 14 LOCATION : SHOWN IN LOCATION PLAN.
VILLAGE : PADVA,
GHOGHA
APPARENT RESISTIVITY (Ohm.m.) ALL DIRECTION.

S.NO. S (m.)
3S/2
(m.)
S/2 (m.)
NORTH
-
SOUTH
NORTH
EAST-
SOUTH
WEST
EAST
-
WEST
NORTH
WEST-
SOUTH
EAST
AVERAGE
RESISTIVITY.
(Ohm.m.)
1 1.5 2.25 0.75 11.786 12.022 11.126 11.315 11.562
2 3.0 4.50 1.50 11.786 12.257 11.503 12.728 12.068
3 6.0 9.00 3.00 9.429 9.617 7.920 8.674 8.910
4 8.0 12.00 4.00 7.543 8.046 3.570 8.297 6.864
5 10.0 15.00 5.00 6.160 6.254 5.814 6.191 6.105


ERT NO. - 14. SPREADING : NORTH - SOUTH
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.250 1.250 1.250 11.786
2 3.0 4.50 1.50 18.857 0.630 0.620 0.625 11.786
3 6.0 9.00 3.00 37.714 0.250 0.250 0.250 9.429
4 8.0 12.00 4.00 50.286 0.150 0.150 0.150 7.543
5 10.0 15.00 5.00 62.857 0.096 0.100 0.098 6.160
6 12.0 18.00 6.00 75.429 0.077 0.074 0.076 5.695

ERT NO. - 14. SPREADING : NORTH EAST- SOUTH WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.280 1.270 1.275 12.022
2 3.0 4.50 1.50 18.857 0.650 0.650 0.650 12.257
3 6.0 9.00 3.00 37.714 0.260 0.250 0.255 9.617
4 8.0 12.00 4.00 50.286 0.170 0.150 0.160 8.046
5 10.0 15.00 5.00 62.857 0.099 0.100 0.100 6.254
6 12.0 18.00 6.00 75.429 0.073 0.072 0.073 5.469




.

* 165*

M.K. Soil Testing Laboratory



ERT.NO. - 14. SPREADING : EAST - WEST.
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.170 1.190 1.180 11.126
2 3.0 4.50 1.50 18.857 0.610 0.610 0.610 11.503
3 6.0 9.00 3.00 37.714 0.210 0.210 0.210 7.920
4 8.0 12.00 4.00 50.286 0.130 0.012 0.071 3.570
5 10.0 15.00 5.00 62.857 0.096 0.089 0.093 5.814
6 12.0 18.00 6.00 75.429 0.065 0.061 0.063 4.752


ERT.-14. SPREADING : NORTH WEST - SOUTH EAST
VILLAGE : PADVA, GHOGHA. LOCATION : SHOWN IN LOCATION PLAN.
S.NO. S (m.) 3S/2 (m.) S/2 (m.) K=2.II.S
DIRECT
V (mv.)
I (ma.)
(Ohm.)
REVERSE
V (mv.)
I (ma.)
(Ohm.)
AVERAGE
V (mv.)
I (ma.)
(Ohm.)
RESISTIVITY R =
K * V/I (Ohm.m.)
1 1.5 2.25 0.75 9.429 1.190 1.210 1.200 11.315
2 3.0 4.50 1.50 18.857 0.660 0.690 0.675 12.728
3 6.0 9.00 3.00 37.714 0.230 0.230 0.230 8.674
4 8.0 12.00 4.00 50.286 0.170 0.160 0.165 8.297
5 10.0 15.00 5.00 62.857 0.099 0.098 0.099 6.191
6 12.0 18.00 6.00 75.429 0.078 0.078 0.078 5.883























.

* 166*

M.K. Soil Testing Laboratory
Tabl e No. 11
READI NG FOR GROUND WATER TEST
DATE TEST NO. TIME WATER LEVEL (mt.)
GWT 1 4.00 PM 11.0 31/5/08
GWT 2 3.40 PM 9.0
GWT 1 10.20 AM 11.60
GWT 2 10.00 AM 9.15
GWT 1 3.15 PM 10.98
GWT 2 3.00 PM 9.05
GWT 1 5.45 PM 12.0
1/06/08
GWT 2 6.00 PM 14.0
GWT 1 10.40 AM 12.02
GWT 2 10.30 AM 9.12
GWT 1 2.00 AM 11.50
GWT 2 2.15 PM 10.20
GWT 1 6.00 PM 12.0
2/06/08
GWT 2 5.45 PM 14.0
GWT 1 11.00 AM 10.80
GWT 2 10.50 PM 9.30
GWT 1 5.20 AM 12.10
3/06/08
GWT 2 5.35 PM 14.46
GWT 1 10.00 AM 12.05
GWT 2 9.45 AM 9.30
GWT 1 3.00 PM 12.50
GWT 2 2.50 PM 12.40
GWT 1 5.15 PM 12.52
4/06/08
GWT 2 5.00 PM 14.35
GWT 1 12.45 PM 11.85 5/6/08
GWT 2 12.30 PM 14.32
GWT 1 9.00 AM 10.00
GWT 2 9.15 AM 9.37
GWT 1 1.10 PM 11.98
GWT 2 1.30 AM 12.40
GWT 1 4.45 PM 12.10
6/6/08
GWT 2 5.00 AM 14.00
.

* 167*

M.K. Soil Testing Laboratory



DATE TEST NO. TIME WATER LEVEL (mt.)
GWT 1 10.00 AM 10.20
GWT 2 10.10 AM 9.55
GWT 1 12.50 PM 12.10
GWT 2 1.05 PM 12.30
GWT 1 4.20 PM 12.10
7/6/08
GWT 2 4.30 PM 14.15
GWT 1 9.25 AM 10.50
GWT 2 9.35 AM 9.43
GWT 1 12.40 PM 11.88
GWT 2 12.55 PM 12.00
GWT 1 5.30 PM 12.00
8/6/08
GWT 2 5.45 PM 13.95
GWT 1 9.45 AM 9.99
GWT 2 10.00 AM 10.05
GWT 1 2.30 PM 11.92
GWT 2 2.45 PM 12.03
GWT 1 5.00 PM 12.01
9/6/08
GWT 2 5.20 PM 14.07
GWT 1 11.00 AM 10.68
GWT 2 11.15 AM 11.00
GWT 1 3.40 PM 12.05
GWT 2 3.15 PM 12.45
GWT 1 6.05 PM 12.10
10/6/08
GWT 2 6.20 PM 14.20
GWT 1 5.30 PM 12.00 11/6/08
GWT 2 5.40 PM 14.0
GWT 1 11.38 AM 11.10 12/06/08
GWT 2 11.30 AM 14.10
GWT 1 10.05 AM 9.20
GWT 2 10.20 AM 9.50
GWT 1 12.10 PM 11.50
13/06/08
GWT 2 12.25 PM 12.10

.

* 168*

M.K. Soil Testing Laboratory


DATE TEST NO. TIME WATER LEVEL (mt.)
GWT 1 9.00 AM 9.00
GWT 2 9.20 AM 9.38
GWT 1 1.00 PM 12.00
GWT 2 1.10 PM 12.20
GWT 1 5.05 PM 12.05
14/6/08
GWT 2 5.20 PM 14.05
GWT 1 9.15 AM 9.10
GWT 2 9.30 AM 9.30
GWT 1 12.30 PM 11.45
GWT 2 12.50 PM 12.05
GWT 1 5.15 PM 12.00
15/6/08
GWT 2 5.40 PM 14.10
GWT 1 2.30 PM 12.18 16/6/08
GWT 2 2.45 PM 13.10
GWT 1 12.20 PM 11.55
GWT 2 12.40 PM 12.10
GWT 1 6.00 PM 12.00
17/6/08
GWT 2 6.20 PM 13.92
GWT 1 11.00 AM 9.15
GWT 2 11.30 AM 9.40
GWT 1 2.05 PM 11.80
GWT 2 2.15 PM 12.05
GWT 1 5.40 PM 11.90
18/6/08
GWT 2 5.55 PM 13.89
GWT 1 8.40 AM 10.00
GWT 2 9.00 AM 9.80
GWT 1 12.20 PM 11.80
GWT 2 12.30 PM 12.10
GWT 1 4.50 PM 12.00
19/6/08
GWT 2 5.00 PM 13.78






169






M.K. Soil Testing Laboratory




Table No. 11/1 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 1
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 16.0

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1445.61m, E. 109.77m, RL of GL = 42.1m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 68 - 32 - 39 22 17 SC - - - - - - -
2. 1.50 - UDS 2.65 - - - - - - SC 1.62 1.34 20.3 DST 0.02 32 -
3. 3.00 34 SPT - 40 28 - 26 - - NP - SM - - - - - - -
4. 4.50 Ref. SPT - ==== Grayish blackish coloured, highly weathered, fractured basalt CR = 37%, RQD = 7% ==
5. 6.00 - CS/
DS
- ==== Grayish blackish coloured, highly weathered, fractured basalt CR = 27%, RQD = 14% ==
6. 7.50 - CS/
DS
- ==== Grayish blackish coloured, highly weathered, fractured basalt CR = 47%, RQD = 15% ==
7. 9.00 - CS/
DS
- ==== Grayish blackish coloured, highly weathered, fractured basalt CR = 33%, RQD = Nil ==
8. 10.50 - CS/
DS
- ==== Grayish blackish coloured, highly weathered, fractured basalt CR = 27%, RQD = 8% ==


170






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 1

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 50%, RQD = 20% ===
10. 13.50 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 27%, RQD = Nil ===
11. 15.00 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 27%, RQD = 7% ===
12. 17.0 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR =30%, RQD = Nil ===
13. 19.0 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 37%, RQD = 21% ===
14. 21.00 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 44%, RQD = 22% ===
15. 23.0 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 69%, RQD = 13% ===
16. 25.0 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 53%, RQD = 8% ===
17. 27.50 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 37%, RQD = 8% ===
18. 30.00 - CS/
DS
- ===== Grayish black coloured, highly weathered Basalt rock CR = 40%, RQD = 31% ===



171






M.K. Soil Testing Laboratory




Table No. 11/2 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 2
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 16.65

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1420.68m, E. 82.77m, RL of GL = 42.6m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 8 50 -42- - NP - SM - - - - - - -
2. 1.50 22 SPT - 16 56 - 28 - - NP - SM - - - - - - -
3. 3.00 - DS - 4 74 -22- - NP - SM - - - - - - -
4. 4.50 59 SPT - 14 60 -26- - NP - SM - - - - - - -
5. 6.00 - DS - 15 66 -19 - - NP - SM - - - - - - -
6. 7.50 Ref. SPT - 40 40 -20 - - NP - GM - - - - - - -
7. 9.00 Ref. SPT - 42 42 -16- - NP - GM - - - - - - -
8. 10.50 Ref. SPT - 42 36 -22- - NP - GM - - - - - - -


172






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 2

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - CS - ===== Reddish brown coloured, fresh rock CR = 90%, RQD = 35% ===
10. 13.50 - CS - ===== Reddish brown coloured, fresh rock CR = 93%, RQD = 41% ===
11. 15.00 - CS - ===== Reddish brown coloured, fresh rock CR = 86%, RQD = 58% ===
12. 17.0 - CS - ===== Reddish brown coloured, fresh rock CR = 97%, RQD = 73% ===
13. 19.0 - CS - ===== Reddish brown coloured, fresh rock CR = 98%, RQD = 80% ===
14. 21.00 - CS - ===== Reddish brown coloured, fresh rock CR = 95%, RQD = 95% ===
15. 23.0 - CS - ===== Reddish brown coloured, fresh rock CR = 90%, RQD = 83% ===
16. 25.0 - CS - ===== Reddish brown coloured, fresh rock CR = 85%, RQD = 43% ===
17. 27.50 - CS - ===== Reddish brown coloured, fresh rock CR = 72%, RQD = 72% ===
18. 30.00 - CS - ===== Reddish brown coloured, fresh rock CR = 76%, RQD = 69% ===


173






M.K. Soil Testing Laboratory




Table No. 11/3 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 3
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 17.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1366.50m, E. 73.03m, RL of GL = 41.08m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 39 42 - 19 - - NP - GM - - - - - - -
2. 1.50 20 SPT - 46 32 -22- - NP - GM - - - - - - -
3. 3.00 - DS - 38 43 -19- - NP - GM - - - - - - -
4. 4.50 22 SPT - 45 37 -18- - NP - GM - - - - - - -
5. 6.00 - DS - 39 44 -17- - NP - GM - - - - - - -
6. 7.50 21 SPT - 46 26 -28- - NP - GM - - - - - - -
7. 9.00 - DS - 39 44 -17- - NP - GM - - - - - - -
8. 10.50 26 SPT - 45 37 -18- - NP - GM - - - - - - -


174






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 3

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - DS - 32 48 -20- - NP - GM - - - - - - -
10. 13.50 27 SPT - 45 36 -19- - NP - GM - - - - - - -
11. 15.00 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 41%, RQD = 13% ====
12. 17.0 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 20%, RQD = Nil ====
13. 19.0 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 21%, RQD = Nil ====
14. 21.00 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 23%, RQD = 15% ====
15. 23.0 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 31%, RQD = 13% ====
16. 25.0 Ref. SPT - === Reddish coloured, moderately weathered Basalt CR = 51%, RQD = 21% ====
17. 27.50 - DS - === Reddish coloured, moderately weathered Basalt CR = 56%, RQD = 51% ====
18. 30.00 - DS - === Reddish coloured, moderately weathered Basalt CR = 5%, RQD = 32% ====





175






M.K. Soil Testing Laboratory





Table No. 11/4 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 4
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.60

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1388.81m, E. 307.22m, RL of GL = 41.62m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - SC - - - - - - -
2. 1.50 29 SPT - 4 60 - 36 - 36 18 18 SC - - - - - - -
3. 3.00 - UDS 2.64 - - - - - - SC 1.79 1.53 16.8 DST 0.05 29.5 -
4. 4.50 25 SPT - 2 42 - 56
H(38)(18)
43 20 23 CI - - - - - - -
5. 6.00 - UDS/
DS
- 2 40 - 58
H(40(18)
48 21 27 CI - - - - - - -
6. 7.50 29 SPT - 4 52 52 - 44 - SM - - - - - - -
7. 9.00 - UDS/
DS
- 2 67 - 34 - - NP - SM - - - - - - -
8. 10.50 25 SPT - 2 42 - 56 - 60 27 33 CH - - - - - - -


176






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 4

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 2 44 - 54
H(33)(21)
59 27 32 CH - - - - - - -
10. 13.50 50 SPT - 2 56 - 42
H(34)(8)
48 23 25 SC - - - - - - -
11. 15.00 46 SPT - 2 58 - 40 - 52 24 28 SC - - - - - - -
12. 17.0 51 SPT - 2 68 - 30 - - NP - SM - - - - - - -
13. 19.0 50 SPT - 2 68 - 30 - - NP - SM - - - - - - -
14. 21.00 52 SPT - 4 68 - 28 - - NP - SM - - - - - - -
15. 23.0 54 SPT - 6 68 - 26 - 38 21 17 SC - - - - - - -
16. 25.0 56 SPT - 4 76 - 20 - - NP - SM - - - - - - -
17. 27.50 59 SPT - 2 76 - 22- - NP - SM - - - - - - -
18. 30.00 Ref. SPT - ===== Highly fractured basaltic rock ========





177






M.K. Soil Testing Laboratory





Table No. 11/5 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 6
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 42.52

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1285.69m, E. 369.53m, RL of GL = 41.52m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 26 44 -30- - NP - SM - - - - - - -
2. 1.50 12 SPT - 24 54 -21 - NP - SM - - - - - - -
3. 3.00 - UDS - 29 53 -18- - NP - SM - - - - - - -
4. 4.50 19 SPT - 36 51 -13- - NP - SM - - - - - - -
5. 6.00 Ref. SPT - == Grayish blackish coloured, completely weathered rock in crushed form CR= Nil, RQD = Nil ==
6. 7.50 - CS - == Grayish blackish coloured, completely weathered rock in crushed form CR= Nil, RQD = Nil ==
7. 9.00 - CS - == Grayish blackish coloured, highly weathered rock Basalt CR= 20%, RQD = Nil ==
8. 10.50 - CS - == Grayish blackish coloured, highly weathered rock Basalt CR= 32%, RQD = 14% ==

178






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 6

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - CS - ===== Grayish black coloured, moderately weathered rock CR = 31%, RQD = 13% ===
10. 13.50 - CS - ===== Grayish black coloured, moderately weathered rock CR = 34%, RQD = 27% ===
11. 15.00 - CS - ===== Grayish black coloured, moderately weathered rock CR = 22%, RQD = 8% ===
12. 17.0 - CS - ===== Grayish black coloured, moderately weathered rock CR = 26%, RQD = Nil ===
13. 19.0 - CS - ===== Grayish black coloured, moderately weathered rock CR = 23%, RQD = 9% ===
14. 21.00 - CS - ===== Grayish black coloured, moderately weathered rock CR = 29%, RQD = 25% ===
15. 23.0 - CS - ===== Grayish black coloured, moderately weathered rock CR = 20%, RQD = 19% ===
16. 25.0 - CS - ===== Grayish black coloured, moderately weathered rock CR = 21%, RQD = 11% ===
17. 27.50 - CS - ===== Grayish black coloured, moderately weathered rock CR = 34%, RQD = 17% ===
18. 30.00 - CS - ===== Grayish black coloured, moderately weathered rock CR = 26%, RQD = 12% ===



179






M.K. Soil Testing Laboratory




Table No. 11/6 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 7
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.15

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company1 Limited, Gandhinagar
Co-Ordinate: N. 1324.13m, E. 653.43m, RL of GL = 42.25m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 3 75 -22- - NP - SM - - - - - - -
2. 1.50 - DS - 2 70 -28- - NP - SM - - - - - - -
3. 3.00 15 SPT - - 8 - 92
H(63)(29)
68 22 36 CH - - - - - - -
4. 4.50 - UDS 2.70 - - - - - - CH 1.7 1.39 21.8 TUU 0.48 6 -
5. 6.00 35 SPT - - 8 - 92
H(62(30)
60 24 36 CH - - - - - - -
6. 7.50 - UDS 2.70 - - - - - - CH 1.85 1.48 24.6 TUU 0.66 5 -
7. 9.00 42 SPT - - 10 -90- 58 24 34 CH - - - - - - -
8. 10.50 47 SPT - - 4 - 96
H(62)(34)
64 28 36 CH - - - - - - -

180






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 7

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 42 SPT - - 7 - 93
H(61)(33)
68 30 38 CH - - - - - - -
10. 13.50 - DS - === Grayish coloured, completely weathered rock in crushed form ====
11. 15.0 55 SPT - - 8 - 92
H(66)(26)
56 24 32 CH - - - - - - -
12. 17.0 Ref. SPT - - 18 - 81
H(59)(22)
52 28 24 CH - - - - - - -
13. 19.0 - DS - === Grayish coloured, highly weathered rock CR=11%, RQD = 10% ===
14. 21.00 - DS - === Grayish coloured, highly weathered rock CR=Nil, RQD = Nil ===
15. 23.0 - DS - === Grayish coloured, highly weathered rock CR=Nil, RQD = Nil ===
16. 25.0 - CS - === Grayish coloured, highly weathered rock CR=28%, RQD = 28%===
17. 27.50 - CS - === Grayish coloured, highly weathered rock CR=25%, RQD = 25% ===
18. 30.00 - CS - === Grayish coloured, highly weathered rock CR=20%, RQD = Nil ===





181






M.K. Soil Testing Laboratory





Table No. 11/7 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 8
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.50

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1277.15m, E. 564.96m, RL of GL = 40.42m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 10 SPT - 4 8 - 88
H(60)(28)
58 23 35 CH - - - - - - -
3. 3.00 - UDS/
DS
- 10 30 - 60 - 66 24 42 CH - - - - - - -
4. 4.50 22 SPT - - 2 - 98
H(67)(31)
59 22 37 CH - - - - - - -
5. 6.00 - UDS - - 30 - 70
H(32(38)
142 32 110 CH - - - - - - -
6. 7.50 29 SPT - - 14 - 86 - 166 37 134 CH - - - - - - -
7. 9.00 33 SPT - - 10 - 90
H(55(35)
68 38 30 CH - - - - - - -
8. 10.50 6 SPT - 10 48 - 42 - 73 32 41 SC - - - - - - -

182






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 8

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- - 8 - 92 - 73 32 41 CH - - - - - - -
10. 13.50 32 SPT - 2 30 - 68 - 68 25 43 CH - - - - - - -
11. 15.0 36 SPT - - 24 - 76 - 69 24 45 CH - - - - - - -
12. 17.0 47 SPT - 2 10 - 88 - 71 32 39 CH - - - - - - -
13. 19.0 54 SPT - 8 16 - 76 - 76 36 40 CH - - - - - - -
14. 21.00 63 SPT - 2 12 - 86 - 74 34 40 CH - - - - - - -
15. 23.0 23.0 SPT - ========= Rock CR = 25%, RQD = 20% ===========
16. 25.0 56 SPT - ========= Rock CR = 28%, RQD = 10% ===========
17. 27.50 59 SPT - ========= Rock CR = 30%, RQD = 15% ===========
18. 30.00 Ref. SPT - ========= Rock CR = 22%, RQD = 10% ===========





183






M.K. Soil Testing Laboratory





Table No. 11/8 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 9
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.75

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1252.45m, E. 462.06m, RL of GL = 40.03m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - === Grayish brown coloured, completely weathered rock in crushed form ===
2. 1.50 Ref. SPT - === Grayish brown coloured, completely weathered rock in crushed form ===
3. 3.00 - CS - === Grayish brown coloured, completely weathered rock in crushed form ===
4. 4.50 - CS - === Grayish brown coloured, completely weathered rock in crushed form ===
5. 6.00 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=53%, RQD = 43%==
6. 7.50 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=33%, RQD = 20%==
7. 9.00 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=40%, RQD = 20%==
8. 10.50 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=43%, RQD = 28%==
184






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 9

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=33%, RQD = 33%==
10. 13.50 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=50%, RQD = 31%==
11. 15.0 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=45%, RQD = 29%==
12. 17.0 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=64%, RQD = 53%==
13. 19.0 - DS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=60%, RQD = 26%==
14. 21.00 - DS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=41%, RQD = 30%==
15. 23.0 - DS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=46%, RQD = 28%==
16. 25.0 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=48%, RQD = 26%==
17. 27.50 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=40%, RQD = 13%==
18. 30.00 - CS - Grayish blackish coloured, moderately weathered hard & compact Basalt CR=50%, RQD = 20%==





185






M.K. Soil Testing Laboratory





Table No. 11/9 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 10
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1179.02m, E. 399.10m, RL of GL = 41.66m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 36 45 -19- - NP - GM - - - - - - -
2. 1.50 9 SPT - 31 35 -54- - NP - GM - - - - - - -
3. 3.00 20 SPT - 32 28 -40- - NP - GM - - - - - - -
4. 4.50 Ref. SPT - === Blackish grayish coloured, completely weathered rock CR = Nil, RQD = Nil ===
5. 6.00 - DS - === Blackish grayish coloured, completely weathered rock CR = Nil, RQD = Nil ===
6. 7.50 - DS - === Blackish grayish coloured, completely weathered rock CR = Nil, RQD = Nil ===
7. 9.00 - DS - === Blackish grayish coloured, completely weathered rock CR = Nil, RQD = Nil ===
8. 10.50 - DS - === Blackish grayish coloured, completely weathered rock CR = Nil, RQD = Nil ===

186






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 10

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 61.33%, RQD = 30% ===
10. 13.50 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 60%, RQD = 6.66% ===
11. 15.0 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 53.33%, RQD = Nil ===
12. 17.0 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 47.5%, RQD = 21% ===
13. 19.0 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 42.5%, RQD = 50% ===
14. 21.00 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 45%, RQD = 24.5% ===
15. 23.0 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 47.5%, RQD = 7.0% ===
16. 25.0 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 50%, RQD = 30% ===
17. 27.50 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 44%, RQD = Nil ===
18. 30.00 - DS - === Reddish brown coloured, moderately weathered, fractured Basalt CR = 40%, RQD = 30% ===





187






M.K. Soil Testing Laboratory





Table No. 11/10 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 11
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.60

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1138.52m, E. 584.32m, RL of GL = 41.85m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 23 SPT - 2 6 - 92
H(53)(39)
127 34 93 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.69 1.43 17.6 TUU 0.62 5 -
4. 4.50 26 SPT - - 2 - 98
H(56)(42)
150 36 114 CH - - - - - - -
5. 6.00 - UDS 2.62 - - - - - - CH 1.78 1.50 18.5 TUU 0.79 4 -
6. 7.50 28 SPT - - 6 - 94
H(54(40)
166 34 132 CH - - - - - - -
7. 9.00 - UDS/
DS
- 8 82 - 10 - - NP - SP/
SM
- - - - - - -
8. 10.50 27 SPT - 6 36 - 36 - - NP - SM - - - - - - -

188






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 11

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 2 58 - 40 - - NP - SM - - - - - - -
10. 13.50 33 SPT - 4 48 - 48 - - NP - SM - - - - - - -
11. 15.0 Ref. SPT - 2 30 - 68 - 38 17 21 CI - - - - - - -
12. 17.0 Ref. SPT - 2 68 - 30 - 37 16 21 SC - - - - - - -
13. 19.0 54 SPT - ========= Rock CR = 20%, RQD = 10% ===========
14. 21.00 63 SPT - ========= Rock CR = 20%, RQD = 6% ===========
15. 23.0 23.0 SPT - ========= Rock CR = 30%, RQD = 12% ===========
16. 25.0 56 SPT - ========= Rock CR = 20%, RQD = Nil ===========
17. 27.50 59 SPT - ========= Rock CR = 21%, RQD = Nil ===========
18. 30.00 Ref. SPT - ========= Rock CR = 20%, RQD = Nil ===========





189






M.K. Soil Testing Laboratory





Table No. 11/11 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 12
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1139.76m, E. 663.47m, RL of GL = 45.88m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - CH - - - - - - -
2. 1.50 10 SPT - - 20 - 80
H(54)(26)
58 32 26 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.52 1.18 27.87 TUU 0.36 4 -
4. 4.50 18 SPT - - 48 -52- 52 31 21 CH - - - - - - -
5. 6.00 - UDS 2.70 - - - - - - CH 1.48 1.22 21.18 TUU 0.58 5 -
6. 7.50 35 SPT - - 10 - 90
H(59(31)
62 31 31 CH - - - - - - -
7. 9.00 Ref. SPT - - 6 -94- 60 30 30 CH - - - - - - -
8. 10.50 26 SPT - - 2 - 98
H(70(28)
59 29 30 CH - - - - - - -
190






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 12

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - - - - - CH 1.66 1.47 12.74 TUU 0.79 6 -
10. 13.50 39 SPT - - 2 - 98
H(66(32)
60 31 29 CH - - - - - - -
11. 15.0 - UDS/
DS
- - 30 -70- 61 31 30 CH - - - - - - -
12. 17.0 46 SPT - - 4 - 96
H(64(32)
68 20 48 CH - - - - - - -
13. 19.00 42 SPT - - 12 -88- 70 19 51 CH - - - - - - -
14. 21.00 51 SPT - - 10 - 90
H(55(35)
64 17 47 CH - - - - - - -
15. 23.00 - CS/
DS
- ==== Reddish yellowish coloured, completely weathered rock (sandstone) CR = Nil, RQD = Nil ===
16. 25.00 - CS/
DS
- ==== Reddish yellowish coloured, completely weathered rock (sandstone) CR = Nil, RQD = Nil ===
17. 27.50 - CS/
DS
- ==== Reddish yellowish coloured, completely weathered rock (sandstone) CR = Nil, RQD = Nil ===
18. 30.00 - CS/
DS
- ==== Reddish yellowish coloured, completely weathered rock (sandstone) CR = 22%, RQD = 12% ===



191






M.K. Soil Testing Laboratory




Table No. 11/12 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 13
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 33.96

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1160.74m, E. 779.11m, RL of GL = 43.26m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 22 SPT - - 36 - 64
H(43)(21)
55 26 29 CH - - - - - - -
3. 3.00 - UDS 2.64 - - - - - - CH 1.58 1.50 5.26 TUU 0.56 8 0.14
4. 4.50 26 SPT - 10 38 - 52 - 43 21 22 CI - - - - - - -
5. 6.00 - UDS 2.65 - - - - - - CI 1.63 1.57 3.09 TUU 0.69 2 -
6. 7.50 20 SPT - - 22 - 78 - 52 22 30 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 54 - 46 - 40 21 19 SC - - - - - - -
8. 10.50 26 SPT - - 54 - 46 - 40 24 16 SC - - - - - - -
9. 12.00 - UDS/
DS
- - 54 - 46 - 52 25 27 SC - - - - - - -
192






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 13

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 24 SPT - - 4 - 96
H(61)(35)
71 26 45 CH - - - - - - -
11. 15.0 37 SPT - - 18 - 82
H(55)(27)
52 23 29 CH - - - - - - -
12. 17.0 35 SPT - - 45 - 55 - 53 26 27 CH - - - - - - -
13. 19.00 25 SPT - 2 26 - 72
H(39)(33)
66 28 38 CH - - - - - - -
14. 21.00 26 SPT - - 4 - 96 - 70 28 42 CH - - - - - - -
15. 23.00 22 SPT - - 48 - 52 - 57 24 33 CH - - - - - - -
16. 25.00 25 SPT - - 40 - 60 - 60 26 34 CH - - - - - - -
17. 27.50 26 SPT - - 38 - 62 - 52 25 27 CH - - - - - - -
18. 30.00 29 SPT - 6 52 - 42 - 47 24 23 SC - - - - - - -
19. 32.5 61 SPT - 8 24 - 68
H(46)(22)
52 26 26 CH - - - - - - -
19. 35.0 Ref. SPT - - 28 - 72 - 53 25 28 CH - - - - - - -
20. 37.5 Ref. SPT - - 22 - 78
H(55)(23)
52 28 24 CH - - - - - - -
21. 40.0 Ref. SPT - 2 39 - 55 - 51 24 27 CH - - - - - - -
193






M.K. Soil Testing Laboratory



Table No. 11/13 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 14
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 14.80

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1086.20m, E. 178.18m, RL of GL = 44.1m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 28 - 72
H(48)(24)
58 27 31 CH - - - - - - -
2. 1.50 65 SPT - - 21 -79- 52 26 26 CH - - - - - - -
3. 3.00 - DS - 40 36 -24- - NP - GM - - - - - - -
4. 4.50 69 SPT - - 6 - 94
H(68)(26)
58 28 30 CH - - - - - - -
5. 6.00 - DS - 46 35 -19- - NP - GM - - - - - - -
6. 7.50 30 SPT - - 76 -24- - NP - SM - - - - - - -
7. 9.00 - DS - - 80 -20- - NP - SM - - - - - - -
8. 10.50 31 SPT - 1 77 -22- - NP - SM - - - - - - -



194






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 14

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - DS - 46 32 -22- - NP - GM - - - - - - -
10. 13.50 Ref. SPT - 50 33 -17- - NP - GM - - - - - - -
11. 15.0 Ref. SPT - 48 30 -22- - NP - GM - - - - - - -
12. 17.0 Ref. SPT - 54 31 -15- - NP - GM - - - - - - -
13. 19.00 Ref. SPT - 47 35 -18- - NP - GM - - - - - - -
14. 21.00 Ref. SPT - 52 33 -15- - NP - GM - - - - - - -
15. 23.00 Ref. SPT - 47 15 -18- - NP - GM - - - - - - -
16. 25.00 Ref. SPT - 55 31 -14- - NP - GM - - - - - - -
17. 27.50 Ref. SPT - 48 23 -29- - NP - GM - - - - - - -
18. 30.00 Ref. SPT - 51 17 -32- - NP - GM - - - - - - -





195






M.K. Soil Testing Laboratory





Table No. 11/14 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 15
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1100.03m, E. 399.95m, RL of GL = 42.44m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 60 -40- 40 24 16 SC - - - - - - -
2. 1.50 13 SPT - - 73 -27- 46 23 23 SC - - - - - - -
3. 3.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock in crushed form ====
4. 4.50 Ref. SPT - === Grayish blackish coloured, completely weathered rock in crushed form ====
5. 6.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock in crushed form ====
6. 7.50 Ref. CS - === Grayish blackish coloured, completely weathered rock in crushed form ====
7. 9.00 - CS - === Grayish blackish coloured, completely weathered rock in crushed form ====
8. 10.50 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 75%, RQD = 18% ==

196






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 15

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 49%, RQD = 22% ==
10. 13.50 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 21%, RQD = Nil ==
11. 15.00 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 78%, RQD = 24% ==
12. 17.0 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 58%, RQD = 13% ==
13. 19.0 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 68%, RQD = 60% ==
14. 21.00 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 50%, RQD = 15% ==
15. 23.0 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 60%, RQD = Nil ==
16. 25.0 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 54%, RQD = 33% ==
17. 27.50 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 77%, RQD = 42% ==
18. 30.00 - CS - == Reddish grayish coloured, moderately weathered, fractured Basalt CR= 84%, RQD = 13% ==


197






M.K. Soil Testing Laboratory




Table No. 11/15 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 16
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.70

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1079.74m, E. 779.11m, RL of GL = 44.26m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 20 SPT - - 16 - 54 - 39 19 20 CI - - - - - - -
3. 3.00 - UDS/
DS
- - 34 - 66
H(45)(21)
41 16 25 CI - - - - - - -
4. 4.50 26 SPT - - 20 - 80
H(58)(22)
46 21 25 CI - - - - - - -
5. 6.00 - UDS/
DS
- - 26 - 74 - 47 20 27 CI - - - - - - -
6. 7.50 28 SPT - - 58 - 42 - - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- 2 74 - 24 - - NP - SM - - - - - - -
8. 10.50 32 SPT - 2 54 - 44- - NP - SM - - - - - - -


198






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 16
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- - 60 - 40 - 42 17 25 SC - - - - - - -
10. 13.50 27 SPT - - 8 - 92
H(66)(26)
56 22 34 CH - - - - - - -
11. 15.0 - UDS/
DS
- 6 28 - 66 - 64 21 43 CH - - - - - - -
12. 17.0 32 SPT - - 4 - 96
H(63)(33)
62 22 40 CH - - - - - - -
13. 19.00 38 SPT - - 4 - 96 - 61 23 38 CH - - - - - - -
14. 21.00 49 SPT - - 26 - 74
H(49)(25)
56 23 33 CH - - - - - - -
15. 23.00 39 SPT - - 42 - 58 - 59 20 39 CH - - - - - - -
16. 25.00 40 SPT - 2 54 - 44 - - NP - SM - - - - - - -
17. 27.50 42 SPT - 4 66 - 30 - - NP - SM - - - - - - -
18. 30.00 Ref. - - - 62 - 38 - - NP - SM - - - - - - -
19. 32.5 Ref. SPT - - 58 - 42 - - NP - SM - - - - - - -
19. 35.0 Ref. SPT - - 46 - 54 - 53 21 32 CH - - - - - - -
20. 37.5 Ref. SPT - 6 42 - 52 - 54 24 30 CH - - - - - - -
21. 40.0 Ref. SPT - - 20 - 80 - 58 22 36 CH - - - - - - -
199






M.K. Soil Testing Laboratory



Table No. 11/16 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 17
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.10

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1045.22m, E. 126.05m, RL of GL = 44.62m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 14 66 -20- - NP - SM - - - - - - -
2. 1.50 20 SPT - 18 65 -17- - NP - SM - - - - - - -
3. 3.00 - UDS/
DS
- 21 56 -23- - NP - SM - - - - - - -
4. 4.50 27 SPT - 16 66 -18- - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- 22 63 -15- - NP - SM - - - - - - -
6. 7.50 36 SPT - 19 57 -24- - NP - SM - - - - - - -
7. 9.00 40 SPT - 24 56 -20- - NP - SM - - - - - - -
8. 10.50 37 SPT - 18 64 -18- - NP - SM - - - - - - -



200






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 17

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 41 SPT - 50 31 -19- - NP - GM - - - - - - -
10. 13.50 Ref. SPT - 45 39 -16- - NP - GM - - - - - - -
11. 15.0 Ref. SPT - 52 36 -12- - NP - GM - - - - - - -
12. 17.0 Ref. SPT - 49 35 -16 - NP - GM - - - - - - -
13. 19.0 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 30%, RQD = 6% ===========
14. 21.00 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 25%, RQD = Nil ===========
15. 23.0 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 23%, RQD = Nil ===========
16. 25.0 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 20%, RQD = Nil ===========
17. 27.50 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 21%, RQD = Nil ===========
18. 30.00 Ref. SPT/
DS
- ========= Grayish black coloured highly weathered rock CR = 20%, RQD = Nil ===========


201






M.K. Soil Testing Laboratory




Table No. 11/17 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 18
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.45

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1057.40m, E. 534.82m, RL of GL = 43.1m:
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - CH - - - - - - -
2. 1.50 14 SPT - - 8 -92- 58 25 33 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.53 1.36 12.23 - - - -
4. 4.50 26 SPT - - 4 -96- 59 35 24 CH - - - - - - -
5. 6.00 - UDS/
DS
- - 10 -90- 56 25 31 CH - - - - - - -
6. 7.50 30 SPT - - 6 -94- 59 24 35 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 14 -86- 59 25 34 CH - - - - - - -
8. 10.50 35 SPT - - 6 -94- 61 21 40 CH - - - - - - -


202






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 18

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - 16 9 - 75
H(74)(21)
54 26 - CH - - - - - - -
10. 13.50 Ref. SPT - 14 16 -70- 53 24 - CH - - - - - - -
11. 15.0 Ref. SPT - 15 9 - 76
H(50)(26)
56 25 31 CH - - - - - - -
12. 17.0 Ref. SPT - 20 15 -65- 55 26 - CH - - - - - - -
13. 19.00 Ref. SPT - 17 22 -61- 54 24 30 CH - - - - - - -
14. 21.00 Ref. SPT - 14 21 - 65
H(43)(22)
57 27 30 CH - - - - - - -
15. 23.00 Ref. SPT - 15 22 -63- 55 28 27 CH - - - - - - -
16. 25.00 Ref. SPT - 19 13 - 68
H(47)(21)
56 24 32 CH - - - - - - -
17. 27.50 Ref. SPT - 19 13 -68- 63 23 40 CH - - - - - - -
18. 30.00 Ref. SPT - 11 17 - 72
H(47)(25)
60 25 35 CH - - - - - - -



203






M.K. Soil Testing Laboratory




Table No. 11/18 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 19
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1057.4m, E. 661.65m, RL of GL = 45.83m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 26 - 74
H(49)(25)
58 28 30 CH - - - - - - -
2. 1.50 20 SPT - - 22 -78- 55 28 27 CH - - - - - - -
3. 3.00 - UDS/
DS
- 4 27 -69- 58 28 30 CH - - - - - - -
4. 4.50 17 SPT - 5 23 - 72
H(46)(26)
55 25 30 CH - - - - - - -
5. 6.00 - UDS 2.68 - - - - - - CH 1.84 1.47 24.5 TUU 0.69 6 -
6. 7.50 Ref. SPT - 5 28 -72- 56 28 38 CH - - - - - - -
7. 9.00 - UDS 2.70 - - - - - - CH 1.90 1.60 18.6 TUU 0.99 2 -
8. 10.50 29 SPT - 5 19 - 76
H(51)(25)
54 26 28 CH - - - - - - -
204






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 19

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.70 - - - - - - CH 1.84 1.51 21.9 TUU 0.88 6 -
10. 13.50 32 SPT - - 11 - 89
H(60)(29)
62 30 32 CH - - - - - - -
11. 15.0 - UDS 2.68 - - - - - - CH 1.95 1.58 23.2 TUU 0.95 4 -
12. 17.0 16 SPT - - 6 - 92
H(61)(31)
61 29 32 CH - - - - - - -
13. 19.00 - UDS 2.68 - - - - - - CH 1.98 1.55 27.7 TUU 0.99 5 -
14. 21.00 26 SPT - - 15 -85- 56 28 28 CH - - - - - - -
15. 23.00 - UDS 2.7 - - - - - - CH - - - - - - -
16. 25.00 Ref. SPT - - 13 -87
H(62)(25)
55 25 30 CH - - - - - - -
17. 27.50 Ref. SPT - - - - - - - CH - - - - - - -
18. 30.00 - CS/
DS
- == Reddish brown coloured, compacted Basalt = CR = 30%, RQD = 20%



205






M.K. Soil Testing Laboratory





Table No. 11/19 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 20
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 1021.07m, E. 538.32m, RL of GL = 43.57m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - 89
H(63)(26)
56 26 30 CH - - - - - - -
2. 1.50 - UDS 2.70 - - - - - - CH 1.79 1.54 10.6 TUU 0.55 2 -
3. 3.00 16 UDS/
DS
- - 8 - 92
H(67)(25)
58 25 33 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH 1.56 1.24 25.47 TUU 0.63 5 0.18
5. 6.00 19 SPT - - 12 - 88
H(60)(28)
71 28 43 CH - - - - - - -
6. 7.50 36 SPT - 10 12 - 78 - 38 20 18 CI - - - - - - -
7. 9.00 23 SPT - - 22 - 78
H(57)(21)
44 19 25 CI - - - - - - -
8. 10.50 Ref. SPT - ====== Rock ===========
206






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 20

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - - 12 - 88
H(62)(26)
51 29 22 CH - - - - - - -
10. 13.50 Ref. SPT - - 8 - 92
H(60)(32)
56 28 28 CH - - - - - - -
11. 15.0 Ref. SPT - ======= Rock ==============
12. 17.0 Ref. SPT - ======= Rock ==============
13. 19.00 Ref. SPT - ======= Rock ==============
14. 21.00 Ref. SPT - ======= Rock ==============
15. 23.00 Ref. SPT - ======= Rock ==============
16. 25.00 - DS - ========== Rock CR = 20%, RQD = 20% ==============
17. 27.50 - DS - ========== Rock CR = 24%, RQD = 10% ==============
18. 30.00 Ref. SPT - ======= Rock ==============



207






M.K. Soil Testing Laboratory





Table No. 11/20 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 21
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 964.28m, E. 178.18m, RL of GL = 43.7m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 6 - 94
H(68)(26)
58 25 33 CH - - - - - - -
2. 1.50 27 SPT - - 2 - 98
H(70)(28)
57 28 29 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.86 1.55 20.3 TUU 0.65 2 -
4. 4.50 29 SPT - 16 48 -36- - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- 18 58 -24- - NP - SM - - - - - - -
6. 7.50 38 SPT - 20 50 -30- - NP - SM - - - - - - -
7. 9.00 41 SPT - 18 60 -22- - NP - SM - - - - - - -
8. 10.50 Ref. SPT - == Grayish blackish coloured, highly weathered rock & fractured rock CR=20%,RQD=Nil==

208






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 21

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - == Grayish blackish coloured, highly weathered rock & fractured rock CR=22%,RQD=Nil==
10. 13.50 Ref. SPT - == Grayish blackish coloured, highly weathered rock & fractured rock CR=20%,RQD=Nil==
11. 15.00 48 SPT - 20 50 -30- - NP - SM - - - - - - -
12. 17.00 43 SPT - 16 67 -17- - NP - SM - - - - - - -
13. 19.00 54 SPT - 14 64 -22- - NP - SM - - - - - - -
14. 21.0 40 SPT - 22 58 -20- - NP - SM - - - - - - -
15. 23.0 50 SPT - 18 64 -18- - NP - SM - - - - - - -
16. 25.0 Ref. SPT - 25 53 -22- - NP - SM - - - - - - -
17. 27.0 Ref. SPT - 15 63 -22- - NP - SM - - - - - - -
18. 30.0 Ref. SPT - 14 67 -19- - NP - SM - - - - - - -



209






M.K. Soil Testing Laboratory



Table No. 11/21 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 22
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.10

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 927.07m, E. 398.76m, RL of GL = 42.15m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 2 - 98
H(62)(36)
68 25 43 CH - - - - - - -
2. 1.50 10 SPT - - 5 - 95
H(63)(32)
58 28 30 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.79 1.49 19.6 TUU 0.68 5 -
4. 4.50 15 SPT - - 6 - 94
H(69)(25)
58 25 33 CH - - - - - - -
5. 6.00 - UDS/
DS
- 18 56 -26- - NP - SM - - - - - - -
6. 7.50 21 SPT - 21 52 -27- - NP - SM - - - - - - -
7. 9.00 - UDS - 26 56 -18- - NP - SM - - - - - - -
8. 10.50 22 SPT - 24 48 -24- - NP - SM - - - - - - -


210






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 22

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 30 48 -22- - NP - SM - - - - - - -
10. 13.50 25 SPT - 28 53 -19- - NP - SM - - - - - - -
11. 15.00 - UDS/
DS
- 20 55 -25- - NP - SM - - - - - - -
12. 17.00 30 SPT - 25 57 -18- - NP - SM - - - - - - -
13. 19.00 - UDS/
DS
- === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ====
14. 21.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ====
15. 23.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ====
16. 25.00 Ref. SPT === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ====
17. 27.50 Ref. SPT - === Grayish blackish coloured, completely weathered rock CR = 25%, RQD= 8%====
18. 30.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock CR = 28%, RQD= 12%====





211






M.K. Soil Testing Laboratory



Table No. 11/22 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 23
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 32.48

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 902.48m, E. 461.67m, RL of GL = 44.28m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 20 SPT - 2 32 - 66 - - NP - ML - - - - - - -
3. 3.00 - UDS/
DS
- 6 28 - 66 - - NP - ML - - - - - - -
4. 4.50 22 SPT - 2 32 - 66
H(44)(22)
68 23 45 CH - - - - - - -
5. 6.00 - UDS/
DS
- 6 28 - 66 - 43 18 25 CI - - - - - - -
6. 7.50 19 SPT - - 4 - 96
H(58)(38)
114 34 80 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 60 - 40 - 40 20 20 SC - - - - - - -
8. 10.50 26 SPT - - 4 - 96
H(62)(34)
91 35 36 CH - - - - - - -


212






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 23

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 4 60 - 36 - 48 21 27 SC - - - - - - -
10. 13.50 32 SPT - 2 8 - 90
H(62)(28)
87 35 52 CH - - - - - - -
11. 15.0 32 SPT - 2 16 - 82 - 76 28 48 CH - - - - - - -
12. 17.0 Ref. SPT - - 10 - 90 - 78 28 50 CH - - - - - - -
13. 19.00 Ref. SPT - 4 12 - 84 - 81 30 51 CH - - - - - - -
14. 21.00 Ref. SPT - 2 62 - 36 - - NP - SM - - - - - - -
15. 23.00 Ref. SPT - 4 54 - 48 - - NP - SM - - - - - - -
16. 25.00 Ref. SPT - 4 54 - 42 - - NP - SM - - - - - - -
17. 27.50 Ref. SPT - - 56 - 44 - - NP - SM - - - - - - -







213






M.K. Soil Testing Laboratory



Table No. 11/23 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 24
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.95

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 920.71m, E. 540.02m, RL of GL = 44.34m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - === Filled type of material ===
2. 1.50 24 SPT - - 12 - 88 -
H(59)(29)
58 25 33 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.90 1.56 21.8 TUU 0.78 4 -
4. 4.50 22 SPT - - 21 - 79-
H(54)(25)
56 26 30 CH - - - - - - -
5. 6.00 - UDS 2.68 - - - - - - CH 1.92 1.59 20.5 TUU 0.8 6 -
6. 7.50 22 SPT - - 6 - 94-
H(61)(33)
69 28 41 CH - - - - - - -
7. 9.00 - UDS - - - - - - - CH 1.99 1.59 24.8 TUU 0.86 5 -
8. 10.50 36 SPT - - 6 - 94-
H(59)(35)
68 28 40 CH - - - - - - -

214






M.K. Soil Testing Laboratory

PAGE 2 FOR BOREHOLE NO. BH 24

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - - - - - CH 2.04 1.67 21.8 TUU 0.96 5 -
10. 13.50 37 SPT - - 3 - 97-
H(66)(31)
66 25 41 CH - - - - - - -
11. 15.00 - UDS 2.68 - - - - - - CH 2.05 1.65 24.2 TUU 0.99 2 -
12. 17.00 48 SPT - - 8 -92- - NP - CH - - - - - - -
13. 19.00 45 SPT - - 6 - 94-
H(59)(35)
65 29 36 CH - - - - - - -
14. 21.00 44 SPT - - 16 - 84-
H(62)(22)
45 26 19 CI - - - - - - -
15. 23.00 49 SPT - - - - - - - CI - - - - - - -
16. 25.00 50 SPT - - 16 - 84-
H(58)(26)
48 23 25 CI - - - - - - -
17. 27.50 50 SPT - - 81 -19- 48 25 23 SC - - - - - - -
18. 30.00 Ref. SPT - - 71 -29- 49 24 25 SC - - - - - - -
19. 32.5 Ref. SPT - - - - - - - SC - - - - - - -
20. 35.00 Ref. SPT - - 69 -31- 40 25 15 SC - - - - - - -
21. 37.5 Ref. SPT - - - - - - - SC - - - - - - -
22. 40.00 Ref. SPT - - 77 -23- 44 23 21 SC - - - - - - -

215






M.K. Soil Testing Laboratory



Table No. 11/24 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 25
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 936.36m, E. 642.70m, RL of GL = 46.91m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 - 92 -
H(61)(31)
61 30 31 CH - - - - - - -
2. 1.50 - UDS 2.68 - - - - - - CH 1.68 1.40 1.95 - - - -
3. 3.00 14 SPT - - 5 - 95-
H(61)(34)
56 26 30 CH - - - - - - -
4. 4.50 - UDS 2.66 - - - - - - CH 1.74 1.49 16.7 TUU 0.78 5 -
5. 6.00 26 SPT - - 12 - 88-
H(58)(30)
60 29 31 CH - - - - - - -
6. 7.50 - UDS 2.70 - - - - - - CH 1.86 1.59 16.9 - - - -
7. 9.00 33 SPT - - 13 -87-
H(59)(28)
58 26 32 CH - - - - - - -
8. 10.50 34 SPT - - 13 - 87-
H(57)(30)
56 26 30 CH - - - - - - -


216






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 25

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 35 SPT - - 13 - 87-
H(56)(31)
61 29 32 CH - - - - - - -
10. 13.50 37 SPT - - - - - - - CH - - - - - - -
11. 15.00 39 SPT - - 12 - 88-
H(60)(28)
55 28 27 CH - - - - - - -
12. 17.00 43 SPT - - 74 -26- - NP - SM - - - - - - -
13. 19.00 47 SPT - - 73 -27- - NP - SM - - - - - - -
14. 21.00 46 SPT - 4 66 -30- - NP - SM - - - - - - -
15. 23.00 27 SPT - - 10 - 90-
H(62)(28)
55 28 27 CH - - - - - - -
16. 25.00 28 SPT - - 13 -87-
H(62)(25)
53 26 27 CH - - - - - - -
17. 27.50 68 SPT - - 3 -97-
H(68)(29)
69 28 41 CH - - - - - - -
18. 30.00 >100 SPT - - 5 -95-
H(59)(36)
75 28 47 CH - - - - - - -




217






M.K. Soil Testing Laboratory



Table No. 11/25 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 26
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.50

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 935.67m, E. 779.11m, RL of GL = 44.78m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 10 SPT - - 6 - 94
H(63)(31)
70 26 44 CH - - - - - - -
3. 3.00 - UDS/
DS
- - 4 - 96
H(58)(38)
89 28 61 CH - - - - - - -
4. 4.50 19 SPT - - 16 - 84
H(53)(31)
66 24 42 CH - - - - - - -
5. 6.00 - UDS/
DS
- - 18 - 82
H(53)(29)
66 25 41 CH - - - - - - -
6. 7.50 27 SPT - - 8 - 92
H(56)(36)
70 27 43 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 10 - 90 - 59 25 34 CH - - - - - - -
8. 10.50 31 SPT - - 16 - 84
H(52)(32)
53 21 32 CH - - - - - - -


218






M.K. Soil Testing Laboratory

PAGE 2 FOR BOREHOLE NO. BH 26

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 35 SPT - - 12 - 88
H(59)(29)
65 24 41 CH - - - - - - -
10. 13.50 37 SPT - - 22 - 78 - 59 22 37 CH - - - - - - -
11. 15.0 39 SPT - - 4 - 96
H(65)(31)
64 23 41 CH - - - - - - -
12. 17.0 43 SPT - - 6 - 94
H(63)(31)
75 28 47 CH - - - - - - -
13. 19.00 46 SPT - - 4 - 96
H(60)(36)
75 27 48 CH - - - - - - -
14. 21.00 48 SPT - - 6 - 94 - - NP - ML - - - - - - -
15. 23.00 51 SPT - - 16 - 84 - 52 25 27 CH - - - - - - -
16. 25.00 64 SPT - - 20 - 80 - 52 25 27 CH - - - - - - -
17. 27.50 68 SPT - - 24 - 76
H(55)(21)
43 24 19 CI - - - - - - -
18. 30.00 82 SPT - - 18 - 82 - 44 25 19 CI - - - - - - -
19. 32.5 Ref. SPT - - 46 - 54 - - NP - ML - - - - - - -
20. 35.0 Ref. SPT - - 20 - 86
H(85)(3)
- NP - ML - - - - - -
21. 37.5 Ref. SPT - - 20 - 80 - 45 23 22 CI - - - - - - -
22. 40.0 Ref. SPT - - 8 - 92 - 56 28 28 CH - - - - - - -

219






M.K. Soil Testing Laboratory



Table No. 11/26 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 27
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.90

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 845.02m, E. 207.45m, RL of GL = 44.95m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 14 SPT - 10 50 - 40 - 42 26 16 SM - - - - - - -
3. 3.00 - UDS/
DS
- 6 80 - 14 - - NP - SM - - - - - - -
4. 4.50 15 SPT - 12 74 - 14 - - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- 10 74 - 16 - - NP - SM - - - - - - -
6. 7.50 15 SPT - 6 76 - 18 - - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- - 76 - 24 - - NP - SM - - - - - - -
8. 10.50 - SPT - ========= BOLDER ========


220






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 27

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 10 SPT - - 72 - 28 - - NP - SM - - - - - - -
10. 13.50 11 SPT - - 86 - 14 - - NP - SM - - - - - - -
11. 15.0 15 SPT - - 88 - 12 - - NP - SM - - - - - - -
12. 17.0 17 SPT - - 82 - 18 - - NP - SM - - - - - - -
13. 19.00 16 SPT - - 82 - 18 - - NP - SM - - - - - - -
14. 21.00 13 SPT - - 72 - 28 - - NP - SM - - - - - - -
15. 23.00 14 SPT - - 74 - 26 - - NP - SM - - - - - - -
16. 25.00 18 SPT - - 82 - 18 - - NP - SM - - - - - - -
17. 27.50 19 SPT - - 86 - 14 - - NP - SM - - - - - - -
18. 30.00 Ref. SPT - ====== Gravelly clayey sand ======


221






M.K. Soil Testing Laboratory


Table No. 11/27 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 28
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 13.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 844.98m, E. 266.76m, RL of GL = 44.98m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 78 -22- 40 23 17 SC - - - - - - -
2. 1.50 16 SPT - - 80 -20- 42 22 20 SC - - - - - - -
3. 3.00 - UDS 2.65 - - - - - - SC 1.75 1.53 14.5 DST 0.05 29 -
4. 4.50 19 SPT - - 70 -50- 43 22 21 SC - - - - - - -
5. 6.00 - UDS/
DS
- 12 62 -26- 40 23 17 SC - - - - - - -
6. 7.50 Ref. SPT - 9 68 -23- 42 24 18 SC - - - - - - -
7. 9.00 - UDS/
DS
- 18 63 -19- - NP - SM - - - - - - -
8. 10.50 Ref. SPT - 20 55 -25- - NP - SM - - - - - - -



222






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 28

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - 22 53 -25- - NP - SM - - - - - - -
10. 13.50 Ref. SPT - 24 54 -22- - NP - SM - - - - - - -
11. 15.0 Ref. SPT - 25 55 -20- - NP - SM - - - - - - -
12. 17.0 Ref. SPT - 22 46 -32- - NP - SM - - - - - - -
13. 19.00 Ref. SPT - 19 42 -39- - NP - SM - - - - - - -
14. 21.00 Ref. SPT - 22 51 -27- - NP - SM - - - - - - -
15. 23.00 Ref. SPT - 23 52 -25- - NP - SM - - - - - - -
16. 25.00 72 SPT - 20 61 -19- - NP - SM - - - - - - -
17. 27.50 65 SPT - 27 51 -22- - NP - SM - - - - - - -
18. 30.00 74 SPT - 19 62 -19- - NP - SM - - - - - - -


223






M.K. Soil Testing Laboratory



Table No. 11/28 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 29
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 879.47m, E. 362.51m, RL of GL = 44.07m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 16 SPT - - 36 - 64
H(43)(22)
53 26 27 CH - - - - - - -
3. 3.00 - UDS/
DS
- 2 26 - 72
H(47)(25)
59 26 33 CH - - - - - - -
4. 4.50 17 SPT - 2 36 - 62
H(41)(21)
55 25 30 CH - - - - - - -
5. 6.00 - UDS/
DS
- 6 54 - 40 - - NP - SM - - - - - - -
6. 7.50 19 SPT - 8 62 - 30 - - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- 2 58 - 40 - - NP - SM - - - - - - -
8. 10.50 20 SPT - 6 48 - 46 - - NP - SM - - - - - - -


224






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 29

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 4 54 - 42 - - NP - SM - - - - - - -
10. 13.50 18 SPT - - 60 - 40 - - NP - SM - - - - - - -
11. 15.0 20 SPT - 24 32 - 44 - - NP - SM - - - - - - -
12. 17.0 Ref. SPT - 22 24 - 54 - - NP - ML - - - - - - -
13. 19.00 Ref. SPT - 10 12 - 78 - - NP - ML - - - - - - -
14. 21.00 Ref. SPT - 10 26 - 64 - - NP - ML - - - - - - -
15. 23.00 Ref. SPT - 18 74 - 26 - - NP - SM - - - - - - -
16. 25.00 Ref. SPT - ======== Rock CR = 28%, RQD = 28% ======
17. 27.50 19 SPT - ======== Rock CR = 10%, RQD = 21% ======
18. 30.00 Ref. SPT - ======== Rock CR = 20%, RQD = Nil ======


225






M.K. Soil Testing Laboratory




Table No. 11/29 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 30
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 868.8m, E. 521.7m, RL of GL = 44.69m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 07 - 93
H(63)(50)
58 27 31 CH - - - - - - -
2. 1.50 14 SPT - - 5 - 95 - 59 28 31 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.70 1.42 19.2 TUU 0.70 5 -
4. 4.50 30 SPT - - 08 - 92
H(61)(31)
65 28 37 CH - - - - - - -
5. 6.00 - UDS 2.66 - - - - - - CH 1.75 1.47 18.5 TUU 0.80 2 -
6. 7.50 49 SPT - - 12 - 88 - 60 30 30 CH - - - - - - -
7. 9.00 - UDS 2.68 - - - - - - CH 1.86 1.54 20.5 TUU 0.96 5 -
8. 10.50 38 SPT - - 7 - 93
H(64)(29)
62 31 31 CH - - - - - - -

226






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 30

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.65 - - - - NP - SM 1.93 1.74 10.8 DST 0 32 -
10. 13.50 37 SPT - 15 63 - 22 - - NP - SM - - - - - - -
11. 15.0 - UDS 2.65 - - - - - - SM 1.98 1.70 16.3 DST 0 33 -
12. 17.0 59 SPT - 23 59 - 18 - - NP - SM - - - - - - -
13. 19.00 - UDS/
DS
- 19 54 - 27 - - NP - SM - - - - - - -
14. 21.00 38 SPT - 26 55 - 19 - - NP - SM - - - - - - -
15. 23.00 - UDS/
DS
- 20 60 - 20 - - NP - SM - - - - - - -
16. 25.00 49 SPT - 28 49 - 23 - - NP - SM - - - - - - -
17. 27.50 - UDS/
DS
- - 11 - 89
H(57)(32)
60 25 35 CH - - - - - - -
18. 30.00 92 SPT - - 8 - 92
H(62)(30)
62 30 32 CH - - - - - - -




227






M.K. Soil Testing Laboratory





Table No. 11/30 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 31
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.50M

Termination depth (m): 35.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 868.8m, E. 578.7m, RL of GL = 44.89m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 10 - 90
H(65)(25)
58 28 30 CH - - - - - - -
2. 1.50 22 SPT - - 4 - 96
H(65)(31)
56 30 26 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.79 1.49 19.8 TUU 0.75 5 -
4. 4.50 25 SPT - - 3 - 97
H(64)(33)
64 26 38 CH - - - - - - -
5. 6.00 - UDS 2.7 - - - - - - CH 1.88 1.51 24.3 TUU 0.82 6 -
6. 7.50 28 SPT - - 10 - 90
H(62)(28)
65 28 37 CH - - - - - - -
7. 9.00 - UDS 2.66 - - - - - - CH 1.96 1.60 22.5 TUU 0.84 6 -
8. 10.50 32 SPT - - 7 - 93
H(65)(28)
60 27 33 CH - - - - - - -
228






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 31

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.67 - - - - - - SM 1.99 1.65 20.5 TUU 0.9 2 -
10. 13.50 37 SPT - - 9 - 91
H(59)(32)
66 29 37 CH - - - - - - -
11. 15.0 - UDS 2.67 - - - - - - CH 2.10 1.72 21.6 DST 1.05 5 -
12. 17.0 Ref. SPT - ==== Grayish black coloured, completely weathered rock =====
13. 19.00 Ref. SPT - ==== Grayish black coloured, completely weathered rock =====
14. 21.00 Ref. SPT - ==== Grayish black coloured, highly weathered rock CR = 22%, RQD = Nil =====
15. 23.00 Ref. SPT - ==== Grayish black coloured, highly weathered rock CR = 25%, RQD = Nil =====
16. 25.00 Ref. SPT - ==== Grayish black coloured, highly weathered rock CR = 24%, RQD = Nil =====
17. 27.50 Ref. SPT - ==== Grayish black coloured, highly weathered rock CR = 28%, RQD = 12% =====
18. 30.00 Ref. SPT - ==== Grayish black coloured, highly weathered rock CR = 32%, RQD = 21% =====
19. 32.50 - DS - ==== Grayish black coloured, highly weathered rock CR = 30%, RQD = 15% =====
20 35.0 - DS - ==== Grayish black coloured, highly weathered rock CR = 28%, RQD = 10% =====
229






M.K. Soil Testing Laboratory





Table No. 11/31 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 32
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 12.70M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 821.91m, E. 390.15m, RL of GL = 44.46m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 -92- 59 25 34 CH - - - - - - -
2. 1.50 15 SPT - - 4 -96- 60 25 35 CH - - - - - - -
3. 3.00 - UDS 2.7 - - - - - - CH 1.79 1.52 17.5 TUU 0.7 5 -
4. 4.50 15 SPT - - 6 -94- 55 25 30 CH - - - - - - -
5. 6.00 - UDS 2.65 12 58 -30- - NP - SM 1.85 1.64 12.8 DST 0 29 -
6. 7.50 23 SPT - 15 58 -27- - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- 22 54 -24- - NP - SM - - - - - - -
8. 10.50 31 SPT - 22 56 -22- - NP - SM - - - - - - -
230






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 32

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 37 SPT - 14 59 -27- - NP - SM - - - - - - -
10. 13.50 38 SPT - 18 58 -24 - NP - SM - - - - - - -
11. 15.00 43 SPT - 15 65 -20- - NP - SM - - - - - - -
12. 17.00 52 SPT - 18 59 -23- - NP - SM - - - - - - -
13. 19.00 Ref. SPT - 45 37 -18- - NP - GM - - - - - - -
14. 21.00 Ref. SPT - 48 37 -15- - NP - GM - - - - - - -
15. 23.00 Ref. SPT - 47 38 -15- - NP - GM - - - - - - -
16. 25.00 Ref. SPT - ==== Grayish blackish coloured, completely weathered rock ======
17. 27.00 Ref. SPT - ==== Grayish blackish coloured, completely weathered rock ======
18. 30.00 Ref. SPT - ==== Grayish blackish coloured, completely weathered rock ======




231






M.K. Soil Testing Laboratory





Table No. 11/32 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 33
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 13.10M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 818.77m, E. 513.93m, RL of GL = 44.69
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 - 92
H(61)(31)
60 30 30 CH - - - - - - -
2. 1.50 - UDS 2.7 - - - - - - CH 1.89 1.58 19.6 TUU 0.70 5 -
3. 3.00 35 SPT - - 5 - 95
H(66)(29)
62 28 34 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH 1.95 1.61 21.3 TUU 0.76 2 -
5. 6.00 38 SPT - - 4 - 96
H(65)(31)
60 26 34 CH - - - - - - -
6. 7.50 - UDS 2.66 - - - - - - CH 1.99 1.61 23.6 TUU 0.80 6 -
7. 9.00 44 SPT - - 5 - 95
H(64)(31)
60 28 32 CH - - - - - - -
8. 10.50 - UDS 2.66 - - - - - - CH 2.00 1.59 25.8 TUU 0.85 5 -
232






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 33

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 49 SPT - - 7 - 93
H(63)(30)
58 29 27 CH - - - - - - -
10. 13.50 - UDS 2.65 - - - - - - CH - - - - - - -
11. 15.00 53 SPT - - 9 - 91
H(63)(28)
54 28 26 CH - - - - - - -
12. 17.00 58 SPT - - 10 -90- - NP - SM - - - - - - -
13. 19.00 64 SPT - - 7 - 93
H(65)(28)
58 27 31 CH - - - - - - -
14. 21.00 74 SPT - - 10 -90- - NP - CH - - - - - - -
15. 23.00 81 SPT - - 12 - 88
H(60)(28)
56 28 28 CH - - - - - - -
16. 25.00 86 SPT - - 13 -87- 58 28 30 CH - - - - - - -
17. 27.50 Ref. SPT - - 10 - 90
H(60)(30)
58 29 29 CH - - - - - - -
18. 30.00 Ref. SPT - - 8 -92- 56 28 28 CH - - - - - - -



233






M.K. Soil Testing Laboratory





Table No. 11/33 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 34
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.0M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 818.77m, E. 600.0m, RL of GL = 45.73m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 6 -94- 75 25 50 CH - - - - - - -
2. 1.50 18 SPT - - 2 - 98
H(66)(32)
65 28 37 CH - - - - - - -
3. 3.00 - UDS 2.7 - - - - - - CH 1.75 1.45 20.8 TUU 0.59 5 -
4. 4.50 20 SPT - - 3 - 97
H(65)(32)
64 29 35 CH - - - - - - -
5. 6.00 - UDS 2.67 - - - - - - CH 1.84 1.48 24.3 TUU 0.75 2 -
6. 7.50 27 SPT - - 5 - 95
H(61)(34)
28 32 - CH - - - - - - -
7. 9.00 - UDS 2.67 - - - - - - CH 1.92 1.52 26.5 TUU 0.9 5 -
8. 10.50 29 SPT - - 2 - 98
H(64)(34)
65 25 40 CH - - - - - - -
234






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 34

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.66 - - - - - - CH 1.98 1.65 19.6 TUU 0.92 8 -
10. 13.50 40 SPT - - 17 - 83
H(57)(26)
58 29 29 CH - - - - - - -
11. 15.00 45 SPT - - 8 -92- 58 25 33 CH - - - - - - -
12. 17.00 50 SPT - - 10 - 90
H(62)(28)
55 28 27 CH - - - - - - -
13. 19.00 53 SPT - - 11 -89- 61 28 33 CH - - - - - - -
14. 21.00 57 SPT - - 8 - 92
H(60)(32)
60 25 35 CH - - - - - - -
15. 23.00 Ref. SPT - - ===== Grayish black coloured, highly weathered rock CR = 25%, RQD = 10% ====
16. 25.00 Ref. CS - - ===== Grayish black coloured, highly weathered rock CR = 30%, RQD = 15% ====
17. 27.50 - DS - - ===== Grayish black coloured, highly weathered rock CR = 32%, RQD = 16% ====
18. 30.00 - DS - - ===== Grayish black coloured, highly weathered rock CR = 35%, RQD = 20% ====



235






M.K. Soil Testing Laboratory





Table No. 11/34 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 35
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.50M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 811.97m, E. 208.80m, RL of GL = 45.19m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 73 -27- - NP - SM - - - - - - -
2. 1.50 9 SPT - - 76 -24- - NP - SM - - - - - - -
3. 3.00 - UDS 2.65 - - - - - - SM 1.64 1.45 12.8 DST 0 28 -
4. 4.50 59 SPT - - 75 -25- - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- - 80 -20- - NP - SM - - - - - - -
6. 7.50 48 SPT - 15 59 -26- - NP - SM - - - - - - -
7. 9.00 Ref. SPT - 20 50 -30- - NP - SM - - - - - - -
8. 10.50 Ref. SPT - 4 6 -90- 59 28 31 CH - - - - - - -
236






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 35

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- - 70 -30- - NP - SM - - - - - - -
10. 13.50 Ref. SPT - - 8 -92- 56 28 28 CH - - - - - - -
11. 15.00 Ref. SPT - - 80 -20- - NP - SM - - - - - - -
12. 17.00 Ref. SPT - 19 57 -24 - NP - SM - - - - - - -
13. 19.00 Ref. SPT - 15 60 -28- 36 23 13 SC - - - - - - -
14. 21.00 Ref. SPT - 9 63 -28- 39 25 14 SC - - - - - - -
15. 23.00 Ref. SPT - 8 69 -23- 35 24 11 SC - - - - - - -
16. 25.00 Ref. SPT - 52 18 -30- 40 26 14 GC - - - - - - -
17. 27.50 - DS - 50 34 -16- 38 24 14 GC - - - - - - -
18. 30.00 Ref. SPT - - 11 - 89
H(58)(31)
65 29 36 CH - - - - - - -



237






M.K. Soil Testing Laboratory





Table No. 11/35 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 36
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 14.45M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 784.29m, E. 265.03m, RL of GL = 44.52m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 61 -39- 46 25 21 SC - - - - - - -
2. 1.50 26 SPT - - 70 -30- 40 23 17 SC - - - - - - -
3. 3.00 - UDS 2.66 - - - - - - SC 1.89 1.66 13.8 DST 0.09 29 -
4. 4.50 29 SPT - 10 68 -22- - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- 15 66 -19- - NP - SM - - - - - - -
6. 7.50 Ref. SPT - ==== Grayish blackish coloured, highly weathered rock CR = 22%, RQD = 12% ===
7. 9.00 Ref. SPT - ==== Grayish blackish coloured, highly weathered rock CR = 25%, RQD = 20% ===
8. 10.50 Ref. SPT - ==== Grayish blackish coloured, highly weathered rock CR = 45%, RQD = 36% ===
238






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 36

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 43 SPT - 16 66 -18- - NP - SM - - - - - - -
10. 13.50 Ref. SPT - 18 65 -17- - NP - SM - - - - - - -
11. 15.00 Ref. SPT - 20 55 -25- - NP - SM - - - - - - -
12. 17.00 Ref. SPT - 19 55 -26- - NP - SM - - - - - - -
13. 19.00 45 SPT - 20 62 -18- - NP - SM - - - - - - -
14. 21.00 44 SPT - 26 50 -24- - NP - SM - - - - - - -
15. 23.00 46 SPT - 13 42 -29- - NP - SM - - - - - - -
16. 25.00 48 SPT - 22 58 -20- - NP - SM - - - - - - -
17. 27.50 53 SPT - 53 25 -22- - NP - GM - - - - - - -
18. 30.00 62 SPT - 50 32 -18- - NP - GM - - - - - - -



239






M.K. Soil Testing Laboratory





Table No. 11/36 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 37
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.00M

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 805.34m, E. 485.64m, RL of GL = 44.23m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 10 - 90
H(61)(29)
59 28 31 CH - - - - - - -
2. 1.50 19 SPT - - 4 - 96
H(66)(30)
62 30 32 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.84 1.53 19.8 TUU 0.65 3 -
4. 4.50 31 SPT - - 6 -94- 55 29 26 CH - - - - - - -
5. 6.00 - UDS 2.7 - - - - - - CH 1.89 1.53 23.6 TUU 0.81 9 -
6. 7.50 35 SPT - - 7 - 93
H(64)(29)
58 29 29 CH - - - - - - -
7. 9.00 - UDS 2.7 - - - - - - CH 2.00 1.56 28.3 TUU 0.85 2 -
8. 10.50 43 SPT - - 7 - 93
H(63)(30)
59 25 34 CH - - - - - - -
240






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 37

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS - - - - - - - CH - - - - - - -
10. 13.50 47 SPT - - 9 - 91
H(60)(31)
60 30 30 CH - - - - - - -
11. 15.00 - UDS - - - - - - - CH - - - - - - -
12. 17.00 55 SPT - - 10 - 90
H(63)(27)
56 29 27 CH - - - - - - -
13. 19.00 64 SPT - 20 52 -28- 36 24 12 SC - - - - - - -
14. 21.00 71 SPT - 21 49 -30- 38 22 16 SC - - - - - - -
15. 23.00 Ref. SPT - === Grayish blackish coloured, highly weathered rock (Basalt) CR=24%, RQD=7% ==
16. 25.00 - DS - === Grayish blackish coloured, highly weathered rock (Basalt) CR=43%, RQD=13% ==
17. 27.50 - DS - === Grayish blackish coloured, highly weathered rock (Basalt) CR=30%, RQD=Nil ====
18. 30.00 - DS - === Grayish blackish coloured, highly weathered rock (Basalt) CR=25%, RQD=Nil ====



241






M.K. Soil Testing Laboratory





Table No. 11/37 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 38
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 14.85

Termination depth (m): 19.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 753.63m, E. 475.2m, RL of GL = 44.61m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 12 SPT - 14 58 - 28 - 70 24 46 SC - - - - - - -
3. 3.00 - UDS 2.65 - - - - - - SC 1.65 - 19.2 TUU 0.39 6 0.32
4. 4.50 55 SPT - 8 10 - 82
H(53)(29)
65 23 42 CH - - - - - - -
5. 6.00 - UDS 2.66 - - - - - - CH 1.78 - 1.75 TUU 0.85 9 -
6. 7.50 59 SPT - 10 12 - 78
H(54)(24)
59 26 33 CH - - - - - - -
7. 9.00 62 SPT - 16 38 - 46- 52 24 28 SC - - - - - - -
8. 10.50 42 SPT - - 66 - 34 - - NP - SM - - - - - - -
242






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 38

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - ========= Rock CR = 42%, RQD = 15% =========
10. 13.50 Ref. SPT - ========= Rock CR = 45%, RQD = 20% =========
11. 15.0 Ref. SPT - ========= Rock CR = 42%, RQD = 22% =========
12. 17.0 Ref. SPT - ========= Rock CR = 30%, RQD = 15% =========
13. 19.00 Ref. SPT - ========= Rock CR = 35%, RQD = 10% =========




243






M.K. Soil Testing Laboratory




Table No. 11/38 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 39
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N.777.8m, E. 514.01m, RL of GL = 45.45m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 10 - 90 - 58 28 30 CH - - - - - - -
2. 1.50 - UDS 2.68 - - - - - - CH 1.70 1.41 20.3 TUU 0.59 6 -
3. 3.00 20 SPT - - 7 -93- 56 26 30 CH - - - - - - -
4. 4.50 - UDS 2.7 - - - - - - CH 1.81 1.52 18.7 TUU 0.65 5 -
5. 6.00 27 SPT - - 8 - 92
H(60)(32)
68 29 39 CH - - - - - - -
6. 7.50 - UDS 2.70 - - - - - - CH 1.90 1.61 17.5 TUU 0.81 9 -
7. 9.00 32 SPT - - 1 - 99
H(64)(35)
76 25 31 CH - - - - - - -
8. 10.50 - UDS 2.68 - - - - - - CH 1.95 1.60 21.8 TUU 0.96 2 -

244






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 39

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 37 SPT - - 6 -94- 55 28 27 CH - - - - - - -
10. 13.50 - UDS 2.68 - - - - - - CH - - - - - - -
11. 15.00 80 SPT - - 4 -96- 58 25 33 CH - - - - - - -
12. 17.00 Ref. SPT - === Grayish blackish coloured, highly weathered rock CR = 23%, RQD = Nil ====
13. 19.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 23%, RQD = Nil ====
14. 21.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 28%, RQD = 5% ====
15. 23.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 20%, RQD = Nil ====
16. 25.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 22%, RQD = Nil ====
17. 27.50 - DS - === Grayish blackish coloured, highly weathered rock CR = 22%, RQD = 4% ====
18. 30.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 25%, RQD = 10% ====
245






M.K. Soil Testing Laboratory




Table No. 11/39 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 40
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 777.8m, E. 586.4m, RL of GL = 46.8m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 3 - 97
H(66)(31)
59 25 34 CH - - - - - - -
2. 1.50 14 SPT - - 2 - 98
H(68)(30)
56 26 30 CH - - - - - - -
3. 3.00 - UDS 2.7 - - - - - - CH 1.72 1.43 20.3 TUU 0.53 5 -
4. 4.50 35 SPT - - 10 - 90
H(62)(28)
55 28 27 CH - - - - - - -
5. 6.00 - UDS 2.68 - - - - - - CH 1.86 1.50 23.5 TUU 0.78 4 -
6. 7.50 39 SPT - - 10 -90- 60 29 31 CH - - - - - - -
7. 9.00 - UDS 2.68 - - - - - - CH 1.95 1.57 24.0 TUU 0.89 5 -
8. 10.50 29 SPT - - 3 - 97
H(64)(33)
58 29 29 CH - - - - - - -

246






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 40

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - - - - - CH 1.98 1.64 20.3 TUU 0.90 8 -
10. 13.50 35 SPT - - 6 - 94
H(63)(31)
58 28 30 CH - - - - - - -
11. 15.00 - UDS 2.68 - - - - - - CH 2.03 1.67 21.5 TUU 0.95 2 -
12. 17.00 37 SPT - - 8 - 92
H(62)(30)
55 29 26 CH - - - - - - -
13. 19.0 - UDS 2.68 - - - - - - CH 2.05 1.65 23.8 TUU 0.99 5 -
14. 21.00 47 SPT - - 3 - 97
H(66)(31)
69 28 41 CH - - - - - - -
15. 23.00 - UDS 2.67 - - - - - - CH 2.08 1.67 24.5 TUU 1.05 2 -
16. 25.00 Ref. SPT - - 4 - 96
H(66)(30)
58 27 31 - - - - - - - -
17. 27.5 - CS - === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ===
18. 30.00 Ref. SPT - === Grayish blackish coloured, completely weathered rock CR = Nil, RQD= Nil ===
247






M.K. Soil Testing Laboratory




Table No. 11/40 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 41
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m):

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 777.8m, E. 578.7m, RL of GL = 44.89m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 4 -96- 57 29 28 CH - - - - - - -
2. 1.50 8 SPT - - 12 -88- 58 23 30 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.75 1.42 23.2 TUU 0.50 5 -
4. 4.50 11 SPT - - 15 -85- 55 27 28 CH - - - - - - -
5. 6.00 - UDS 2.68 - - - - - - CH 1.79 1.39 28.5 TUU 0.58 2 -
6. 7.50 14 SPT - - 13 -87- 58 28 30 CH - - - - - - -
7. 9.00 - UDS 2.66 - - - - - - CH 1.85 1.46 26.4 TUU 0.65 8 -
8. 10.50 19 SPT - - 15 -85- 57 29 28 CH - - - - - - -

248






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 41

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - 4 - 96
H(64)(32)
- NP - CH 1.90 1.55 22.8 TUU 0.86 5 -
10. 13.50 25 SPT - - 5 -95- 59 29 30 CH - - - - - - -
11. 15.00 - UDS 2.65 - - - - - - CH 1.90 1.54 23.6 TUU 0.86 2 -
12. 17.00 50 SPT - - 9 - 91
H(63)(28)
58 29 29 CH - - - - - - -
13. 19.0 53 SPT - - 11 -89- 58 28 30 CH - - - - - - -
14. 21.00 57 SPT - - 3 - 87
H(62)(25)
58 28 30 CH - - - - - - -
15. 23.00 61 SPT - - 12 -88- 61 30 31 CH - - - - - - -
16. 25.00 67 SPT - - 11 - 89
H(61)(28)
60 28 32 CH - - - - - - -
17. 27.50 69 SPT - - 8 -92- 58 28 30 CH - - - - - - -
18. 30.00 77 SPT - - 6 - 94
H(64)(30)
59 29 30 CH - - - - - - -
249






M.K. Soil Testing Laboratory




Table No. 11/41 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 42
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 711.96m, E. 193.85m, RL of GL = 45.93m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 16 -72- - NP - SM - - - - - - -
2. 1.50 35 SPT - - 75 -25- - NP - SM - - - - - - -
3. 3.00 - UDS 2.66 - - - - - - SM 1.85 1.62 14.2 DST 0 32 -
4. 4.50 29 SPT - - 68 -32- - NP - SM - - - - - - -
5. 6.00 - UDS/
DS
- - 73 -27- - NP - SM - - - - - - -
6. 7.50 38 SPT - - 72 -28- - NP - SM - - - - - - -
7. 9.00 - UDS 2.70 - - - - - - CH 1.96 1.51 29.8 TUU 0.89 6 -
8. 10.50 60 SPT - - 6 - 94
H(64)(30)
61 29 32 CH - - - - - - -

250






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 42

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 2 12 - 86
H(61)(25)
59 26 33 CH - - - - - - -
10. 13.50 Ref. SPT - 2 13 - 85
H(60)(25)
58 25 33 CH - - - - - - -
11. 15.00 Ref. SPT - - 14 -86- 57 25 32 CH - - - - - - -
12. 17.00 Ref. SPT - 1 16 -83- 58 26 32 CH - - - - - - -
13. 19.0 Ref. SPT - 2 8 - 90
H(62)(28)
57 27 30 CH - - - - - - -
14. 21.00 Ref. SPT - 2 12 -86- 55 28 27 CH - - - - - - -
15. 23.00 Ref. SPT - 1 9 - 90
H(63)(27)
58 29 29 CH - - - - - - -
16. 25.00 Ref. SPT - 2 11 -87- 57 27 30 CH - - - - - - -
17. 27.50 Ref. SPT - 2 11 -87- 59 25 34 CH - - - - - - -
18. 30.00 - DS - - 8 - 92
H(61)(31)
57 27 30 CH - - - - - - -
251






M.K. Soil Testing Laboratory




Table No. 11/42 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 43
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.70

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 697.29m, E. 254.69m, RL of GL = 45.93m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 5 -95- 58 25 33 CH - - - - - - -
2. 1.50 18 SPT - - 5 - 95
H(66)(29)
59 26 33 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.70 1.41 20.5 TUU 0.52 8 -
4. 4.50 16 SPT - 2 68 -30- - NP - GM - - - - - - -
5. 6.00 - UDS/
DS
- 10 68 -22- - NP - GM - - - - - - -
6. 7.50 17 SPT - 17 63 -20- - NP - GM - - - - - - -
7. 9.00 - UDS - 8 6 -26- - NP - GM - - - - - - -
8. 10.50 22 SPT - 10 68 -22- - NP - GM - - - - - - -

252






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 43

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 4 73 -23- - NP - SM - - - - - - -
10. 13.50 Ref. SPT - 42 30 -28- - NP - GM - - - - - - -
11. 15.00 - UDS/
DS
- 38 30 -32- - NP - GM - - - - - - -
12. 17.00 Ref. SPT - 40 33 -27- - NP - GM - - - - - - -
13. 19.0 18 SPT - 15 50 -35- - NP - SM - - - - - - -
14. 21.00 17 SPT - 19 42 -39- - NP - SM - - - - - - -
15. 23.00 Ref. SPT - === Grayish blackish coloured, highly weathered rock CR = 29%, RQD = 15% ===
16. 25.00 Ref. SPT - === Grayish blackish coloured, highly weathered rock CR = 40%, RQD = 22% ===
17. 27.50 Ref. SPT - === Grayish blackish coloured, highly weathered rock CR = 31%, RQD = 10% ===
18. 30.00 Ref. DS - === Grayish blackish coloured, highly weathered rock CR = 26%, RQD = 10% ===
253






M.K. Soil Testing Laboratory





Table No. 11/43 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 44
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.00M

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 792.37m, E. 390.16m, RL of GL = 45.16m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 - 89 - 58 24 34 CH - - - - - - -
2. 1.50 14 SPT - - - - 93
H(62)(31)
61 29 32 CH - - - - - - -
3. 3.00 - DS - ==== Grayish blackish coloured, completely weathered rock =====
4. 4.50 28 SPT - - 11 - 89
H(60)(29)
59 28 31 CH - - - - - - -
5. 6.00 - UDS 2.70 - - - - - - CH 1.75 1.43 21.8 TUU 0.65 4 -
6. 7.50 Ref. SPT - ==== Blackish coloured, completely weathered rock CR = Nil, RQD = Nil ===
7. 9.00 - CS - ==== Blackish coloured, highly weathered rock CR = 30%, RQD = Nil ===
8. 10.50 - CS - ==== Blackish coloured, highly weathered rock CR = 22%, RQD = Nil ===
254






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 44

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - DS - ==== Blackish coloured, highly weathered rock CR = 20%, RQD = Nil ===
10. 13.50 - DS - ==== Reddish coloured, highly weathered rock CR = 44%, RQD = 37% ===
11. 15.0 - DS - ==== Reddish coloured, highly weathered rock CR = 45%, RQD = 45% ===
12. 17.0 - DS - ==== Reddish coloured, highly weathered rock CR = 36%, RQD = 36% ===
13. 19.00 - DS - ==== Reddish coloured, highly weathered rock CR = 39%, RQD = 32% ===
14. 21.00 - DS - ==== Reddish coloured, highly weathered rock CR = 46%, RQD = 27% ===
15. 23.00 - DS - ==== Reddish coloured, highly weathered rock CR = 31%, RQD = 6% ===
16. 25.00 - DS - ==== Reddish coloured, highly weathered rock CR = 26%, RQD = 10% ===
17. 27.50 - DS - ==== Reddish coloured, highly weathered rock CR = 30%, RQD = Nil ===
18. 30.00 - DS - ==== Reddish coloured, highly weathered rock CR = 21%, RQD = 6% ===
19. 32.50 - DS - ==== Reddish coloured, highly weathered rock CR = 20%, RQD = Nil ===
20 35.0 - DS - ==== Reddish coloured, highly weathered rock CR = 25%, RQD = 12% ===
21. 37.50 - DS - ==== Reddish coloured, highly weathered rock CR = 42%, RQD = 36% ===
22. 40.0 - DS - ==== Reddish coloured, highly weathered rock CR = 45%, RQD = 45% ===
255






M.K. Soil Testing Laboratory


Table No. 11/44 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 45
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.35M

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 725.83m, E. 499.97m, RL of GL = 45.08m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 4 - 96
H(65)(31)
59 28 31 CH - - - - - - -
2. 1.50 18 SPT - - 7 - 93 - 55 29 26 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.70 1.43 18.8 TUU 0.65 6 -
4. 4.50 24 SPT - - 4 - 99
H(66)(30)
57 28 29 CH - - - - - - -
5. 6.00 - UDS 2.68 - - - - - - CH 1.89 1.56 21.3 TUU 0.58 5 -
6. 7.50 31 SPT - - 6 - 94
H(63)(31)
61 30 31 CH - - - - - - -
7. 9.00 - UDS/
DS
- 14 64 - 22 - - NP - SM - - - - - - -
8. 10.50 57 SPT - 15 65 - 20 - - NP - SM - - - - - - -
9. 12.00 61 SPT - 15 62 - 23 - - NP - SM - - - - - - -
10. 13.50 65 SPT - 19 55 - 26 - - NP - SM - - - - - - -

256






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 45

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 15.00 75 SPT - 25 56 - 19 - - NP - SM - - - - - - -
12. 17.00 Ref. DS - ===== Grayish black coloured, highly weathered rock CR = 24%, RQD = 15% ===
13. 19.00 - DS - ===== Grayish black coloured, highly weathered rock CR = 21%, RQD = Nil ===
14. 21.00 - DS - ===== Grayish black coloured, highly weathered rock CR = 41%, RQD = 25% ===
15. 23.00 - DS - ===== Grayish black coloured, highly weathered rock CR = 36%, RQD = 12% ===
16. 25.00 - DS - ===== Grayish black coloured, highly weathered rock CR = 32%, RQD = 40% ===
17. 27.50 - DS - ===== Grayish black coloured, highly weathered rock CR = 22%, RQD = Nil ===
18. 30.00 - DS - ===== Grayish black coloured, highly weathered rock CR = 25%, RQD = 6% ===
19. 32.5 - DS - ==== Grayish black coloured, highly weathered rock CR = 20%, RQD = Nil =====
20. 35.0 - DS - ==== Grayish black coloured, highly weathered rock CR = 39%, RQD = 21% =====
21. 37.5 - DS - ==== Grayish black coloured, highly weathered rock CR = 52%, RQD = 52% =====
22 40.0 - DS - ==== Grayish black coloured, highly weathered rock CR = 61%, RQD = 61% =====
257






M.K. Soil Testing Laboratory




Table No. 11/45 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 46
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.90

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 725.83m, E. 599.97m, RL of GL = 47.34m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 1.50 17 SPT - 8 66 - 26 - 54 27 27 SC - - - - - - -
2. 3.00 - UDS/
DS
- 6 68 - 26 - - NP - SM - - - - - - -
3. 4.50 20 SPT - - 42 - 58 - 69 28 41 CH - - - - - - -
4. 6.00 - UDS/
DS
- - 8 - 92
H(61)(31)
68 25 43 CH - - - - - - -
5. 7.50 24 SPT - 10 28 - 62 - 73 28 45 CH - - - - - - -
6. 9.00 - UDS/
DS
- - 6 - 94
H(60)(34)
70 28 42 CH - - - - - - -
7. 10.50 39 SPT - 4 40 - 56 - 55 28 27 CH - - - - - - -



258






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 46

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
8. 12.00 - UDS/
DS
- 2 32 - 66
H(45)(21)
61 26 35 CH - - - - - - -
9. 13.50 53 SPT - 8 40 - 52 - 65 17 48 CH - - - - - - -
10. 15.0 - UDS/
DS
- - 44 - 56 - 57 22 25 CH - - - - - - -
11. 17.0 Ref. SPT - - 36 - 64 - 55 22 33 CH - - - - - - -
12. 19.00 - UDS/
DS
- - 40 - 60 - - NP - SM - - - - - - -
13. 21.00 Ref. SPT - 2 26 - 72 - 53 25 28 CH - - - - - - -
14. 23.00 - UDS/
DS
- 2 40 - 52 - - NP - ML - - - - - - -
15. 25.0 Ref. SPT - 12 28 - 60 - - NP - ML - - - - - - -
16. 27.50 - UDS/
DS
- 6 40 - 54 - - NP - ML - - - - - - -
17. 30.00 - UDS/
DS
- ======= Rock Bolder =========




259






M.K. Soil Testing Laboratory




Table No. 11/46 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 47
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.00

Termination depth (m): 50.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 734.8m, E. 733.42m, RL of GL = 46.7m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 5 - 95
H(63)(32)
62 29 33 CH - - - - - - -
2. 1.50 39 SPT - - 8 -92- 57 25 32 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.86 1.55 19.6 TUU 0.89 5 -
4. 4.50 32 SPT - - 7 - 93
H(63)(30)
58 29 29 CH - - - - - - -
5. 6.00 - DS - 15 56 -29- - NP - SM - - - - - - -
6. 7.50 - UDS 2.65 9 66 -25- 38 24 14 SC - - - - - - -
7. 9.00 32 SPT - 8 61 -31- 39 25 14 SC - - - - - - -
8. 10.50 Ref. SPT - ======= Grayish white coloured, completely weathered rock =======

260






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 47

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - ======= Grayish white coloured, completely weathered rock CR = Nil, RQD = Nil =======
10. 13.50 - UDS - - - - - - - CH 1.98 1.56 26.5 TUU 0.95 2 -
11. 15.0 46 SPT - - 13 -87- 68 29 39 CH - - - - - - -
12. 17.0 - UDS - - - - - - - CH 1.99 1.63 21.8 TUU 0.98 5 -
13. 19.00 34 SPT - 2 12 -86- 60 28 32 CH - - - - - - -
14. 21.00 66 SPT - - 6 -94- 57 28 29 CH - - - - - - -
15. 23.00 29 SPT - 27 51 -22- - NP - SM - - - - - - -
16. 25.0 31 SPT - 22 48 -30- - NP - SM - - - - - - -
17. 27.50 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
18. 30.00 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
19. 32.50 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
20. 35.0 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
261






M.K. Soil Testing Laboratory





PAGE 3 FOR BOREHOLE NO. BH 47

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
21. 37.50 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
22. 40.00 Ref. SPT - ====== Reddish coloured, completely weathered rock (sandstone) ======
23. 42.50 Ref. SPT - ===== Reddish coloured, completely weathered rock (sandstone) CR = Nil, RQD = Nil ====
24. 45.00 Ref. SPT - ===== Reddish coloured, completely weathered rock (sandstone) CR = 20%, RQD = 12% ====
25. 47.50 Ref. SPT - ===== Reddish coloured, completely weathered rock (sandstone) CR = 20%, RQD = 13% ====
26. 50.00 Ref. SPT - ===== Reddish coloured, completely weathered rock (sandstone) CR = 26%, RQD = 16% ====












262






M.K. Soil Testing Laboratory




Table No. 11/47 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 48
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 13.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 663.66m, E. 699.97m, RL of GL = 47.47m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 7 -93- 58 28 30 CH - - - - - - -
2. 1.50 35 SPT - - 6 - 94
H(65)(29)
56 26 30 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.75 1.42 23.8 TUU 0.70 6 -
4. 4.50 19 SPT - - 8 - 92
H(60)(32)
69 28 41 CH - - - - - - -
5. 6.00 - UDS/
DS
- - 8 - 92
H(63)(29)
55 29 26 CH - - - - - - -
6. 7.50 Ref. SPT - - - - - - - CH - - - - - - -
7. 9.00 41 SPT - - 9 - 91
H(60)(31)
60 29 31 CH - - - - - - -
8. 10.50 - UDS 2.70 - - - - - - CH 1.84 1.45 26.3 TUU 0.86 4 -

263






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 48

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 53 SPT - - 10 -90- 58 28 30 CH - - - - - - -
10. 13.50 57 SPT - - - - - - - CH - - - - - - -
11. 15.00 - UDS 2.65 - - - - - - CH 1.89 1.51 24.8 TUU 0.96 5 -
12. 17.00 63 SPT - - 13 -87- 55 29 26 CH - - - - - - -
13. 19.00 66 SPT - - 14 -86- 60 29 31 CH - - - - - - -
14. 21.00 67 SPT - - 14 -86- 60 29 31 CH - - - - - - -
15. 23.00 - UDS/
DS
- - - - - - - CH - - - - - - -
16. 25.00 46 SPT - 28 45 -27- - NP - SM - - - - - - -
17. 27.50 - UDS/
DS
- - 5 - 95
H(64)(31)
65 28 37 CH - - - - - - -
18. 30.00 - SPT - - 11 - 89
H(61)(28)
60 25 35 CH - - - - - - -



264






M.K. Soil Testing Laboratory



Table No. 11/48 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 49
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 13.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 687.54m, E. 779.47m, RL of GL = 44.91m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - CH - - - - - - -
2. 1.50 - UDS/
DS
- 2 24 -74- 57 23 34 CH - - - - - - -
3. 3.00 20 SPT - 8 26 -66- 78 26 52 CH - - - - - - -
4. 4.50 - UDS/
DS
- === Reddish brown coloured, completely weathered rock ====
5. 6.00 85 SPT - === Reddish brown coloured, completely weathered rock ====
6. 7.50 - UDS 2.68 - - - - - - CH 1.74 1.51 15.19 - - - -
7. 9.00 Ref. SPT - - 5 -95- 58 29 29 CH - - - - - - -
8. 10.50 - UDS 2.68 - - - - - - CH 1.84 1.37 19.8 - - - -
9. 12.00 Ref. SPT - ==== Reddish coloured, completely weathered rock (sandstone) ====
265






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 49

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 - UDS/
DS
- ==== Reddish coloured, completely weathered rock (sandstone) ====
11. 15.00 Ref. SPT - ==== Reddish coloured, completely weathered rock (sandstone) ====
12. 17.00 31 SPT - - 26 - 74
H(48)(26)
59 23 26 CH - - - - - - -
13. 19.00 - UDS 2.70 - - - - - - CH 1.96 1.66 18.1 - - - -
14. 21.00 66 SPT - - 4 - 96
H(66)(30)
59 23 36 CH - - - - - - -
15. 23.00 Ref. SPT - 4 40 -56- 57 23 34 CH - - - - - - -
16. 25.00 Ref. SPT - - 8 - 92
H(64)(28)
56 25 31 CH - - - - - - -
17. 27.50 - UDS/
DS
- - 2 - 98
H(65)(33)
65 26 39 CH - - - - - - -
18. 30.00 58 SPT - - 24 -76- 78 27 51 CH - - - - - - -
19. 32.50 - UDS - - 30 - 70
H(45)(25)
52 23 29 CH - - - - - - -
20. 35.00 Ref. SPT - 2 40 -58- 55 25 30 CH - - - - - - -
21. 37.50 Ref. SPT - - 48 -52- 56 22 34 CH - - - - - - -
22. 40.00 Ref. SPT - - 38 - 62
H(36)(26)
54 21 33 CH - - - - - - -
266






M.K. Soil Testing Laboratory




Table No. 11/49 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 50
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.40

Termination depth (m): 35.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 718.9m, E. 857.14m, RL of GL = 47.32m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 13 - 87
H(59)(28)
59 28 31 CH - - - - - - -
2. 1.50 - UDS 2.68 - - - - - - CH 1.70 1.47 15.3 TUU 0.62 5 -
3. 3.00 20 SPT - - 7 - 93
H(62)(31)
57 27 30 CH - - - - - - -
4. 4.50 - UDS/
DS
- 20 42 -38- - NP - SM - - - - - - -
5. 6.00 52 SPT - 20 53 -27- - NP - SM - - - - - - -
6. 7.50 - UDS/
DS
- 18 60 -22- - NP - SM - - - - - - -
7. 9.00 44 SPT - 24 56 -20- - NP - SM - - - - - - -
8. 10.50 - UDS/
DS
- 4 58 -38- 45 24 21 SC - - - - - - -

267






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 50

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 37 SPT - - 70 -30- 44 24 20 SC - - - - - - -
10. 13.50 - UDS/
DS
- - 72 -28- 46 24 22 SC - - - - - - -
11. 15.00 39 SPT - - 8 -92- 58 28 30 CH - - - - - - -
12. 17.00 - UDS/
DS
- - 4 -96- 60 25 35 CH - - - - - - -
13. 19.00 34 SPT - - 8 -92- 56 25 31 CH - - - - - - -
14. 21.00 - UDS 2.68 - - - - - - CH 1.86 1.54 20.5 TUU 0.85 8 -
15. 23.00 51 SPT - - 13 -87- 58 28 30 CH - - - - - - -
16. 25.00 - UDS 2.68 - - - - - - CH 1.94 1.57 23.5 TUU 0.92 6 -
17. 27.50 55 SPT - 48 32 -20- - NP - GM - - - - - - -
18. 30.00 Ref. SPT - 51 24 -25- - NP - GM - - - - - - -
19. 32.50 - UDS/
DS
- 48 33 -19- - NP - GM - - - - - - -
20. 35.00 Ref. SPT - 54 24 -22- - NP - GM - - - - - - -
268






M.K. Soil Testing Laboratory



Table No. 11/50 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 51
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.0

Termination depth (m): 36.5m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 728.07m, E. 932.78m, RL of GL = 47.610m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 to 0.5 - DS - 2 22 - 76
H(55)(21)
37 21 16 CI - - - - - - -
2. 0.5-1.5 - UDS 2.70 - - - - - 46 CI 1.78 1.65 7.52 TUU 1.06 3 -
3. 1.5-3.0 28 SPT - - 18 - 82
H(50)(32)
73 32 41 CH - - - - - - -
4. 3.0-4.5 31 SPT - 6 16 - 78
H(49)(29)
65 27 38 CH - - - - - - -
5. 4.5-6.0 - UDS 2.68 - - - - - - CH 1.68 1.44 16.5 TUU 1.18 5 0.08
6. 6.0-7.5 70 SPT - - 70 - 30 - - NP - SM - - - - - - -
7. 7.5-9.0 - UDS/
DS
- - 60 - 40 - 46 28 18 SM - - - - - - -
8. 9.0-10.5 91 SPT - - 54 - 46 - 48 29 19 SM - - - - - - -


269






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 51

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 10.50 12.0 - UDS/
DS
- - 76 - 24 - - NP - SM - - - - - - -
10. 12.0 13.5 99 SPT - - 74 - 26 - - NP - SM - - - - - - -
11. 13.5 15.0 - UDS/
DS
- - 70 - 30 - - NP - SM - - - - - - -
12. 15.0 17.0 65 SPT - - 78 - 22 - - NP - SM - - - - - - -
13. 17.0-19.0 - UDS/
DS
- - 64 - 36 - 43 27 16 SM - - - - - - -
14. 19.0 21.0 65 SPT - 6 26 - 68
H(43)(25)
64 26 38 CH - - - - - - -
15. 21.0-23.0 - UDS 2.7 - - - - - - CH 1.71 1.45 18.1 TUU 1.85 5 0.08
16. 23.0 25.0 Ref. SPT - 4 44 - 52
H(33)(19)
52 26 26 CH - - - - - - -
17. 25.0 27.0 - UDS/
DS
- - 4 - 96
H(68)(28)
50 27 23 CH - - - - - - -
18. 27.5 30.0 - UDS/
DS
2.7 - - - - - - CH 1.83 1.55 18.3 TUU 1.60 5 -
19. 30.0 32.5 - DS - 14 37 - 52
H(30)(22)
56 27 29 CH - - - - - - -
20. 35.0 35.0 - DS - ==== Bold =======
21. 35.0 36.0 - DS ==== Bold =======
270






M.K. Soil Testing Laboratory




Table No. 11/51 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 52
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 7.85

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 657.7m, E. 908.42m, RL of GL = 47.05m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 to 0.5 - DS - 4 32 - 64
H(42)(22)
43 25 18 CI - - - - - - -
2. 0.5-1.5 - UDS 2.70 - - - - - - CI 1.68 1.44 16.68 TUU 0.86 2 -
3. 1.5-3.0 27 SPT - 8 14 - 78
H(54)(24)
52 29 23 CH - - - - - - -
4. 3.0-4.5 - UDS 2.68 - - - - - - CH 1.74 1.37 27.38 TUU 0.94 2 0.08
5. 4.5-6.0 82 SPT - - 48 - 52
H(32)(20)
52 30 22 CH - - - - - - -
6. 6.0-7.5 - UDS 2.70 - - - - - - CH 1.91 1.57 21.50 TUU 0.22 6 -
7. 7.5-9.0 81 SPT - 10 38 - 52
H(31)(21)
53 30 23 CH - - - - - - -
8. 9.0-10.5 - UDS 2.68 - - - - - - CH 1.83 1.49 22.5 TUU 1.40 2 0.04

271






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 52

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 10.50 12.0 90 SPT - 8 41 - 51 - 50 27 23 CH - - - - - - -
10. 12.0 13.5 - UDS 2.70 - - - - - - CH 1.82 1.50 21.06 TUU 1.54 5 -
11. 13.5 15.0 61 SPT - - 20 - 80
H(52)(28)
55 26 26 CH - - - - - - -
12. 15.0 17.0 - UDS 2.68 - - - - - - CH 1.80 1.46 2300 TUU 1.75 5 -
13. 17.0-19.0 61 SPT - - 6 - 94
H(64)(30)
52 25 27 CH - - - - - - -
14. 19.0 21.0 - UDS/
DS
- 6 38 - 56 - 52 24 28 CH - - - - - - -
15. 21.0-23.0 95 SPT - 10 14 - 76
H(52)(24)
51 26 25 CH - - - - - - -
16. 23.0 25.0 - UDS/
DS
- 6 38 - 56 - 52 24 28 CH - - - - - - -
17. 25.0 27.0 Ref. SPT - 4 22 - 74
H(52)(22)
51 23 28 CH - - - - - - -
18. 27.5 30.0 Ref. DS - - 60 - 40 - 47 20 27 SC - - - - - - -



272






M.K. Soil Testing Laboratory




Table No. 11/52 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 53
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 671.74m, E. 300.53m, RL of GL = 46.11m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 21 SPT - 4 38 - 58 - 40 27 13 ML - - - - - - -
3. 3.00 - UDS/
DS
- - 34 - 66 - 37 28 9 ML - - - - - - -
4. 4.50 22 SPT - - 20 - 80 - 45 30 15 ML - - - - - - -
5. 6.00 - UDS/
DS
- 4 56 - 40 - - NP - SM - - - - - - -
6. 7.50 Ref. SPT - 4 66 - 30 - - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- ======= Bolder ======
8. 10.50 Ref. SPT - ======= Bolder ======

273






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 53

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - ===== Bolder ==========
10. 13.50 Ref. SPT - 32 50 - 18 - - NP - SM - - - - - - -
11. 15.0 21 SPT - 4 50 - 46 - - NP - SM - - - - - - -
12. 17.0 Ref. SPT - 8 88 - 04 - - NP - SP/
SM
- - - - - - -
13. 19.00 Ref. SPT - 24 58 - 18 - - NP - SM - - - - - - -
14. 21.00 Ref. SPT - 4 62 - 34 - - NP - SM - - - - - - -
15. 23.00 Ref. SPT - 4 86 - 10 - - NP - SP/
SM
- - - - - - -
16. 25.00 Ref. SPT - - 88 - 12 - - NP - SP/
SM
- - - - - - -
17. 27.5 Ref. SPT - - - - - - - SP/
SM
- - - - - - -
18. 30.00 Ref. SPT - 4 86 - 10 - - NP - SP/
SM
- - - - - - -


274






M.K. Soil Testing Laboratory




Table No. 11/53 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 54
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 685.47m, E. 499.97m, RL of GL = 45.76m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 12 - 88
H(59)(29)
61 28 33 CH - - - - - - -
2. 1.50 17 SPT - - 6 - 94
H(64)(30)
56 28 28 CH - - - - - - -
3. 3.00 - UDS 2.69 - - - - - - CH - - - - - - -
4. 4.50 15 SPT - - 6 - 94
H(63)(31)
58 29 29 CH - - - - - - -
5. 6.00 - UDS/
DS
- 4 68 - 28 - - NP - SM - - - - - - -
6. 7.50 20 SPT - 8 72 - 20 - - NP - SM - - - - - - -
7. 9.00 - UDS/
DS
- 2 75 - 23 - - NP - SM - - - - - - -
8. 10.50 17 SPT - 8 64 - 28 - - NP - SM - - - - - -

275






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 54

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- 14 66 - 20 - - NP - SM - - - - - - -
10. 13.50 24 SPT - 20 58 - 22 - - NP - SM - - - - - - -
11. 15.00 - UDS/
DS
- 18 65 - 17 - - NP - SM - - - - - - -
12. 17.00 22 SPT - 22 53 - 25 - - NP - SM - - - - - - -
13. 19.00 25 SPT - 12 65 - 23 - - NP - SM - - - - - - -
14. 21.00 28 SPT - 18 60 - 22 - - NP - SM - - - - - - -
15. 23.00 25 SPT - 22 60 - 18 - - NP - SM - - - - - - -
16. 25.00 29 SPT - 15 61 - 24 - - NP - SM - - - - - - -
17. 27.5 29 SPT - 10 68 - 22 - - NP - SM - - - - - - -
18. 30.00 31 SPT - 14 60 - 26 - - NP - SM - - - - - - -




276






M.K. Soil Testing Laboratory





Table No. 11/54 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 55
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.85

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 685.47m, E. 599.97m, RL of GL = 47.42m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 1.50 18 SPT - 18 26 - 56 - - NP - ML - - - - - - -
3. 3.00 - UDS 2.65 - - - - - - CH 1.65 1.29 27.71 TUU 0.46 5 -
4. 4.50 22 SPT - 4 18 - 78 - 55 26 29 CH - - - - - - -
5. 6.00 - UDS/
DS
- 4 7 - 89
H(67)(21)
54 24 30 CH - - - - - - -
6. 7.50 40 SPT - 2 18 - 80 - 67 27 40 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 12 - 88 - 56 28 28 CH - - - - - - -
8. 10.50 24 SPT - - 4 - 88
H(64)(24)
73 25 48 CH - - - - - - -


277






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 55

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS - - 12 - 88
H(64)(24)
73 25 48 CH - - - - - - -
10. 13.50 30 SPT - - 4 - 96
H(71)(25)
53 26 27 CH - - - - - - -
11. 15.0 - UDS/
DS
- - 8 - 92 - 55 23 32 CH - - - - - - -
12. 17.0 Ref. SPT - - - - - - - CH - - - - - - -
13. 19.00 - UDS/
DS
- 2 56 - 42 - - NP - SM - - - - - - -
14. 21.00 Ref. SPT - - 8 - 92
H(62)(30)
74 26 48 CH - - - - - - -
15. 23.00 - UDS/
DS
- 2 72 - 26 - - NP - SM - - - - - - -
16. 25.0 Ref. SPT - - 58 - 42 - 30 23 7 SM - - - - - - -
17. 27.50 - UDS/
DS
- 2 59 - 28 - - NP - SM - - - - - - -
18. 30.00 Ref. SPT - - 59 - 41 - 30 25 5 SM - - - - - - -




278






M.K. Soil Testing Laboratory




Table No. 11/55 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 56
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate:
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 - 89
H(61)(28)
44 25 29 CI - - - - - - -
2. 1.50 19 SPT - - 26 - 74 - 46 24 22 CI - - - - - - -
3. 3.00 - UDS 2.66 - - - - - - CI 1.74 1.42 21.8 TUU 0.69 5 -
4. 4.50 22 SPT - - 4 - 96
H(65)(31)
58 25 33 CH - - - - - - -
5. 6.00 - UDS 2.7 - - - - - - CH 1.86 1.52 22.5 TUU 0.74 4 -
6. 7.50 28 SPT - - 8 - 92
H(61)(31)
61 28 33 CH - - - - - - -
7. 9.00 - UDS 2.68 - - - - - - CH 1.96 1.57 24.6 TUU 0.86 5 -
8. 10.50 Ref. SPT - - 64 - 36 - - NP - SM - - - - - -

279






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 56

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref. SPT - 18 54 - 28 - - NP - SM - - - - - - -
10. 13.50 Ref. SPT - 20 55 - 25 - - NP - SM - - - - - - -
11. 15.00 Ref. SPT - 23 57 - 20 - - NP - SM - - - - - - -
12. 17.00 Ref. SPT - 18 62 - 24 - - NP - SM - - - - - - -
13. 19.00 Ref. SPT - 22 58 - 20 - - NP - SM - - - - - - -
14. 21.00 Ref. SPT - 19 64 - 17 - - NP - SM - - - - - - -
15. 23.00 Ref. SPT - 26 49 - 25 - - NP - SM - - - - - - -
16. 25.00 Ref. SPT - 23 55 - 22 - - NP - SM - - - - - - -
17. 27.5 Ref. SPT - 27 43 - 30 - - NP - SM - - - - - - -
18. 30.00 Ref. SPT - 16 61 - 23 - - NP - SM - - - - - - -




280






M.K. Soil Testing Laboratory




Table No. 11/56 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 57
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 651.05m, E. 599.97m, RL of GL = 48.63m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 1.50 19 SPT - - 34 - 66 - 76 25 51 CH - - - - - - -
2. 3.00 - UDS 2.68 - - - - - - CH 1.68 1.35 24.69 TUU 0.35 6 0.27
3. 4.50 22 SPT - - 22 - 78
H(73)(5)
- NP - ML - - - - - - -
4. 6.00 - UDS 2.65 - - - - - - ML 1.78 1.47 21.12 DST 0 28 -
5. 7.50 28 SPT - - 26 - 74 - 67 25 112 CH - - - - - - -
6. 9.00 - UDS/
DS
- - 24 - 94
H(63)(31)
62 25 37 CH - - - - - - -
7. 10.50 31 SPT - - 20 - 80 - 64 25 39 CH - - - - - - -



281






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 57

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
8. 12.00 - UDS/
DS
- - 2 - 98
H(73)(25)
67 25 42 CH - - - - - - -
9. 13.50 54 SPT - - 12 - 46 - 56 26 30 SC - - - - - - -
10. 15.0 - DS - - 14 - 86 - 64 25 39 CH - - - - - - -
11. 17.0 35 SPT - - 12 - 88
H(65)(23)
63 25 38 CH - - - - - - -
12. 19.00 - DS - - 10 - 90 - 62 25 37 CH - - - - - - -
13. 21.00 32 SPT - - 10 - 90
H(60)(30)
61 25 36 CH - - - - - - -
14. 23.00 - DS - - 8 - 92 - 65 26 39 CH - - - - - - -
15. 25.0 Ref. SPT - - 12 - 88
H(65)(23)
46 25 21 CI - - - - - - -
16. 27.50 - DS - - 56 - 44 - 50 24 26 SC - - - - - - -
17. 30.00 Ref. SPT - - 18 - 82 - - NP - ML - - - - - - -




282






M.K. Soil Testing Laboratory



Table No. 11/57 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 58
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 1140

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 632.78m, E. 398.16m, RL of GL = 45.03m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 - 92
H(63)(29)
58 28 30 CH - - - - - - -
2. 1.50 - UDS 2.68 - - - - - - CH 1.86 1.55 19.8 TUU 0.65 4 -
3. 3.00 30 SPT - - 3 - 97
H(66)(31)
57 29 28 CH - - - - - - -
4. 4.50 35 SPT - - - - - - - CH - - - - - - -
5. 6.00 38 SPT - - 8 - 92
H(62)(30)
58 25 33 CH - - - - - - -
6. 7.50 44 SPT - - 3 -97- 68 30 38 CH - - - - - - -
7. 9.00 47 SPT - - - - - - - CH - - - - - - -
8. 10.50 53 SPT - - 2 -98- - NP - CH - - - - - -
9. 12.00 57 SPT - - 11 - 89
H(61)(28)
63 29 34 CH - - - - - - -
283






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 58

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 64 SPT - - - - - - - CH - - - - - - -
11. 15.00 67 SPT - - 10 - 90
H(59)(31)
60 30 30 CH - - - - - - -
12. 17.00 Ref. SPT - === Grayish blackish coloured, highly weathered rock CR = 22%, RQD = Nil ===
13. 19.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 35%, RQD = 11% ===
14. 21.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 31%, RQD = Nil ===
15. 23.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 37%, RQD = Nil ===
16. 25.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 31%, RQD = 5% ===
17. 27.5 - DS - === Grayish blackish coloured, highly weathered rock CR = 37%, RQD = Nil===
18. 29.0 - DS - === Grayish blackish coloured, highly weathered rock CR = 60%, RQD = Nil===
19. 31.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 65%, RQD = Nil===
20. 33.0 - DS - === Grayish blackish coloured, highly weathered rock CR = 70%, RQD = 36%===
21. 36.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 90%, RQD = 60%===
22. 38.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 92%, RQD = 65%===
23. 40.00 - DS - === Grayish blackish coloured, highly weathered rock CR = 95%, RQD = 71%===
284






M.K. Soil Testing Laboratory



Table No. 11/58 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 59
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.50

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 600.03m, E. 444.12m, RL of GL = 46.03m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 -92- 58 28 30 CH - - - - - - -
2. 1.50 19 SPT - - 7 - 93
H(65)(28)
56 26 30 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.76 1.47 19.2 TUU 0.65 4 -
4. 4.50 Ref. SPT - ==== Reddish coloured, completely weathered rock CR = Nil, RQD = Nil ====
5. 6.00 - DS - ==== Reddish coloured, completely weathered rock CR = Nil, RQD = Nil ====
6. 7.50 - DS - ==== Reddish coloured, completely weathered rock CR = Nil, RQD = Nil ====
7. 9.00 - DS - ==== Reddish coloured, highly weathered rock CR = 25%, RQD = Nil ====
8. 10.50 - DS - ==== Reddish coloured, highly weathered rock CR = 21%, RQD = Nil ====
9. 12.00 - DS - === Reddish brown coloured, highly weathered rock CR = 30%, RQD = 10% ===
285






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 59

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 - DS - === Reddish brown coloured, highly weathered rock CR = 20%, RQD = Nil ===
11. 15.00 - DS - === Reddish brown coloured, highly weathered rock CR = 22%, RQD = Nil ===
12. 17.00 - DS - === Reddish brown coloured, highly weathered rock CR = 20%, RQD = Nil ===
13. 19.00 - DS - === Reddish brown coloured, highly weathered rock CR = 25%, RQD = Nil ===
14. 21.00 - DS - === Reddish brown coloured, highly weathered rock CR = 23%, RQD = Nil ===
15. 23.00 - DS - === Grayish black coloured, completely weathered rock ===
16. 25.00 - DS - === Grayish black coloured, completely weathered rock ===
17. 27.5 38 SPT - === Grayish reddish black coloured, highly weathered rock ===
18. 30.00 46 SPT - === Grayish reddish black coloured, highly weathered rock ===
19. 32.50 - DS - === Grayish reddish black coloured, highly weathered rock CR = 24%, RQD = Nil ===
20. 35.00 - DS - === Grayish reddish black coloured, highly weathered rock CR = 22%, RQD = Nil ===
21. 37.00 - DS - === Grayish reddish black coloured, highly weathered rock CR = 21%, RQD = Nil ===
22. 40.00 - DS - === Grayish reddish black coloured, highly weathered rock CR = 25%, RQD = Nil ===
286






M.K. Soil Testing Laboratory



Table No. 11/59 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 60
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.70

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 600.03m, E. 493.62m, RL of GL = 45.95
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 71 - 29 - 40 26 14 SC - - - - - - -
2. 1.50 - UDS 2.65 - - - - - - SC 1.85 1.64 12.9 DST 0.06 28 -
3. 3.00 19 SPT - - 8 - 92
H(62)(30)
58 29 29 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH - - - - - - -
5. 6.00 23 SPT - - 3 - 97
H(66)(31)
60 28 32 CH - - - - - - -
6. 7.50 - UDS 2.68 - - - - - - CH 1.78 1.50 18.6 TUU 0.78 5 -
7. 9.00 26 SPT - - 10 - 90
H(60)(30)
57 25 32 CH - - - - - - -
8. 10.50 - UDS 2.70 - - - - - - CH 1.80 1.47 22.5 TUU 0.86 8 -
9. 12.00 39 SPT - - 11 - 89
H(59)(30)
58 28 30 CH - - - - - - -
287






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 60

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 Ref. SPT - ==== Reddish coloured, highly weathered rock =====
11. 15.00 - DS - ==== Reddish coloured, highly weathered rock =====
12. 17.00 - DS - ==== Reddish coloured, highly weathered rock CR = 25%, RQD = 10% =====
13. 19.00 - DS - ==== Reddish coloured, highly weathered rock CR = 20%, RQD = Nil =====
14. 21.00 Ref. SPT - - 5 - 95
H(64)(31)
60 28 32 CH - - - - - - -
15. 23.00 Ref. SPT - - 5 - 95
H(67)(28)
56 26 - CH - - - - - - -
16. 25.00 49 SPT - - 6 - 94
H(63)(31)
59 25 34 CH - - - - - - -
17. 27.5 72 SPT - - 11 - 89 - 59 25 34 CH - - - - - - -
18. 30.00 Ref. SPT - - 5 - 95
H(65)(30)
62 29 33 CH - - - - - - -
19. 32.5 Ref. SPT - - 14 - 86 - 57 25 32 CH - - - - - - -
20. 35.0 Ref. SPT - - 13 - 87
H(62)(25)
58 29 29 CH - - - - - - -
21. 37.50 Ref. SPT - - - - - - - CH - - - - - - -
22. 40.0 Ref. SPT - - 13 - 87 - 59 28 31 CH - - - - - - -
288






M.K. Soil Testing Laboratory



Table No. 11/60 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 61
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 11.20m

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 600.03m, E. 545.15m, RL of GL = 46.62m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 12 - 88
H(63)(25)
59 26 33 CH - - - - - - -
2. 1.50 - UDS 2.7 - - - - - - CH 1.70 1.43 18.5 TUU 0.65 6 -
3. 3.00 13 SPT - - 16 - 84 - 60 25 35 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH 1.79 1.47 21.6 TUU 0.78 2 -
5. 6.00 20 SPT - - 19 - 81
H(52)(29)
55 28 27 CH - - - - - - -
6. 7.50 - UDS 2.70 - - - - - - CH 1.83 1.51 20.7 TUU 0.86 5 -
7. 9.00 47 SPT - - 8 - 92
H(59)(33)
64 29 35 CH - - - - - - -
8. 10.50 - UDS/
DS
- 22 46 - 32 - - NP - CH - - - - - - -
9. 12.00 49 SPT - - 20 - 80
H(50)(30)
65 29 36 CH - - - - - - -
289






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 61

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 55 SPT - - 11 - 89
H(57)(32)
60 25 35 CH - - - - - - -
11. 15.00 63 SPT - - 10 - 90
H(61)(29)
66 28 38 CH - - - - - - -
12. 17.00 61 SPT - - 5 - 95
H(63)(32)
69 28 41 CH - - - - - - -
13. 19.00 59 SPT - - - - - - - CH - - - - - - -
14. 21.00 59 SPT - - 17 - 83
H(52)(31)
65 29 36 CH - - - - - - -
15. 23.00 62 SPT - 39 59 - 02 - - NP - SP - - - - - - -
16. 25.00 65 SPT - - 13 - 87
H(58)(29)
67 29 38 CH - - - - - - -
17. 27.5 69 SPT - - 9 - 91
H(60)(31)
59 25 34 CH - - - - - - -
18. 30.00 73 SPT - - - - - - - CH - - - - - - -
19. 32.5 78 SPT - - 11 - 89
H(61)(28)
60 25 35 CH - - - - - - -
20. 35.0 Ref. SPT - 40 40 - 20 - - NP - GM - - - - - - -
21. 37.50 Ref. SPT - 46 35 - 19 - - NP - GM - - - - - - -
22. 40.0 Ref. SPT - 42 36 - 22 - - NP - GM - - - - - - -
290






M.K. Soil Testing Laboratory




Table No. 11/61 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 62
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 600.04m, E. 592.52m, RL of GL = 48.06m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 17 SPT - - 4 - 96
H(65)(31)
57 20 37 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.56 1.14 36.23 TUU 0.58 6 -
4. 4.50 20 SPT - - 4 - 96
H(74)(22)
53 19 34 CH - - - - - - -
5. 6.00 - UDS - - 6 - 94 - 60 21 39 CH - - - - - - -
6. 7.50 22 SPT - - 4 - 96
H(69)(27)
53 18 35 CH - - - - - - -
7. 9.00 - UDS - - 6 - 94 - 53 18 35 CH - - - - - - -
8. 10.5 23 SPT - - 10 - 90
H(60)(30)
63 18 45 CH - - - - - - -

291






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 62

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
11. 12.0 - DS - - 20 - 80 - 57 21 36 CH - - - - - - -
10. 13.50 31 SPT - 4 26 - 70 - 51 19 32 CH - - - - - - -
11. 15.0 - DS - - 8 - 92 - 58 29 29 CH - - - - - - -
12. 17.0 Ref. SPT - ===== Crushed soft rock ========
13. 19.00 Ref. SPT - ===== Crushed soft rock ========
14. 21.00 Ref. SPT - ===== Crushed soft rock ========
15. 23.00 Ref. SPT - ===== Crushed soft rock ========
16. 25.00 Ref. SPT - ===== Crushed soft rock ========
17. 27.5 Ref. SPT - ===== Crushed soft rock ========
18. 30.00 Ref. SPT - ===== Crushed soft rock ========


292






M.K. Soil Testing Laboratory




Table No. 11/62 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 63
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 10.15

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 601.42m, E. 644.51m, RL of GL = 48.94m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 50 38 -12- - NP - GM - - - - - - -
2. 1.50 25 SPT - 46 38 -16- - NP - GM - - - - - - -
3. 3.00 28 SPT - 42 38 -20- - NP - GM - - - - - - -
4. 4.50 - UDS/
DS
- 42 49 -12- - NP - GM - - - - - - -
5. 6.00 33 SPT - 45 40 -15- - NP - GM - - - - - - -
6. 7.50 - UDS 2.68 - - - - - - CH - - - - - - -
7. 9.00 - UDS 2.68 - - - - - - CH - - - - - - -
8. 10.50 26 SPT - - 6 - 94
H(63)(31)
60 29 31 CH - - - - - - -

293






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 63

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 42 SPT - - 9 -91- 58 28 30 CH - - - - - - -
10. 13.50 43 SPT - - - - - - - CH - - - - - - -
11. 15.00 26 SPT - - 10 - 90
H(65)(25)
57 25 32 CH - - - - - - -
12. 17.00 28 SPT - - - - - - - CH - - - - - - -
13. 19.00 26 SPT - - 11 -89- 55 28 27 CH - - - - - - -
14. 21.00 32 SPT - - - - - - - CH - - - - - - -
15. 23.00 Ref. SPT - - 5 - 95
H(65)(30)
56 26 30 CH - - - - - - -
16. 25.00 Ref. SPT - - - - - - - CH - - - - - - -
17. 27.5 Ref. SPT - 10 20 - 70
H(41)(29)
56 26 - CH - - - - - - -
18. 30.00 Ref. SPT - 14 14 -72- 58 28 - CH - - - - - - -





294






M.K. Soil Testing Laboratory




Table No. 11/63 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 64
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 7.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 628.54m, E. 815.75m, RL of GL = 47.10m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 1.50 24 SPT - 2 26 - 72
H(51)(21)
52 27 25 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.69 1.44 17.37 TUU 0.55 8 0.22
4. 4.50 Ref. SPT - 48 26 - 26 - - NP - GM - - - - - - -
5. 6.00 - UDS/
DS
- - - - - - - GM 1.84 1.61 14.40 - - - -
6. 7.50 13 SPT - - 18 - 82 - 52 28 24 CH - - - - - - -
7. 9.00 - UDS/
DS
- - 56 - 44- - NP - SM - - - - - - -
8. 10.50 24 SPT - - 70 - 30 - - NP - SM - - - - - - -



295






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 64

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS/
DS
- - 52 - 48 - - NP - SM - - - - - - -
10. 13.50 43 SPT - 12 30 - 58 - 50 26 24 CH - - - - - - -
11. 15.0 - UDS - - - - - - - CH 1.87 1.62 15.20 - - - -
12. 17.0 36 SPT - - 2 - 98
H(64)(34)
57 27 30 CH - - - - - - -
13. 19.00 - UDS/
DS
- - 60 - 40 - - NP - SM - - - - - - -
14. 21.00 63 SPT - - 32 - 68 - 47 25 22 CI - - - - - - -
15. 23.00 - UDS/
DS
- - 24 - 76 - 48 25 23 CI - - - - - - -
16. 25.0 56 SPT - - 8 - 92 - 43 24 19 CI - - - - - - -
17. 27.50 - UDS/
DS
- - 54 - 46 - - NP - CI - - - - - - -
18. 30.00 Ref. SPT - - 54 - 46 - 44 27 17 SM - - - - - - -





296






M.K. Soil Testing Laboratory




Table No. 11/64 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 65
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.10m.

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N-574.64m, E-478.42m. RL of GL : 46.68m.

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 12 -- 88 --
H(60)(28)
58 27 31 CH - - - - - - -
2. 1.50 - UDS 2.7 - - - - - - CH 1.62 1.35 19.6 TUU 0.38 5 -
3. 3.00 10 SPT - - 22 -- 78 -- 56 28 28 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH 1.68 1.39 20.7 TUU 0.55 5 -
5. 6.00 20 SPT - - 12 -- 88
H(63)(25)
59 29 30 CH - - - - - - -
6. 7.50 - UDS 2.70 - - - - - - CH 1.76 1.45 21.3 TUU 0.66 2 -
7. 9.00 56 SPT - - 12 -- 88

60 25 35 CH - - - - - - -
8. 10.50 61 SPT - - 5 -- 95

58 29 29 CH - - - - - - -
297






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 65

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 88 SPT - - 7 -- 93
H(62)(31)
58 28 30 CH - - - - - - -
10. 13.5 96 SPT - - 11 -- 90
H(60)(31)
60 23 32 CH - - - - - - -
11. 15.0 Ref. SPT - 29 43 -- 28

-- NP -- SM - - - - - - -
12. 17.0 Ref. SPT - === Greyish black coloured highly weathered rock ===== CR = 15%, RQD = Nil
13. 19.00 - DS - === Reddish brown coloured moderately weathered rock ===== CR = 60%, RQD = 40%
14. 21.0 Ref. SPT - === Reddish brown coloured moderately weathered rock ===== CR = 80%, RQD = 57%
15. 23.00 - DS - === Reddish brown coloured moderately weathered rock ===== CR = 82%, RQD = 61%
16. 25.00 - DS - === Reddish brown coloured moderately weathered rock ===== CR = 77%, RQD = 49%
17. 27.5 - DS - === Reddish brown coloured moderately weathered rock ===== CR = 75%, RQD = 23%
18. 30.00 - DS - === Reddish brown coloured moderately weathered rock ===== CR = 87%, RQD = 35%



298






M.K. Soil Testing Laboratory



Table No. 11/65 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 66
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.00m.

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N-558.42m, E-532.35m. RL of GL : 46.95m.

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 10 -- 90 --
H(61)(29)
59 25 34 CH - - - - - - -
2. 1.50 15 SPT - - - -- 93
H(62)(31)
56 28 28 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.72 1.44 19.8 TUU 0.52 8 -
4. 4.50 19 SPT - - 3 -- 97

66 24 42 CH - - - - - - -
5. 6.00 - UDS 2.70 - - - - - - CH 1.79 1.49 20.2 TUU 0.69 6 -
6. 7.50 23 SPT - - 8 -- 92

60 25 35 CH - - - - - - -
7. 9.00 - UDS 2.70 - - - - - - CH 1.83 1.51 21.3 TUU 0.75 2 -
8. 10.5 30 SPT - - 6 -- 94

58 26 32 CH - - - - - - -
299






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 66

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS - - - - - - - CH 1.87 1.55 20.3 TUU 0.85 6 -
10. 13.5 33 SPT - - 19 -- 81
H(51)(30)
68 28 40 CH - - - - - - -
11. 15.0 37 SPT - - 18 -- 82

64 29 35 CH - - - - - - -
12. 17.0 46 SPT - - 18 -- 82
H(54)(28)
65 28 37 CH - - - - - - -
13. 19.0 56 SPT - - - -

- - - CH - - - - - - -
14. 21.0 57 SPT - - 13 -- 87

61 26 35 CH - - - - - - -
15. 23.0 Ref. SPT - === Greyish black coloured, highly weathered basalt ===== CR = 22%, RQD = Nil
16. 25.0 - DS - === Greyish black coloured, highly weathered basalt ===== CR = 42%, RQD = 22%
17. 27.5 - DS - === Greyish black coloured, highly weathered basalt ===== CR = 50%, RQD = 28%
18. 30.0 - DS - === Greyish black coloured, highly weathered basalt ===== CR = 45%, RQD = 35%




300






M.K. Soil Testing Laboratory



Table No. 11/66 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 67
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.70

Termination depth (m): 40.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 558.45m, E. 589.4m, RL of GL = 48.47m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 19 SPT - - 28 - 72 - 41 35 6 ML - - - - - - -
3. 3.00 - UDS 2.65 - - - - - - ML 1.64 1.38 18.62 DST 0.02 28 -
4. 4.50 21 SPT - - 18 - 82 - - NP - ML - - - - - - -
5. 6.00 - UDS - - - - - - - CH 1.68 1.23 36.42 TUU 0.69 6 0.26
6. 7.50 20 SPT - - 4 - 96
H(68)(28)
86 30 56 CH - - - - - - -
7. 9.00 - UDS/
DS
- 2 12 - 86 - 91 29 62 CH - - - - - - -
8. 10.5 24 SPT - - 20 - 80
H(53)(27)
76 33 43 CH - - - - - - -
11. 12.0 - UDS/
DS
- - 12 - 88
H(60)(28)
57 26 31 CH - - - - - - -
301






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 67

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
10. 13.50 35 SPT - 4 76 - 20 - - NP - SM - - - - - - -
11. 15.0 34 SPT - 2 9 - 89 - 53 26 27 CH - - - - - - -
12. 17.0 30 SPT - - 20 - 80 - 55 25 30 CH - - - - - - -
13. 19.0 34 SPT - - 12 - 88 - 54 33 31 CH - - - - - - -
14. 21.0 35 SPT - 14 76 - 42 - - NP - SM - - - - - - -
15. 23.0 30 SPT - 10 76 - 14 - - NP - SM - - - - - - -
16. 25.0 Ref. SPT - - 30 - 70 - 36 32 4 ML - - - - - - -
17. 27.5 Ref. SPT - 4 32 - 64 - - NP - ML - - - - - - -
18. 30.0 44 SPT - 2 80 - 18 - - NP - ML - - - - - - -
19. 32.5 43 SPT - 4 60 - 36 - 57 23 34 SC - - - - - - -
20. 35.0 Ref. SPT - ===== Bolder ======
21. 37.5 Ref. SPT - ===== Bolder ======
22. 40.0 Ref. SPT - ===== Bolder ======
302






M.K. Soil Testing Laboratory



303






M.K. Soil Testing Laboratory


Table No. 11/67 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 68
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.20

Termination depth (m): 35.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 513.56m, E. 485.71m, RL of GL = 47.0m
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - - - - - - - - - - - - - -
2. 1.50 21 SPT - - 2 - 98
H(59)(39)
93 28 65 CH - - - - - - -
3. 3.00 - UDS 2.66 - - - - - - CH 1.60 1.32 20.73 TUU 0.50 6 0.24
4. 4.50 20 SPT - - 2 - 86
H(60)(38)
96 28 68 CH - - - - - - -
5. 6.00 - UDS 2.70 - - - - - - CH 1.68 1.32 26.42 TUU 0.55 6 -
6. 7.50 25 SPT - 10 38 - 52 - 60 26 34 CH - - - - - - -
7. 9.00 - DS - - 30 - 70
H(40)(30)
59 26 33 CH - - - - - - -
8. 10.5 21 SPT - - 10 - 90
H(70)(20)
78 38 40 CH - - - - - - -



304






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 68

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
11. 12.0 - UDS 2.68 - - - - - - CH 1.65 1.45 13.63 TUU 0.68 10 -
10. 13.50 32 SPT - - 14 - 86
H(66)(22)
73 39 34 ML - - - - - - -
11. 15.0 - DS - 2 46 - 52 - 37 25 12 ML - - - - - - -
12. 17.0 37 SPT - - 12 - 88
H(67)(21)
76 38 38 ML - - - - - - -
13. 19.0 41 SPT - - 12 - 88
H(66)(22)
72 38 34 ML - - - - - - -
14. 21.0 Ref. SPT - - 8 - 92
H(72)(20)
70 38 32 ML - - - - - - -
15. 23.0 Ref. SPT - - 10 - 90 - 68 37 28 ML - - - - - - -
16. 25.0 Ref. SPT - ====== Crushed soft rock ========
17. 27.5 - DS - ====== Crushed soft rock ========
18. 30.0 20 SPT - ====== Crushed soft rock ========
19. 32.5 - DS - ====== Crushed soft rock ========
20. 35.0 20 SPT - ====== Crushed soft rock ========


305






M.K. Soil Testing Laboratory



Table No. 11/68 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 69
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.90m.

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N-517.18m, E-539.42m. RL of GL : 47.39m.
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 -- 92
H(62)(30)
58 28 30 CH - - - - - - -
2. 1.50 14 SPT - - 6 -- 94
H(65)(29)
59 25 34 CH - - - - - - -
3. 3.00 - UDS 2.70 - - - - - - CH 1.70 1.42 19.8 TUU 0.50 2 -
4. 4.50 18 SPT - - 14 -- 86

60 25 35 CH - - - - - - -
5. 6.00 - UDS 2.65 - - - - - - CH 1.74 1.45 20.2 TUU 0.62 5 -
6. 7.50 26 SPT - - 8 -- 92
H(61)(31)
55 29 26 CH - - - - - - -
7. 9.0 - UDS 2.68 - - - - - - CH 1.88 1.62 15.5 TUU 0.89 2 -
8. 10.5 37 SPT - - 12 -- 88

62 28 34 CH - - - - - - -
306






M.K. Soil Testing Laboratory





PAGE 2 FOR BOREHOLE NO. BH 69

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 40 SPT - - 8 -- 92
H(61)(31)
68 25 33 CH - - - - - - -
10. 13.50 45 SPT - - 12 -- 88

65 29 36 CH - - - - - - -
11. 15.0 49 SPT - - - -

- - - CH - - - - - - -
12. 17.00 55 SPT - 8 12 -- 80

61 28 33 CH - - - - - - -
13. 19.00 58 SPT - - - -

- - - CH - - - - - - -
14. 21.00 63 SPT - 4 18 -- 78
H(50)(28)
58 29 29 CH - - - - - - -
15. 23.00 64 SPT - - - -

- - - CH - - - - - - -
16. 25.00 68 SPT - 6 16 -- 78
H(49)(29)
52 28 24 CH - - - - - - -
17. 27.5 Ref. SPT - 50 23 -- 27 --

-- NP -- GM - - - - - - -
18. 30.00 Ref. SPT - 51 23 -- 26 --

-- NP -- GM - - - - - - -



307






M.K. Soil Testing Laboratory



Table No. 11/69 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 70
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.0m.

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N-514.54m, E-590.33m. RL of GL : 51.55m.
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 71 -- 29

-- NP -- SM - - - - - - -
2. 1.50 5 SPT - 56 27 -- 17 -- NP -- GM - - - - - - -
3. 3.00 - UDS /
DS
- 53 27 -- 20

-- NP -- GM - - - - - - -
4. 4.50 17 SPT - 58 18 -- 24

40 23 17 GC - - - - - - -
5. 6.00 - DS - 52 29 -- 19

-- NP -- GM - - - - - - -
6. 7.50 23 SPT - 56 29 -- 15

-- NP -- GM - - - - - - -
7. 9.00 - UDS 2.70 - 10 -- 90
H(62)(28)
58 29 29 CH 1.70 1.42 19.2 TUU 0.79 4 -
8. 10.5 25 SPT - - 6 -- 94
H(63)(31)
68 27 41 CH - - - - - - -

308






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 70

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - - - - - CH 1.88 1.60 17.5 TUU 0.89 5 -
10. 13.50 28 SPT - - 9 -- 91
H(61)(30)
58 25 33 CH - - - - - - -
11. 15.00 - UDS 2.70 - - - - - - CH 1.92 1.59 20.3 TUU 0.92 8 -
12. 17.00 8 SPT - - 64 -- 36

-- NP -- SM - - - - - - -
13. 19.00 - UDS /
DS
- 4 69 -- 27 -- -- NP -- SM - - - - - - -
14. 21.0 Ref. SPT - === Greyish brown coloured, highly weathered rock === CR = 29%, RQD = Nil
15. 23.00 Ref. SPT - === Greyish brown coloured, highly weathered rock === CR = 46%, RQD = 31%
16. 25.00 Ref. SPT - === Greyish brown coloured, highly weathered rock === CR = 35%, RQD = Nil
17. 26.50 - DS - === Greyish brown coloured, highly weathered rock === CR = 34%, RQD = 34%
18. 27.00 - DS - === Greyish brown coloured, highly weathered rock === CR = 43%, RQD = 38%
19. 30.00 - DS - === Greyish brown coloured, highly weathered rock === CR = 33%, RQD = 20%


309






M.K. Soil Testing Laboratory


Table No. 11/70 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 71
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 8.8

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 446.46m E. 445.81m RL of GL. 47.07
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 6 - 94
H(66)(28)
55 29 26 CH - - - - - - -
2. 1.50 18 SPT - - 10 - 90
H(63)(27)
56 24 32 CH - - - - - - -
3. 3.00 - UDS 2.68 - - - - - - CH 1.69 1.44 17.6 - - - -
4. 4.50 34 SPT - - 11 - 89
H(60)(29)
58 25 33 CH - - - - - - -
5. 6.00 - UDS 2.7 4 13 - 83
H(55(28)
53 28 25 CH 1.82 1.49 22.2 - - - -
6. 7.50 57 SPT - - 4 - 96
H(65) (31)
60 30 30 CH - - - - - - -
7. 9.00 - DS - 28 48 - 24- - NP - SM - - - - - - -
8. 10.50 49 SPT - - 11 - 89
H(59) (30)
59 28 31 CH - - - - - - -

310






M.K. Soil Testing Laboratory






PAGE 2 FOR BOREHOLE NO. BH 71

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref SPT - - 13 - 87
H(58)(29)
59 25 34 CH - - - - - - -
10. 13.50 32 SPT - - - - - - - CH - - - - - - -
11. 15.00 Ref SPT - - 13 - 87
H(57(30)
56 28 28 CH - - - - - - -
12. 17.0 Ref SPT - - - - - - - CH - - - - - - -
13. 19.0 54 SPT - - 10 - 90
H(60)(30)
55 27 28 CH - - - - - - -
14. 21.00 Ref SPT - - - - - - - CH - - - - - - -
15. 23.0 Ref SPT - - 8 - 92
H(62)(30)
58 28 30 CH - - - - - - -
16. 25.0 46 SPT - - - - - - - CH - - - - - - -
17. 27.50 Ref SPT - 58 22 - 20

- NP - GM - - - - - - -
18. 30.00 Ref SPT - 52 29 -19- - NP - GM - - - - - - -
311






M.K. Soil Testing Laboratory



Table No. 11/71 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 72
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 9.15

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 446.46m E. 513..81m RL of GL. 47.57
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 10 - 90
H(62)(28)
58 26 32 CH - - - - - - -
2. 1.50 - UDS 2.7 - - - - - - CH 1.76 1.44 21.8 Tuu 0.58 5 -
3. 3.00 24 SPT - - 7 - 93
H(62)(31)
62 29 33 CH - - - - - - -
4. 4.50 - UDS 2.68 - - - - - - CH 1.80 1.52 18.5 Tuu 0.79 4 -
5. 6.00 25 SPT - - 8 - 92
H(61(31)
58 30 28 CH - - - - - - -
6. 7.50 - UDS/
DS
- 8 58 - 34-

- NP - SM - - - - - - -
7. 9.00 27 SPT - - 6 -94-
H(62)(32)
56 28 28 CH - - - - - - -
8. 10.50 - DS - ===============Grayish coloured completely weathered rock Basalat==============
312






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 72

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 Ref SPT - ===============Grayish coloured completely weathered rock Basalt==============
10. 13.50 Ref SPT - ===============Grayish coloured completely weathered rock Basalt==============
11. 15.00 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR =22% RQD = 13% =======
12. 16.0 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR =20% RQD = Nil=======
13. 17.0 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR =21% RQD = Nil =======
14. 19.00 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR =25% RQD = Nil =======
15. 2100 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR =26% RQD = Nil =======
16. 23.00 Ref SPT - ===== Greenish brown coloured highly weathered compact Basalt CR 30% RQD = Nil =======
17. 25.00 DS - ===== Greenish brown coloured highly weathered compact Basalt CR =28% RQD = 10% =======
18. 27.50 - DS - ===== Greenish brown coloured highly weathered compact Basalt CR =23% RQD = Nil =======
19. 30.00 - DS - ===== Greenish brown coloured highly weathered compact Basalt CR =27% RQD = 8% =======



313






M.K. Soil Testing Laboratory


Table No. 11/72 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 73
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 15.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 446.47m E. 597.65m RL of GL. 51.46
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 - 89
H(61)(28)
58 28 30 CH - - - - - - -
2. 1.50 5 SPT - 14 58 - 28
H(63)(27)
- Np - SM - - - - - - -
3. 3.00 - UDS/
DS
- 15 61 - 24

- Np - SM - - - - - - -
4. 4.50 3 SPT - 16 64 - 18-

- Np - SM - - - - - - -
5. 6.00 - UDS 2.68 - 10 - 90
H(58(32)
60 28 32 CH 1.60 1.33 20.3 Tuu 0.46 2 -
6. 7.50 14 SPT - - 11 - 89

56 28 28 CH - - - - - - -
7. 9.00 - UDS 2.66 - - - - - - CH 1.72 1.47 16.5 Tuu 0.60 5 -
8. 10.50 25 SPT - - 9 - 91

65 28 37 CH - - - - - - -
314






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 73

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 36 SPT - - 12 - 88
H(63)(25)
63 28 35 CH - - - - - - -
10. 13.50 - UDS 2.7 - - - - - - CH 1.88 1.71 9.8 Tuu 1.08 6 -
11. 15.00 38 SPT - - 6 - 94

62 29 33 CH - - - - - - -
12. 17.0 15 SPT - - 7 -93- 60 28 32 CH - - - - - - -
13. 19.0 41 SPT - - - - - - - CH - - - - - - -
14. 21.00 - DS - - 6 -94-
H (65( (29)
62 29 33 CH - - - - - - -
15. 23.0 37 SPT - - - - - - - CH - - - - - - -
16. 25.0 38 SPT - - 8 -92-
H(61)(31)
65 25 40 CH - - - - - - -
17. 27.50 48 SPT - - 9 - 91
H(62)(29)
55 29 26 CH - - - - - - -
18. 30.00 57 SPT - 2 6 -90- 58 28 30 CH - - - - - - -
315






M.K. Soil Testing Laboratory


Table No. 11/73 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 74
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.80

Termination depth (m): 32.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 489.32m E. 699.98m RL of GL. 48.37
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 72 - 28

40 23 17 SC - - - - - - -
2. 1.50 16 SPT - - 78 - 22

42 25 17 SC - - - - - - -
3. 3.00 - UDS/
DS
- 4 76 - 20

40 23 17 SC - - - - - - -
4. 4.50 30 SPT - - 9 - 91-
H(62)(29)
58 24 34 CH - - - - - - -
5. 6.00 - UDS 2.70 - - - - - - SC 1.89 1.59 18.3 DST 0.10 29 -
6. 7.50 24 SPT - 9 62 - 29

43 25 18 SC - - - - - - -
7. 9.00 - UDS 2.64 - - - - - - SC 1.94 12.8 DST 0.10 30.5 - -
8. 10.50 33 SPT - 3 71 -26-

45 24 21 SC - - - - - - -
316






M.K. Soil Testing Laboratory




PAGE 2 FOR BOREHOLE NO. BH 74

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 12 SPT - - 12 - 88
H(59)(29)
60 28 32 CH - - - - - - -
10. 13.50 - DS - - 16 - 84
H(54)(30)
56 29 27 CH - - - - - - -
11. 15.00 13 SPT - - - - - - - CH - - - - - - -
12. 17.0 - DS - - 21 -79-
H(51)(28)
60 23 37 CH - - - - - - -
13. 19.0 23 SPT - - - - - - - CH - - - - - - -
14. 21.00 - DS - 20 21 -59- 54 28 26 CH - - - - - - -
15. 23.0 23 SPT - 19 19 -62-
H(41)(21)
58 25 33 CH - - - - - - -
16. 25.0 - DS - - - - - - - CH - - - - - - -
17. 27.50 28 SPT - 19 19 - 62

55 24 28 CH - - - - - - -
18. 30.00 - SPT - - - - - - - CH - - - - - - -
19. 32.00 Ref DS 20 16 -64- 52 26 26 CH

317






M.K. Soil Testing Laboratory


Table No. 11/74 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 75
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 7.10

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 445.22m E. 781.63m RL of GL. 46.67
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - 18 5 - 54

- Np - SM - - - - - - -
2. 1.50 - UDS 2.65 - - -

- - - SM 1.69 1.53 10.5 DST 0 28.5 -
3. 3.00 11 SPT - 9 71 - 20

- Np - SM - - - - - - -
4. 4.50 - UDS 2.65 - - - - - - SM 1.73 1.56 10.8 DST 0 29 -
5. 6.00 22 SPT - - 11 -89-
H(60)(29)
58 28 30 CH - - - - - - -
6. 7.50 - UDS 2.7 - - -

- - - CH 1.83 1.59 14.8 Tuu 0.80 4 -
7. 9.00 31 UDS 2.70 - - - - - - CH 1.91 1.65 15.3 TDuu 0.92 6 -
8. 10.50 - UDS 2.70 - - -

- - - CH 1.91 1.65 15.3 Tuu 0.92 6 -
318






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 75
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 30 SPT - - 7 - 93
H(63)(30)
52 29 23 CH - - - - - - -
10. 13.50 - UDS - - - - - - - CH 1.99 1.70 16.8 Tuu 0.98 6 -
11. 15.00 34 SPT - - 11 - 89

58 29 29 CH - - - - - - -
12. 17.0 - UDS/
DS
- - - - - - - CH - - - - - - -
13. 19.0 37 SPT - - 15 -85-
H(60)(25)
58 26 32 CH - - - - - - -
14. 21.00 - UDS/
DS
- - - - - - - CH - - - - - - -
15. 23.0 Ref DS - ===== Greenish brown coloured highly weathered rock CR =36% RQD = 36% =======-
-
16. 25.0 Ref DS - ===== Greenish brown coloured highly weathered rock CR =31% RQD = 20% =======-
-
17 27.0 DS - ===== Greenish brown coloured highly weathered rock CR =20% RQD = 10% =======-
-
18. 30.0 DS - ===== Greenish brown coloured highly weathered rock CR =20% RQD = 4% =======-
-

319






M.K. Soil Testing Laboratory


Table No. 11/75 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 76
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.30

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N.387.78m E. 445.81m RL of GL. 47.62
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 68 - 32

48 26 22 SC - - - - - - -
2. 1.50 20 SPT - - - - -- - - SC - - - - - - -
3. 3.00 - UDS/
DS
- - 18 - 29

45 24 21 SC - - - - - - -
4. 4.50 18 SPT - 20 52 -28- - Np - SM - - - - - - -
5. 6.00 - UDS/
DS
- - 6 -94-
H(62)(32)
62 29 33 CH - - - - - - -
6. 7.50 23 SPT - 26 52 -22- - Np - SM - - - - - - -
7. 9.00 - UDS/
DS
- - 15 -85-
H(56)(29)
58 25 33 CH - - - - - - -
8. 10.50 21 SPT - - 62 -38- - Np - SM 1.91 1.65 15.3 Tuu 0.92 6 -



320






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 76
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - DS - 20 56 - 24

48 25 23 SC - - - - - - -
10. 13.50 24 SPT - 29 33 -38- - Np - SM - - - - - - -
11. 15.00 - DS - - - -

- - - - - - - - - - -
12. 17.0 23 SPT - 28 48 -24- - - - SM - - - - - - -
13. 19.0 73 SPT - - - - - Np -
SM
- - - - - - -
14. 21.00 68 SPT - 24 54 -22- - Np - SM - - - - - - -
15. 23.0 66 SPT -

- Np - SM

16. 25.0 55 SPT - 18 53 -29- - Np - SM
17 27.5 Ref DS -
===== Grayish brown coloured highly weathered rock CR =20% RQD = Nil =======-
18. 30.0 Ref DS - ===== Grayish brown coloured highly weathered rock CR =22% RQD = Nil% =======-
-
321






M.K. Soil Testing Laboratory


Table No. 11/76 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 77
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.65

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 387.78m E. 513.81m RL of GL. 48.12
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 13 - 87

58 29 29 CH - - - - - - -
2. 1.50 7 SPT - - 11 -89-
H(60)(29)
55 26 29 CH - - - - - - -
3. 3.00 - UDS 27 - - -

- - - CH 1.64 1.36 20.3 Tuu 0.4 5 -
4. 4.50 15 SPT - - 8 -92-
H(61)(31)
57 27 30 CH - - - - - - -
5. 6.00 - UDS 2.66 - - - - - - CH 1.78 1.52 16.5 Tuu 0.68 3 -
6. 7.50 31 SPT - - 14 -86- 61 25 36 CH - - - - - - -
7. 9.00 - UDS 2.68 - - - - - - CH 1.82 1.52 19.2 Tuu 0.81 5
8. 10.50 35 SPT - - 56 -89- 59 27 32 CH - - - - - - -


322






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 77
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - -

- - - CH 1.99 1.75 13.3 Tuu 10 6 -
10. 13.50 Ref SPT - - 15 -85- 66 30 36 CH - - - - - - -
11. 15.00 Ref SPT - - - -

- - - CH - - - - - - -
12. 17.0 Ref SPT - - 8 -92- 64 28 36 CH - - - - - - -
13. 19.0
Ref
SPT - - - - - - - CH - - - - - - -
14. 21.00
Ref
SPT - - 12 -88- 65 31 34 CH - - - - - - -
15. 23.0
Ref
SPT -
- - -
- - - CH

16. 25.0
Ref
DS - ===== Greenish brown coloured highly weathered rock Basalt CR =20% RQD = 20% =======-

17 27.5 Ref DS - ===== Greenish brown coloured highly weathered rock Basalt CR =22% RQD = 22% =======-

18. 30.0 Ref DS - ===== Greenish brown coloured highly weathered rock Basalt CR =20% RQD = 15% =======-


323






M.K. Soil Testing Laboratory


Table No. 11/77 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 78
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 387.79m E. 597.65m RL of GL. 50.16
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 3 - 97
H(64)(33)
59 28 31 CH - - - - - - -
2. 1.50 14 SPT - - 10 -90- 68 28 40 CH - - - - - - -
3. 3.00 - UDS 2.68 - - -

- - - CH 1.72 1.47 16.9 Tuu 0.58 2 -
4. 4.50 10 SPT - - 12 -88-
H(59)(29)
65 29 36 CH - - - - - - -
5. 6.00 - UDS 2.7 - - - - - - CH 1.79 1.46 20.3 Tuu 0.78 5 -
6. 7.50 33 SPT - - 4 -96- 66 25 49 CH - - - - - - -
7. 9.00 - UDS 2.7 - - - - - - CH 1.85 1.53 20.8 Tuu 0.85 9
8. 10.50 12 SPT - - 6 -94-
H(65)(29)
52 29 23 CH - - - - - - -



324






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 78
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.68 - - -

- - - CH 1.94 1.63 18.7 Tuu 0.92 6 -
10. 13.50 28 SPT - - 10 -90-
H(60)(30)

62 22 40 CH - - - - - - -
11. 15.00 - UDS 2.68 - - -

- - - CH 1.98 1.66 19.2 Tuu 0.99 5 -
12. 17.0 33 SPT - - 10 -90-
H(62)(28)
58 29 29 CH - - - - - - -
13. 19.0
-
UDS 2.70 - - - - - - CH 1.99 1.73 14.6 Tuu 1.11 8 -
14. 21.00
Ref
SPT - ===== Reddish Yellow coloured Sandstone Pebble =======-
15. 23.0

UDS -
- - -
- - - CH
- - - - - - -
16. 25.0 37 SPT - 8 16 -76-
H(47)(29)
58 28 30 CH - - - - - - -
17. 27.5 - UDS/
DS
- - - - - - - CH - - - - - - -
18. 30.0 49 SPT - 8 10 -90-
H(60)(30)
60 29 31 CH - - - - - - -
325






M.K. Soil Testing Laboratory




Table No. 11/78 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 79
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.60

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 366.97m E. 713.37m RL of GL. 48.24
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 71 - 29

- Np - SM - - - - - - -
2. 1.50 - UDS 2.68 - - - - - - CH 1.80 1.51 19.2 - - - -
3. 3.00 35 SPT - 5 21 -74-

56 24 32 CH - - - - - - -
4. 4.50 - UDS 2.7 - - - - - - CH 1.68 1.45 15.8 Tuu 0.50 6 -
5. 6.00 17 SPT - 4 19 -77-
H(52)(25)
55 25 30 CH - - - - - - -
6. 7.50 - UDS 2.7 - - - - - - CH 1.77 1.55 14.3 Tuu 0.63 5 -
7. 9.00 16 SPT - 2 12 -86-
H(55)(31)
58 29 29 CH - - - - - -
8. 10.50 - UDS 2.7 - - - - - - - 1.83 1.56 1.72 Tuu 0.75 9 -

326






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 79
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 20 SPT - - 12 -88- 57 27 30 CH - - - - - - -
10. 13.50 - UDS - - - -

- - - CH 1.93 1.59 21.3 Tuu 0.90 6 -
11. 15.00 28 SPT - - 10 -90-

61 29 32 CH - - - - - - -
12. 17.0 - UDS - - - - - - - CH 1.95 1.61 20.8 Tuu 0.93 5 -
13. 19.0 24 SPT - 2 58 -40- 45 24 21 SC - - - - - - -
14. 21.00
-
UDS/
DS
- 4 69 -27- 40 23 17 SC - - - - - - -
15. 23.0
29
SPT -
- - -
-
===
- - SC
- - - - - - -
16. 25.0 - DS - =================== Grayish black coloured Crushed weathered rock ====================

17. 27.5 Ref SPT/D
S
- =================== Grayish black coloured Crushed weathered rock ====================

18. 30.0 - DS - =================== Grayish black coloured Crushed weathered rock ====================

327






M.K. Soil Testing Laboratory


Table No. 11/79 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 80
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.00

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 366.97m, E. 829.56m, RL of GL = 46.6m
SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 to 0.5 - DS - 16 32 - 52
H(32)(20)
39 25 14 CI - - - - - - -
2. 0.5-1.5 29 SPT - 8 56 - 36 - 41 30 11 SM - - - - - - -
3. 1.5-3.0 - UDS 2.65 - - - - - - CH 1.58 1.33 18.8 TUU 0.50 5 -
4. 3.0-4.5 16 SPT - - 36 - 64
H(43)(21)
51 24 27 CH - - - - - - -
5. 4.5-6.0 - UDS 2.68 - - - - - - CH 1.66 1.37 21.4 TUU 0.61 6 -
6. 6.0-7.5 30 SPT - 18 26 - 56
H(36)(20)
62 22 40 CH - - - - - - -
7. 7.5-9.0 - UDS 2.70 - - - - - - CH 1.60 1.32 20.9 TUU 0.85 5 0.092
8. 9.0-10.5 36 SPT - 10 50 - 40 - 39 22 17 SM - - - - - - -



328






M.K. Soil Testing Laboratory



PAGE 2 FOR BOREHOLE NO. BH 80

SR.
No.
Depth In mt. N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 10.50 12.0 - UDS 2.70 - - - - - - CH 1.74 1.46 19.3 TUU 0.95 2 0.05
10. 12.0 13.5 41 SPT - 6 26 - 68
H(65)(23)
54 20 34 CH - - - - - - -
11. 13.5 15.0 - UDS 2.70 - - - - - - CH 1.75 1.46 19.5 TUU 0.99 8 -
12. 15.0 17.0 41 SPT - - 22 - 78 - 52 23 29 CH - - - - - - -
13. 17.0-19.0 - UDS 2.7 - - - - - - CH 1.82 1.51 20.3 TUU 1.25 8 -
14. 19.0 21.0 48 SPT - - 6 - 94
H(63)(31)
60 30 30 CH - - - - - - -
15. 21.0-23.0 - UDS/
DS
- 70 78 - 12 - - NP - GM - - - - - - -
16. 23.0 25.0 27 SPT - 6 28 - 66 - 45 25 20 CI - - - - - - -
17. 25.0 27.0 - SPT - ====== Highly weathered soft rock =========
18. 27.5 30.0 Ref. DS - 4 38 - 58
H(38)(20)
55 25 30 CH - - - - - - -





329






M.K. Soil Testing Laboratory


Table No. 11/80 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 81
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 5.85

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 321.25m E. 445.81m RL of GL. 48.00
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 71 - 29 - Np - SM - - - - - - -
2. 1.50 43 SPT - - 77 -23- - Np - SM - - - - - - -
3. 3.00 - UDS 2.68 - - -

- - - CH 1.70 1.44 17.5 Tuu 0.78 5 -
4. 4.50 29 SPT - - 18 -82-
H(52)(30)
57 28 29 CH - - - - - - -
5. 6.00 - UDS 2.67 - - - - - - CH 1.86 1.59 16.9 Tuu 0.90 2 -
6. 7.50 28 SPT - - 10 -90-
H(62)(28)
59 28 31 CH - - - - - - -
7. 9.00 - UDS 2.68 2 - - - - - CH 1.90 158 20.3 Tuu 0.96 5 -
8. 10.50 20 SPT - - 10 -90-
H(62)(28)
50 23 27 SC - - - - - - -




330






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 81
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 - UDS 2.65 - - - - - - SC 1.92 11.63 17.7 DST 0.06 29 -
10. 13.50 18 SPT - 14 53 -33- 52 28 24 SC - - - - - - -
11. 15.00 - UDS/
DS
- - - -

- - - SC - - - - - - -
12. 17.0 19 SPT - 48 26 -26- - Np- - GM - - - - - - -
13. 19.0 Ref SPT - - 11 -89-
H(60)(29)
58 29 29 CH - - - - - - -
14. 21.00
Ref
SPT - - 8 -92-
h(94)(28)
55 27 28 CH - - - - - - -
15. 23.0
Ref
SPT - ============Greenish brown coloured Highly weathered rock, Cr =21%, RQD = 8%============

16. 25.0 Ref SPT - ============Greenish brown coloured Highly weathered rock, Cr =20%, RQD =10%============

17. 27.5 Ref SPT - ============Greenish brown coloured Highly weathered rock, Cr =25%, RQD =11%============

18. 30.0 Ref SPT - ============Greenish brown coloured Highly weathered rock, Cr =22%, RQD =8%============


331






M.K. Soil Testing Laboratory



Table No. 11/81 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 82
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.20

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 321.25m E. 513.81m RL of GL. 48.36
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 70 - 30 44 25 19 SC - - - - - - -
2. 1.50 18 SPT - - 71 -29- 45 24 21 SC - - - - - - -
3. 3.00 - UDS 2.65 - - -

- - - CH 1.69 1.47 14.5 DST 0.08 28 -
4. 4.50 Ref SPT - - 32 -68-

61 29 32 CH - - - - - - -
5. 6.00 - UDS - - - - - - - CH 1.73 1.52 13.8 - - - -
6. 7.50 143 SPT - - 26 -74-
H(47)(27)
58 30 28 CH - - - - - - -
7. 9.00 - UDS 2.67 - - - - - - CH 1.75 1.45 20.5 Tuu 0.6 3 -
8. 10.50 27 SPT - - 21 -79-

55 28 27 SC - - - - - - -



332






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 82
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 -
UDS
2.70 - -
-
- - - CH 1.85 1.56 18.3 Tuu 0.85 2 -
10. 13.50 26
SPT
- - 11 -89- 68 29 39 CH - - - - - - -
11. 15.00 119
SPT
- - - -

- - - CH - - - - - - -
12. 17.0 79
SPT
- - 4
-96-
H(65)(31)

65 29 36 CH - - - - - - -
13. 19.0
79 SPT
- - - -

- - - CH - - - - - - -
14. 21.00
Ref SPT
-
- 5
-95-

68 31 37 CH - - - - - - -
15. 23.0
Ref SPT
-

16. 25.00
Ref SPT
-
- 8
-92-
H(60)(32)
65 30 35 CH - - - - - - -
17. 27.50
Ref SPT
-
============ Greenish Black coloured Highly weathered Rock Basalt CR=25 % RQD =10%=======
18. 30.0
Ref SPT
-
============ Greenish Black coloured Highly weathered Rock Basalt CR=23 % RQD =12%=======

333






M.K. Soil Testing Laboratory


Table No. 11/82 SOIL CHARACTERISTICS FOR BOREHOLE NO. BH 83
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): 6.40

Termination depth (m): 30.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar
Co-Ordinate: N. 321.25m E. 597.65m RL of GL. 51.25
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 - 89 59 28 31 CH - - - - - - -
2. 1.50 20 SPT - - 10 -90-
H(62)(28)
56 27 29
CH
- - - - - - -
3. 3.00 - UDS 2.68 - - -

- - - CH 1.70 1.43 18.5 - - - -
4. 4.50 22 SPT - - 9 -91-
H(57)(34)
65 30 35 CH - - - - - - -
5. 6.00 - UDS 2.7 - - - - - - CH 1.78 1.46 21.6 Tuu 0.76 5 -
6. 7.50 24 SPT - - 6 -94- 63 28 35 CH - - - - - - -
7. 9.00 - UDS 2.7 - - - - - - CH 1.86 1.50 23.8 - - - -
8. 10.50 23 SPT - - 10 -90-
H(62)(28)
58 28 30 CH - - - - - - -




334






M.K. Soil Testing Laboratory


PAGE 2 FOR BOREHOLE NO. BH 83
SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
9. 12.00 -
UDS
- - -
-
- - - CH - - - - - - -
10. 13.50 27
SPT
- - 10 -90- 62 30 32 CH - - - - - - -
11. 15.00 -
UDS
- - - -

- - - CH - - - - - - -
12. 17.0 23
SPT
- - 12
-88-
H(62)(26)

59 29 30 CH - - - - - - -
13. 19.0
26 SPT
- - - -

- - - CH - - - - - - -
14. 21.00
Ref SPT
-
- 8
-92-
H(62)(30)
58 25 33 CH - - - - - - -
15. 23.0
Ref.
SPT
-
============ Greenish Black coloured Completely wethered Rock Basalt CR=Nil RQD =Nil=======
16. 25.00
Ref.
SPT
-
============ Greenish Black coloured Highly wethered Rock Basalt CR=32% RQD =15%=========
17. 27.50
Ref SPT
-
============ Greenish Black coloured Highly wethered Rock Basalt CR=28% RQD =12%=========
18. 30.0
Ref SPT
-
============ Greenish Black coloured Highly weathered Rock Basalt CR=25 % RQD =10%=======

335






M.K. Soil Testing Laboratory




Table No. 12/1 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 1
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 56 -30-

40 23 17 SC - - - - - - -
2. 1.00 - UDS 2.65 16 62 -22- 39 25 14 SC 1.72 1.52 12.8 DST 0.08 28.5 -
3 2.00 - UDS 2.65 22 52 -26- 42 22 20 SC 1.79 1.58 13.6 DST 0.03 31
4 3.00 - UDS 2.66 18 55 -27- 46 24 22 SC 1.87 1.63 14.9 DST 0.06 30.5 -

336






M.K. Soil Testing Laboratory


Table No. 12/2 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 3
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 -89-

58 28 30 CH - - - - - - -
2. 1.00 - UDS 2.7 - 7 -93-
H(62)(31)
60 29 31 CH 1.74 1.53 13.9 TUU 0.70 4 -
3 2.00 - UDS 2.7 - 12 -88- 58 28 30 CH 1.78 1.55 14.8 TUU 0.81 6 -
4 3.00 - UDS 2.7 - 5 -95-
H(61)(34)
58 29 29 CH 1.84 1.58 16.3 TUU 0.94 2 -













337






M.K. Soil Testing Laboratory



Table No. 12/3 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 4
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - === Reddish grayish coloured, highly weathered & fractured Basalt ====

338






M.K. Soil Testing Laboratory



Table No. 12/4 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 5
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 9 -91-

58 28 30 CH - - - - - - -
2. 1.00 - UDS 2.7 - 5 -95-
H(64)(31)
61 29 32 CH 1.72 1.44 19.5 TUU 0.69 5 -
3 2.00 - UDS 2.68 - 8 -92- 60 28 32 CH 1.84 1.53 20.4 TUU 0.86 5 -
4 3.00 - UDS 2.68 - 10 -90-
H(62)(28)
59 28 31 CH 1.96 1.60 20.8 TUU 0.94 2 -

339






M.K. Soil Testing Laboratory


Table No. 12/5 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 6
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 -92-
H(61)(31)
56 24 32 CH - - - - - - -
2. 0.90 - UDS 2.68 - 10 -90- 62 29 33 CH 1.85 1.57 17.6 TUU 0.96 5 -
3 2.00 - UDS - === Grayish blackish coloured, highly weathered & fractured Basalt ===
4 3.00 - UDS 2.68 === Grayish blackish coloured, highly weathered & fractured Basalt ===

340






M.K. Soil Testing Laboratory


Table No. 12/6 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 7
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.50m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 5 -95-
H(63)(32)
60 28 32 CH - - - - - - -
2. 1.00 - UDS 2.7 - 8 -92- 58 29 29 CH 1.84 1.59 15.9 TUU 0.65 4 -
3. 2.00 - UDS 2.7 - 9 -91-
H(57)(34)
58 28 30 CH 1.94 1.66 16.7 TUU 0.86 2 -
4. 3.00 - UDS 2.7 - 9 -91- 64 29 35 CH 1.90 1.58 20.5 TUU 0.89 5 -

341






M.K. Soil Testing Laboratory


Table No. 12/7 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 8
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 68 -32-

42 28 14 SC - - - - - - -
2. 1.00 - UDS 2.65 - 61 -39- 40 22 18 SC 1.84 1.58 16.2 DST 0.08 29.5 -
3. 1.45-
3.00
- - - === Grayish blackish coloured, highly weathered rock fractured Basalt ===

342






M.K. Soil Testing Laboratory


Table No. 12/8 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 9
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 7 -93-
H(62)(31)
59 28 31 CH - - - - - - -
2. 1.00 - UDS 2.68 - 8 -92- 60 25 35 CH 1.80 1.54 17.2 TUU 0.76 5 -
3. 2.00 - UDS 2.68 - 9 -91-
H(61)(30)
56 29 27 CH 1.88 1.61 16.5 Tuu 0.89 4 -
4. 3.00 - UDS 2.70 - 6 94 55 26 29 CH 1.90 1.62 17.5 Tuu 0.89 4 -













343






M.K. Soil Testing Laboratory

Table No. 12/9 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 10
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 8 -92-
H(63)(29)
58 29 29 CH - - - - - - -
2. 1.00 - UDS 2.7 - 8 -92- 61 30 31 CH 1.75 1.52 15.2 TUU 0.69 4 -
3. 2.00 - UDS 2.7 - 10 -90-
H(60)(30)
59 28 81 CH 1.84 1.64 12.2 Tuu 0.78 5 -
4. 3.00 - UDS 2.70 - 8 92 64 30 34 CH 1.87 1.63 14.9 Tuu 0.89 4 -














344






M.K. Soil Testing Laboratory

Table No. 12/10 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 11
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 -89-
H(58)(31)
60 28 32 CH - - - - - - -
2. 1.00 - UDS 2.68 - 10 -90-
H(61)(29)
60 24 36 CH 1.74 1.52 14.5 TUU 0.65 2 -
3. 2.00 - UDS 2.70 - 8 -92-
H(60)(32)
64 29 35 CH 1.79 1.56 14.5 Tuu 0.81 4 -
4. 3.00 - UDS 2.70 - 6 -94-
H(64)(30)
62 28 34 CH 1.85 1.55 19.6 Tuu 0.86 5 -














345






M.K. Soil Testing Laboratory

Table No. 12/11 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 12
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 12 -88-
H(58)(30)
54 24 30 CH - - - - - - -
2. 1.00 - UDS 2.69 - 8 -92-
H(63)(29)
60 25 35 CH 1.84 1.63 12.8 TUU 0.76 2 -
3. 2.00 - UDS 2.66 - 4 -94-
H(63)(31)
64 26 38 CH 1.88 1.65 13.6 Tuu 0.81 5 -
4. 3.00 - DS - - 2 -98-
H(84)(34)
60 24 36 CH - - - - - - -














346






M.K. Soil Testing Laboratory

Table No. 12/12 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 13
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 66 -34-

40 24 16 SC - - - - - - -
2. 1.00 - UDS 2.68 - 6 -94-
H(66)(28)
54 26 28 CH 1.74 1.57 10.9 TUU 0.59 8 -
3. 2.00 - UDS 2.68 - 5 -95-
H(64)(31)
62 28 34 CH 1.81 1.60 12.8 Tuu 0.75 2 -
4. 3.00 - UDS 2.70 - 9 -91-
H(63)(28)
59 29 30 CH 1.85 1.63 13.6 Tuu 0.89 4 -














347






M.K. Soil Testing Laboratory

Table No. 12/13 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 14
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 15 -85-
H(65)(20)
42 25 27 CI - - - - - - -
2. 1.00 - UDS 2.66 - 10 -90-
H(67)(23)
46 24 22 CI 1.74 1.59 9.6 TUU 0.58 5 -
3. 2.00 - UDS 2.68 - 15 -85-
H(63)(22)
45 24 21 CI 1.88 1.64 14.2 Tuu 0.79 8 -
4. 3.00 - UDS 2.66 - 10 -90-
H(64)(26)
45 23 22 CI 1.90 1.64 15.6 Tuu 0.85 2 -














348






M.K. Soil Testing Laboratory

Table No. 12/14 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 15
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 18 -82-
H(56)(26)
58 24 34 CH - - - - - - -
2. 1.00 - UDS 2.68 - 17 -83-
H(58)(25)
61 29 32 CH 1.72 1.50 14.2 TUU 0.59 4 -
3. 2.00 - UDS 2.65 - 7 -93-
H(63)(30)
58 25 33 CH 1.76 1.60 9.9 Tuu 0.69 5 -
4. 3.00 - UDS 2.70 - 13 -87-
H(58)(29)
62 29 33 CH 1.85 1.65 11.8 Tuu 0.78 2 -














349






M.K. Soil Testing Laboratory


Table No. 12/15 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 16
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 11 -89-
H(64)(25)
52 26 26 CH - - - - - - -
2. 1.00 - UDS 2.68 - 9 -91-
H(62)(29)
62 28 32 CH 1.69 1.54 9.7 TUU 0.58 5 -
3. 2.00 - UDS 2.70 - 12 -88-
H(64)(24)
57 27 30 CH 1.74 1.52 14.5 Tuu 0.74 1 -
4. 3.00 - UDS 2.70 - 6 -94-
H(64)(30)
64 28 36 CH 1.84 1.60 14.8 Tuu 0.81 6 -













350






M.K. Soil Testing Laboratory

Table No. 12/16 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 17
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 6 -94-
H(69)(25)
40 26 14 CI - - - - - - -
2. 1.00 - UDS 2.68 - 8 -92-
H(58)(34)
60 25 35 CH 1.70 1.51 12.6 TUU 0.59 2 -
3. 2.00 - UDS 2.65 - 8 -92-
H(62)(30)
58 25 33 CH 1.86 1.64 12.9 Tuu 0.69 4 -
4. 3.00 - UDS 2.68 - 16 -84-
H(54)(30)
62 29 33 CH 1.89 1.65 14.6 Tuu 0.85 2 -














351






M.K. Soil Testing Laboratory

Table No. 12/17 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 18
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00
to
3.000
- DS - Grayish black colure fractured and weathered Basalt rock
















352






M.K. Soil Testing Laboratory

Table No. 12/18 SOIL CHARACTERISTICS FOR TRIAL PIT NO. TP 19
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.
W.T. below G.L. (m): - Not met with

Termination depth (m): 3.0m.
Client : Bhavnagar Energy Company Limited, Gandhinagar

SR.
No.
Depth
In mt.
N value
Obsed
Type of
Sample
Specific
Gravity
Grain Size Analysis

Gravel Sand Silt& Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Soil
Group
Natural Density
Field Dry
Density Density
(g/cc) (g/cc)
Natural
Water
Content
(%)
Shear Parameters
Types C angle of
of Test int. friction
(kg/cm
2
) (degree)
Compress
ion Index
(Cc)
1. 0.00 - DS - - 9 -91-
H(63)(28)
58 28 30 CH - - - - - - -
2. 1.00 - UDS 2.68 - 5 -95-
H(65)(30)
55 26 29 CH 1.69 1.50 12.8 TUU 0.58 2 -
3. 2.00 - UDS 2.70 - 4 -96-
H(64)(32)
58 29 29 CH 1.78 1.55 14.5 Tuu 0.65 8 -
4. 3.00 - UDS 2.70 - 8 -92-
H(61)(31)
60 28 32 CH 1.86 1.65 12.5 Tuu 0.79 2 -














353






M.K. Soil Testing Laboratory




LABORATORY CBR TEST RESULTS
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.


Client : Bhavnagar Energy Company Limited, Gandhinagar

STANDARD
Proctor
Results
CBR TEST
Unsoaked
(%)
Soaked
(%)
TP.
No.
Site Depth
In mt
Sieve Analysis

Gravel Sand Silt &
Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Type
of
Soil
MDD
(g/Cc
OMC
(%)
2.5
mm
5.0
mm
2.5
mm
5.0
mm
Design CBR
(%)
1 PADVA 0.00 14 56 -30- 43 23 17 SC 1.79 10.6 9.6 9.2 6.2 6.0 6
3. PADVA 0.00 - 11 -89- 58 28 30 CH 1.69 15.8 7.8 7.2 3.2 3.0 3
PADVA 0.00 - 9 -91- 58 28 30 CH 1.66 16.5 6.8 6.2 3.2 3.2 3 5.
PADVA 3.00 - 10 -90-
H(62)(28)
59 28 31 CH 1.72* 14.5 7.9 6.5 3.8 3.5 10
PADVA 0.00 - 8 -92-
H(61)(31)
56 24 32 CH 1.70 16.1 6.5 6.0 3.4 3.6 8 6.
PADVA 3.00 - 10 -90- 62 29 33 CH 1.76* 15.5 - - - - -
7. PADVA 0.00 - 5 -95-
H(63)(32)
60 28 32 CH 1.69 15.5 6.0 5.8 3.3 3.4 3
8 PADVA 0.00 - 68 -32- 42 28 14 SC 1.83* 10.8 9.5 9.0 6.5 6.5 7
9 PADVA 0.00 - 7 -93-
H(62)(31)
59 28 31 CH 1.72* 15.9 6.2 6.0 4.2 4.0 4

354






M.K. Soil Testing Laboratory


LABORATORY CBR TEST RESULTS
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.


Client : Bhavnagar Energy Company Limited, Gandhinagar

STANDARD
Proctor
Results
CBR TEST
Unsoaked
(%)
Soaked
(%)
TP.
No.
Site Depth
In mt
Sieve Analysis

Gravel Sand Silt &
Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Type
of
Soil
MDD
(g/Cc
OMC
(%)
2.5
mm
5.0
mm
2.5
mm
5.0
mm
Design CBR
(%)
PADVA 0.00 - 8 -92-
H(63)(29)
58 29 29 CH 1.70 16.6 6.4 6.0 4.1 4.2 4 10.
2.00 - 8 -92- 61 30 31 CH 1.74* 15.5 7.2 7.0 5.2 5.5 5
11. PADVA 0.00 - 11 -89-
H(58)(31)
60 28 32 CH 1.65 14.2 6.5 6.5 3.9 3.6 4
12. PADVA 0.00 - 12 -88-
H(58)(30)
54 24 30 CH 1.72* 15.6 6.6 6.2 4.4 4.2 4
PADVA 0.00 - 66 -34- 40 24 16 SC 1.80* 14.5 7.2 7.0 5.6 5.5 6 13.
PADVA 3.00 - 9 -91-
H(63)(28)
59 29 30 CH 1.69 16.0 6.2 6.0 3.9 3.8 4
14. PADVA 0.00 - 15 -85-
H(65)(20)
42 25 27 CI 1.74 15.5 6.9 6.6 3.8 3.6 4
15. PADVA 0.00 - 18 -82-
H(56)(26)
58 24 34 CH 1.70 16.4 7.8 7.5 4.2 4.2 4



355






M.K. Soil Testing Laboratory



LABORATORY CBR TEST RESULTS
Project: Geotechnical Investigation work proposed 2 x 250 MW Lignite Based Thermal Power Plant in Padva Village,
Tal: Ghogha, Dist: Bhavnagar.


Client : Bhavnagar Energy Company Limited, Gandhinagar

STANDARD
Proctor
Results
CBR TEST
Unsoaked
(%)
Soaked
(%)
TP.
No.
Site Depth
In mt
Sieve Analysis

Gravel Sand Silt &
Clay
(%) (%) (%)
Atterbergs Limits

LL PL PI
(%) (%) (%)
Type
of
Soil
MDD
(g/Cc
OMC
(%)
2.5
mm
5.0
mm
2.5
mm
5.0
mm
Design CBR
(%)
15. PADVA 3.00 - 13 -87-
H(58)(29)
62 29 33 CH 1.78* 14.5 6.8 6.4 4.5 4.5 5
16. PADVA 0.00 - 11 -89-
H(64)(25)
52 26 26 CH 1.69 15.8 6.4 6.0 4.6 4.6 5
17. PADVA 0.00 - 6 -94-
H(69)(25)
40 26 14 CI 1.75* 13.9 7.5 7.2 5.8 5.5 6
19. PADVA 0.00 - 9 -91-
H(63)(28)
58 28 30 CH 1.72* 15.5 6.4 6.2 4.5 4.4 5

.

* 169*

M.K. Soil Testing Laboratory

ABBREVIATIONS

DS Disturbed Soil Sample
UDS Undisturbed Soil Sample
SPT Standard Penetration Test
SBC Safe Bearing Capacity
NP Non Plastic
DST Direct Shear Test
LL Liquid Limit
PL Plastic Limits
PI Plasticity Index
* Remolded Sample
Ref. Refusal
SM Silty sand
ML Sandy Silt
SC Clayey sand
CI Silty clay having medium plasticity
CH Silty Clay Having High Plasticity
GM Gravelly Silty Sand
H Hydrometer











.

* 170*

M.K. Soil Testing Laboratory

CODES AND STANDARDS

All work shall be carried out strictly in accordance with the Technical specifications, unless otherwise
approved by the ENGINEER in writing. Where not specified, the latest edition of the applicable code of
practice or procedure as laid down by the Bureau of Indian Standards (BIS) shall be followed. The earth
manual of the United States Bureau of Reclamation shall also be referred to in the absence or relevant
information, procedures and guidelines by BIS. Only the SI system shall be observed. Metric system may
be used only if approved by the ENGINEER. Some of the relevant standards issued by BIS are listed
below. In case of any discrepancy between these specifications and BIS, these specifications shall govern.

IS : 1080-1995 Reaffirmed-2002 Code of Practice for Design and construction of Shallow
foundations in soils (other than Raft, Ring & Shell)
IS : 1498-1970 Reaffirmed-2002 Classification and identification of soil for General Engineering
Purpose
IS : 1988-1985 Reaffirmed-2002 Method of Load Tests on soils

IS : 1092-1979 Reaffirmed-2002 Code of Practice for subsurface investigations for foundations

IS : 1904-1986 Reaffirmed-2000 Code of Practice for Design and construction of foundations in
soils General requirement
IS : 2131-1981 Reaffirmed-2002

Methods of Standard Penetration Test for soils
IS : 2132-1986 Reaffirmed-2000 Code of practice for Thin walled tube sampling of soils

IS : 2470-1985 Reaffirmed-2001

(Part 1 & Part 2) code of practice for installation of septic tanks
IS : 2720-1983 Reaffirmed-2002

(Part 1 to Part XLI) Method of Test for soils
IS : 2809-1972 Reaffirmed-2001 Glossary of Terms and Symbols relating to Soil Engineering

IS : 2810-1979 Reaffirmed-2002

Glossary of Terms and Symbols relating to Soil Dynamics
IS : 2911-1979 Reaffirmed-2000 & 2002 (Part I to Part IV and all sections) Code of practice for design
and constructions of piles
IS : 2950-1981 Reaffirmed-2003 Code of practice for design and construction of raft foundations

IS : 2174-1981 Reaffirmed-2003 & 2000 (Part I to Part V) Code of practice for design and construction of
machine foundations
IS : 3043-1987 Reaffirmed-2001

Code of practice for earthing
IS : 4078-1980 Reaffirmed-2004 Code of practice for indexing and storage of drill cores

IS : 4091-1979 Reaffirmed-2000 Codes of practice for design and construction of foundations for
transmission line towers and poles
IS : 4032-1969 Reaffirmed-2001

(Part I to Part X) Methods of test for stabilized soils


.

* 171*

M.K. Soil Testing Laboratory

IS : 4434-1978 Reaffirmed-2002 Code of practice for in-situ vane shear test for soils

IS : 4453-1980 Reaffirmed-2002 Code of practice for subsurface exploration by pits, trenches,
shafts
IS : 4464-1985 Reaffirmed-2004 Code of practice for presentation of drilling information and core
description in foundation investigation
IS : 4451-1985 Reaffirmed-2000 & 02 (Part 1 to Part 4) code of practice for design and construction of
Dock and Harbour structures
IS : 4468-1976 Reaffirmed-2002

(Part 1 to Part III) Methods of sub-surface sounding for soils
IS : 5249-1992 Reaffirmed-2000 Method of test for determination of in-situ Dynamic properties of
soils
IS : 5313-1980 Reaffirmed-2004

Guide for core drilling observations
IS : 5529-1985 Reaffirmed-2004

(Part I and Part II) Code of practice for in-situ permeability
IS : 6603-1981 Reaffirmed-2002

Code of practice for determination of allowable bearing capacity
of shallow foundations
IS : 6926-1972 Reaffirmed-2001

Diamond core drilling site investigation for river valley projects
code of practice
IS : 6935-1973 Reaffirmed-2002

Method for determination of water level in a borehole
IS : 6955-1972 Reaffirmed-2004

Code of practice for subsurface exploration for earth and rock fill
dams
IS : 8009 (Part I01976, Reaffirmed-2003
& Part II_1980, Reaffirmed 2000)
Code of practice for calculation of settlement of foundations
IS : 8763-1978 Reaffirmed-2002

Guide for undisturbed sampling of sands & sandy soils
IS : 8764-1998 Reaffirmed-2003

Method of determination of point load strength index of rocks
IS : 9214-1979 Reaffirmed-2002

Methods of determination of modulus of sub grade reaction
(k value) of soils in the field
IS : 10042-1981 Reaffirmed-2002

Code of practice for site investigations for foundation in gravel-
boulder deposit
IS : 10082-1981 Reaffirmed-2001

Method of test for determination of tensile strength by indirect
tests on rock specimens
IS : 10108-1982 Reaffirmed-2001

Code of practice for sampling of soils by thin wall sampler with
stationary piston
IS : 11315 Reaffirmed-2000 & 2001

(Part 1 to Part 12) Method for quantitative description of
discontinuities in rock mass
IS : 11550-1985 Reaffirmed-2002

Code of practice for field instrumentation of swelling pressure in
expansive soil
IS : 12070-1987 Reaffirmed-1987

Code of practice for design and construction

You might also like