Professional Documents
Culture Documents
= 1 )
4
ln(
2 a
L
L
R
(2)
were L is the rod length, a the radius of the transversal rod
section.
TABLE I
COMPARISON OF GROUNDING RESISTANCE RESULTS CONSIDERING
DIFFERENT VALUES OF SOIL ELECTRIC RESISTIVITY.
Resistivity
(m)
R ()
from TLM
R ()
from analytic
expression [4]
Relative
Variation
(%)
10,0 4,28 4,18 -2,39
50,0 19,90 20,88 4,69
100,0 37,76 41,76 9,58
150,00 54,33 62,64 13,27
200,0 70,23 83,53 15,92
300,0 100,74 125,29 19,59
400,0 129,76 167,05 22,32
500,0 158,00 208,82 24,33
1.000,0 293,00 417,63 29,84
1.500,0 423,35 626,44 32,42
2.000,0 550,00 835,26 34,15
The Fig.3 and Fig.4 show the transient grounding
resistance curves, obtained through the TLM simulation for
the values of resistivity of the soil listed in the Table I.
Fig. 3 Transient grounding resistance obtained from TLM simulation:
Resistivity of the soil from 10 to 200 m.
1507
Fig. 4 Transient grounding resistance obtained from TLM simulation:
Resistivity of the soil from 300 to 2000 m.
VI. THE ATP SIMULATION
The ATP [10] was used to perform the simulations for the
analysis of the overvoltage on a costumer connected to the
secondary of the distribution transformer modeled in [5].
It was simulated the case of direct lightning discharges in
the primary of the transformer and was adopted in the
simulations, a lightning current with standardized waveform
presented in Fig. 2.
The basic configuration used in the simulations is shown
in Fig. 5. This figure shows the transformer and the costumer
being grounded with a transient grounding resistance (TGR),
obtained using the TLM method.
The Table II and Fig. 6 show the results obtained in
this stage of the research: The peak of the overvoltage in a
phase of the costumer submitted to the lightning discharge
that occurred in the primary of the distribution transformer,
considering the constant grounding resistance (CGR),
transient grounding resistance and different values of the soil
electric resistivity.
TABLE II
OVERVOLTAGE VALUES OBTAINED WITH ATP SIMULATION
Resistivity
(m)
Peak of overvoltage (V)
Relative
Variation
(%)
Using
CGR
Using
TRG
10,0
544 564 3,68
50,0
669 672 0,45
100,0
698 700 0,29
200,0
709 710 0,14
300,0
677 709 4,73
400,0
631 700 10,93
500,0
588 686 16,67
1.000,0
509 647 27,11
1.500,0
322 624 93,79
2.000,0
261 610 133,72
Fig. 5 Modeling that was used for simulation in the ATP.
Fig. 6 Comparison of the overvoltage level between two models of the
grounding resistance, considering different values of the resistivity.
VII. ANALYSIS OF THE RESULTS
The results of the simulation show that for the grounding
topology presented (a vertical rod in the homogeneous soil),
the steady-state values of the resistance obtained from the
TLM method were lower than the values obtained from the
analytic formulation (the exception for10 .m).
1508
The higher the soil resistivity, the higher the difference
between the values for the analytical grounding resistance and
the values obtained from the TLM (see Table I).
To identify which of the two models that presents the
higher accuracy, the experimental measurements should be
developed to establish comparisons.
The overvoltage levels obtained from the simulation using
the model with the transient grounding resistance were bigger
for all cases than the overvoltage values obtained applying
the traditional grounding resistance (see Fig. 6). This means
that the grounding model proposed (using the TGR) is more
conservative than the traditional model.
Regarding the soil resistivity, the higher the resistivity, the
higher the relative difference between the two models of the
grounding. For low values of the soil resistivity (until 400
m approximately), the difference of the overvoltage
between the two models were not significant (until 11% of
difference, approximately). This also means that for the
grounding configurations with low resistivity, the traditional
model (simplified model) can be applied without
compromising the accuracy of the results in the studies of
overvoltage in the distribution systems.
VIII. CONCLUSIONS
In this work was presented the simulation results with the
ATP-TLM model to observe the overvoltage levels in the
customer, considering constant and transient values of the
grounding resistance applied in the transformer and customer.
The results show that there is a significant difference in the
overvoltage levels, with the increase of the soil resistivity and
modeling the grounding systems with transient resistance.
It can lead to an under rating of the protection associated
to the distribution network, once that overvoltage levels do not
are observed when constant grounding resistances are
considered.
In the next step of this research, new simulations will be
performed with different values of the grounding resistance in
the transformer and customer, also increasing the number of
the customers connected to the distribution network and to
implement others configurations of the grounding topologies
(ex. three vertical and interconnected rods, soil stratification).
Some laboratory tests have been initiated with the
configuration modeled in the ATP and utilizing a typical
distribution transformer to observe the overvoltage levels in
the secondary side, when it is subjected to the atmospheric
impulse.
ACKNOWLEDGMENT
The authors would like to thank the Companhia Estadual de
Distribuio de Energia Eltrica CEEE-D in Rio Grande do
Sul State and University of Blumenau - FURB in Santa
Catarina State, Brazil for their financial support in the
researches.
REFERENCES
[1] A. Piantini and J. M. Janiszewski, Induced voltages on distribution
lines due to lightning discharges on nearby metallic structures, IEEE
Transactions on Magnetics, vol. 34, n. 5, pp. 2799-2802, Sep. 1998
[2] C. A. Nucci, A. Borghetti, A. Piantini and J. M. Janiszewski,
Lightning-induced voltages on distribution overhead lines:
comparison between experimental results from a reduced-scale model
and most recent approaches in Proceedings of the International
Conference on Lightning Protection (24th ICLP), vol. 1, pp. 314-320,
Birmingham, U.K., Sep. 1998.
[3] M. Tell, G. Dias, A. Raizer, H. D. Almaguer, T. I. Mustafa and V.
Coelho, Aterramento Eltrico Impulsivo em Baixa e Altas Freqncias,,
EDIPUCRS, 1
a
Edition, 2008.
[4] S. F. Visacro, Aterramentos Eltricos. So Paulo: Ed. Artliber, 2002.
[5] A. G. Kanashiro and A. Piantini, Surges transferred to the low-
voltage network via transformer The influence of the load connected
to the secondary in Proceedings of GROUND2002- Internatiional
Conference on Grounding and Earthing & 3
rd
Brazilian Workshop on
Atmospheric Electricity, Rio de Janeiro, Brazil, Nov. 2002.
[6] C. Christopoulos, The Transmission-Line Modeling Method- TLM,
New York: IEEE Press and Oxford University Press, 1995.
[7] H. D. Almaguer, Contribuio ao Mtodo da Modelagem por Linhas
de Transmisso (TLM) e sua Aplicao aos Estudos em
Bioeletromagnetismo, Thesis of PhDs Degree in Electrical
Engineering, Federal University of Santa Catarina, Brazil, 2003
[8] P. Naylor and R. Ait-Said, Simple Method for Determining 3 D
TLM Nodal Scattering in Nonscalar Problems, Electronics Letters,
vol. 38, n. 25, pp. 2353 2354, December 1992.
[9] IEC - International Electrotechnical Commission, Section of IEC
1000 4 5, pp. 39, 1995.
[10] M. Kizilcay, M. and L. Prikler, ATP-EMTP Beginners Guide for
EEUG Members, Osnabruck University of Applied Science, Germany,
June 2000.
1509