Professional Documents
Culture Documents
1.1
PDO COMMENTS
PDO
Reference
Indicator
TRE/GEC RESPONSES
STATUS
PDO
CONFIRMATION/
APPROVAL
Complied.
MU5575
Steve Niu,
UEOA13
Complied.
MU5575
Steve Nlu,
UEOA13
MU5575
Steve Nlu,
UEOA13
Complied
Page1 of 10
12-07-13
.
4
PDO COMMENTS
PDO
Reference
Indicator
TRE/GEC RESPONSES
STATUS
PDO
CONFIRMATION/
APPROVAL
321
5.2
'
MU5575
Steve Nlu,
UEOA13
MU5575
Steve Nlu,
UEOA13
Complied.
The average level" Is used for
control as this will give more
time for the separator to make
up the level and also the same
type of control Is being used In
NRPS
CPI
the
existing
separators.
Page2 of 10
12-07-13
PDQ COMMENTS
on the selection of
"average" level for control. It Is more
typical to use the "maximum" or
"minimum" level for controldepending on
whether operation concerns more on the
potential overflow or underflow of the
liquid.lt Is less common to use "average"
level.
Page 24, Sec 5.2:For the section under
"FWKO Tank, Process Control": Rewrite
this section. The description of the
control purpose and functionality is
absolutely confusing. Change to
something like this
"The pressure in the tank T-48350 is
maintained between 0.5 kPa(g) and 1.0
kPa(g) by dualpressure controllers 48PIC3502A and 48PIC-3502B. The process
value for the two pressure
controllers comes from the same pressure
transmitter 48PT-3502. When the tank
pressure Is above.
1.0 kPa(g), controller 48PIC-3502B will
open the flare valve 48PCV3502B and
send the excess gasln the tank to flare. In
case the tank pressure falls below 0.5
kPa(g), the controller 48PIC-3502A
would open the blanket gas valve
48PCV3502A to bring In more fuel gas to
brlnQ the pressure backto normal range.
PDQ
Reference
Indicator
TRE/GEC RESPONSES
STATUS
PDQ
CONFIRMATION/
APPROVAL
Page3 of 10
12-07-13
.
7
PDQ COMMENTS
PDQ
Reference
Indicator
STATUS
PDO
CONFIRMATION/
APPROVAL
j
!
Water
Disposal
pump
discharge flow Is controlled by
the flow controller 48FIC-3520
cascaded with average level
controller (48LIC-3542A) of the
new CPI separators, through a
manual bias 48Y-3512. It Is not
flow control with level override.
Pressure controller PIC-3561 &
subsequently control valve
PCV-3561 are removed from
the motive water line to Solid
handling system, which is
tapped-off from Disposal water
booster
pumps'
discharge
header. Because the flow rate
of motive water will be
controlled to the solid handling
system (I.e. motive water to Jet
pumps and Tores).
Accordingly,
related
Page4 of 10
I
I
12-07-13
---
PDQ
Reference
Indicator
PDQ COMMENTS
--------------------------------------------
STATUS
PDQ
CONFIRMATION/
APPROVAL
Complied.
I
--
--
------
PageS of 10
12-07- 13
PDQ COMMENTS
control?)
- L1C3541 B provides the high level
protection In case the tank level rise
above a prescribed hlghllmit. In case of
high level, the level control LIC3541 B will
override the Inlet flow controller FC3502,
vlaa low selector, to reduce the Inlet flow
to help bring the tank level to normal.
(explain what protectionis provided forT48350 level If FC3502 Is overridden by
L1C3541 B)
Remove the sentence "The flow is
controlled at set point provided say 8500
m3/d ... ". This is a typicalcascade loop,
and the flow set point Is determined by
the level controller output, and Is varying
all thetime
10
11
I 5.2
PDQ
Reference
Indicator
PDQ
TRE I GEC RESPONSES
I STATUS I CONFIRMATION/
APPROVAL
12-07-13
PDO COMMENTS
12
13
PDO
Reference
Indicator
I STATUS I
PDO
CONFIRMATION/
APPROVAL
12-07-13
'
14
15
PDQ COMMENTS
PDO
Reference
Indicator
I STATUS I
PDO
CONFIRMATION/
APPROVAL
12-07-13
'
PDQ COMMENTS
PDQ
Reference
Indicator
TRE/GEC RESPONSES
STATUS
PDQ
CONFIRMATION/
APPROVAL
16
17
18
19
App II
Gen
MU5575
Steve Nlu,
UEOA13
MU5575
Steve Niu,
UEOA13
i
I
I
Page9 of 10
12-07-13
20
PDQ COMMENTS
PDQ
Reference
Indicator
TRE/GEC RESPONSES
STATUS
PDQ
CONFIRMATION/
APPROVAL
Page10 of 10
12-07-13
_ ___.,Lib.
TECNICAS RfUN IDAS
TR EnglnMring LLC
G11far
GALFAR ENGINEERING &
CONTRACTING SAOG
TR ENGINEERING LLC
DOCUMENT NO
TRE PROJECT NO
J63881
REVISION
04
DATE
22-09-2013
TR Engineering UC
P 0 Box 1597. PC 112, Ruwi, Sultanate of Oman
Tel: +968 24642100
Fax: +968 24604 414
NIM-48-1 02017-PX-5680-00002-0000
Page 1 of 43
Revision: 04
22-09-2013
...
~"'
tij
lAb
Qllfar
TE<:NICAS REONIDAS
TR Engineering LLC
TR ENGINEERING LLC
Criticality Level:
REV
DATE
DESCRIPTION
PREPD
BY
CHKD
BY
APPD
BY
TA
01
23/11/11
02
14/05/12
Issued for
Review
03
06/03/13
APPD.BY
EM
GEC
STB
RK
RK
VR
STB
RK
RK
DVS
PDO
GEC
Issued as final
PDO
GEC
HAZOP
MRM
04
Verification Level:
~~
HRD/JMB
RK
RK
1/t 46
DVS
PDO
~-QJ--
GEC
DVS
PDO
~.-
REUANCE NOTICE
This report is issued pursuant to an Agreement between JnitecPfantaslndustriales SAU (Member of TR
Group of Companies) and/or its subsidiary or affiliate companies TR Group, and "Gaffar Engineering &
Contracting S.AO.G" on behalf of Petroleum Development Oman (PDO) which agreement sets forth the
entire rights, obligations and liabilities of those parties with respect to the content and use of the report.
Reliance by any other party on the contents of the report shall be at its own risk_ TR Group makes no
warranty or representation, expressed or implied, to any other party with respect to the accuracy,
completeness, or usefulness of the information contained in this report and assumes no liabiUties with
respect to any other party's use of or damages resulting from such use of any information, conclusions or
recommendations disclosed in this report.
Page 2 of 43
Revision: 04
22-()9-2013
....
.....
PETROLEUM DEVELOPMENT OMAN
Lib.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TCNICAS REUNIOAS
TR Englnoering U.C
CONTENTS
FRONT PAGE
DOCUMENT REVISION RECORD
CONTENTS
ABBREVIATIONS
HOLDS
1.0
2.0
INTRODUCTION
1.1
Document Objective
SCOPE OF WORK
2.1
2.3 Exclusions
10
PROCESSDESC~PTION
11
11
15
4.0
CONTROL SYSTEM
23
5.0
24
24
25
REFERENCES
43
3.0
6.0
NIM48-1 02017-PX-5680-00002
Page 3 of 43
Rev1s1on : 04
22-09-2013
..~.
~
tij
lab.
Qllfar
TECNICAS REUNJOAS
TR Engineering I.LC
TR ENGINEERING LLC
ABBREVIATIONS
AP
Atmospheric Pressure
BS&W
CCR
CPI
cs
Carbon Steel
CWT
DCS
DWD
EORD
EPC
ESD
Emergency shutdown
ESP
FAR
FCS
FOP
FEED
FO
Fibre Optic
F&G
FWKO
GFU
GOR
GRE
HEX
Heat Exchanger
HMI
IPF
IPS
t<JNWF
LAN
N IM-48-1 02017-PX-5680-00002
Page4af43
Revision: 04
22-09-2013
.....
.e:1P-e
Lib.
Glllfar
tij
"reCNICAS IU:UNIOAS
TR engi,.nng LLC
TR ENGINEERING LLC
LP
Low Pressure
MOS
MSV
NFA
No Further Activity
NGD
Nimr-G Development
NRPS
ODCB
OPC
PAS
PCV
PDO
PE
Polyethylene
PEFS
PI
Plant lnfonnation
PLC
PPM
RMS
SIL
SOE
Sequence of Events
TRE
TR Engineering LLC
NIM-48-102017-PX-5680-00002
Page 5 of 43
Revision 04
22-09-2013
__.lAb.
Qllfar
PETROLEUM DEVELOPMENT OMAN
TR ENGINEERING LLC
HOLDS
1. Deleted.
2. Deleted.
NIM-48-1 02017-PX-5680.00002
Page 6 of 43
Revision: 04
22..09-2013
___.,l_n_l,_
Gfllfar
PETROLEUM DEVELOPMENT OMAN
TEO~ICAS
R.EUNlDAS
TR Engirwering U.C
TR ENGINEER.I NG LLC
1.0
INTRODUCTION
1.1
Document Objective
The purpose of this document is to provide the process control narratives for Nimr-G
Development Project (NGD Project). This document supplements with the process flow
schematics (PFS) and Process Engineering Flow Schematics (PEFS) to provide detailed
and unambiguous descriptions on the objectives, strategy, functionality, implementation
and operation of the process control system.
1.2
Project Objective
Nimr-G is a part of Nimr field and is located about 5 km North of Nimr Production Station
(NRPS). Nimr-G field will be developed by drilling 140 new wells. The current NFA
production from Nimr-G is 15364 m3 /d and with the planned infill drilling, the peak gross
product.ion is expected to reach 59605 m3 /d in year-2021 with addition of 140 new wells
in the field. The production of gross fluid from the new wells is routed to NRPS for
dehydration. To accommodate the increased gross production, new facilities are required
to be developed, i.e. On-plot & Off-plot facilities at Nimr-G and on-plot facilities at NRPS.
New FWKO tank. CPI Separators (with online solid removal system), Emulsion Transfer
pumps and Water Disposal Booster pumps will be installed at NRPS to adhere to the
tank maintenance philosophy and to avoid deferment
The FEED for the NGD Project was carried out by PDO FEED office.
Galfar Engineering & Contracting SAOG is awarded the EPC contract TR-Engineering
(TRE) Muscat will carry out the Detailed EngineeringD for the EPC contractor. The
project code is "KPH.
1.3
Site Location
A brief overview of the Nimr field is shown in Rg 1.1 below:
NIM-48-102017-PX-5680-00002
Page7 of43
Revision 04
22-09-2013
....
4,
lAb.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Engl.-ring lLC
TR ENGINEERING LLC
M1Jll NORTH
NIM48-1 02017-PX-5680-00002
Page 8 of43
a 20 aN
Revision: 04
22-09-2013
.,.,
.....
PETROLEUM DEVELOPMENT OMAN
li..6.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
1:ij
TECNICAS REUNTOAS
TR EnglDMring LLC
TR ENGINEERING LLC
2.0
SCOPE OF WORK
Following new major equipment/items will be provided as a part of scope of this job:
2.1
2.2
16 concrete Drain pits at Nimr-G field for collection of maintenance drains from
RMS and Pig Launcher for 24" CS-PE pipeline.
Coriolis and High water cut meter to be installed on each MSV test line.
Two number of gross infield 14 GRE buried pipeline (one 6.8km and 6.2 km long)
from RMS area to Nimr-G for collection of gross fluid from all new MSV units.
C8-PE lined externally 3 LPE coated buried pipeline (24 size and 5.0 km long)
from Nimr G to NRPS for transporting gross from new wells in Nimr G area to
NRPS.
De-emulsifier chemical injection at the start of 24" CS-PE gross fluid pipeline from
a De-emulsifier chemical injection skid ().
NRPS (On-Plot)
Bulk meter/s for Nimr-G new wells gross flow measurement at NRPS.
One FWKO tank of normal capacity of 140000 m3 /day NRPS identical to existing
FWKO tank T -4819.
Emulsion transfer pumps (3 working and 1 standby, each of capacity 8500 m3 /d)
(*).
Water disposal booster pumps (2 working and 1 standby, each of capacity 20000
m3 /d) r).
Page 9 of 43
Revision 04
22-09-2013
..,.
....
PETROLEUM DEVELOPMENT OMAN
tij
lAb.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TfC~IICAS
~
llfUNlDAS
Engl . -ring
u.c
TR ENGINEERING LLC
Tie in with the existing utilities like Instrument air, Drain system, flare system , fuel
gas system and chemical injection systems.
Tie in with the existing ring main header for inlet to new FWKO tank, emulsion
transfer pumps discharge header and water disposal booster pumps discharge
header.
2.3
Exclusions
Following items are excluded from the scope of this job.
Off-Plot
Well head facilities for 140 wells
Well flow lines from wellhead to the RMS fence
NIM-48-102017-PX-5680-00002
Page 10 of43
Revision 04
22-09-2013
....
tij
lab.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TR ENGINEERING LLC
3.0
PROCESS DESCRIPTION
3.1
3.1 .1
Existing Facilities
The gross fluid production from existing oil producer wells of Nimr-G flows to NRPS via
an 18", 5 km long CS-PE lined pipeline. Some of the Nimr-G gross fluid flows to Nimr-A
directly through a 12", 4.5 km long GRE pipeline which combines with Nimr-A gross fluid
production and flows to NRPS via a 30", 9 .7 km long, CS-PE lined pipeline as shown (in
blue color) in fig 3.1.
3.1.2
NIM-48-102017 PX-5680-00002
Page 11 of43
Revision: 04
22-09-201 3
..,.
.:..
Qllfar
GALFAR ENGINEERJNG &
CONTRACTING SAOG
tij
lA6.
TECNIC.AS REUNIDAS
TR fn11inMI!ng LLC
TR ENGINEERING LLC
Nimr G field
~----------- --- --------- - -------- ---,
:
:
Nimr G existing
G :r'~
1 2_'_'._ _4_.s_k_m~ Nimr-A
I
I
I
I
I
I
I
I
I
30", 9.7km, CS + PE
;1
24" , 5km, CS + PE
NRPS
EXISTING LINES
-
The detailed process description of the MSVs, GRE headers and the gross fluid pipeline
are given item wise below.
3.1.3
Page 12 of 43
Revision 04
22-09-2013
_ ___.,lAb
Qllfar
PETROLEUM DEVELOPMENT OMAN
TCNICAS REUNIOAS
TR Engineering LLC
TR ENGINEERJNG LLC
.
7 new RMS's having 11 New MSV's
NRPS
3.1.4
Drain Pit
As the H2S concentration in process fluid is approximately 4000 ppm in gas phase, it was
decided that Nimr-G off plot (MSV's, Drain system, Off plot pipelines) facilities shall be
designed with 25 % margin i.e 5000 ppm concentration in gas phase. Accordingly all the
off-plot facilities is considered as high risk sour service. Therefore, maintenance drains
from MSV units will be routed to closed drain pit. The vent from each drain pit will be
discharged through elevated vent line so that during venting the H2S concentration at
ground level shall be less than 10 ppm (as per the standards). For each RMS unit. one
drain pit is provided. Therefore, there will be 15 drain pit required for 15 RMS units. One
more drain pit is provided near pig launcher area of 24e CS-PE pipeline. Drains from GRE
header 1 & 2 temporary launcher area to be routed to RMS-8 and RMS-1 drain pit. Drain
pit is sized for collecting the maintenance drains of two MSV units.
3.1.5
NIM-48-102017-PX-5680-00002
Page 13 of43
Revision o.s
22-09-2013
4Pe
~,
IA6.
G11far
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Engmeering U.C
TR ENGINEERING LLC
3.1.6
GRE Headers
Please refer following schematic diagram Fig 3.3 for NIMR-G MSV and locations routing
of GRE headers
A-53104
A-53105
GRE HEADER1
A-53100
A-53101
A-53102
A-53103
A-53118
A-53119
A-53113
A-53114
GRE HEADER2
CS PE PIPELINE
GRE Headers /Pipelines
NRPS
CSPE lined Pipeline
Fig 3.3 Schematic diagram for Nimr-G MSV locations and routing of GRE headers
NIM-48-102017-PX-5680-00002
Page 14 of 43
Reviston: 04
22-09-2013
_ _...lAb.
Qllfar
TR ENGINEERING LLC
RMS
MSVTAG No.
RMS
MSVTAG No.
MSVTAG No.
A-53106
A-53110
A-53107
MSVTAG No.
RMS
RMS
A-53111
11
A-53115
14
A-53112
12
A-53116
15
10
13
A-53117
3.1.7
3.2
NRPS (On-Plot)
3.2.1
Existing Facilities
Gross fluids are received at NRPS in existing three Free Water Knockout (FWKO) tanks,
T -4817, T-4818 & T-4819. The bulk of the water is removed in the FWKO tanks leaving
an emulsion of oil and water. The high viscosity emuJsion , downstream of the FWKO
tanks, is dehydrated in four parallel dehydration trains. In each dehydration train, the
emulsion is heated to break the emulsion and oil-water separation is achieved in a
Concentric Wash Tank (CWT).
Nimr production station schematic with Nimr-G Project scope is shown in fig 3.4 below:
NIM-48-1 02017-PX-5660.00002
Page 15 of43
Revision: 04
22-()9-2013
..4Ph
_.
PETROLEUM DEVELOPMENT OMAN
lAb.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS Ra.INIOAS
OR Eng"-ring LLC
TR ENGINEERING LLC
MIIIRPRODUCTION STATlOM
SOtf;I.&AllC DIAGRAM
NIM~B-1 02017-PX-5680.00002
Page 16 of 43
Revis1on: 04
22-09-2013
4Ph
a
PETROLEUM DEVELOPMENT OMAN
lab.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNTDAS
TR EngJ.......nng U.C
TR ENGINEERING LLC
Nimr Production Station (NRPS) has full accommodation, logistics, oil processing and
electric power generation infrastructure.
3.2.2
New Facilities
3.2.2.1
FWKO TANK
T-48350
The gross production from all the Nimr fields and gathering stations are fed to the NRPS
Free Water Knock Out (FWKO) tanks T-4817118/19 where free water is knocked out.
As a part of this project, new FWKO tank (T-48350) will be installed. The inlet tapping for
new FWKO tank will taken from Ring main header which will installed as part of 'NRPS
on plot piping to T -4817, 18 & 19 replacement' ongoing project (Worley Parsons job
number- PAIP00238, Project code - CN ).
The function of FWKO tank T-48350 is:
The FWKO tank is used to de-gas the incoming mixed phase feed stream. The
degassing is done in the outer tank of the concentric FWKO tank. The separated gas is
routed to the AP flare system. The produced water then flows by gravity to downstream
CPI separators, this is to knock out the free water and de-oil the knocked out water to the
lowest possible level of several hundred ppm of oil.
The FWKO tank is identical to existing Nimr-G FWKO tank (T-4819). FWKO tank has two
concentric tanks of diameter 33/39 m (inner I outer tank) and height of 10.45/12.5 m
(inner I outer tank). The water transfer port level has been kept at 300 mm above the tank
bottom to allow for solid settling in the tanks and to prevent solid carry over to the
downstream CPI separators.
Flow to the new FWKO tank is from the gross fluid ring header which also supplies to the
existing FWKO tanks. A motor operated V-notch type throttling ball valve is provided
close to ring header to regulate the inlet flow to the tank to provide hydraulic balance of
flows to the new & existing FWKO tanks. Gross-fluid to T-48350 is evenly distributed to
six nozzles around the tank, to provide a flow pattern that enhances the separation
performance. Each inlet nozzle is provided with a ramp inlet device that assists in
degassing and free-water knockout processes by decreasing the mixing action as the
feed enters the tank. The oil outlet device is a standard oil draw-off pan with a serrated
lip and a vortex breaker to avoid the introduction of gas into the oil stream. The water
draw-off is provided with a vortex breaker and a deflector plate, to minimise the quantity
of oil entrained into the water stream as a result of flow short circuiting from the
dispersion layer above.
NIM-48-102017-PX-5680-00002
Page 17 of43
Revision: 04
22..{)9-2013
,.
...
PETROLEUM DEVELOPMENT OMAN
liJ.:a.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Engineering UC
TR ENGINEERING UC
Water from FWKO tank is further routed to two banks of CPI separators i.e. new CPI
separators (40000 m3/d) and existing North CPI separators(80590m3/d). When the
FWKO tank is under maintenance, the new CPI separators will receive water from the
ring main header and aJso from the other existing FWKO tanks currently in operation.
The emulsion will be routed to new emulsion transfer pumps.
Tank Pressure, Oil level and Interface level is available for control & monitoring in the
NRPS FCS.
3.2.2.2
NIM-48-1 02017-PX-5680..()0002
Page 18of 43
Revasion: 04
22..()9-2013
..,.
....
PETROLEUM DEVELOPMENT OMAN
lA6.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TE<:NICAS RfUNIDAS
"TR Engineering UC
TR ENGINEERING LLC
3.2.2.3
CPI SEPARATORS
v-48350/351/352/353/354
The Produced water (Oily water) from the FWKO tank (T-48350) will flow by gravity, to
the new CPI separators and also to the existing North CPI separators.
The CPI separator package A-48392 contains CPI separators (4 working and 1 standby),
each of design capacity is 10000 m3/d along with on-line solid handling and removal
system.
CPI Separator reduces the oil in water concentration from 250 ppm to 100 ppm. The
separated oil from new CPI separators is connected to the separated oil header from
north bank CPI separators, which is finally routed to Dry Oil Sump vessel (V-4882) by
gravity flow. The oil-water mixture from dry oil sump vessel will be pumped to the suction
header of existing and new emulsion transfer pumps.
In case, North CPI train is not in operation (which is unlikely scenario), then part of the
produced water can further diverted to both South 'A' and 'B' CPI Separator banks from
the same header which brings water from T-4817/18 tanks to North CPI train.
During the new FWKO tank (T-48350) maintenance, supply of the water to the new bank
D CPI separator shall be routed from the existing FWKO tanks (T-4817 & T-4818). Due to
location of the existing FWKO tank (T-4819), which is far away from the new bank -D CPI
separators, the probability of water being fed from T-4819 is an unlikely event. The flow
will be "reversed" from the water ring main header with a 30" tie-in located upstream of
the existing LCV-0111 B.
Each CPI Separator will have its own on-line Solids handling system to transfer any
settled solids to a downstream solid disposal system. Similar arrangement for receiving
solid from the GFU will be provided under the Karim West Water Aooding Project. Each
CPI separator will have a dedicated solid removal eductor. The outlet of the eductors will
be connected to a common hydro-cyclone to separate solids and water. The common
hydro-cyclone will receive slurry from the all the five CPis as well as from the GFU. The
recovered water will be recycled back to the gross fluid ring header. The solids as slurry
will be routed to evaporation pond. Motive fluid for solid removal system shall be provided
from Water Disposal Booster pumps common discharge header.
Motive water for the operation of the online solid removal system shall be supplied from
the common discharge header of the disposal water booster pump. The header shall
include a pressure control valve for regulating the pressure and the water is distributed to
new CPI separators package (A-48392) and to the Gas Floatation tank T -48301 (to be
installed as part of Karim West Water Flood Project) . For each CPI separators the
Page 19 of43
Revision: 04
22-09-2013
6. . .
IJr
lAb.
G11far
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TEC NICAS REU N IDAS
lR Engineering U.C
TR ENGINEERING LLC
motive water flow rate is-72 m3 /hr including hydrocyclone at a pressure of 15.6 bar(g) at
the package battery limit. The motive water requirement is intermittent nature and shall
operate for approximately 15 minutes per day. Refer CPI vendor's Operating Philosophy
(Ref 4) & Solid handling vendor's Operating and Control Philosophy (Ref 6) for further
details.
3.2.2.4
3.2.2.5
EVAPORATION POND
An open pond with PE liner is provided outside the NRPS. The Evaporation pond has two
compartments. The evaporation pond will receive slurry from the Hydro-cyclone (part of
the CPI separator package). The Surface area of the pond will be sized for evaporation of
the water received on a daily basis & also to dry the received solids. The solids on drying
will be removed from the evaporation pond by shoveling periodically during maintenance.
3.2 .2.6
Off Plot
Maintenance drains from MSV area for off plot area shall be connected to closed drain pit
inside RMS . One drain pit is provided for each RMS. The drain pits will be decanted by
vacuum Trucks.
The vents from the drain pits will be routed to atmosphere through vent pipes to a safe
location to cater to the H2S limits in atmosphere.
The vent from CS PE line is routed to atmosphere through vent pipe provided at either
end of flange section to a safe location to cater H2S limit in atmosphere.
On Plot
NIM-48-102017-PX-568~0002
Page 20 of 43
Revis1on: 04
22..()9.2013
..,.
...,
PETROLEUM DEVELOPMENT OMAN
IA6.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Englneering LLC
TR ENGINEERING LLC
Process drains from all various new facilities at NRPS and from the PE liner vents shall
be connected to a nearby suitable closed drain header which shall be further routed
underground to LP flare knockout drum (V-4858). The vent from FWKO tank including
level instruments, CPI Separators shall be connected to the nearby vent header which
shall be further routed to LP Flare Knock Out drum (V-4858).
Instrument Air
Off Plot
No requirement
On Plot
Supply of Instrument air for the new facilities for this project shall be taken from the
existing instrument air network at NRPS.
Fuel Gas system
Off Plot
No fuel gas is required in the off plot facility.
On Plot
Fuel gas will be required for new FWKO tank and CPI Separators for blanketing purpose.
This will be tapped from the existing system at NRPS.
AP Flare system
The vents from FWKO tank and CPI units will be connected to the existing AP flare
network.
Chem ical i njection system
Off Plot
De-emulsifier chemical injection is required. The de-emulsifier will be injected
continuously at the start of 24" C$-PE gross fluid pipeline from a De-emulsifier chemical
injection skid (*) .
(*)-Free issue item by PDO to Galfar.
On Plot
The scale inhibitor chemical injection is required for the emulsion outlet line from new
FWKO tank. The scale inhibitor line from the existing chemical injection pumps discharge
manifold will be routed to new FWKO tank.
NIM-48-102017-PX-5680-00002
Page 21 of43
ReVISion 04
22-09-2013
.,.
~
PETROLEUM DEVELOPMENT OMAN
lAb.
Gfllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REiJNIDAS
TR Engl.-ring LLC
TR ENGINEERING LLC
Antifoam agent is required for the new Nimr-G pipeline bringing all gross fluid from Nimr
G new wells to NRPS. The antifoam agent injection tapping is provided on this pipeline at
NRPS before joining to Ring main header. The antifoam connection is tapped from
nearby antifoam line joining to ring main header.
NIM-48-~020~ 7-PX-5680-00002
Page 22 of43
Rev1sion: 04
22-09-2013
...
~-
lAb.
Gtlfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS RE\JNIDAS
lltEngi~UC
TR ENGINEERING LLC
4.0
CONTROL SYSTEM
Two nos. field mounted TUV certified , class AKS, SIL3 PLC based, field IPS (one each
for Nimr-A and Nimr-G pipeline overpressure protection) shall be installed as part of this
project Both the field IPS shall be of same make as the new station IPS at FAR-1 . The
existing Nimr-A pipeline overpressure protection Maglog make IPS shall be replaced with
the new field IPS.
The field IPS for Nimr-G pipeline overpressure protection shall trip the ODCB's supplying
power to existing and new Nimr-G wells. This IPS shall be located approximately 3 kM
from NRPS and shall communicate over FOC.
The field IPS for Nimr-A pipeline overpressure protection shall transfer the Nimr-G wells
shutdown signal to Nimr-G pipeline overpressure protection IPS through FOC which shall
transfer this shutdown signal through hardwire to the ODCB's located in Nimr West
substation which is approximately 500 m away.
The Control and Automation system for the new facilities to be built in NRPS as part of
Nimr-G Development and Karim West Water flood project shall be a stand-alone system
with interface with the existing Foxboro DCS and Triconex IPS for control and
safeguarding signals to & from the existing NRPS facilities.
The new control system shall be Foundation Fieldbus Control System and IPS shall be
PLC based IPS. The F&G shall be part of Station IPS but will be physically and
electrically segregated from station IPS.
The new FCS, IPS and F&G shall be interfaced to the existing control system through FO
cable for control signals and safeguarding signals (including SIL-3 functions).
A new HMI shall be installed in the existing NRPS control. The ESD and MOS switches
shall be installed in the new console installed as part of NRPS Control System Upgrade
Project.
The SOE for the new facilities PAS shall be integrated into the existing SOE so as to
have a single SOE record for complete NRPS.
The existing OPC server shall be utilised for integrating the new facilities PAS with PDO
LAN . This shall be confirmed by PAS vendor. If found not possible additional OPC server
shall be provided by PAS vendor.
NIM48-102017-PX-5680-00002
Page 23 of43
Revisron 04
22-09- 2013
..,.
..: ..
PETROLEUM DEVELOPMENT OMAN
lAb.
G11far
GAlFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS llEU N IOAS
TR Engl.-nng U.C
TR ENGINEERING LLC
5.0
5.1
Page 24of 43
Revision 04
22-09- 2013
..,.
.,,
PETROLEUM DEVELOPMENT OMAN
lAb.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SADG
tij
TECNICAS REUNIDAS
TR Engineering LLC
TR ENGINEERING LLC
distribution is hydraulically balanced. There are no FCS controls provided on the gross
fluid line to the existing and new FWKO tanks.
5.2
5.2.1
Control Description
This section provides the functional description and the design intent of all the control
loops for NRPS (on-plot) facilities. Controls are further categorized equipment /system
wise for ease of understanding.
5.2.1.1
NIM-48-102017-PX-5680-00002
Page 25 of 43
Revision: 04
22-09-2013
..,.
..4,
lAb.
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Engl neorir>g LLC
TR ENGINEERING LLC
A fixed oil pan will draw-out the oil from FWKO tank (T-48350) to the suction header of
the emulsion pumps (P-48350/48351/48352/48353). 48LIC-3501 (Direct acting) will
maintain oil level in the tank by varying the speed of the emulsion transfer pumps
(P-48350/48351/48352/48353) , cascaded through the flow controllers. Flow element is
located on the discharge of each emulsion pumps. The level controller acts as master
controller and provides remote set point to flow controllers located on the each pump
discharge line. During normal operation, each flow controller set point (for the 3 pumps
operating scenario) is decided by the level controller (Master controller) based on
emulsion level in the tank. Flow controller of each pump (48FICA-3503/3504/3505/3506)
shall provide remote set point to the respective pump speed controllers {48SIC3508/3509/351 0/3511) which will vary the speed of the respective pumps and hence the
emulsion flow across pump to maintain (control) the emulsion level inside the tank. Flow
through each running pump is be totalized in 48FIQ-3507, providing the total emulsion
flow from the tank to dehydration system.
The level control range in the FWKO tank shall be from 7400 mm to 7900 mm referenced
from Tank BTL The set point of the level controller will be 7650 mm from tank BTL
FWKO tank (T-48350) level controller 48LICA-3501 is cascaded to the emulsion pump
discharge flow controllers provided via a manually set 'bias' control, similar to the existing
emulsion pump system. The 'bias' function will enhance flexibility to set uniform or
desired flow through each pump, to the downstream dehydration train. The 'Bias' values
shall be set during commissioning and will not be changed during normal operation.
Access to change of 'bias' values shall be provided to authorised personnel only.
When the emulsion level is increased the emulsion draw rate is increased by increasing
the speed of the emulsion transfer pumps through the respective flow I speed controllers.
When the emulsion level is decreased the emulsion draw rate is decreased by reducing
the speed of the emulsion transfer pumps through the respective flow I speed controllers.
The variable speed range of the emulsion pumps is from 400 to 960 rpm. The speed of
900 rpm is at the rated flow rate of 8500 m3/d.
An additional oil level transmitter (48LI-3500) is provided to measure the emulsion level in
the tank. 48Y-3500 compares level measured by both level transmitters (48LI-3500 and
48LICA-3501 ) and it gives deviation alarm 48LA-3504 if difference between both
readings is more than 400 mm. This indicates that operator action is required for the
re-calibration of the level instruments.
Level control : Water
48LIC-3503 is used to maintain and control the water-emulsion interface level in the
FWKO tank (T-48350).
NIM-48- t 02017 -PX-5680-00002
Page 26 of43
Revision: 04
22-09-2013
_______.lab.
Qllfar
PETROLEUM DEVELOPMENT OMAN
TECNICAS REUNIDAS
TR Engineering U.C
TR ENGINEERING LLC
NIM-48-1 02017-PX-5680-00002
Page 27 of 43
Revision 04
22-09-2013
~.........lAb.
Qllfar
TECNICAS REUNIDAS
TR Eng!noering LLC
TR ENGINEERING UC
In addition to the above control functions, local pressure gauges (48PG-3501), level
indicators (48LI-351 0/3511) are available for field monitoring.
Tank T -48350 is provided with two different type of level sensing instrument, Differential
Pressure (DP) and Admittance probe to measure the interface level. The operator selects
via a FCS manual select switch 48HS-3500 either of the two level transmitters for
interface level measurement and control. The switching between the two different types
of interface level measurement shall be done through manual transfer. The admittance
probe type of transmitter shall be used for daily control and production. The DP type shall
be used for the stock calculation in future.
5.2.1.2
Page 28 of43
Revision 04
22-09-2013
....
...
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS REUNIDAS
TR Engi,...,ring LLC
TR ENGINEERING LLC
There is no control on the on-line solid removal system fitted in the CPI separator. It is an
intermittent operation of removal of solids accumulated in the bottom of CPI separator.
The control philosophy of the online solid removal system is provided in an independent
Process control philosophy. (Ref: 6).
Level Control
48LIC-3542AJB is used to maintain and control the water level in the CPI Separators
48350/51/52/53/54).
0/-
The new CPI units will receive water from new FWKO tank. The individual CPI level
controllers (48LIA-3521/26/31/36/41) output signal will be averaged by a averaging
function block (48-Y-3508) for the CPI separators which are in operation. This averaged
level signal from the above averaging function block, shall be connected to two separate
level controllers 48LIC-3542A (Direct acting) and 48LIC-3542B (Reverse acting). The
"average level signal is used for level control, as this will give more time for the separator
to make up the level. Similar control philosophy is being used in the in the existing NRPS
CPI separators.
48LIC-3542A will have lower setting where as 48LIC-3542B will have a higher setting.
The set point of the LIC-3542A is preliminary set at 1300 mm from BTL and the same of
LIC-3542B is preliminary set at 1700 mm from BTL. The controller "A" will regulate the
control valve (48FCV-3520) on the common discharge header of water disposal booster
pumps and the controller B" will regulate control valve 48FCV-3502 through a low
selector 48Y-3502 on T-48350 water outlet line to going to new CPI train.
Similarly, produced water flow from FWKO tank to the existing CPI separators (48FCV3503) is controlled through a low selector 48Y-3511 function block, which compares the
signal input from level-flow cascade loop pertaining to the FWKO tank (T-48350) and the
existing CPI separators average level controller (48LIC-111) output signal.
A duty/stand by selector switch (48HS-3552/53/54/55/56) has been provided for each of
the CPI separator. The signal from individual CPI level indicator will be activated and will
be averaged once; the respective CPI separator's selector switch has been selected for
duty mode.
Low selector function block 48Y-3502 is provided for comparing flow controller 48FIC3502 output and CPI separators average level output (48LIC-3542B) and low selector
value will be used for regulating control valve 48FCV-3502 located on the FWKO tank
water outlet line going to new CPI separators.
When the average level of the new CPI increases above set point of 48LIC-3542 8 the
inlet flow rate of the water to new CPI separators is decreased by giving the net signal
Page 29 of 43
Revision 04
22-09-2013
.........~.Lt.l.:a.
Qllfar
TR ENGINEERING LLC
input to a low selector 48Y-3502, comparing the inputs from FWKO tank level-flow
cascading controller. When the average level of the new CPI decreases below set point
of 48LIC-3542 B the inlet flow rate of the water to new CPI Separators is increased by
giving the net signal input to a low selector 48Y-3502, comparing the inputs from FWKO
tank level-flow cascading controller. In case, at the same time, FWKO tank level
controller (48LICA-3503) or flow controller (48FIC-3502) operating above their respective
set points then low selector (48Y-3502) will not allow opening of control valve in order to
control the desired level / flow in the FWKO tank.
The FWKO tank volume (approx 14900 m3) is very high compared to the individual CPI
volume (approx 210 m3 } . Hence, the level in the FWKO tank does not vary much with
respect to the CPI level range. The change in new and the existing CPI level are very
much dynamic and in most times the low select on the 48FCV-3502 and 48FCV-3503 will
mostly be functional based on CPI separator average level controls when compared to
the level-flow cascade control of FWKO tank.
The control valve (48FCV-3503) on the water outlet line going to existing north CPI units
will be controlled by interface level (48LICA-3503) of new FWKO tank T-48350 and also
by level in the existing north CPI separators (48LIC-111 ). The FWKO tank interface level
control signal is cascaded to the flow controllers (48FIC-3503) located on the tank outlet
water line going to north CPI separators via a manually set 'bias' control. The bias
function is introduced to build in the flexibility for the operator to regulate the water flow
rates to each CPI banks based on availability of the downstream CPI separators and the
booster pumps. Low selector block 48Y-3511 is provided for comparing Flow controller
49FIC-3503 output and north CPI separators average level output (48LIC-111 ) and low
selector value will be used for regulating control valve 48FCV-3503 located on the FWKO
tank outlet water line going to north CPI separators.
Average level control of existing CPI separators also follows same philosophy as
described above for new CPI separator.
NIM-48-1 02017-PX-5680-00002
Page 30 of 43
Revision. 04
22-09-2013
..4.,
tij
lab.
Gtlfar
G.ALF.AR ENGINEERING &
CONTRACTING SAOG
TECNJCAS RflJNJOAS
"TR EngiiMerilliJ LLC
TR ENGINEERING LLC
which compares signal from the level controller 48LIC-3503 {on T-48350). Since, the
"reverse" flow happens when the FWKO tank T-48350 is under maintenance, the signal
from the T-48350 to low selector Y-3502 shall be overridden by selecting FIC-3502 in
manual selection mode, with 100% output so that the 48FCV-3502 receives signal only
from "average" level controller 48LIC-3542B. Also during this scenario, the 48FCV-3503
should be forced to open (100%) and 48-USV-3504 (on T -48350 produced water outlet
header) shall be closed (de-energized) using T-48350 shutdown signal, flow is routed
through FCV-3502. The other controls shall remain same. Refer to the Appendix - II:
Process Control Schematic (for Reverse flow operation) for more details.
Change-over from Reverse flow scenario to Normal flow scenario
During changeover from reverse flow scenario to normal flow scenario, the following
steps need to be carried out:
5.2.1.3
Flow controller 48FIC-3503 and flow control vatve 48FCV-3503 shall be switched
to normal operating mode, i.e. cascade control mode.
N IM-48-102017 -PX-5680-00002
Page 31 of43
Revision: 04
22..{)9-201 3
..,.
.:.
PETROLEUM DEVELOPMENT OMAN
lab.
Gllfar
GALFAR ENGINEERING &
CONTRACnNG SAOG
tij
TC~liCAS
REUNIOAS
TR Engineering LLC
TR ENGINEERING LLC
When the average level of the new CPI falls below set point of LIC-3542 A , the outlet
water flow rate from new CPI Separators is decreased by cascading through the flow
controllers 48FIC-3520 which will regulate the opening of FCV-3520.
NIM-48-1 02017-PX-5680-00002
Page 32 of43
Revision. 04
22-09-2013
..,.
....
PETROLEUM DEVELOPMENT OMAN
tij
lAb
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TR ENGINEERING LLC
A suction strainer is provided with differential pressure indicator (48PDIA3536f3538/3540) in FCS and suction I discharge pressure gauge (48PG3520/21/22/23/24/25) is available for field monitoring.
5.2.1.4
cwr
The suction strainer will be provided with differential pressure indicator (48PDIA3505/3510/3515/3524) in FCS and suction I discharge pressure gauge (48PG3503/04/05/06/07/08/09/1 0) shall be available for field monitoring, also FCS indication for
discharge (48PIA-3507/12/17/21) is available.
At each emulsion pump discharge total flow indication 48FIQ-3507 shall be provided in
FCS with high alarm.
5.2.2
5.2.2.1
);>
);>
FWKO Tank Emulsion level Control Loop cascaded with Flow control & Pump
speed control.
);>
FWKO Tank Water (Interface) Level Control Loop cascaded with Flow control &
CPI Separators level control.
);>
);>
NIM-48-102017-PX-5680-00002
Page 33of43
Revision 04
22-0~2013
_ . . . . . 1&6.
Glllfar
PETROLEUM DEVELOPMENT OMAN
TECNICAS llcUNIOAS
TR Engli'IIMiring lLC
TR ENGINEERING LLC
The blanket gas pressure is measured with 48-PI-3502. The 48-PICA-3502A and 8
controllers modulates the control valves 48-PCV-3502A and 8 respectively to maintain
the blanket gas pressure within the range of 0.5 kPa(g) to 1.0 kPa(g).
See the control overview diagram in Appendix I for an illustration.
Controller Design and Configuration:
Algorithm
48PIC-3502A&B shall be configured with PID control algorithm enabling PI settings.
Controller Action
48PIC-3502A is Reverse Acting controller and 48PIC-35028 is Direct Acting controller.
PV tracking
PV tracking shall be disabled to retain set point value during mode change.
Alarming
48PIA-3502 shall be configured with low and high alarms.
Calculations
None
Anti-Reset Wind Up Protection
Not applicable
Bump-less transfer
No explicit bumpless transfer block is needed.
Special considerations
None
Operational and Implementation Aspects:
Start-up: Both the controllers are kept in AUTO mode with a fixed set point during
start-up.
Cripple Mode of Operation: In case of input signal failure (bad process input or input
signal failure). the mode of the controller would be changed to manual and the output
set equal to 100%. When the input signal returns back to the healthy condition I the
fault is cleared, the controller shall be put back to AUTO mode by operator.
NIM-48-102017-PX-5680-00002
Page 34 of 43
Revision 04
22-09-2013
...
"'a9
tij
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TECNICAS RfUNIDAS
TR EngiMering LLC
TR ENGINEERING LLC
5.2.2.2
Shutdown: Both the controllers are kept in AUTO mode with a fixed set point during
shutdown.
Operator Interface: The controller is managed by means of its detailed PID action
group display. The operator access for auto/ manual mode change is available during
crippled mode of operation.
NIM-48-1 02017-PX-5680-00002
Page 35 of 43
Revision. 04
22-09-2013
_ _...lAb.
Gllfar
PETROLEUM DEVELOPMENT OMAN
TECNICAS REUNIDAS
TR Engineering LLC
TR ENGINEERING UC
Bumo=tess transfer
Applicable, for controller changeover from manual to auto mode.
Special considerations
None
Operational and Implementation Aspects:
5.2.2.3
Start-up: 48LIC-3501 initially in manual mode and then switched to automatic mode
and cascaded with 48FIC-3503/3504/3505/3506.
Cri pple Mode of Operation: In case of input signal failure (bad process input or input
signal failure) in any of the loops LIC or FtC then the controller output signal shall be
automatically frozen to the last value. When the input signal returns back to the
healthy condition I the fault is cleared , the controller shall put in AUTO mode by
operator, the changeover shall be bump less.
Shutdown: No special provisions are required for the LIC, but for the FlC switch the
controller mode to Manual and set the controller output to zero.
Operator Interface: The controller is managed by means of its detailed PID action
group display. The operator access for auto/ manual mode change is available during
crippled mode of operation.
History: Data archiving is incorporated in the DCS. In addition, 48-LIC3501 .PV, 48FIC3503/04/05/06.PV,
48-SIC3508/09/1 0/11 .PV,
48-LIC3501 .SP,
48FIC3503/04/05/06.SP,
48-SIC3508/09/10/11 .SP,
48-LIC3501-0P,
48FIC3503/04/05/06.0P, 48-SIC3508/09/10/ 11 .0P and 48-LIC3501 .MODE, 48FIC3503/04/05/06.MODE, 48-SIC3508/09/10/11 .MODE to be logged in the PI
Historian database for long-term data storage.
NI~8-102017~X-5680~002
Page 36 of 43
Revision: 04
22-09-2013
..,.
.:.
PETROLEUM DEVELOPMENT OMAN
tij
lAb.
Qllfar
G.A LFAR ENGINEERING &
CONTRACTING SAOG
TECNICAS REUNIDAS
TR Engineering UC
TR ENGINEERiNG LLC
for new CPI & 48Y-3511 for existing CPis}, which will compare the FWKO tank level-flow
cascade signal input with t he signal from the average level controller (48LIC-3542B &
48LIC-111 } of the new I existing CPI separators. The low signal selector output from t he
respective block regulates the flow rate through the control valves 48FCV-3502 and
48FCV-3503 respectively.
Controller Design and Configuration:
Algorithm
48LIC-3503 shall be configured with PID control algorithm enabling PI settings.
Controller Action
Direct Acting.
PV tracking
It is not enabled ; controller remains in auto mode and has a fixed level set point, to retain
set point value during mode change.
Alarm
The controller shall be configured with low and high alarms.
Calculations
Applicable, Manual bias provided to divert water to North-D or existing CPI separators.
Low selector is provided for FCV-3502 and FCV-3503.
Anti-Reset Wind Up Protection
During normal operation, the output of level controller LIC3503 is not selected by the low
selector, and anti reset windup protection needs to be configured for controller LIC3503.
The feedback for the anti-reset windup shall come from the valve position FCV3502/03.
In Foxboro, the anti-reset windup can be achieved by proper config uration of backcalculation originating from the valve.
Bumo=less transfer
Applicable, for controller changeover from manual to auto mode.
Special considerations
None
Operational and Implementation Aspects:
Page 37 of43
Revision 04
22-09-2013
......
~.
tij
Qllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TECNICAS REUNIOAS
T1'l Eni!IMering u.c
TR ENGINEERING LLC
Start-up: 48LIC-3503 in automatic mode and switch the 48FIC-3502 and 48FC-3503
from manual to Auto/cascade based on healthy condition of the FWKO tank.
Normal Operation: The FWKO tank interface level controller 48LJC-3503 shall be
cascaded to 48FIC-3502 and 48 FIC-3503.
Cripple Mode of Operation: In case of input signal failure (bad process input or input
signal failure) in any of the loops LIC or FIC then the controller output signal shall be
automatically frozen to the last value, the operation mode of the controllers shall be
changed to manual, upon automatic control resumption, the changeover shall be
bump less.
Shutdown: No special functional will be required for the LIC, but for the FIC, switch
the controller mode to Manual and set the controller output to zero.
Operator Interface: The controller is managed by means of its detailed PID action
group display. The operator access for auto/ manual mode change Is available during
crippled mode of operation.
History: The mode, set point, measurement, and output values of all controllers
LJC3503, FIC3502, FIC3503 shall be configured to be historized in the historian
database (PI). The output of the low selector Y3502 and Y3511 shall be historized as
well.
5.2.2.4
NIM-48-1 02017-PX-5680-00002
Page 38 of43
Revision. 04
22-09-2013
_ __..lAb.
Gllfar
PETROLEUM DEVELOPMENT OMAN
TECNICAS REUNIDAS
TR Engineering uc
TR ENGINEER.I NG LLC
Controller Action
48PIC-3540A is Reverse Acting controller and 48PIC-3540B is Direct Acting controller.
PV tracking
PV tracking shall be disabled to retain set paint value during made change.
Alarming
48PIA-3540 shall be configured with low and high alarms.
Calculations
None
Anti-Reset Wlnd Up Protection
Nat applicable
Bumo=less transfer
No explicit bumpless transfer block is needed.
Special considerations
None
Operational and Implementation Aspects:
Start-up: Both the controllers are kept in AUTO mode with a fixed set point during
start-up.
Cripple Mode of Operation: In case of input signal failure (bad process input or input
signal failure), the mode of the controller would be changed to manual and the output
set equal to 100%. When the input signal returns back to the healthy condition I the
fault is cleared, the controller shall be put back to AUTO mode by operator.
Shutdown: Both the controllers are kept in AUTO mode with a fixed set paint during
shutdown .
Operator Interface: The controller is managed by means of its detailed PID action
group display. The operator access for auto/ manual mode change is available during
crippled mode of operation.
NIM-48-10201 7-PX-5680-00002
Page 39 of 43
Revision 04
22-09-2013
~-
..: ..
Lib.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS ltEUN IDAS
TR E"glnoering LLC
TR ENGINEERING LLC
5.2.2.5
NIM-48-1 02017-PX-5680-00002
Page 40 of43
Revision: 04
22-09-2013
..,.
..:
...
tij
L;.6.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
TECNICAS RfiJNIDAS
lR Engi"""ng u..c
TR ENGINEERING LLC
Both level controller UC3542A and LIC3542B shall be configured to NOT allow Setpoint
to track measurement when switched to MAN. The flow controller FIC3520, however,
shall be configured to enable PV tracking to avoid bump during mode change.
Alarm
Both low and high alarms shall be configured on the average level (Y3506).
Calculations
The level measurement is taken as the average of all the CPI levels U3521 , Ll3526,
Ll3531, Ll3536, and U3541 . In case any of the inputs to the Average calculation goes
BAD, the average calculation continues with the remaining good inputs. Alarm shall be
issued for the BAD level measurement.
Anti-Reset Wind Up Protection
During normal operation, the output of level controller LIC3542B is not selected by the
low selector, and anti reset windup protection needs to be configured for controller
LIC3542B. The feedback for the anti-reset windup shall come from the valve position
FCV3502. In Foxboro, the anti-reset windup can be achieved by proper configuration of
back-calculation originating from the valve.
No explicit anti-reset windup configuration is needed for LIC3542A.
Bump Less transfer
No additional bumpless transfer block is needed.
Special considerations
None
Operational and Implementation Aspects:
Start-up: 48LIC-3542B in automatic mode and switch the 48FIC-3502 from manual
to Auto/cascade based on healthy condition of the CPI Separator.
48LIC-3542A in automatic mode and switch the 48FIC-3520 from manual to
Auto/cascade based on healthy condition of the CPI Separator & Disposal Water
Booster Pumps.
Nonnal Operation: Both level controller LIC3542A and LIC3542B shall be in AUTO
mode during normal operation. LIC3542A provides normal regulatory control on the
CPI level by manipulating the flow controller FIC3520. In case of plant upset, and the
CPIIevel rises above the high limit set by LIC3542B set point, the protective controller
LIC3542B may override the CPI inlet flow controller FIC3502 via the low selector
Y3502, and reduces the inlet flow to bring the CPI level back to normal range.
NIM-48 102017-PX-5680-00002
Page 41 of 43
Revis1on . 04
22-09-2013
~~,
lAb.
Gllfar
GALFAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS RfUNfOAS
TR Engineering LLC
TR ENGINEERING LLC
Cripple Mode of Operation: In case of input signal failure (bad PV value or input
card failure) in any of the loops LIC or FIC then the controller output signal shall be
automatically frozen to the last value, the operation mode of the controllers shall be
changed to manual, When the input signal returns back to the healthy condition I the
fault is cleared the controller shall be put back to AUTO mode by operator.
Shutdown: No special provisions are required for the LIC, but for the FtC, switch the
controller mode to Manual and set the controller output to zero.
Operator lnterfac.e: The controller is managed by means of its detailed PID action
group display. The operator access for auto/ manual and cascade mode change is
available during crippled mode of operation.
History: The mode, set point, measurement, and output values of all controllers
LIC3542A, LIC35428, FIC3520 shall be configured to be historized in the historian
database (PI}. The output of the low selector Y3502 shall be historized as well.
Special Consideration: Not applicable
NIM-48-102017-PX-5680-00002
Page42 of 43
Revision 04
22-09-2013
..,,
..,,
PETROLEUM DEVELOPMENT OMAN
lAb..
Gfllfar
GAL.FAR ENGINEERING &
CONTRACTING SAOG
tij
TECNICAS RSJNIOAS
TR Engir>Mring UC
TR ENGINEERING L.L.C
6.0
REFERENCES
Docum ents
1. Project Design Basis- Nimr-G (NIM-48-102017-AA-n04-00001-0000).
2. Control and Automation Philosophy (NIM-48-102017-IN-5505-00001-0000)
3. FEED Process Control Narrative (NIM-370-PX-5680-00001-0001 Rev A01)
4. Operating Philosophy for CPI Separators Package (NIM-48-104473-0A-5522-000010001)
5. H2S Management Procedure (PR-1 078)
6. Operating & Control Philosophy- Solid Handling System (NIM-48-104473-0A-552200001-0003)
7 . Narrative Writing Guideline, OG 00.20489, Version 2.0.
NIM-48-1 02017-PX-5680-00002
Page 43 of 43
Revision: 04
22-W-2013
lAb.
Qllfar
-b1
n<:NICA5 REUNIDAS
TR Engin.....tng U..C
TR ENGINEERING LLC
APPENDIX I
PROCESS CONTROL SCHEMATIC
NIM-48-1 02017-PX-5680-00002-0000
Append1x r
Rev1saon 04
22-09-2013
____.,1_"_,_,_
Gllfar
PETROLEUM DEVELOPMENT OMAN
TECNICAS IIEUNIDAS
TR Engl-ng LLC
TR ENGINEERING LLC
APPENDIX II
PROCESSCONTROLSCHEMATIC (REVERSEFLOVij
NIM-43-102017-PX-5680-00002
Appendoc- II
Revtslon 04
22-09-2013
._._..
'I
....._
.. .,.. i
'
Tank 17
'
Bank8
-------
..... ....
_.
'I'
'
Tank 18
LtUII
I
I
: ------- -----l
'
I
I
I
I
I
--r-.
I
I
'
:
l :
Tank 19
BankC
- -,
$----w-----rL~ :I~
FEED FROW
GRQSS FWID
INLET HEADER
T-48350
FWKOTANK
1........._
~ - ..u
_..J
:
I
"=
i - - -- ----------- - ---
____ _ _ _ _ _ _ _ _ __ _ _JI
~~~.....
-~ KUrJ
,.J
- - ~1.1!SE
now
WATER DISPOSAl
BOOSTER PUMP
(P-48354/55/56)
_j
NIMR G
c--------------------------1I
EWl.t.SK>
~~
~~;!_'!!(~ ~~~
I
r--- -~---(TYPICAI.)
I
L
~~--------~----------------------------------------~--------------~__.TOHEATEX~AN~S
TRAINS
FEED FROM
GROSS FLUIO~IN~LET~H'""E""'AD
"""ER=--,---.1
I
r--""~--~
~
~-1
I
I
I
I
I
I
I
I
L_
--~
P-48350/51/52/53
L _ -+--9:-----.~
(OAA.SJaN
!RNISF[A
PUIM'S)
T-48350
FWKO TANK
ro~
RARE .------------------------,
BlANKET CAS - - - - - - - - -
r-----------
I
I
I
I
I
-----,
I
I
~~
r -----~
A~9--w-~
~!'Cl
l----L..!!ULJ-~
(llPICAL.)
~-------------------,
I
I
I
(V-48350/51 I
52/53/54-)
NEW CPI
SEPARATORS
(4W+1S)
(BANK D)
I
I
FCV 3509
(nPicAl)
PU~P ~NlMU~
- ----,
I
~.Q-
I
I
~~
WATER RING
HEADER
WATER DISPOSAL
BOOSTER PUMP
I
I
I
I
I
I
I
I
I
I
IL __________ _____________ IL __________ _
( lli'ICAI.)
FLOW