UNIT 3
HVDC Converter
Unit-03/Lecture-01
Components of EHV D.C. System
Components of EHV D.C. System [RGPV/ Dec 2008/ 7]

The conversion from AC to DC and vice versa is done in HVDC converter stations by using
three phase bridge converters. A converter has two types of circuits:
1. Main Circuits through which high power flows. The main circuit comprises of converter
transformers, thyristor valves, bus bar, series reactor etc.
2. Control and Protection circuit for firing or blocking the valve in desired sequence,
monitoring, etc.
The main circuit of converters in HVDC terminal stations are made-up of series connected
thyristor valves. The converter valves are connected between converter transformer and
DC switchyard. Each thyristor valve is made up of several thyristor connected in series.
Individual thyristor rating is about 1.5 kV, 600 to 4000 A. The configuration of rectifier and
inverter is identical.
The triggering pulse to thyristor gates are delayed by angle called the delay angle, w.r.t.
the instant of natural commutation i.e. the instant when the phase voltage across
subsequently conducting valve exceeds that across the preceding value. The delay angle is
varied by means of control circuit which gives the triggering pulse to the gates of the
thyristor in each arm of the bridge in a definite sequence. With delay angle less than 90 o,
the converter acts in the rectifier mode and with delay angle between 90o and 180o the
converter works as a inverter.

Figure 1 HVDC System Connecting two AC systems


S.NO
RGPV QUESTIONS
Q.1 Draw a schematic diagram of HVDC System
identifying its main components. Explain about
each components.

Year
Dec 2008

Marks
20

UNIT 3/ LECTURE 02
Rectifier used in HVDC System
Three Phase Fully Controlled Rectifier in HVDC System [RGPV/ Dec 2008, Dec 2007/ 10]
The three phase fully controlled bridge converter has been probably the most widely used
power electronic converter in the medium to high power applications. Three phase circuits are
preferable when large power is involved. The controlled rectifier can provide controllable
output dc voltage in a single unit instead of a three phase autotransformer and a diode bridge
rectifier. The controlled rectifier is obtained by replacing the diodes of the uncontrolled rectifier
with thyristors. Control over the output dc voltage is obtained by controlling the conduction
interval of each thyristor. This method is known as phase control and converters are also called
phase controlled converters. Since thyristors can block voltage in both directions it is possible
to reverse the polarity of the output dc voltage and hence feed power back to the ac supply
from the dc side. Under such condition the converter is said to be operating in the inverting
mode. The thyristors in the converter circuit are commutated with the help of the supply
voltage in the rectifying mode of operation and are known as Line commutated converter. The
same circuit while operating in the inverter mode requires load side counter emf. For
commutation and are referred to as the Load commutated inverter.
In phase controlled rectifiers though the output voltage can be varied continuously the load
harmonic voltage increases considerably as the average value goes down. Of course the
magnitude of harmonic voltage is lower in three phase converter compared to the single phase
circuit. Since the frequency of the harmonic voltage is higher smaller load inductance leads to
continuous conduction. Input current wave shape become rectangular and contain 5th and
higher order odd harmonics. The displacement angle of the input current increases with firing
angle. The frequency of the harmonic voltage and current can be increased by increasing the
pulse number of the converter which can be achieved by series and parallel connection of basic
6 pulse converters. The control circuit become considerably complicated and the use of coupling
transformer and / or interphase reactors become mandatory.
With the introduction of high power IGBTs the three phase bridge converter has all but been
replaced by dc link voltage source converters in the medium to moderately high power range.
However in very high power application (such as HV dc transmission system, cycloconverter
drives, load commutated inverter synchronous motor drives, static scherbius drives etc.) the

basic B phase bridge converter block is still used.


Operating principle of 3 phase fully controlled bridge converter
A three phase fully controlled converter is obtained by replacing all the six diodes of an
uncontrolled converter by six thyristors as shown in Fig. 15

Figure 14

For any current to flow in the load at least one device from the top group (T1, T3, T5) and one
from the bottom group (T2, T4, T6) must conduct. It can be argued as in the case of an
uncontrolled converter only one device from these two groups will conduct.
Then from symmetry consideration it can be argued that each thyristor conducts for 120 of the
input cycle. Now the thyristors are fired in the sequence T1 T2 T3 T4 T5 T6 T1
with 60 interval between each firing. Therefore thyristors on the same phase leg are fired at an
interval of 180 and hence cannot conduct simultaneously. This leaves only six possible
conduction mode for the converter in the continuous conduction mode of operation. These are
T1T2, T2T3, T3T4, T4T5, T5T6, T6T1. Each conduction mode is of 60 duration and appears in the
sequence mentioned. The conduction table of Fig. 15 (b) shows voltage across different devices
and the dc output voltage for each conduction interval. The phasor diagram of the line voltages
appear in Fig. 15 (c). Each of these line voltages can be associated with the firing of a thyristor
with the help of the conduction table-1. For example the thyristor T1 is fired at the end of T5T6
conduction interval. During this period the voltage across T1 was vac. Therefore T1 is fired
angle after the positive going zero crossing of vac. Similar observation can be made about other
thyristors. The phasor diagram of Fig. 15 (c) also confirms that all the thyristors are fired in the
correct sequence with 60 interval between each firing.
Fig. 16 shows the waveforms of different variables (shown in Fig. 15 (a)). To arrive at the
waveforms it is necessary to draw the conduction diagram which shows the interval of
conduction for each thyristor and can be drawn with the help of the phasor diagram of fig. 15
(c). If the converter firing angle is each thyristor is fired angle after the positive going zero
crossing of the line voltage with which its firing is associated. Once the conduction diagram is
drawn all other voltage waveforms can be drawn from the line voltage waveforms and from the
conduction table of fig. 15 (b). Similarly line currents can be drawn from the output current and
the conduction diagram. It is clear from the waveforms that output voltage and current
waveforms are periodic over one sixth of the input cycle. Therefore this converter is also called
the six pulse converter. The input current on the other hand contains only odds harmonics of
the input frequency other than the triplex (3rd, 9th etc.) harmonics. The next section will
analyze the operation of this converter in more details.

Analysis of the converter in the rectifier mode

The input phase current i is expressed as


a

From Fig. 16 it can be observed that i itself has a ripple at a frequency six times the input
0

frequency. The closed from expression of i , as will be seen later is somewhat complicated.
0

However, considerable simplification in the expression of i can be obtained if i is replaced by its


a

average value I . This approximation will be valid provided the ripple on i is small, i.e, the load is
0

highly inductive. The modified input current waveform will then be i which can be expressed in
a

terms of a fourier series as

in particular i = fundamental component of i


a1

From figure 16

Since displacement factor = displacement factor = cos


Distortion factor

Power factor = Displacement factor Distortion factor = 3cos (13.16)


The closed form expression for i in the interval
0

in this interval

can be found as follows:

Since i is periodic over /3


0

To find out the condition for continuous conduction it is noted that in the limiting case of
continuous conduction.

then i is minimum at t = . Condition for continuous conduction is 0t=i. However


0

discontinuous conduction is rare in these conversions and will not be discussed any further.

S.NO
Q.1
Q.2

RGPV QUESTIONS
Year
Justify the suitability of 3-phase full bridge converter for Dec 2008
HVDC application.
Explain with current and voltage waveforms and deduce Dec 2007
relationship for output voltage and current considering
the commutation angle.

Marks
10
10

10

UNIT 3/ LECTURE 03
Inverter used in HVDC System
Analysis of the converter in the inverting mode.
In all the analysis presented so far it has been assumed that < 90. It follows from equation 16
that the output dc voltage will be positive in this case and power will be flowing from the three
phase ac side to the dc side. This is the rectifier mode of operation of the converter. However if
is made larger than 90 the direction of power flow through the converter will reverse
provided there exists a power source in the dc side of suitable polarity. The converter in that
case is said to be operating in the inverter mode. It has been explained in connection with single
phase converters that the polarity of EMF source on the dc side [Fig. 15(a)] would have to be
reversed for inverter mode of operator. Fig. 17 shows the circuit connection and wave forms in
the inverting mode of operation where the load current has been assumed to be continuous
and ripple free.

11

Analysis of the converter in the inverting mode is similar to its rectifier mode of operation. The
same expressions hold for the dc and harmonic compounds in the output voltage and current.
The input supply current Fourier series is also identical to Equation 13.8. In particular

For values of in the range 90 < < 180 it is observed from Fig. 13.3(b) that the average dc
voltage is negative and the displacement angle of the fundamental component of the input ac
line current is equal to > 90. Therefore, power in the ac side flows from the converter to the
source.
It is observed form Fig. 13.3(b) that an outgoing thyristor (thyristor T6 in Fig. 13.3(b)) after
commutation is impressed with a negative voltage of duration = . For successful
commutation of the outgoing thyristor it is essential that this interval is larger than the turn off

12

time of the thyristor i.e,


tq, tq is the thyristor turn off time
Therefore - tq or -tq.
This imposes an upper limit on the value of . In practice this upper value of is further
reduced due to commutation overlap.

13

UNIT 3/ LECTURE 04
Harmonics Generation in the Converter
Harmonic Generation in the Converter [RGPV/ Dec 2007, Dec 2008/10]
There are different types of loads that generate harmonics in power systems.
The linear time-invariant loads are designed such a way so that the sinusoidal voltage
results in a sinusoidal flow of current. These loads have constant steady-state impedances
during the applied sinusoidal voltage. When the voltage is increased, the current increases in
direct proportion. The transformers and rotation machines are the examples of this kind of
loads when operated in normal condition.
In nonlinear load, the applied sinusoidal voltage does not result in a sinusoidal flow of
current. These loads are not constant impedances during the entire cycle of the applied
sinusoidal voltage. For example, wind and solar power generation, switching mode power
supplies, computers, copy machines and television sets.
In utility distribution feeders and industrial plant power systems, the main tendency is
for the harmonic currents to flow from the harmonic producing load to the power system
source. This is shown in Figure 17. The impedance of the power system is normally the lowest
impedance seen by the harmonic currents. That means the bulk of the current flows in to the
source. The source of harmonics can be located by using this general tendency of the harmonic
current flow. The power quality meters can be used to measure the harmonic currents in each
branch starting at the beginning of the circuit and trace the harmonics to the source.

14

Figure 17 General flow of harmonic currents in a power system


The power factor correction capacitors can alter this flow pattern. For example, adding
a capacitor to this circuit as shown in the following circuit may draw a large amount of harmonic
current into that portion of the circuit as shown in figure 18.

Figure 17 Power factor capacitors can alter the direction of flow of the harmonic component
of the current.
S.NO
RGPV QUESTIONS
Q.1 What are the causes of harmonics in HVDC
system.
Q.2 Write a short note on Causes of harmonics in
HVDC Converter.

Year
Dec 2007

Marks
10

Dev 2008

05

15

UNIT 3/ LECTURE 05
Adverse Effect of Harmonics in the Converter
Effect of Harmonics [RGPV/ June 2008, June 2010, Dec 2010, June 2007, Dec 2009/ 10]
Harmonics practically effect to every equipment in the power system. The effect of voltage
distortion is divided in three major categories, the thermal stress, the dielectric stress and load
disruptions.
Heating effects: Harmonic current flowing in the circuits cause heating effects in the
conductors. Especially eddy current losses are proportional to the square of the frequency.
Some harmonics, notably the 5th, are negative sequence or backward rotating and tease can
increase losses by inducing even higher frequency currents in machine rotors.
Interference: Harmonics can cause interference to communications systems, protections
systems and signaling circuits due to electromagnetic induction or to the flow of the ground
currents.
Resonance: Harmonics generated in one part of circuit may increase the resonance effects in
another part of the circuit. Some resonance can be dangerous if the magnification is large
because of high circuit Q-factor or low damping.
Even harmonics: Even harmonics may cause asymmetrical magnification and can lead to
saturation.
Some more adverse effects of harmonics listed as follows:
- Malfunction in electronics devices and computer equipments
- Errors in measurements
- Overheating and over stressing of insulations
- Lamp flicker when harmonic pulses involved.
- Sometimes machine vibrates

16

- Blowing out of small auxiliary devices like fluorescent lamp capacitors.


Harmonics Analysis
The first step in solving harmonic related problem is to perform an analysis to determine
the specific needs of power system. The analysis then applied to study of resonant conditions
and harmonic filter design. The in-depth study is involved because of the interaction between
harmonics producing source and power system, the limitations of modeling equipments in the
power system and need to check for the accuracy.

S.NO
RGPV QUESTIONS
Q.1 Discuss the problems associated with the
harmonics introduced by the HVDC Converters.
Q.2

Write a short note on Adverse affects of


harmonics in HVDC System.`

Year
June 2008
June 2010
Dec 2010
June 2007
Dec 2009

Marks
10

10

17

UNIT 3/ LECTURE 06
Harmonics Mitigation and Filters

Harmonics Mitigation and Filters [RGPV / Dec 2010, Dec 2009, Dec 2007, June 2010, Dec
2004/ 10]
The harmonics is becoming a bigger concern now a day with the increase nonlinear load
in the power system. There are multiple ways to control the harmonics as follow:
- Find the nonlinear load and reduce the harmonic current
- Add filter to remove the harmonic current or block the harmonic current from

entering

to the system
- Modify the system frequency response to avoid harmful interaction with harmonic current.
Passive filters
Nonlinear load produces harmonic currents that can travel to other part of the power
systems and eventually goes back to the source. As we review that harmonics current can
damage power systems many ways. One of the ways to block this unwanted characteristic of
the system is to block it by using filters.
There are two types of filters, active and passive filter. The interest of this project is to
design a single tuned notch filter since it is sufficient for the application and importantly it is
inexpensive. Figure 19 shows configuration of the filter, equivalent circuit of the filter and the
frequency response of the filter. This filter has two advantages, it suppresses the harmonics and
increases power factor. This filter is tuned slightly lower than the harmonic to be filtered to
provide a safely margin in case there is some change in the system parameters that may raise
the notch frequency.

18

Figure 19 Creating a fifth-harmonic notch filter and its affect on the system response
S.NO
RGPV QUESTIONS
Q.1 Write a short note on tuned power filter.
Q.2 Explain different types of AC filters giving their
configuration and impedance characteristics.
Q.3 Explain the remedial measures of harmonics.
Q.4 Explain DC filters, mentioning the criteria by
which the effectiveness of the DC filters can be
judged.

Year
Dec 2004
June 2010

Marks
10
10

Dec 2010
Dec 2007
Dec 2009

10
10

19

UNIT 3/ LECTURE 07
HVDC Characteristics
HVDC Characteristics.
An important factor when considering multiple inverters operating into a common AC system is
the static characteristics of each inverter. These characteristics (normally plotted as DC current
Versus DC voltage) represent the converters dynamic response to transient behaviour in the AC
system. They can be considered as the cerebral cortex of the HVDC controller as, in the same
way as if you touch something hot you will undoubtedly move your hand rapidly without higher
brain functions being involved, the HVDC converter static characteristics define the way in
which the converter will respond without involving higher level control functions.
The selection of static characteristics will influence, to some extent, the susceptibility of a HVDC
converter to a commutation failure. As an example, the static characteristics can be configured
to maintain the DC voltage at a constant value for small reductions in the AC system voltage, As
shown in Figure 20. This will help to mitigate the increase in DC current flowing from the stored
energy of the DC conductor into the inverter as a consequence of an AC system dip. However,
when considering multiinfeed HVDC converters the static characteristics can have a significant
impact on the converters ability following a commutation failure.

20

Vd

Rectifier

Inverter

Id

Constant DC
Voltage

FIGURE 20 Static Characteristics of a HVDC scheme including a constant DC voltage operating


range
Consider only one inverter feeding into an AC system. The speed of recovery of the inverter
following a commutation failure can be optimised against the inertia and performance of the AC
system synchronous machines in order to optimise the system stability. However, when two or
more inverters are attempting to recover into the same AC system they can interact such that
subsequent commutation failures on one or more of the inverters is invoked; potentially leading
to an instability in the AC power system. It may, therefore, be more appropriate to actually slow
down the recovery of one converter with respect to another so that the total power flow into
the receiving AC system is achieved more stably and hence quicker. Figure 21 shows two
different scheme static characteristics.
From Figure 21 it can be seen that in Scheme 1 Area A is much smaller than Area B of Scheme 2,
hence the recovery charging current and the speed in which the converter angles respond will
be different so, for physically identical schemes, Scheme 2 will recover faster than Scheme 1.
Moreover, in Figure 2 an approximate constant reactive power absorption (constant Q) line is
plotted. It can be seen that for Scheme 1 the recovery characteristic takes the converter
operating point to the right of the constant Q line and hence the converter will absorb more
reactive power during recovery, leading to an AC voltage dip which could cause a commutation

21

failure in neighbouring inverters. Now consider Scheme 2; its recovery characteristic passes to
the left of the constant Q curve and hence will always absorb less reactive power during
recovery, consequently leading to an AC overvoltage and therefore less likely to initiate a
commutation failure in nearby inverters.

Scheme 2

Scheme 1
Vd

Vd

Rectifier

Rectifier
Constant Q

Constant Q
Inverter

Area A

Inverter

Area B

Id

Id

FIGURE 21 Static Characteristics of two HVDC schemes which will have different recovery
times and different reactive power absorption from the AC system during recovery

Whilst it may not be practical to have all HVDC schemes causing an AC system overvoltage
following an AC system disturbance which resulted in a commutation failure there maybe some
system benefits to having a combination of different characteristics in a multi in feed system. It
is therefore suggested that, whenever possible, the static characteristics of any existing HVDC
schemes are established and modelled as accurately as possible in order to obtain the most
realistic representation of the expected dynamic behaviour of the HVDC schemes.