Basic Guidelines
1. Select a louver design that
will safely separate the
discharge from the intake
air stream to ensure that air
recirculation will not occur.
2. The intake louver should be
designed to minimize and
virtually eliminate water
penetration at a reasonable
face area velocity (fpm).
3. The discharge duct must
be as short and straight as
possible but of sufficient
length to guarantee uniform
airflow distribution though
the louver for maximum
velocity.
4. In most cases, the crosssectional free area of
Regardless if it is a vertical or
horizontal unit, it is critical that
the two air streams be directed
in different directions so that no
recirculation of discharge air
is allowed to enter the inlet air
stream. In some cases it may be
necessary to provide a deflector
vane or separator between the
two air streams. We recommend a
field fabricated air deflector for the
C-Series similar to the one included
with our Outdoor Modification kit
in the figure below. If recirculation
of the discharge air does occur,
the unit will likely trip on high head
pressure and continue to trip until
the louver design is corrected.
Horizontal Deflector
General Ductwork
Recommendations
All ductwork must be designed
in accordance with industry
accepted practices. Consult
ASHRAE, AMCA or SMACNA
guidelines or standards for details.
Ducts should be insulated in
accordance with ASHRAE Standard
90.1 or per local codes, particularly
if the unit will be operated during
cold weather. We recommend
utilizing a suitable flexible duct
connector to minimize or isolate
any vibration transmission to the
structure. The condensing unit
intake duct should include a
provision to access the inlet side
of the coil for periodic cleaning. It
is also best to design for sufficient
clearances for servicing the blower
motors, expansion valves, filters,
and any options installed.
Length of Ductwork for Discharge
Air
The VertiCool and C-Series units
should be located a minimum
distance from the louvered wall to
maximize efficiency of the blower.
Discharge
Louver
Height in
Inches Louver Width in Inches
12 18 24 30 36 42 48 54 60
12 0.22 0.36 0.51 0.65 0.80 0.90 1.05 1.19 1.33
18 0.52 0.85 1.20 1.55 1.89 2.14 2.48 2.82 3.15
24 0.84 1.38 1.92 2.45 3.00 3.41 3.95 4.49 5.03
30 1.15 1.90 2.55 3.40 4.15 4.71 5.46 6.20 6.95
36 1.47 2.43 3.38 4.34 5.29 6.01 6.95 7.91 8.86
42 1.77 2.92 4.07 5.22 6.37 7.23 8.38 9.53 10.68
48 2.08 3.42 4.76 6.11 7.46 8.46 9.81 11.16 12.50
54 2.38 3.92 5.45 7.00 8.54 9.70 11.24 12.78 14.33
60 2.58 4.42 6.15 7.89 9.63 10.93 12.57 14.41 16.15
66 2.98 4.91 6.85 8.78 10.72 12.16 14.10 15.03 17.96
72 3.28 5.41 7.54 9.57 11.80 13.40 15.53 17.56 19.79
78 3.59 5.91 8.24 10.55 12.89 14.53 16.96 19.28 21.51
84 3.89 6.41 8.93 11.45 13.97 15.86 18.39 20.91 23.43
90 4.19 6.91 9.53 12.34 15.05 17.10 19.82 22.53 25.25
96 4.49 7.41 10.33 13.24 16.16 18.34 21.26 24.17 27.09
102 4.81 7.93 11.05 14.17 17.30 19.54 22.76 25.58 29.00
108 5.13 8.46 11.78 15.11 18.44 20.93 24.26 27.59 30.91
114 5.44 8.96 12.50 15.02 19.55 22.20 25.72 29.25 32.78
120 5.74 9.46 13.19 15.91 20.54 23.43 27.15 30.88 34.50
References
It is extremely important to
select a louver that separates
the direction of the discharge
air stream from the intake air
stream to avoid short-circuiting
of the air and promote optimum
unit performance. Free area,
water penetration rating, and
pressure drop are all criteria
used to select intake and
discharge louvers for VertiCool
and C-Series applications. Intake
louvers should be sized so that
water penetration is virtually
eliminated and located an
appropriate distance away from
discharge and contaminated air.
Discharge ducts should provide
sufficient straight length of duct
to ensure maximum velocity
through the louver with minimum
obstructions.
As with all
installations, we
recommend documenting
unit performance at
start-up.