Altistart 01
The starting solution...
Catalogue
February
04
General contents
Soft starters
for asynchronous motors
1 Altistart 01
2 Altistart U01
3 Services
1/0
Contents
1/1
Soft starters
for asynchronous motors
Presentation
563783
Altistart 01
Presentation
The Altistart 01 soft starter operates either as a torque limiter on starting or as a soft
start/soft stop unit for asynchronous motors.
1
2
DF563892
4
5
6
7
8
Description
b Altistart 01 soft starters (ATS 01N1ppp) are equipped with:
v a potentiometer 1 for controlling the starting time
v a potentiometer 2 for adjusting the start voltage threshold according to the motor
load
v 2 inputs 3:
- 1 z 24 V input or 1 a 110240 V input for powering the control part that
controls the motor
b Altistart 01 soft start/soft stop units (ATS 01N2ppp) are equipped with:
v a potentiometer 6 for controlling the starting time
v a potentiometer 8 for controlling the deceleration time
v a potentiometer 7 for adjusting the start voltage threshold according to the motor
load
v 1 green indicator LED 4: device switched on
v 1 yellow indicator LED 5: motor powered at nominal voltage
v a connector 9:
- 2 logic inputs for Run/Stop commands
- 1 logic input for the BOOST function
- 1 logic output to indicate the end of starting
- 1 relay output to indicate the starter has a power supply fault or the motor has
reached a standstill at the end of the deceleration stage.
Characteristics:
pages 1/4 and 1/5
1/2
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
Soft starters
for asynchronous motors
Presentation (continued)
Altistart 01
Functions
Description (continued)
Equivalence table for contact reference
Functions
Relay outputs
ATS 01N2ppLU/QN/RT
R1A
R1C
0 V external power supply C0M
Stop command
LI1
Run command
LI2
Control power supply
LI + (+ 24 V positive
logic)
BOOST
BOOST
End of starting
LO1
115 V external power
supply
ATS 01N2ppLY
04
05
02
03
01 (0 V negative
logic)
06
07
ATS 01N2ppQ
04
05
02
03
01 (0 V negative
logic)
Functions
b 2-wire control:
The run and stop commands are controlled by a single logic input. State 1 of logic
input LI2 controls the run process and state 0 controls the stop process.
ATS 01N2ppLU/QN/RT
ATS 01N2ppLY/Q
LI +
LI1
LI2
01
02
03
b 3-wire control:
The run and stop commands are controlled by 2 different logic inputs.
Stopping is achieved when logic input LI1 opens (state 0).
The pulse on input LI2 is stored until input LI1 opens.
Altistart 01 control terminals
LI +
LI1
LI2
01
02
03
b Starting time
Controlling the starting time means that the time of the voltage ramp applied to the
motor can be adjusted and a gradual starting time achieved, which is dependent on
the motor load.
U
100 %
Un
Voltage ramp
50 %
Un
initial voltage
t
200 ms
Application of a voltage BOOST equal to 100% of the nominal
motor voltage
b End of starting
v Application function via logic output LO1
Soft start/soft stop units ATS 01N206pp to ATS 01N232pp are equipped with an
open collector logic output LO, which indicates the end of starting when the motor
has reached nominal speed.
v Application function via an option
For ATS01N2ppLY/Q soft start/soft stop units end of starting information can be
obtained by adding the option LAD 8N11 with N/O+N/C contacts.
The option can be easily connected to the bypass contactor of the electronic(s) unit
without dismantling the product.
b Fault relay
Soft start/soft stop units ATS 01N206pp to ATS 01N232pp have a relay which opens
when a fault is detected.
Relay contact R1A-R1C (04-05 for ATS 01N2ppLY/Q) closes with the LI2 command
(02-03 for ATS 01N2ppLY/Q) and opens when the motor voltage is around 0 with a
decelerated stop or stop immediately on a fault.
This information can be used for controlling the line contactor and achieving
deceleration (by maintaining the line contactor until the motor has stopped).
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
1/3
Soft starters
for asynchronous motors
Characteristics
Altistart 01
Environment
Type of starter
Conformity to standards
Product certification
Degree of protection
Degree of pollution
Vibration resistance
Shock resistance
Relative humidity
Ambient air
temperature around
the device
Storage
Operation
IEC 61000-4-11
IEC 61000-4-12 level 3
The starters bear e marking in accordance with the European low voltage directives
IEC/EN 60947-4-2
UL, CSA and C-Tick
B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
IP 20
IP 20 on front panel
2 conforming to IEC/EN 60947-4-2
3 conforming to IEC 60664-1 and UL 508
1.5 mm peak to peak from 3 to 13 Hz,
2 gn
1 gn from 13 to 150 Hz conforming to
IEC/EN 60068-2-6
15 gn for 11 ms conforming to
8 gn for 11 ms conforming to
IEC/EN 60068-2-27
IEC/EN 60068-2-27
5...95% without condensation or dripping water, conforming to IEC/EN 60068-2-3
- 25+ 70 conforming to
- 25+ 70 conforming to
IEC/EN 60947-4-2
IEC/EN 60947-4-2
- 10+ 40 without derating,
0+ 55
up to 50C with current derating of 2% per
C above 40C
1000 without derating (above this, derate 2000 without derating (above this, derate
the current by 2.2% per additional 100 m) the current by 0.5% per additional 100 m)
Operating position
Maximum permanent angle in relation to the normal vertical
mounting position
10
10
Electrical characteristics
Type of starter
Category of use
Rated operating voltage
ATS
Conforming to IEC 60947-4-2
V
Three-phase voltage
Frequency
Output voltage
Control power supply voltage
Hz
A
s
s
%
Type of starter
Use
I
ATS
Starting time
Maximum number of cycles per
hour
Starting time
01N1ppFT
01N2ppLU 01N2ppQN 01N2ppRT 01N2ppLY 01N2ppQ
Ac-53b
200 - 15% to 200 - 15% to 380 - 15% to 440 - 15% to 230 - 15% to 400
480 + 10%
240 + 10%
415 + 10%
480 + 10%
690 + 10% -15+ 10%
50 - 5% to 60 + 5%
Maximum 3-phase voltage equal to line supply voltage.
a 110...220 Built into the starter
a 110
Built into the
10%
10%
starter
z 24 10%
3...12
6...32
32...85
1...5
1...10
1...25
1...10
1...25
30...80% of starting torque of motor connected directly on the line supply
01N206pp to 01N222pp
01N232pp
1
310
1
180
5
20
t
Operating cycle
Presentation:
pages 1/2 and 1/3
1/4
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
01N2ppLY/01N2ppQ
5
10
1
360
12
30
Soft starters
for asynchronous motors
Characteristics (continued)
Altistart 01
ATS 01N1
03FT
06FT
09FT/12FT
z 24 V, 25 mA,
z 24 V, 30 mA,
a 110 V, 30 mA
a 110 V, 35 mA,
a 240 V, 65 mA
a 240 V, 80 mA
Power dissipated
At full load at end of starting
W
4
1
1
1
In transient state
W
19
31
46
61
A
15
30
45
60
Starting current at nominal load (1)
Type of starter
ATS 01N2
06LU/QN/RT
09LU/QN/RT
12LU/QN/RT
22LU/QN/RT
32LU/QN/RT
Power dissipated
At full load at end of starting
W
4
4
4
4.5
4.5
W
64
94
124
224.5
324.5
In transient state
Starting current at nominal load (1)
A
30
45
60
110
160
Type of starter
ATS 01N2
30LY/Q
44LY/Q
72LY/Q
85LY/Q
W
22
22
23
23
Power dissipated
At full load at end of starting
In transient state
W
184
268
436
514
Starting current at nominal load (1)
A
90
132
216
255
Type of starter
ATS 01N2
ppLU/QN/RT
ppLY/Q
Logic input power supply: For LI1, LI2 and BOOST only
24 V power supply
ATS
Power circuit
mm2
mm2
mm2
mm2
mm2
mm2
N.m
2.5 14 AWG
1
17 AWG
2.5 14 AWG
0.75 18 AWG
2.5 14 AWG
1
17 AWG
0.8
Cage type connector
1.510 8 AWG
1.56 10 AWG
16
10 AWG
16
10 AWG
110
8 AWG
16
10 AWG
1.92.5
Screw connector
6...25
6...25
4...25
4...16
6...35
6...25
5
mm2
mm2
mm2
mm2
mm2
mm2
2.5
1
2.5
0.75
2.5
1
0.52.5
0.51.5
0.51.5
0.51.5
0.52.5
0.51
Tightening torque
N.m
0.8
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
0.75...1.5
Tinned connector. Fixed
using 6 screws
0.7
Control circuit
14 AWG
17 AWG
14 AWG
18 AWG
14 AWG
17 AWG
14 AWG
16 AWG
16 AWG
16 AWG
14 AWG
17 AWG
0.5
3 Tn
0,85 U
2 Tn
0,6 U
Tn
0,25
Presentation:
pages 1/2 and 1/3
0,5
Tr
0,75
N/Ns
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
1/5
Soft starters
for asynchronous motors
References
Altistart 01
Motor
Motor power (1)
Single phase 3-phase
230 V
210 V 230 V 230 V 400 V 460 V
kW
HP
kW
HP
kW
HP
Starter
Nominal
current
Reference
Weight
kg
0.37
0.55
0.75
1.1
1.5
0.5
1
1.5
2
1.1
2.2
0.5
1.5
2
3
5
ATS 01N103FT
0.160
ATS 01N106FT
0.160
1.1
0.5
ATS 01N109FT
0.280
1.5
1.5
2.2
5.5
7.5
12
ATS 01N112FT
0.280
0.75
ATS 01N103FT
Motor
Motor power (1)
DF563902
kW
Starter
Nominal
current
A
HP
Reference
Weight
kg
1/1.5
ATS 01N206LU
0.420
1.5
ATS 01N209LU
0.420
2.2/3
3/
12
ATS 01N212LU
0.420
4/5.5
5/7.5
22
ATS 01N222LU
0.560
7.5
10
32
ATS 01N232LU
0.560
ATS 01N206QN
0.420
3/4
ATS 01N209QN
0.420
5.5
12
ATS 01N212QN
0.420
7.5/11
22
ATS 01N222QN
0.560
15
32
ATS 01N232QN
0.560
2/3
ATS 01N206RT
0.420
ATS 01N209RT
0.420
7.5
12
ATS 01N212RT
0.420
10/15
22
ATS 01N222RT
0.560
20
32
ATS 01N232RT
0.560
DF563903
DF563901
Motor
Motor power
230 V 230 V
kW
HP
7.5
10
(1)
400 V 400 V 460 V 575 V 690 V
kW HP
HP
HP
kW
15
15
20
30
30
11
15
22
25
30
40
18.5
25
37
40
50
60
22
30
45
50
60
75
Starter
Nominal
current
Reference
Weight
A
32
ATS 01N230LY
kg
2.400
37
44
ATS 01N244LY
2.400
55
72
ATS 01N272LY
3.800
75
85
ATS 01N285LY
3.800
HP
25
Starter
Nominal
current
A
44
37
40
45
50
Reference
Weight
ATS 01N244Q
kg
2.400
72
ATS 01N272Q
3.800
85
ATS 01N285Q
3.800
Accessories
Description
1/6
Weight
kg
ATS 01N230LY,
VY1 H4101
ATS 01N244p
Adaptor for mounting on 4 DZ5 MB rail
ATS 01N103FT,
RHZ 66
0.005
ATS 01N106FT
ATS 01N230LY
Presentation:
pages 1/2 and 1/3
Reference
Characteristics:
pages 1/4 and 1/5
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
Soft starters
for asynchronous motors
Dimensions
Altistart 01
Screw fixing
1
130,7
30,2
112,8
100,4
45
(1)
145
132,5
100
124
50
52,7
22,5
(1)
(1) Retractable fixings
Screw fixing
Screw fixing
130,7
30,2
(1)
(1)
175
154
145
124
132,5
52,7
72,2
45
(1)
162,5
112,8
30,2
45
112,8
130,7
(1)
76
Quick mounting on 5 rail (35 or 70 mm) using plate VY1 H4101 (1)
132
146
76
97
(1)
References:
page 1/6
4xM4
180
126
180
Characteristics:
pages 1/4 and 1/5
156
97
156
126
Presentation:
pages 1/2 and 1/3
242
254,5
4xM4
Schemes:
pages 1/8 to 1/15
1/7
Soft starters
for asynchronous motors
Schemes
Altistart 01
For 0.37 to 5.5 kW motors
3/L2
5/L3
a 110 V, 220 V
1/L1
200480 V
Q1
F2
F1
S1
KM1
3/L2
5/L3
6/T3
A1
S2
4/T2
KM1
1/L1
13
(1)
14
24 V
CL2
CL1/0
KM1
2/T1
M1
3
Note : For single-phase motors, use the ATS 01N1ppFT without connecting the 2nd phase 3/L2, 4/T2.
Wait 5 seconds after switching the soft starter off before switching it on again.
(1) A line contactor must be used in the sequence.
Compatible components (For full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
Description
A1
Soft starter
Q1
GV2 ME circuit-breaker
KM1
LC1 ppp + LA4 DA2U
F1, F2
Control protection fuses
S1, S2
XB4 B or XB5 B pushbuttons
Function chart
Green LED
Yellow LED
Motor voltage
Presentation:
pages 1/2 and 1/3
1/8
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Schemes (continued)
Soft starters
for asynchronous motors
Altistart 01
For 0.75 to 15 kW motors
5/L3
3/L2
Q1
5/L3
1/L1
1/L1
Q1
110 V, 220 V
F1
F2
F3 (1)
F3 (1)
LO1
LI +
KM3
KM2
LI1
KM2
A1
KM3
M1
3
R1A
KM2
LO1
KM3
BOOST
KM2
S2
5/L3
KM3
3/L2
LI2
S3
1/L1
COM
LI +
LI1
COM
R1C
6/T3
ATS 01N2
4/T2
6/T3
4/T2
R1C
2/T1
ATS 01N2
2/T1
R1A
BOOST
6/T3
5/L3
3/L2
1/L1
A1
4/T2
2/T1
S1
LI2
M1
3
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/9
Soft starters
for asynchronous motors
Schemes (continued)
Altistart 01
For 0.75 to 15 kW motors
3/L2
5/L3
2/T1
4/T2
6/T3
z 250 V max.
5/L3
3/L2
1/L1
Q1
F2
F1
Q2
KM1
S3
LO1
5/L3
3/L2
R1A
LI +
KM1
COM
S2
6/T3
R1C
LI2
S3
LI1
S2
4/T2
LI1
COM
6/T3
4/T2
A1
BOOST
LI +
ATS 01N2
R1C
F4
S1
S1
F4
2/T1
LO1
BOOST
R1A
Q2
2-wire
control
1/L1
3-wire
control (1)
6/T3
5/L3
3/L2
1/L1
A1
4/T2
2/T1
F3 (2)
2/T1
S2
LI2
M1
3
M1
3
Function charts
2-wire control with deceleration
Power supply
voltage
Green LED
Green LED
Logic input LI2
Logic input LI2
Logic input LI1
Relay output R1
Relay output R1
Logic output
LO1
Motor voltage
Motor voltage
10 s
10 s
Yellow LED
Yellow LED
Presentation:
pages 1/2 and 1/3
1/10
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Soft starters
for asynchronous motors
Schemes (continued)
Altistart 01
For 0.75 to 15 kW motors
5/L3
6/T3
1/L1
3/L2
4/T2
Q1
z 250 V max.
F3 (1)
F1
F2
R1A
LO1
BOOST
5/L3
A1
LI +
LI1
COM
6/T3
R1C
4/T2
ATS 01N2
S2
2/T1
KM1
1/L1
2/T1
S1
3/L2
KM1
LI2
KM1
M1
3
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/11
Soft starters
for asynchronous motors
Schemes
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (compatible components, see page 1/13)
Manual control without deceleration (freewheel), with GV3 and GV7 motor circuit-breaker
ATS 01N230LY to ATS 01N285LY
5/L3
1/L1
3/L2
400 V
5/L3
F2
3/L2
F1
230690 V
1/L1
115 V
Q1
Q1
F3 (1)
02
05
4/T2
03
6/T3
3/L2
ATS 01N2
01
Q 02
6/T3
04
5/L3
4/T2
2/T1
01
2/T1
6/T3
1/L1
6/T3
5/L3
3/L2
A1
00
ATS 01N2ppLY
06
07
4/T2
05
1/L1
A1
04
4/T2
2/T1
F3 (1)
2/T1
03
F1
1/L1
F2
F2
5/L3
400 V
5/L3
1/L1
F1
3/L2
230690 V
115 V
3/L2
Q1
Q1
S1
F3 (1)
F3
(1)
S1
S3
5/L3
3/L2
A1
00
01
06
07
ATS 01N2ppLY
02
05
03
1/12
References:
page 1/6
Dimensions:
page 1/7
01
ATS 01N2ppQ 02
2/T1
05
Presentation:
pages 1/2 and 1/3
KM2
04
KM2
6/T3
KM3
KM3
4/T2
KM2
1/L1
KM3
A1
04
KM3
5/L3
KM2
KM3
KM2
6/T3
S2
KM2
3/L2
KM3
S2
4/T2
S3
KM3
KM3
1/L1
KM2
2/T1
03
Soft starters
for asynchronous motors
Schemes (continued)
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (continued)
Automatic control with or without deceleration (freewheel), without contactor
5/L3
1/L1
5/L3
3/L2
F2
Q1
Q1
LY
00
01
3-wire
control (1)
2-wire
control
A1
5/L3
ATS 01N2
5/L3
05
3/L2
A1
04
3/L2
F3 (2)
(2)
1/L1
04
S1
S1
S3
02
3-wire
control (1)
05
ATS 01N2
S3
Q 02
S2
6/T3
03
4/T2
2/T1
4/T2
2/T1
2-wire
control
01
S2
06
07
6/T3
F3
1/L1
F1
1/L1
115 V
03
Compatible components (For full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
Description
A1
Soft start/soft stop unit
Q1
GV3 or GV7 circuit-breaker
KM2, KM3
LC1 ppp + LA4 DA2U
F1, F2
Control protection fuses
F3
3 fast-acting fuses
S1, S2, S3
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/13
Soft starters
for asynchronous motors
Schemes (continued)
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (continued)
Automatic control with or without deceleration (freewheel), with contactor
ATS 01N230LY to ATS 01N285LY
5/L3
1/L1
5/L3
3/L2
1/L1
F2
F1
3/L2
z 250 V max.
115 V
F2
F1
Q1
Q1
KM1
KM1
F4
F4
F4
F4
S1
S2
05
5/L3
3/L2
5/L3
3/L2
1/L1
01
ATS 01N2ppQ
S3
02
S2
03
S2
KM1
6/T3
06
07
ATS 01N2ppLY 02
A1
04
4/T2
KM1
05
KM1
01
2/T1
KM1
00
S3
6/T3
S2
4/T2
KM1
1/L1
S1
A1
04
2/T1
03
Compatible components (For full references, see pages 1/16 and 1/17 or refer to our catalogue: Motor starter solutions - Control and protection components.)
Code
Description
A1
Soft start/soft stop unit
Q1
GK1 disconnector
KM1
LC1 ppp + LA4 DA2U
F1, F2
Control protection fuses
F4
LR2 D thermal overload relay
S1, S2, S3
XB4 B or XB5 B pushbuttons
Presentation:
pages 1/2 and 1/3
1/14
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
Soft starters
for asynchronous motors
Schemes (continued)
Altistart 01
For 15 to 75 kW motors
ATS 01N2ppLY and ATS 01N2ppQ soft start/soft stop units (continued)
Automatic control without deceleration (freewheel), with a maintaining function
F2
F1
5/L3
1/L1
3/L2
z 250 V max.
5/L3
1/L1
115 V
F1
F2
Q1
Q1
F3
F3
(1)
KM1
KM1
S1
(1)
KM1
5/L3
3/L2
1/L1
5/L3
3/L2
ATS 01N2ppLY 02
01
04
ATS 01N2ppQ
S2
05
03
KM1
6/T3
KM1
01
4/T2
06
07
A1
00
2/T1
05
6/T3
KM1
4/T2
S2
A1
04
2/T1
KM1
1/L1
S1
02
03
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Dimensions:
page 1/7
1/15
Soft starters
for asynchronous motors
Combinations
Altistart 01
400 V power supply, type 1 coordination
Components to be combined in accordance with standards IEC 60947-1 and IEC 60947-4-2
Combine either circuit-breaker (light blue columns), contactor, starter, or switches/fuses (dark blue columns), contactor, starter
Motor
Starter
Type of circuit-breaker
Type of
Type of switch Am fuses
I2t
or switch
Class 10
Telemecanique
Rating contactor
Reference
Rating
disconnector
(base unit)
kW
M1
0.37
A
0.98
A1
Q1
ATS 01N103FT GV2 ME05
0.55
1.5
ATS 01N103FT
GV2 ME06
1.6
0.75
ATS 01N103FT
GV2 ME07
2.5
1.1
2.5
ATS 01N103FT
GV2 ME08
GV2 ME08
ATS 01N106FT
GV2 ME10
6.3
6.3
Thermal
overload relay
A2 s
7.5
14.8
17
18.1
21
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 21
11
21
23
LC1 D25
LS1 D2531
DF2 CA25
25
6050
LRD 22
15
28.5
32
LC1 D32
GK1 EM
DF2 EA40
40
7200
LR2 D3353
18.5
35
ATS 01N244Q
GV3 ME40
40
LC1 D38
GK1 EM
DF2 EA40
40
8000
LR2 D3355
22
42
ATS 01N244Q
GV3 ME63
63
LC1 D50
GK1 FM
DF2 FA63
63
8000
LR2 D3357
30
57
ATS 01N272Q
GV3 ME63
63
LC1 D65
GK1 FM
DF2 FA63
63
9000
LR2 D3359
37
69
ATS 01N272Q
GV3 ME80
80
LC1 D80
GK1 FM
DF2 FA80
80
9000
LR2 D3363
45
81
ATS 01N285Q
GV7 RE100
100
LC1 D95
GK1 FM
DF2 FA100
100
9000
LR2 D3365
1.5
2.2
3.5
6.5
8.4
5.5
11
ATS 01N106FT
GV2 ME14
GV2 ME14
ATS 01N112FT
GV2 ME16
13
13
ATS 01N106FT
ATS 01N109FT
Presentation:
pages 1/2 and 1/3
1/16
Characteristics:
pages 1/4 and 1/5
References:
page 1/6
Q2
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA02
265
LS1 D2531
DF2 CA04
265
LS1 D2531
DF2 CA04
265
LS1 D2531
DF2 CA06
265
LS1 D2531
DF2 CA06
265
LS1 D2531
DF2 CA08
265
LS1 D2531
DF2 CA08
265
LS1 D2531
DF2 CA12
12
265
LS1 D2531
DF2 CA12
12
265
LS1 D2531
DF2 CA12
12
610
LS1 D2531
DF2 CA12
12
610
LS1 D2531
DF2 CA16
16
610
LS1 D2531
DF2 CA16
16
610
LS1 D2531
DF2 CA20
20
6050
F4
LR2 K0306
LRD 05
LR2 K0307
LRD 06
LR2 K0308
LRD 07
LR2 K0308
LRD 08
LR2 K0308
LRD 08
LR2 K0310
LRD 08
LR2 K0310
LRD 08
LR2 K0312
LRD 10
LR2 K0312
LRD 10
LR2 K0314
LRD 12
LR2 K0314
LRD 12
LR2 K0316
LRD 14
LR2 K0316
LRD 14
LR2 K0321
LRD 16
LR2 K0321
LRD 16
LRD 21
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
Soft starters
for asynchronous motors
Combinations (continued)
Altistart 01
690V power supply, type 1 coordination
Components to be combined in accordance with standards IEC 60947-1 and IEC 60947-4-2
Combine either circuit-breaker (light blue columns), contactor, starter, or switches/fuses (dark blue columns), contactor, starter
Motor
Starter
Type of circuit-breaker
Type of
Type of switch Am fuses
I2t
contactor
or switch
Class 10
Telemecanique
Rating
Reference
Rating
disconnector
(base unit)
kW
M1
30
A
33
37
40
55
58
75
75.7
A2 s
DF2 EA40
40
7200
F4
LR2 D3355
GK1 FM
DF2 FA63
63
8000
LR2 D3359
LC1 D115
GK1 FM
DF2 FA80
80
9000
LR2 D3363
LC1 D150
GK1 FM
DF2 FA100
100
9000
LR2 D3365
A
A1
Q1
ATS 01N230LY GV3 ME40 +
GV3 A01
ATS 01N244LY GV3 ME63 +
GV3 A01
ATS 01N272LY GV3 ME80 +
GV3 A01
ATS 01N285LY GV7 RE100 +
GV7 A11
Presentation:
pages 1/2 and 1/3
Characteristics:
pages 1/4 and 1/5
Thermal
overload relay
2540
KM1
LC1 D50
Q2
GK1 EM
4063
LC1 D65
5680
60100
References:
page 1/6
Dimensions:
page 1/7
Schemes:
pages 1/8 to 1/15
1/17
2/0
Contents
2/1
Soft starters
for asynchronous motors
Presentation
Presentation
The Altistart U01 is a soft start/soft stop unit for asynchronous motors. It is designed
primarily for combinations with TeSys model U controller-starters.
When combined with a TeSys model U 1 controller by means of a connector 2, the
Altistart U01 3 is a power option which provides the Soft start/soft stop function. The
result is a unique, innovative motor starter.
Using the Altistart U01 starter enhances the starting performance of asynchronous
motors by allowing the motor to start gradually, smoothly and in a controlled manner.
It can also prevent mechanical shocks which lead to wear and tear, and limits the
amount of maintenance work and production downtime.
The Altistart U01 limits the starting torque and current peaks on starting, on machines
which do not require a high starting torque.
DF563960
2
1
Description
4
5
6
7
8
Characteristics:
pages 2/4 and 2/5
2/2
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
Presentation (continued)
Soft starters
for asynchronous motors
b 3-wire control:
The run and stop commands are controlled by 2 different logic inputs.
Stopping is achieved when logic input LI1 opens (state 0).
The pulse on input LI2 is maintained until input LI1 opens.
Altistart U01 control terminals
+ 24 V
LI1
LI2
b Starting time
The starting time setting can be used to adjust the voltage ramp time applied to the
motor and to obtain a gradual starting time depending on the motor load.
b Voltage BOOST function via logic input:
Activating the BOOST logic input enables the function for supplying a starting
overtorque capable of overcoming any mechanical friction.
When the input is at state 1, the function is active (input connected to the + 24 V) and
the starter supplies a fixed voltage to the motor for a limited time before starting.
U
100 %
Un
Voltage ramp
50 %
Un
Initial voltage
t
200 ms
Application of a voltage BOOST equal to 100% of the nominal
motor voltage
b End of starting
v Logic output LO1 application function
ATSU 01N2ppLT soft start/soft stop units are equipped with an open collector logic
output LO, which indicates the end of starting when the motor has reached nominal
speed.
b Fault relay
ATSU 01N2ppLT soft start/soft stop units have a relay which opens when a fault is
detected.
The contact of relay R1A-R1C closes when the LI2 run command is sent and opens
when the motor voltage approaches 0V on a decelerated stop or instantly in the
event of a fault.
This information can be used for controlling the line contactor and achieving motor
deceleration (by maintaining the line contactor until the motor has stopped).
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
2/3
Characteristics
Soft starters
for asynchronous motors
Environment
Type of starter
Conformity to standards
ATSU 01N2ppLT
Altistart U01 electronic starters have been developed to conform to the strictest
international standards and the recommendations relating to electrical industrial
control devices (IEC, EN), in particular standard IEC/EN 60947-4-2.
Product certification
Degree of protection
Degree of pollution
Vibration resistance
Shock resistance
Relative humidity
Ambient temperature
around the unit
Storage
Operation
Maximum operating altitude
Operating position
Maximum permanent angle in relation to the normal vertical
mounting position
C
C
m
10
Electrical characteristics
Type of starter
Category of use
Conforming to IEC 60947-4-2
Rated operating voltage
3-phase a voltage
Frequency
Output voltage
Control supply voltage
Rated operating current
Adjustable starting time
Adjustable deceleration time
Starting torque
Type of starter
ATSU
Control power supply consumption
Power dissipated
At full load at end of starting
In transient state at 5 times the
rated operating current
Type of starter
Use
I
Starting time
Starting time
Maximum number of cycles per
hour
V
Hz
A
s
s
%
W
W
ATSU 01N2ppLT
Ac-53b
200 - 15% to 480 + 10%
50 - 5% to 60 + 5%
Maximum 3-phase voltage equal to line supply voltage.
c 24 V, 100 mA 10%
6...32
1...10
1...10
30...80% of starting torque of motor connected directly on the line supply
01N206LT
01N209LT
01N212LT
01N222LT
01N232LT
c 24 V, 65 mA
c 24 V, 100 mA
1.5
1.5
1.5
2.5
2.5
61.5
91.5
121.5
222.5
322.5
ATSU 01N206LT to ATSU 01N222LT
ATSU 01N232LT
1
310
1
180
5
20
t
Operating cycle
Presentation:
pages 2/2 and 2/3
2/4
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
5
10
Characteristics (continued)
Soft starters
for asynchronous motors
24 V 10%
Isolated
Max. current 100 mA
Logic inputs with impedance 27 kohms; 24 V power supply (U max 40 V)
Max current 8 mA
State 0 if U < 5 V and I < 0.2 mA
State 1 if U > 13 V and I > 0.5 mA
Open collector logic output
External 24 V power supply (minimum 6 V maximum 30 V)
Max current 200 mA
Normally open (N/O) contact (contact open in fault mode)
Minimum switching capacity: 10 mA for c 6 V
Max. switching capacity on inductive load (cos = 0.5 and L/R = 20 ms):
2 A for a 250 V or c 30 V (AC-15)
Max. operating voltage 440 V
Starter powered up
Nominal voltage reached
LED signalling
Green LED
Yellow LED
Power circuit
Flexible wire without cable
end
Flexible wire with cable end
Rigid wire
1 conductor
2 conductors
1 conductor
2 conductors
1 conductor
2 conductors
mm2
mm2
mm2
mm2
mm2
mm2
N.m
1 conductor
2 conductors
1 conductor
2 conductors
1 conductor
2 conductors
mm2
mm2
mm2
mm2
mm2
mm2
N.m
Tightening torque
1.510
1.56
16
16
110
16
1.92.5
8 AWG
10 AWG
10 AWG
10 AWG
8 AWG
10 AWG
Screw connector
Control circuit
Flexible wire without cable
end
Flexible wire with cable end
Rigid wire
Tightening torque
0.52.5
0.51.5
0.51.5
0.51.5
0.52.5
0.51
0.5
14 AWG
16 AWG
16 AWG
16 AWG
14 AWG
17 AWG
0,85 U
2 Tn
0,6 U
Tn
The diagram opposite shows the torque/speed characteristic of a cage motor in relation to the
supply voltage.
The torque varies in line with the square of the voltage at a fixed frequency. The gradual increase
in the voltage prevents the instantaneous current peak on power-up.
3 Tn
0,25
Presentation:
pages 2/2 and 2/3
0,5
Tr
0,75
N/Ns
References:
page 2/6
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
2/5
Soft starters
for asynchronous motors
References
400 V
kW
460 V
HP
Starter
Nominal
current
Reference
Weight
kg
ATSU 01N222LT
0.75
1.1
1
1.5
1.5
2.2
2
3
ATSU 01N206LT
0.340
1.5
3
4
ATSU 01N209LT
0.340
2.2
3
5.5
7.5
12
ATSU 01N212LT
0.340
4
5.5
5
7.5
7.5
11
10
15
22
ATSU 01N222LT
0.490
7.5
10
15
20
32
ATSU 01N232LT
0.490
Accessories
DF510362
LUBp2BL
Description
Power connector between
ATSU 01N2ppLT and
TeSys model U
Reference
ATSU 01N2ppLT
VW3 G4104 r
Weight
kg
0.020
LUCM ppBL
Motor power
Voltage
230 V
400 V
kW/HP
kW
0.75/1
1.5
1.1/1.5
2.2
1.5/2
3
4
2.2/3
3/
5.5
4/5
7.5
5.5/7.5
11
7.5/10
15
Soft starter
460 V
HP
2
3
7.5
10
15
20
ATSU 01N206LT
ATSU 01N206LT
ATSU 01N209LT
ATSU 01N209LT
ATSU 01N212LT
ATSU 01N212LT
ATSU 01N222LT
ATSU 01N222LT
ATSU 01N232LT
LUCp 05BL
LUCp 12BL
LUCp 12BL
LUCp 12BL
LUCp 12BL
LUCp 18BL
LUCp 18BL
LUCp 32BL
LUCp 32BL
(1) Standard motor power ratings, HP power ratings indicated according to standard UL 508.
(2) Depending on the configuration of the chosen TeSys model U starter, replace the p with A for
standard, B for expandable, and M for multifunction.
ATSU 01N2ppLT
2/6
LUB 12
LUB 12
LUB 12
LUB 12
LUB 12
LUB 32
LUB 32
LUB 32
LUB 32
Presentation:
pages 2/2 and 2/3
TeSys model U
Power base
Control unit (2)
Characteristics:
pages 2/4 and 2/5
Dimensions:
page 2/7
Schemes:
pages 2/8 to 2/11
Soft starters
for asynchronous motors
Dimensions
45
135
124
150
284
154
72,2
99
135
99
314
170
154
72,2
45
46,6
44,8
28
20
Presentation:
pages 2/2 and 2/3
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Schemes:
pages 2/8 to 2/11
2/7
Schemes
3/L2
1/L1
5/L3
1/L1
Power wiring
QF1
QF1
TeSys
model U
CU
TeSys
model U
with
reversing
unit
CU
2/T1
4/T2
6/T3
1/L1
3/L2
5/L3
TeSys model U
TeSys model U
2/T1
4/T2
6/T3
3/L2
5/L3
6/T3
A1
2/T1
6/T3
ATSU 01N2ppLT
M1
3
4/T2
4/T2
2/T1
ATSU 01N2ppLT
1/L1
A1
M1
3
Compatible components (For full references, see pages 1/16 and 1/17 or consult our Motor starter solutions - control and protection components specialist
catalogue.)
Code
Description
A1
Soft start/soft stop unit
QF1
TeSys model U controller-starter
CU
TeSys model U control unit
Presentation:
pages 2/2 and 2/3
2/8
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
Schemes (continued)
c 24 V
c 24 V
A1
S1
LO1
+ 24 V
BOOST
LI2
LI1
COM
R1C
R1A
A1
Stop
Run
S1
S2
A1
A2
QF1
ATSU 01N2ppLT
17
Stop
Run
18
LUA1 C20
LO1
+ 24 V
LI2
COM
LI1
R1C
R1A
18
BOOST
17
ATSU 01N2ppLT
LUA1 C20
A1
A2
QF1
Functional diagrams
Power supply
voltage
Green LED
Power supply
voltage
Green LED
Yellow LED
Yellow LED
U1
U1
10 s
10 s
Motor voltage
Motor voltage
t1
t1
t2
With deceleration
c 24 V
c 24 V
A1
A1
A1
14
LO1
BOOST
+ 24 V
LI2
LI1
R1C
COM
13
S2
S2
13
QF1
14
QF1
A2
A1
QF1
S1
QF1
A2
R1A
18
LUA1 C20
LO1
+ 24 V
LI2
LI1
COM
R1C
R1A
18
S1
BOOST
17
ATSU 01N2ppLT
LUA1 C20
ATSU 01N2ppLT
17
Functional diagrams
Power supply
voltage
Green LED
Power supply
voltage
Green LED
500 ms
Pushbutton S1
Pushbutton S2
U1
Yellow LED
Yellow LED
10 s
Motor voltage
10 s
Motor voltage
t1
t1
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
2/9
Schemes (continued)
Run
direction 2
Run
direction 2
S2
Run
direction 1
S1
S2
Stop
S3
Stop
17
17
S3
LUA1 C20
18
18
LUA1 C20
+
c 24 V
c 24 V
LO1
BOOST
LT
+ 24 V
LI2
LI1
COM
R1C
R1A
ATSU 01N2
To PLC
Presentation:
pages 2/2 and 2/3
2/10
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
LO1
+ 24 V
BOOST
LI2
LI1
COM
ATSU 01N2ppLT
R1C
B1
A1
B3
A3
LI2
+ 24 V
BOOST
LO1
LI1
COM
R1C
R1A
A2
Run
direction 1
S1
A1
LU2B p2BL
ATSU 01N2ppLT
B1
A1
B3
A3
LU2B p2BL
QF1
A1
R1A
QF1
A2
Without deceleration
Schemes (continued)
c 24 V 24 V Aux.
D(B)
D(A)
Gnd
LO1
COM
OA3
COM
OA1
BOOST
+ 24 V
LI2
LI1
4 5 8
COM
R1A
c 24 V 24 V Aux.
D(B)
D(A)
Gnd
LO1
COM
LO1
BOOST
+ 24 V
LI2
LU9B N11C
Pre-wired coil
Modbus Module
LUL C031
ATSU 01N2ppLT
4 5 8
13
LI1
COM
R1C
R1A
Modbus Module
LUL C031
ATSU 01N2ppLT
A1
A1
R1C
A1
LO1
c 24 V
14
+
c 24 V
QF1
Function
Register
Bit
Powering down TeSys U and ATSU
704
0
Value
A2
B1
A1
Function
Register
Bit
Value
Powering up TeSys U and ATSU
Forward
704
0
1
Reverse
704
1
1
Powering down TeSys U and ATSU
Forward
704
0
0
Reverse
704
1
0
Automatic control without deceleration
Run
700
0
1
Stop forward
704
0
0
Stop reverse
704
1
0
Automatic control with deceleration (forward or reverse)
Run
700
0
1
Soft stop
700
0
0
A1: Soft start/soft stop unit
QF1: TeSys model U controller-starter with reversing unit
B3
A3
LU2B p2BL
1
0
1
0
A1
OA3
COM
OA1
A2
B1
LO1
BOOST
+ 24 V
LI2
ASI LUFC5
c 24 V AS-Interface
c 24 V
c 24 V
Function
Bit
Value
Power-up and automatic control without deceleration
Run
D0
1
Stop
D0
0
Function
Bit
Value
Power-up and automatic control without deceleration
Run forward
D0
1
Stop
D0
0
Run reverse
D1
1
Stop
D1
0
A1: Soft start/soft stop unit
QF1: TeSys model U controller-starter with reversing unit
Presentation:
pages 2/2 and 2/3
A1
B3
14
LU2B p2BL
c 24 V AS-Interface
LI1
QF1
A3
LU9B N11C
Pre-wired coil
R1C
R1A
LO1
BOOST
13
+ 24 V
LI2
LI1
COM
R1C
R1A
ASI LUFC5
COM
ATSU 01N2ppLT
ATSU 01N2ppLT
Characteristics:
pages 2/4 and 2/5
References:
page 2/6
Dimensions:
page 2/7
2/11
3/0
Contents
3 - Services
3/1
Up-dated: 28-07-2003
Afghanistan
Albania
Algeria
b Schneider Electric
Andorra
Angola
Anguilla
Antartica
Argentina
b Schneider Argentina
Armenia
Aruba
Australia
Austria
Tel. : +213 21 92 97 02 09
Fax : +213 21 92 97 00 01
www.schneider-electric.com.ar
www.schneider.com.au
www.schneider-electric.at
www.squared.com
Azerbaijan
Bahamas
b Schneider Electric
Union Village
PO Box 3901 - Nassau
Bahrain
b Schneider Electric
Bangladesh
Barbados
Belarus
Belgium
Dieweg 3
B - 1180 Brussels
Tel.: +3223737711
Fax: +3223753858
www.schneider-electric.be
Belize
Benin
Bermuda
Bhutan
Bolivia
Botswana
Bouvet island
Brazil
Tel.: +55 55 24 52 33
Fax: +55 55 22 51 34
www.schneider-electric.com.br
www.schneiderelectric.bg
Brunei (Darussalam)
Bulgaria
b Schneider Electric
Burkina Faso
Burundi
Cambodia
Cameroon
Canada
b Schneider Canada
Cape Verde
Caribee
Cayman islands
Chad
Chile
Avda. Pdte Ed. Frei Montalva, 6001-31 Tel.: +56 2 444 3000
Conchali - Santiago
Fax: +56 2 423 9335
www.schneider-electric.co.cl
China
b Schneider Beijing
www.schneider-electric.com.cn
3/2
Tel.: +86 10 65 90 69 07
Fax: +86 10 65 90 00 13
www.schneider-electric.ca
Up-dated: 28-07-2003
Christmas island
Colombia
S.A.
Comoros
Congo
Cook islands
Costa Rica
Croatia
b Schneider Electric SA
Fallerovo Setaliste 22
HR - 10000 Zagreb
Cuba
b Schneider Electric
Cyprus
Czech Republic
Thmova 13
Praha 8 - 186 00
www.schneider-electric.cz
Denmark
Baltorpbakken 14
DK-2750 Ballerup
Tel.: +45 44 73 78 88
Fax: +45 44 68 5255
www.schneider-electric.dk
www.schneider-ca.com
Djibouti
Dominican Republic
b Schneider Electric
Ecuador
Egypt
El Salvador
Equatorial Guinea
Eritrea
Estonia
b Lexel Electric
Ethiopia
Falkland islands
Faroe islands
Fiji
Finland
b Schneider Electric Oy
Sinimentie 14
02630 Espoo
www.schneider-electric.fi
France
b Schneider Electric SA
5, rue Nadar
92500 Rueil Malmaison
www.schneider-electric.fr
French Polynesia
Gabon
Gambia
Georgia
Germany
Gothaer Strae 29
D-40880 Ratingen
www.schneiderelectric.de
Ghana
PMB Kia
3rd Floor Opeibea House
Airport Commercial Center
Liberation road - Accra
Gilbraltar
Greece
b Schneider Electric AE
14th km - RN Athens-Lamia
GR - 14564 Kifissia
Greenland
Grenada
Guadeloupe
Guam
Tel.: +20 24 01 01 19
Fax: +20 24 01 66 87
www.schneider.com.eg
www.schneider-electric.com.gr
3/3
Up-dated: 28-07-2003
Guatemala
Guinea-Bissau
Guinea
Guyana
Haiti
Honduras
Hong Kong
Tel.: +852 25 65 06 21
Fax: +852 28 11 10 29
www.schneider-electric.hu
Ltd
Hungary
Iceland
India
www.schneiderelectric-in.com
Indonesia
www.schneider-electric.co.id
b Telemecanique Iran
Irak
Tel.: +33 04 76 60 54 27
Fax: +33 04 76 60 56 60
Ireland
Maynooth Road
Cellbridge - Co. Kildare
www.schneiderelectric.ie
Italy
www.schneiderelectric.it
Ivory Coast
Tel.: +225 21 75 00 10
Fax: +225 21 75 00 30
l'Ouest
Jamaica
b Schneider Electric
Japan
Torigoe F. Bldg
1-8-2, Torigoe
Taito-Ku - 111-0054 Tokyo
Jordan
Kazakstan
Tel.: 962 65 16 78 87
Fax: 962 65 16 79 1
Kenya
Kiribati
Korea
Kurdistan
Kuwait
Kyrgyz Republic
Laos
Latvia
b Lexel Electric
Lebanon
Tel. : +961 1 20 46 20
Tel. : +961 1 20 31 19
Lesotho
Liberia
Libya
Liechtenstein
Lithuania
b Lexel Electric
Loro Sae
Luxembourg
3/4
www.schneider-electric.co.jp
www.csinfo.co.kr/schneider/
Tel.: 33 03 87 39 06 03
Fax: 33 03 87 74 25 96
www.schneider-electric.fr
Up-dated: 28-07-2003
Macau
Macedonia
Madagascar
Malawi
Malaysia
Maldives
Mali
Malta
Marshall islands
Martinique
b Schneider Electric
Schneider Electric
Immeuble Cottrell - ZI de la Lzarde
97232 Le Lamentin
Mauritania
Mauritius
b Schneider Electric
Route ctire
Calodyne - Mauritius
Mayotte
Mexico
Micronesia
Moldova
Monaco
Mongolia
Montserrat
Morocco
Mozambique
Myanmar
Namibia
Nauru
Nepal
Netherlands
b Schneider Electric BV
Netherlands Antilles
New Caledonia
New Zealand
Nicaragua
Niger
Nigeria
b Schneider Electric Nigeria Limited Biro plaza - 8th Floor - Plot 634
Abeyemo Alakija Street
Victoria Islan - Lagos
www.schneiderelectric.com.my
Tel.: +05 96 51 06 00
Fax: +05 96 51 11 26
3
Tel.: 230 282 18 83
Fax: 230 282 18 84
www.schneiderelectric.com.mx
www.schneider.co.ma
www.schneider-electric.nl
www.schneider-electric.co.nz
Niue
Norfolk island
North Korea
Norway
Solgaard Skog 2
Postboks 128 - 1501 Moss
Oman
b Schneider Electric CA
Pakistan
Palau
Panama
Paraguay
www.schneider-electric.no
3/5
Up-dated: 28-07-2003
Peru
Philippines
Pitcairn
Poland
www.schneider-electric.com.pe
Portugal
Av.do Forte, 3
Edificio Sucia II, Piso 3-A
CP 2028 Carnaxide
2795 Linda-A-Velha
www.schneider-electric.pl
www.schneiderelectric.pt
Puerto Rico
Qatar
Reunion
b Schneider Electric
Immeuble Futura,
190, rue des 2 canons
BP 646 - 97497 Sainte Clothilde
Tel.: +262 28 14 28
Fax: +262 28 39 37
Romania
b Schneider Electric
Bd Ficusului n42
Apimondia, Corp.A, et.1, Sector 1
Bucuresti
www.schneider-electric.ro
Russian Federation
Enisseyskaya 37
129 281 Moscow
www.schneider-electric.ru
Rwanda
Samoa
San Marino
Saudi Arabia
b Schneider Electric
Senegal
BP 15952 - Dakar-Fann
Rond point N'Gor - Dakar
Seychelles
Sierra Leone
Singapore
Slovak Republic
www.schneider-electric.com.sg
Borekova 10
SK-821 06 Bratislava
www.schneider-electric.sk
www.schneider-electric.si
#02-17/20 TechPoint
Singapore 569059
Slovenia
Dunasjka 47
1000 Ljubljana
Solomon islands
Somalia
South Africa
www.schneider-electric.co.za
(PTY) Ltd
Spain
www.schneiderelectric.es
Sri Lanka
Tel. : +94 77 48 54 89
www.schneiderelectric-in.com
St Helena
St Lucia
St Pierre et Miquelon
Sudan
Suriname
Swaziland
Sweden
b Schneider Electric AB
Djupdalsvgen 17/19
19129 Sollentuna
www.schneider-electric.se
Switzerland
Schermenwaldstrasse 11
CH - 3063 Ittigen
www.schneider-electric.ch
S.A.
3/6
Up-dated: 28-07-2003
Syrian Arab Republic
b Schneider Electric Taiwan Co Ltd 2FI., N37, Ji-Hu Road, Nei-Hu Dist., Tel. : +886 2 8751 6388
Tel. : +963 11 37 49 88 00
Fax : +963 11 37 17 55 9
Tajikistan
Thailand
Togo
Tokelau
Tonga
b Schneider Electric
Tunisia
Turkey
Ticaret A.S.
Turkmenistan
www.schneider-electric.com.tw
Tuvalu
www.schneider-electric.co.th
3
www.schneiderelectric.com.tr
Tel. : +993 12 46 29 52
Fax : +993 12 46 29 52
Uganda
Ukraine
b Schneider Electric
Rue Krechtchalik 2
252601 Kiev
PO Box 29580
Office Floor 2/Lulu Street
Al Marina Plaza Tower
Abu Dhabi
United Kingdom
www.schneider.co.uk
United States
b Schneider Electric
www.squared.com
Uruguay
Uzbekistan
Vanuatu
Venezuela
Viet Nam
Virgin islands
Western Sahara
Yemen
Yugoslavia
d.o.o.
Zambia
b Schneider Zambia
Zambia Office
c/o Matipi Craft Center Building
Plot 1036 - Accra Road
PO Box 22792 - Kitwe
Zimbabwe
b Schneider Electric
www.schneider-electric.com.ua
www.schneider-electric.com.ve
3/7
Headquarters
ART. 071789
http://www.schneider-electric.com
DIA2ED2040201EN