Professional Documents
Culture Documents
GOVERNMENT OF KUWAIT
MINISTRY OF ELECTRICITY & WATER
SUPPLY & INSTALLATION OF 132 KV XLPE
POWER CABLES, OPTICAL FIBER CABLES AND ACCESSORIES
GENERAL SPECIFICATIONS
3.1
Extent of Contract
The contract shall be for the manufacturing, testing in the factory, packing, shipment
and delivery CIF to Ministry of Electricity & Water, customs and import duties,
handling charges, transport to site, excavations, laying and installations, pulling
through ducts, backfilling, reinstating of the ground, jointing and terminating, testing
at site and putting to work the circuits, outlined in Detailed Scope of Work.
3.1.1 Supply
The lengths of the various circuits as indicated in Detailed Scope of Work are
approximate and will have to be worked out after the layout of the various equipment
are finalized. The payments for the supply shall be based on measured lengths of the
circuits installed.
N.B.: This contract covers the supply of all jointing materials, compounds and metals
necessary for the installation and jointing of all these cables to their respective
terminations.
The contract covers the installations and jointing of the circuits outlined in Detailed
Scope of Work.
The lengths of the various circuits as indicated in Detailed Scope of Work are
approximate and will have to be worked out after the layout of the various equipment
are finalized.
The payments for the installations shall be based on measured lengths of the circuits
installed. To facilitate easy determination of installation charges, uniform flat rates
shall be quoted for cable installation whether buried (including excavations in ground
or soil of any nature, tiling, install of protection nets and warning tapes and backfilling)
or pulled through ducts, or laid in concrete trenches or on trays or supported by cleats.
The quoted rates for installations shall be firm and shall not be subject to any variation
throughout the contract period.
The arrangement of circuits in Detailed Scope of Work does not depict the
chronological sequences of installation operations. The actual sequence of operations
will be fixed at the time of installation of the circuits with respect to the prevailing
load conditions.
The installation work shall be carried out during the normal working hours of the
Ministry of Electricity & Water. If the contractor wishes to carry out the installation
works after the normal working hours for his own convenience or to meet the contract
completion dates, he should get the approval of the purchaser.
3.1.3 Surplus Cables
Expense of surplus cables will not be paid by the purchaser. Accordingly, the
contractor shall make an accurate survey to meet the actual lengths of the cables
required to complete the items detailed in the scope of works. Disposal of excess or
scrap materials is the contractor's responsibility.
3.2
33kV System
a)
Voltage
132000V+10%
33000V+10%
b)
No. of Phases
Three
Three
c)
Frequency
50 Hz
50 Hz
d)
Fault Level
10000 MVA at
145 KV
1000 MVA
e)
1.25 seconds
1.5 seconds
f)
directly earthed
Through 39 ohms
resistor.
3.3
Site Conditions
Climatic conditions in Kuwait are rigorous and during summer, the ambient
shade temperature rises to 55 C and the sun temperature to 85 C as measured
with a black bulb thermometer. Periods of high humidity are common and a
relative humidity of 100% at 30 C has been recorded. Violent sand and dust
storms occur, even on comparatively still days, fine dust is carried in
suspension in the atmosphere.
The cables will be laid partly in ducts or concrete trenches and partly buried in
the ground at a depth of 1.4 meters for 33 KV cables and 1.5 meters for 132kV
cables where the soil varies from sandy to rock-like gatch compared to dry hard
clay with a corresponding ground thermal resistivity "g" of 120 C cm/watt and
a ground temperature varying from 35 C in summer to 15 C in winter.
The cables called for in this specification shall, therefore give trouble free
service under the worst conditions encountered in Kuwait and shall carry rated
currents continuously under the worst temperature conditions which prevail
in summer and shall also withstand maximum fault current without damage or
deterioration.
The cables will be exposed to direct rays of the sun at the terminations of the
outdoor sealing ends and at the transformers. They should be capable of
withstanding such exposure continuously in service without any deleterious
effect on the insulation, sheathing or covering, by using sun shielding for cables
and sealing-ends. They should also be suitable for storage in the open for a
period of at least two years with patterns.
The soil in Kuwait is very corrosive. Sulphate reducing bacteria is common to
all soils in the Kuwait Area and as the soil is generally rich in sulphate, the
anaerobic conditions which may arise in contact with buried pipes and cables,
favors the development of these anaerobic organisms which generate
hydrogen sulphide and consequently render these areas more corrosive.
In view of the above and the high temperatures encountered in Kuwait, it
should be stressed that PVC plasticizers should be of the long chain; high
molecular weight type to reduce the loss of plasticizers in the hot and corrosion
conditions. This prevents shrinkage of the PVC with subsequent cracking of the
film.
Typical analysis of a soil sample is as follows:
-
Appearance
10.0
:
:
Sodium Chloride as Na Cl
Iron as Fe2O3
Present
Moisture
15.00 %
N.B.: The sand is not corrosive under dry aerated conditions, but under anaerobic
conditions, the sulphate reducing bacteria in the sand will result in serious
corrosion of metals in contact with the sand. The cables coverings over the
lead sheath as stated in these specifications are designed to combat this.
Where PVC (as sheath serving or overall covering) is used, the PVC should be
suitable for the above soil conditions. Tenderers should confirm in their offers
that the PVC will be suitable for these conditions.
3.4
Details and General Requirements Applicable to Power Cables & Fiber Optic
Cables, Coaxial Cables and Accessories
3.4.A
XLPE Cables
The cables called for in this specification shall have insulation levels to withstand to
voltage surges that may occur due to switching operations, sudden load variations and
faults ...etc. The cable shall satisfy the requirement of:
IEC 60502 for 33 KV cables and IEC 60840 for 132 KV Cables as a minimum:
a)
Conductors
The strands used in the making -up of different sizes of conductors shall be
plain, smooth, annealed high conductivity copper wires laid up and shaped into
circular cores complying with IEC 60228 and BSS 6480 recommendations.
Oval or sector shaped cores will not be accepted sizes and numbers of wires
shall be stated in the schedules. Also aluminum conductors will not be
accepted.
b)
Insulation
Insulation for the cables shall be of the best quality dry cured XLPE type. The
insulation for 132kV cables shall be designed for an impulse voltage level of
650kV peak and the 33 KV cables shall be designed for impulse voltage level of
195kV peak the insulation should be designed for a life time of 50 years.
c)
Sheath
d)
Armour Wires
All armour wires shall be of the galvanized steel to B.S. 1442 Galvanizing shall
be carried out in accordance with BBS 443. Sizes and numbers of wires shall be
stated in the schedules of this specification.
e)
Compound
The compound used shall not melt or run when exposed to the temperature
conditions prevailing during transit or at site in Kuwait or during operation.
e)
Serving
The soil in Kuwait is naturally very corrosive and it is essential, therefore, that
the serving of the cables be designed to prevent corrosion. Reference should
3.4.A.1
The XLPE cables for 132kV should comply generally with the requirements of latest IEC
840-88
1)
Conductor
The conductor shall be water sealed by adding a swelling material between the
conductor strands.
3)
Conductor Screen
This screen consists of an extruded layer firmly bonded to the XLPE insulation.
The material is a semi-conductive compound. The interface between the
screen and the insulation must be smooth as much as possible. The conductor
screen, the insulation and the insulation screen are to be extruded in one single
Insulation
5)
> tn - 0.1 tn mm
Metallic Screen
7)
Metallic Sheath
N.B: The calculation of short circuit current shall consider the flow of the
current in the metallic layers on parallel basis.
8)
Armour
The cable shall be armoured over the lead alloy sheath, using stainless steel
tapes or Tine Bronze or copper tape A suitable bedding of extruded PVC under
the armour shall be used.
9)
10)
Graphite Coating
3.4.A.2
The XLPE cables for 132kV should comply generally with the requirements of latest IEC
840-88
1)
Conductor
The conductor shall be water sealed by adding a swelling material between the
conductor strands.
3)
Conductor Screen
This screen consists of an extruded layer firmly bonded to the XLPE insulation.
The material is a semi-conductive compound. The interface between the
screen and the insulation must be smooth as much as possible. The conductor
screen, the insulation and the insulation screen are to be extruded in one single
table
thermal and mechanical properties.
A non-hygroscopic semi conducting tape is to be applied between the
conductor and the extruded semi conducting material.
4)
Insulation
> tn - 0.1 tn mm
5)
Metallic Screen
Metallic Sheath
The cable shall be armoured over the lead alloy sheath, using stainless steel
tapes or Tine Bronze or copper tape A suitable bedding of extruded PVC under
the armour shall be used.
9)
10
10)
Graphite Coating
A thin layer of resin bonded graphite coating is to be applied to the anticorrosion covering to permit electrical tests.
3.4.A.3
83.
1)
Conductor
Same as 3.4.1.1 above, except that the cross sectional area of conductor is
300 sq.mm.
2)
Conductor Screen
Insulation
Insulation Screen
Same as 3.4.1.5 above
6)
Metallic Screen
11
Metallic Sheath
Same as 3.4.1.7 above except that, the nominal thickness of lead sheath
should not be less than 2.5 mm.
8)
Armour
Same as 3.4.1.9 above except that the PVC outer covering shall be 3 mm.
10)
Graphite coating
3.4.A.4
Conductors
The conductor shall be water sealed by adding a swelling material between the
conductor strands.
3)
Conductor Screen
12
Insulation
> tn - 0.1 tn mm
6)
Metallic Screen
Each core shall have separate metallic screen. The metallic screen shall consist
of a combination of plain annealed copper wires applied concentrically and
copper tapes applied helically semi conducting layer to be applied over the
copper tape (as bedding) The metallic screen shall be capable to carry the
return earth fault currents specified. However, the total cross-section of
copper screen, covering the three cores shall not be less than 35 mm2.
13
7)
The inner coverings and fillers shall be of materials suitable for the operating
temperature of the cable and compatible with the insulation. Fillers shall be
non- hygroscopic.
Inner covering material shall be PVC type 9 of table of BSS 67 46 - 84.
8)
Metallic Sheath
The cable shall be armoured over the lead alloy sheath, using stainless steel
tapes or Tine Bronze or copper tape A suitable bedding of extruded PVC under
the armour shall be used.
10)
Anti-Corrosion Covering
The cable shall have an outer covering of PVC jacket, the PVC shall conform to
type 9 of table 1 of BSS 6746 the nominal thickness of the PVC outer covering
shall be 3.6mm.
11)
Graphite Coating
A thin layer of resin bonded graphite coating is to be applied to the anticorrosion covering to permit electrical tests.
3.4.B
3.4.B .1 General