Professional Documents
Culture Documents
Rio de Janeiro
April 23-25, 2006
Transformer
protection IED
RET 670
Applications
Power transformers, including
autotransformers, reactors and
generator transformer blocks
Two or three vector group (or
winding) transformers
Single- or multi circuit breaker
arrangements
Three-winding Transformer
Three-winding variant up to
6 restraint three-phase CT
inputs
Ensures enhanced throughfault stability for multibreaker arrangements
Auto Transformer
Phased segregated
biased differential
protection for
Autotransformers in 1 CB
applications
Serial and common
windings
Up to 4 three-phase CT
inputs
Project aspects
Cooperation between End
User, Relay Manufacturer &
PST Manufacturer is of
outmost importance
Back-up protection
functionality
Differential Protection
Two-winding or three-winding functions
Two-winding variant up to 4 three-phase CT inputs
Enhanced through-fault stability for multi-breaker arrangements
Differential Protection
A differential current does not always mean there is a
fault in the transformer
Inrush current in power transformers
Saturation of current transformers
Overexcitation
Tap changer position
etc.
Differential Protection
Ability is included to handle two tap changers, i.e. one
tap changer per winding on any two windings
Functionality
Three-section settable restrain characteristic
High set unrestrained operation
Idiff
Idunre
Unrestrained operation
operate
1.0 pu
restrain
Idmin
1.25 pu
2006-04-20 PTSX Gunnar Stranne
15
Ibias
Delayed trip of
the restrained
differential
function due to
the traditional
use of second
harmonic blocking
(Set level 15 %)
Overvoltage Stabilization
The fifth
harmonic
component
is used for
stabilization
Magnetizing current at
system overvoltage
iL1
iL2
iL3
0
-1
-2
-3
Differential Protection
DIFP- application
Differential Protection
Blocking condition:
2nd harmonic, 5th harmonic
waveblock, cross block
Neg Seq Int / internal
Ext Fault
Discriminator sensitive
restrained
&
&
TRIP
unrestrained
START
Differential Protection
IminNegSeq
2% - 20%
Default 4%
NegSeqROA
30 120
Default 60
excursion
from 0 degrees
due to
CT saturation
60
120
35 ms
30
150
180
external
fault
region
0.5 kA
210
330
1.0 kA
definitely
an internal
fault
240
300
1.5 kA
trip command
in 12 ms
Internal
fault
declared
7 ms after
internal
fault
occurred
270
HV side contribution to the total negative sequence differential current in kA
Directional limit (within the region delimited by 60 degrees is internal fault)
2006-04-20 PTSX Gunnar Stranne
24
If one or
the other
of currents
is too low,
then no
measurement
is done
60 (negSeqROA = 60 deg)
120
150
30
180
External
fault
region
20 A
210
10
19
330
steady-state
position
for this
internal
fault
Internal fault
declared
12 ms after
fault
30 A
40 A
240
50 A
300
270
Contribution to total neg. seq. diff. current from HV side (in A)
Directional limit (within negSeqROA degrees is internal fault)
The operating time is about 30ms for very lowlevel turn-to-turn faults
This sensitive negative sequence protection is
blocked for high fault current conditions
2006-04-20 PTSX Gunnar Stranne
26
Step : 1 % transformer
rated current
0
6
1.25 pu
External fault
zone of protection
IL1
IL1
IL2
IL2
IL3
IL3
3I0
IN
IFAULT
IN
IFAULT
zone of protection
IN
3I0
internal fault
3I0
external fault
ROA
MTA
ABB Power Technologies AB, 2005
reference is
neutral current
-IN
operate for
internal fault
IN
ROA
restrain for
external fault
3I0
ROA
MTA
operate for
internal fault
ROA
-IN
restrain for
external fault
reference is
neutral current
Differential Protection
Switch-on-to-fault
Built-in logic to improve operating speed for
switch-on-to-fault condition
Possible to record the differential currents and/or bias
current by the disturbance recorder channels 31-40
Differential currents
Instantaneous or RMS
Bias current
RMS
TRIP
START
I3P
I1
I2
I3
I3P
I1
I2
I3
I3P
I1N
REFx
I1
I3PRI1
I3PRI2
I3SEC1
I3SEC2
RMS
Bus differential
Overexcitation Protection
V/Hz measurement
Positive sequence or single phase-to-phase voltage
Transformer magnetic core cooling time constant setting
IEEE inverse time and User defined trip curves available
49-1
Ith
86/94
I->O
49-1
Ith
86/94
I->O
Over frequency
Generation shedding
Remedial action schemes
Rate-of-change of frequency
Generation shedding
Load shedding
DR
50BF
3I>BF
50/51-1
3I>
51N-1
86/94
I->O
87N-1
Ind>
87T
3Id/I>
52PD
PD
87N-2
Ind>
59N
UN
24
U/f>
59N
UN
59
3U>
51N-2
50BF
3I>BF
25/27
SC/VC
90
VCTR
50/51-2
3I>
59
3U>
27
3U<
60
FF
DR
O5
O4
O2
27
3U<
60
FF
81O/81U
f</>
86/94
21
Z<
I->O
Contr
Interl
O1
O3
50BF
3I>BF
2* SC/VC
DR
50BF
3I>BF
51N-1
50/51-1
3I>
86/94
I->O
87N-1
Ind>
87T
3Id/I>
SC/VC
O6
O4
O5
O2
27
3U<
50/51-2
3I>
86/94
I->O
21
Z<
59
3U>
27
3U<
60
FF
52PD
2* PD
59
3U>
25/27
O8
59N
UN
51N-2
50BF
3I>BF
2* f</>
50BF
3I>BF
59N
UN
60
FF
81O/81U
24
U/f>
87N-2
Ind>
O7
DR
Contr
Interl
O1
O3
RET 670-A20
86/94
I->O
60
FF
25/27
O6
SC/VC
24
U/f>
O4
51N-3
51N-1
50BF
3I>BF
87N-1
Ind>
87T
3Id/I>
87N-3
INd>
87N-2
Ind>
59N
UN
59N
UN
50/51-3
3I>
59
3U>
51N-2
50BF
3I>BF
25/27
SC/VC
60
FF
2006-04-20 PTSX Gunnar Stranne
41
50/51-2
3I>
59
3U>
27
3U<
DR
O2
27
3U<
60
FF
O5
86/94
I->O
86/94
I->O
21
Z<
O1
Contr
Interl
81O/81U
f</>
52PD
PD
O3
O7
RET670 B40
DR
50BF
3I>BF
51N-1
50BF
3I>BF
50/51-1
3I>
86/94
I->O
24
U/f>
87N-1
Ind>
87T
3Id/I>
25/27
SC/VC
59
3U>
42
60
FF
DR
O4
O5
59N
UN
59
3U>
27
3U<
87N-3
INd>
50/51-2
3I>
O6
51N-2
50BF
3I>BF
O8
51N-3
59N
UN
60
FF
52PD
PD
60
FF
25/27
O7
SC/VC
87N-2
Ind>
50BF 50/51-3
3I>BF 3I>
f</>
86/94
I->O
86/94
I->O
O2
27
3U<
21
Z<
Contr
Interl
O1
O3
Benefits of RET670
Functional flexibility
Configuration flexibility
High performance
User friendly
Pre-defined packages
IED 670 series member means;