You are on page 1of 2

Unitron

UC Controllers

UC16PG-R

UC16PG-R Universal Programmable Controller with Relay output


DESCRIPTION
The UC16PG-R is a programmable controller, with 8 inputs and 8 outputs.

DIN rail

MECHANICAL
Size

225 x 130 x 45 mm

Enclosure

Injection moulded ABS

Mounting

DIN rail

130mm

(8.86 x 5.12 x 1.78")

ENVIRONMENT
Ambient Temperature
Ambient Humidity
EMC Immunity
EMC Emission

Note: This equipment is intended for field installation within


another enclosure.
0% - 90% RH non-condensing
0 - 50C (32-122F) ambient.
EN 50082-1
EN55011 Class B

225mm
Injection
Moulded
ABS
enclosure

WIRING
Termination
Conductor Area

PCB mounted plug terminal connections.


Max: AWG 12 (3.09 mm2)
Min: AWG 22 (0.355 mm2)
Note: Use Copper or Copper Clad Aluminium conductors only.

ELECTRICAL
Supply Requirements
Power Rating

24 V AC +/- 20% 50/60 Hz


10 VA

Fuse Rating

2 A anti-surge (250 V AC - 2AT)

45mm

PROCESSOR
Type

Motorola 68HC11

Clock Speed

8 MHz

Operating System Memory

128K

User Programmable Memory


Real-Time Clock

128K RAM Battery backed for 2 years minimum


Battery backed for 2 years minimum

INPUTS/OUTPUTS
8 Universal Inputs

8 Universal Outputs

Note: Screened cable is recommended for all input connections.


Active voltage input: 0-10 V@ 134 K
Passive input recommended sensor: PT1000
Resolution: 12 bits (with exponential filter applied to the input block in the controller's strategy)
Note: 10k option controllers use 10k3A1 sensors only
Active current input: 0-20 mA @ 120 (screened cable)
Digital Volt Free Contact: Pulse up to 12 Hz, minimum pulse width 42ms.
Jumper selectable: 0 10 V DC 10mA max
or 24 V AC Relay, 2 A continuous / 15 A max inrush.

COMMUNICATIONS
Local RS232 TTL port

@ 1200, 2400, 9600, 19200 or 38400 Baud

Network RS485 port

@ 1200, 2400, 9600, 19200 or 38400 Baud

Keypad port

@ 9600 Baud, RJ11 socket

Modem

Modem connection supported through RS232 service port

INTERFACE
Software

WN3000 software suite, Unitron Palmtop program

Remote Keypad

UCKRA420 Serial Text Keypad connected via RJ11 port


Maximum cable length 50m

SOFTWARE FEATURES
Maximum number of strategy blocks

255

Maximum number of Datalog Modules 16


Maximum Datalog Module capacity

192 entries per Datalog

Maximum Controller Address

16
Note: The maximum controller address is 8 for UC16PG-R controllers with firmware versions of 5.5.0 or earlier.
Cylon Controls Limited
Clonshaugh Industrial Estate
Clonshaugh
Dublin 17
Ireland
Tel: +353 (0) 1 2450 500
Fax: +353 (0) 1 2450 501
Email: askus@cylon.ie

Cylon Controls UK Limited


50 Centenary Business Centre
Hammond Close
Attleborough Fields
Nuneaton
Warwickshire CV11 6RY
Tel: (024) 7632 7777
Fax: (024) 7632 7878
Email: askus@cylon.ie

Due to Cylon's policy of continuous improvements these specifications may be upgraded without notice.

UCDS0032 rev 3.00

Cylon Controls Limited

UC Controllers

Keypad
Port

Universal Input Ports

10 11 12

BUS
A B
35 36
8

DIP

ON

J1

V
I
P

V
I
P

GND

V
I
P

V
I
P

GND

V
I
P

GND

V
I
P

GND

V
I
P

V
I
P

RS485 Network
Terminator Terminator

Legend

IN

Legend

V
I
P

Pins covered
by jumper

Pins open

Pins open

Terminator
OUT
Terminator
OUT

LINK1

Pins covered
by jumper

0-10 V
input

LINK1

V
I
P

0-20 mA
input

LINK1

U/I 7+

U/I 6+

CMN

U/I 5+

RS485 Network
Port

U/I 4+

U/I 8+

CMN

CMN

U/I 3+

V
I
P

U/I 2+

V
I
P

Passive
input

CMN

Volt free
contacts

U/I 1+

Universal Input Selection Jumpers

UC16PG-R

LINK1

Unitron

Address/Baud-Rate Selector Switch


1

RS232
Service Port

Binary 1
Binary 0

ON

DIP

Sub-Network Baud MSB


LSB
Sub-Network Address
Rate
7

The Baud Rate of the


controller on the SubNetwork is set on DIP
switches 6,7, and 8:

Baud Rate
9600 baud

DIP
6

8
1200 baud

19200 baud

DIP

unitron

DIP

38400 baud

2400 baud

UC16PG-R

DIP

DIP
Sub-Network Address

The address of the controller on the Sub-Network is set on


these DIP switches as binary numbers as illustrated in the
examples below:
LSB
MSB

Binary 1

ON
MSB

LSB

Address 16

Relay pack
'Quick Connector'

Address 1

Binary 0

"Watchdog" LED
(green)
Binary 1
Binary 0

"Power On" LED


(red)

ON

Universal Output Configuration


0-10 V 1
Jumpers

1
2
3

Fuse
COM

10

11

12

13

14

15

16

GND

Output 2

23

24

U/O 14+

U/O 16+

CMN

CMN

33

34

24V AC

22

CMN

20 21

U/O 15+

18 19

U/O 13+

17

U/O10+

15 16

RLY CMN

Note:
To avoid potential damage to controller
during installation, it is recommended that
RLY CMN be connected to a fused 24 V AC
supply.

13 14

U/O 12+

Pins open

U/O 11+

U/O 9+

(24 V AC only)

Legend
Pins covered
by jumper

RLY CMN

Relay 2

Power input (24v AC)


IMPORTANT
Earth this controller by connecting the CMN
wire (Go), on the secondary side of the 24 V AC
transformer, to Earth at one point.

Universal
Output Ports

Note:
Outputs which are configured as relay outputs must use terminals 13 and
14 (RLY CMN) as their common point.

Controller
Internal
Connections

Digital Inputs and Outputs configured as Universal Outputs must use


terminals 23 and 24 (CMN) as their common point.

Controller
Terminals

24V AC
CMN

CMN

Cylon Controls Limited

33 34

CMN

UCDS0032 rev 3.00

13 14 15 16 17 18 19 20 21 22 23 24

RLY CMN
RLY CMN

This is because inside the UC controller, terminals 13 and 14 (RLY CMN)


are connected to the relays only, whereas terminals 23 and 24 are
connected to the Power Input's CMN line on pin 33 as shown in this
diagram: