Professional Documents
Culture Documents
Fire blanket
Manual
Fire bucket
Fire extinguisher
Automatic
(INDOOR).
FHS series audible / visual signals can be
connected either independently or in unison.
The horn can be silenced while the strobe
remains flashing.
(1) Alarm actuated by heat, gas, smoke, flamesensing devices, or waterflow in a sprinkler
system conveyed to local alarm bells or the fire
station. (2) Alarm boxes that automatically
transmit a coded signal to the fire station to
give the location of the alarm box. - Automatic
Alarm
(1) Alarm system that alert and notifies only
occupants on the premises of the existence of a
fire so that they can safely exit the building and
call the fire department. If a response by a
public safety agency (police or fire department)
is required, an occupant hearing the alarm must
notify the agency. - Protected Premises Alarm
System
(1) Connecting link device that fuses or melts
when exposed to heat. Used in sprinklers, fire
doors, dampers, and ventilators. (2) Two-piece
link held together with a metal that melts or
fuses at a specific temperature. Also known as
Fusible Link. - Fusible Device
1. A common term for the most basic alarm
system is:
A. Alert system
B. Fire detection system
C. Water control system
D. Local warning system - D
1. A system of water pipes, discharge nozzles,
and control valves designed to activate during
fires by discharging enough water to control a
fire is formally known as a(n):
A. Water control system.
B. Automatic sprinkler system.
C. Fire Extinguishment system.
D. Downpour discharge system. - B
10. Where are control valves usually located?
A. Separate from the sprinkler system.
B. Immediately above the sprinkler alarm
valve.
C. Outside the building far away from the
system they control.
A. Rate-compensated detector
B. Hydraulic rate-of-rise spot detector
C. Pneumatic rate-of-rise line detector
D. Pneumatic rate-of-rise spot detector - D
11. What is an indicating control valve?
A. Ionization detector
B. Ion/current detector
C. Electricity-based detector
D. Beta particle energy detector - A
2. Fire pumps and foam extinguishing systems
that sense heat, smoke, or gas and activate
automatically are known as:
A. Flame control systems.
B. Water control systems.
C. Automatic control systems
D. Automatic suppression systems. - D
2. The temperature of the surrounding
environment is known as:
A. Climate
B. Weather
C. Normal temperature
D. Ambient temperature - D
20. Which of the following detectors generally
responds faster to flaming fires than
smoldering ones and automatically resets when
the atmosphere has cleared?
A. Ionization detector
B. Thermoelectric detector
C. Rate-compensated detector
D. Pneumatic rate-of-rise spot detector - A
20. Which of the following types of sprinkler
systems is the simplest type and generally
requires little maintenance?
A. Dry-pipe
B. Wet-pipe
C. Pre-action
D. Residential - B
21. An alarm device used in some fire
detection systems that detects light in the
ultraviolet wave spectrum is a(n):
A. Light detector
B. Flame detector
C. Ultraviolet wave alarm
D. Pneumatic rate-of-rise spot detector - B
21. Newer wet-pipe systems with a back-flow
prevention check valve and an electronic flow
alarm are sometimes referred to as:
A. Mobile systems
B. Straight stick systems
C. Crooked stick systems
D. Back-flow alarm systems - B
22. Which of the following is a chamber that
catches excess water that may be sent through
the alarm valve during momentary water
pressure surges?
A. Retard chamber
B. Holding chamber
C. Water surge chamber
D. Alarm valve overflow chamber - A
22. Which of the following is NOT one of the
three basic types of flame detectors?
A. Those that detect no light
B. Those that detect only UV light
C. Those that detect only IR light
D. Those that detect UV and IR light - A
23. A device used to detect gases produced by
a fire within a confined space is a:
A. Fire-gas detector
B. Confined gas alarm
C. Combination detector
D. Fuel-containment alarm - A
23. Which of the following is a firesuppression system that consists of closed
sprinklers attached to a piping system that
contains air under pressure?
A. Dry-pipe
B. Wet-pipe
C. Deluge
D. Residential - A
24. The required air pressure for dry-pipe
systems is usually about:
A. 20 psi (140 kPa) above the trip pressure.
B. 20 psi (140 kPa) below the trip pressure.
C. 40 psi (280 kPa) above the trip pressure.
D. 40 psi (280 kPa) below the trip pressure. - A
24. Which of the following is an alarminitiating device capable of detecting an
abnormal condition by more than one means?
A. Fire-gas detector
B. Confined gas alarm
C. Combination detector
D. Fuel-containment alarm - C
25. An alarm actuated by heat, gas, smoke, or
water-flow in a sprinkler system conveyed to
local alarm bells or the fire station is a(n):
A. Preset alarm
B. Automatic alarm
C. Self-actuated alarm
D. Fire station notification alarm - B
25. Dry systems that employ a deluge-type
valve, fire detection devices, and closed
sprinklers are known as:
A. Deluge systems
B. Pre-action systems
C. Residential systems
D. Closed detection systems - B
26. What is a local energy system?
A. Deluge system
B. Pre-action system
C. Residential system
D. Industrial occupancy system - C
31. A fire protection system owned and
operated by the property owner is commonly
known as a(n):
A. Flooding detector
B. Pre-discharge
C. Disaster-aversion
D. Discharge notification signal - B
35. Which of the following statements
regarding auxiliary services is MOST accurate?
A. Fire alarm systems hinder evacuation.
B. Fire detection systems cannot override
elevator controls.
C. Fire detection systems detect toxic and
combustible gases.
D. The primary objective of a fire alarm system
is to alert the media. - C
36. A vertical water pipe used to carry water
for fire protection systems above ground is a:
A. Riser
B. Carry
C. Supplier
D. Water lift - A
37. What pipe connects the riser to the cross
mains?
A. Feed main
B. Branch main
C. Water rise pipe
D. Cross connection pipe - A
38. Which of the following components
directly service a number of branch lines on
which the sprinklers are installed?
A. Heads
B. Risers
C. Feed mains
D. Cross mains - D
39. The water-flow device in a sprinkler system
is known as a:
A. Link
B. Bulb
C. Pellet
D. Sprinkler - D
4. A temperature-sensitive device that senses
temperature changes and sounds an alarm at a
specific point is a(n):
A. No-temperature heat detector.
B. Fixed-temperature heat detector.
C. Temperature change heat detector.
D. Ambient-temperature heat detector. - B
4. Sprinklers in an automatic sprinkler system
are sometimes called:
A. Sprinkler sets
B. Watering pipes
C. Sprinkler heads
D. Individual setups - C
40. Which of the following components holds
the levers together until the link is melted by
the heat of a fire?
A. Sprinkler
B. Fusible link
C. Chemical pellet
D. Frangible bulb - B
41. A small nodule filled with liquid and an air
bubble to hold the orifice shut is a:
A. Sprinkler
B. Fusible link
C. Chemical pellet
D. Frangible bulb - D
42. Which of the following sprinkler
components allows a plunger to move down
and release the valve cap parts?
A. Sprinkler
B. Fusible link
C. Chemical pellet
D. Frangible bulb - C
43. The most common type of sprinkler is the:
A. Upright
B. Pendant
C. Sidewall
D. Special-purpose - B
44. The sprinkler that screws into the top of the
piping and discharges water into a solid
deflector that breaks it into a hemispherical
spray pattern directed at the floor is the:
A. Upright sprinkler
B. Pendant sprinkler
C. Sidewall sprinkler
D. Special-purpose sprinkler - A
45. The sprinkler that extends from the side of
a pipe and is used in small rooms where the
branch line runs along a wall is a(n):
A. Upright sprinkler
B. Pendant sprinkler
C. Sidewall sprinkler
D. Special-purpose sprinkler - C
46. Which of the following types of sprinklers
includes those with corrosive-resistant
coatings?
A. Upright
B. Pendant
C. Sidewall
D. Special-purpose - D
47. A minimum water supply has to deliver the
required volume of water to the highest
sprinkler in a building at a residual pressure of:
A. 10 psi (70 kPa)
B. 15 psi (105 kPa)
C. 20 psi (140 kPa)
D. 25 psi (175 kPa) - B
48. Sprinkler fire department connections
should be supplied with water from pumpers
that have a capacity of at least:
A. 1,000 gpm (4,000 L/min)
B. 1,500 gpm (6,000 L/min)
C. 2,000 gpm (8,000 L/min)
D. 2,500 gpm (10,000 L/min) - A
49. The sprinkler that is the simplest and
requires little maintenance is the:
A. Dry-pipe
B. Wet-pipe
C. Pre-action
D. Residential - B
5. A small glass vial fitted into the discharge
orifice of a fire sprinkler is the:
A. Fusible device
B. Frangible bulb
C. Two-piece link
D. Resistance indicator - B
5. Which of the following is a sprinkler system
that protects an entire building?
A. Partial sprinkler system
B. Complete sprinkler system
C. Small-facility sprinkler system
D. Large-facility sprinkler system - B
50. Which of the following is a newer wet-pipe
system with a back-flow prevention check
valve and an electronic flow alarm?
A. Mobile systems
B. Straight stick systems
C. Crooked stick systems
D. Back-flow alarm systems - B
51. The chamber that catches excess water that
may be sent through the alarm valve during
momentary water pressure surges is the:
A. Retard chamber
B. Holding chamber
C. Water surge chamber
D. Alarm valve overflow chamber - A
52. The fire-suppresion system that consists of
closed sprinklers attached to a piping system
that contains air under pressure is known as a:
A. Dry-pipe system
B. Wet-pipe system
C. Deluge system
D. Residential system - A
53. What is usually the required air pressure for
dry-pipe systems?
A. 20 psi (140 kPa) above the trip pressure.
A. Bimetallic detector
B. Continuous line detector
C. Rate-of-rise heat detector
D. Rate compensated detector - B
8. Which of the following is a reason that a
sprinkler system may not perform?
A. Open water valve
B. Painted-over sprinklers
C. Objects stacked far apart
D. Lack of debris in the pipes - B
8. Which of the following types of heat
detectors uses two metals that have different
thermal expansion characteristics?
A. Bimetallic detector
B. Continuous line detector
C. Rate-of-rise heat detector
D. Pneumatic rate-of-rise spot detector - A
9. A temperature-sensitive device that sounds
an alarm when the temperature changes at a
preset value is a:
A. Bimetallic detector
B. Continuous line detector
A. Deluge system
B. Pre-action system
C. Residential system
D. Industrial occupancy system - C
6. The two-piece link held together with a
metal that melts or fuses at a specific
temperature is a:
A. Standard link
B. Fusible device
C. Frangible bulb
D. Resistance indicator - B
6. Which of the following is a sprinkler system
that only protects high-hazard areas?
A. Partial sprinkler system
B. Complete sprinkler system
C. Small-facility sprinkler system
D. Large-facility sprinkler system - A
7. Which of the following NFPA standards is
used as a guide for installing sprinkler
protection in one- and two-family dwellings?
A. 13A
B. 13B
C. 13 C
D. 13 D - D
A. Three (3)
B. Four (4)
C. Five (5)
D. Six (6) - D
A type of control valve for a sprinkler system
in which the position of the center screw
indicates whether the valve is open or closed. OS&Y Valve
A type of valve used to control underground
water mains that provides a visual means for
indicating "open" or "shut" position; found on
the supply main of installed fire protection
systems. - Post Indicator Valve (PIV)
Alarm that sounds before a total flooding fire
extinguishing system is about to discharge.
This gives occupants the opportunity to leave
the area. - Predischarge Alarm
Alarm-initiating device capable of detecting an
abnormal condition by more than one means.
The most common combination detector is the
fixed-temperature/rate-of-rise heat detector. Combination Detector
Alarm-initiating device designed to actuate
when visible or invisible products of
combustion (other than fire gases) are present
in the room or space where the unit is installed.
- Smoke Detector
Approximately what percentage of all fires are
controlled by the activation of five or fewer
sprinklers?
A. 50%
B. 60%
C. 70%
D. 80% - C
Automatic sprinkler designed for placement
and operation with the head pointing
downward from the piping. - Pendant Sprinkler
Chapter 16: IFSTA Q's - ...
Chapter 16: Key Terms - ...
Chapter 16: Study Guide - ...
Chapter 16: Study Guide FFII - ...
Contemporary emergency signaling systems
may integrate a number of process and
environmental
controls,
security,
and
personnel-access controls. These include:
A. Upright type.
B. Sidewall type.
C. Pendant type.
D. Special purpose type. - C
The three basic types of auxiliary systems
include the local energy system, shunt system,
and:
A. 40F (4C)
B. 50F (10C)
C. 60F (15.5C)
D. 70F (21C) - A
What is the primary difference between a
central station system and a proprietary
system?
A. Manual levers.
B. Fusible wedges.
C. Check valves.
D. Chemical pellets. - D
The two basic types of smoke detectors/alarms
are:
A. Wet-pipe
B. Dry-pipe
C. Preaction
D. Deluge - C
When do fixed-temperature heat detectors
activate?
A. fixed-temperature
B. sectional perceptive
C. central proprietary
D. Rate-of-Rise - D
Which series of NFPA standards specifically
address automatic sprinkler systems?
A. NFPA 13 series
B. NFPA 400 series
C. NFPA 1000 series
D. NFPA 1500 series - A
Which two fire-gases are the two most
practical to monitor using a fire-gas detector?
Rate-Compensated
Heat
Detector
Temperature-sensitive device that sounds an
alarm at a preset temperature, regardless of
how fast temperatures change.
Rate-of-Rise Heat Detector - Temperaturesensitive device that sounds an alarm when the
temperature changes at a preset value, such as
12-15F per minute.
Remote Station Alarm System - System in
which alarm signals from the protected
premises are transmitted over a leased
telephone line to a remote receiving station
with a 24-hour staff; usually the municipal fire
department's alarm communications center.
Riser - Vertical water pipe used to carry water
for fire protection systems above ground such
as a standpipe riser or sprinkler riser.
Sidewall Sprinkler - A sprinkler designed to be
positioned at the wall of a room rather than in
the center of a room. It has a special deflector
that creates a fan-shaped pattern of water that is
projected into the room away from the wall.
Also called Wall Sprinkler.
Smoke Alarm - a device designed to sound an
alarm when the products of combustion are
present in the room where the device is
installed. The alarm is built into the device
rather than being a separate system.
Smoke Detector - Alarm-initiating device
designed to actuate when visible or invisible
products of combustion (other than fire gases)
are present in the room or space where the unit
is installed.
Sprinkler - Waterflow device in a sprinkler
system. The sprinkler consists of a threaded
nipple that connects to the water pipe, a
discharge orifice, a heat-actuated plug that
drops out when a certain temperature is
reached, and a deflector that creates a stream
pattern suitable for fire control.
Upright Sprinkler - Sprinkler that sits on top of
the piping and sprays water against a solid
deflector that breaks up the spray into a
hemispherical pattern that is redirected toward
the floor.
Wet-Pipe Sprinkler System - Fire-suppression
system is built into a structure or site; piping
contains either water or foam solution
continuously; activation of a sprinkler causes
Situations that sprinklers are effective in preventing fire spread upwards in multistory
buildings
protecting the lives of occupants
Sprinkler FDC - should be supplied with water
from pumpers that havee a capacity of at least
1,000gpm with a minimum of two 2.5" or
larger hoses.
Sprinkler system may not function for the
following reasons - partially or completely
completely closed main water control valve
Interruption to the water supply
damaged or painted over sprinklers
damaged pipes
debris/sediment in the pipes
failure of the secondary water supply
tampering/vandalism
sprinklers obstructed by objects stacked too
close
Sprinkler Temp ratings - black/uncoloured ordinary - 135-170F
White - intermediate - 175-225F
Blue - High - 250-300F
Red - Extra high - 325-375F
Green - Very Extra High - 400-475F
Orange - Ultra High - 500-575F
Bad White Girls Rape Girls Often
Times when they are not effective - fires are
too small to activate the system
smoke generation reaches occupants before the
system starts
sleeping, drunk, handicapped persons occupy
the building
Types of Control Valves - four main types
1. OS & Y
2. Post Indicator
3. Wall Post Indicator
4. Post Indicator Valve Assembly
Upright - Screwed into the top of the piping
and discharges water into a solid deflector, that
breaks it into a hemispherical spray pattern that
is redirected to the floor. Cannot be changed
into the pendant position.
WAter supply - every effort should be made to
supply adequate to operating sprinkler system
Water supply - Minimum water supply has to
delive the required volume of water to the
highest sprinkler at a residual pressure of 15psi.
Depends on the hazard, occupancy, and the
Polyethylene,
to