You are on page 1of 16

ACP 1703 Ax 1703

CM-0821
Fieldbus Interface Ring (3x FO, 1x el.)

Bus interface for an optical field bus or


multi-point traffic as

optical ring or
optical star

Features:

Copyright Siemens AG 2007

3 optical transmitter and receiver for


each channel (ST-connector)
for optical fibres up to 1300m long
1 electrical interface V.28 (RJ45-plug)
for patch cable up to 3m long
Transmission rate max. 115.2kbps
Power supply alternatively
via the electrical interface, or
via PS-663x or PS-6621

MC0-031-2.01

Application

CM-0821 is used for the construction of networks with optical or electrical branching (signal
add/drop to/from ring):

Modes of operation
IEC 60870-5-101 Balanced Point-Point (point-to-point-traffic, full-duplex)
IEC 60870-5-101 unbalanced multi-point (multi-point traffic)
IEC 60870-5-103 unbalanced multi-point (multi-point traffic)

Network structure
Ring

redundant masters

(redundant) bi-directional communication in the ring

signaling of a ring interruption

Star, tree

redundant masters

Up to 115.2 kbps transmission rate

3 optical transmit and receive channels


Receive channel stuck at zero monitoring

1 electrical interface V.28


Power supply
Via the electrical interface

can supply power to one module only

PS-6630 or PS-6632

redundant power supply is supported (but not to increase power)

PS-6621
Not more than 6 CM-0821 modules on a power supply PS-663x or PS-6621

Differences between versions --, -A, -B, -C, -D


At present there are three versions of CM-0821 with the following differences
Version --

Version -A

GA0-821--

GA0-821-A

GA0-821-B / -C / -D

Designation in data sheet

CM-0821--

CM-0821-A

CM-0821-B / -C / -D

Supported configurations

Star

Star

ring, star

Star

Star

ring, star

Redundant masters
Balanced point-point
Recognizable outside
differences

Version -B/ -C / -D

Item numbert

from version -D
DIP-switch S2
not present

DIP-switch S2
has 2 switches

DIP-switch S2
has 3 switches

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Configurations

Star, singular master, up to max. 2 slaves

CH2

CH1

CH4

Master

Slaves

Star, redundant masters, > 2 slaves


redundant
masters

CH2

CH1

CH2

CH1

CH4

CH3

CH4

CH3

CH4

CH3
CH1

CH2

CH1

CH2

CH3

CH4

Slaves

Slaves

PS-663x PS-663x CM-0821

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

CM-0822

Ring, redundant masters

CH4

CH4

Slave

Slave

Slave

Slave

CH1

CH2

CH2
CH1

CH1
CH4

CH2

CH2
CH1

CH2
CH4

CH1

CH4

CH2

CH1

CH4

redundant masters

Further configurations see ACP 1703 Platforms Configuration Automation Units and
Automation Networks.

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Features Ring

1 CM-0821 per branch

Supports redundant masters (2 branches)

Channels 3 (CH3, optical) and 4 (CH4, electrical) together can be set for a connection in
direction to a master or in direction to the slaves

Channel 3 (CH3, optical)


transmission rate for stuck at zero monitoring can be set using DIP switch
line-idle state can be set using DIP switch

Using channels 1 (CH1) and 2 (CH2), the ring is made

Features Star / Tree

1 CM-0821 and up to 7 CM-0822 can be attached side by side

Supports redundant masters (optically and electrically connected)

Channels 3 (CH3, optical) and 4 (CH4, electrical) together are set for a connection in
direction to a master

Channels 1 (CH1) and 2 (CH2) connect to one slave each

Optical channels
transmission rate for stuck at zero monitoring can be set using DIP switch
line-idle state can be set for each interface using DIP switch

Protocol Elements that support Power Supply and Signaling


The following protocol elements support supplying power to the CM-0821 and signaling a ring
interruption over the serial interface:
Protocol Elements

Designation

SM-2551/UMPMA0
SM-2551/UMPSA0

Standard Protocol for Multi-Point Traffic

SM-2551/SFBMA1
SM-2551/SFBSA1

Standard Protocol for Field Bus

SM-2551/103MA0
SM-2551/103SA0

Standard Protocol for Interfacing of Protective Devices

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Block Diagram (Module)

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Block Diagrams Data Flow

Ring

CM-0821

from/to either
master or slave

Rx_3

Tx_3

Rx_4

Tx_4

TTL_ Bus

ring administrator

Rx_1

Tx_1

Tx_2

Rx_2

ring

Star / Tree (Module Row)

Rx_3

Tx_3

Rx_4

from/to slaves

Tx_4

CM-0822

CM-0821

from/to redundant masters

Rx_3

Tx_3

Rx_4

TTL_ Bus

Tx_1

Rx_1

Tx_2

Rx_2

Tx_4

TTL_ Bus

Tx_1

Rx_1

Tx_2

Rx_2

from/to slaves

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Technical Specifications

Interfaces
Optical interfaces

Multimode glass fibre optic:


(1) 50/125m fibre
(2) 62.5/125m fibre

channel 1 (CH1, X1/X2)


channel 2 (CH2, X3/X4)
channel 3 (CH3, X5/X6)

(typ. 2.3dB/km)
(typ. 3.0dB/km)

max. 115.2kbps
max. 115.2kbps

In a ring configuration, because of higher data rate, a


62.5/125m fibre must be used in the ring.

Transmitter (820nm):
Power launched into the fibre:
(1)
(2)

(1), (2)
Data rate RD:

-18.8dBm
-15dBm

max

min

-10dBm

-40dBm

max. 115.2kBit/s

Line lenghts (3dB system reserve):


(1)
(2)

-13.8dBm
-10dBm

min

Receiver (820nm):
Received power:

max

0 .. 0.5km
0 .. 1.3km in the ring
0 .. 1.5km else

V.28 asynchronous
Status signal for ring interruption signaling
allwos to supply power via the electrical interface
For connecting patch cables (RJ45 connector), 3m
maximum length
Data rate max. 115.2kBit/s

in the Ring
(CH1  CH2)

TCH1CH2 [s]

= 8,65 + (6,25*105) / RD [Bit/s]

add to ring
(CH3/CH4  CH1/CH2)
drop from ring
(CH1/CH2  CH3/CH4)
in the optical fibre

TCH3/CH4CH1/CH2 [s]

= 4,78 + (5*105) / RD [Bit/s]

TCH1/CH2CH3/CH4 [s]

= 11,5 + (6,25*105) / RD [Bit/s]

Approx. 5ns/m (approximate value)

Electrical interface
channel 4 (CH4, X8)

Signal propagation delays


Ring

The signal propagation delays do not depend on direction.


Note:
In order to obtain the total signal propagation delay from one
master to one specific slave, the above mentioned signal
propagation delays and the signal propagation delay of all fibre
optics sections have to be taken into consideration (see an
example in ACP 1703 Platforms Configuration Automation Units
and Automation Networks)

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Signal propagation delays


Star / Tree
Between CH3/CH4 in the
CM-0821 and an optical channel
in the same CM-0821
(CH1  CH2)
in a CM-0822 of the same
row
(CH1/CH2/CH3/CH4)
in the optical fibre

TCH3/CH4CH1/CH2 [s]

= 4,78 + (5*105) / RD [Bit/s]

TCH3/CH4CM-0822/CHx [s] = 4,78 + (5*105) / RD [Bit/s]

approx. 5ns/m (approximate value)

The signal propagation delays do not depend on direction.


Note:
In order to obtain the total signal propagation delay from one
master to one specific slave, the above mentioned signal
propagation delay (in cascaded structures: repeatedly, if
applicable) and the signal propagation delay of all fibre optics
sections have to be taken into consideration (see an example in
ACP 1703 Platforms Configuration Automation Units and
Automation Networks)
Power Supply
Operating voltage

3.5 .. 5.25 VDC, typ. 0.5W .. 1W (depending on the set line-idle


state)
Power to be supplied by PS-663x or PS-6621

Mechanics and Connectors


Optical interfaces
Ring
channel 1 (CH1, X1/X2)
channel 2 (CH2, X3/X4)
channel 3 (CH3, X5/X6)

Multimode optical fibre (2)


Multimode optical fibre (2)
Multimode optical fibre (1), (2)

ST compatible
ST compatible
ST compatible

Star / Tree
channel 1 (CH1, X1/X2)
channel 2 (CH2, X3/X4)
channel 3 (CH3, X5/X6)

Multimode optical fibre (1), (2)


Multimode optical fibre (1), (2)
Multimode optical fibre (1), (2)

ST compatible
ST compatible
ST compatible

Electrical interface
channel4 (CH4, X8)

RJ45 8-pin according to IEC 60603-7

DIP switch

8 switches

Dimensions

131 x 63 x 73 mm (H x W x D, dimensions w/o DIN rail)

Weight

Approx. 160 g

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Engineering

Front View
CM-0821--

CM-0821-A

10

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

CM-0821-B / -C / -D

Connectors
CM-0821--, CM-0821-A, CM-0821-B / -C / -D

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

11

Settings
CM-0821--

12

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

CM-0821-A

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

13

CM-0821-B / -C / -D

14

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

Literature

ACP 1703 Platforms Configuration Automation Units and Automation


Networks

DC0-021-2

Data Sheet SM-x551/PROTOCOL

MC0-003-2

Data Sheet CM-0822

MC0-033-2

Data Sheet CM-0823

MC0-034-2

Data Sheet PS-663x

MC6-027-2

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

15

16

ACP 1703 Ax 1703, CM-0821


MC0-031-2.01, Edition 12.2007

You might also like