Professional Documents
Culture Documents
12 - 24 kV
630 - 1250 A
16 kA
DEMTA
POWER SYSTEMS
MODULER UNIT
DEMTA
POWER SYSTEMS
CONTENTS
Description
Unit Dimensions
Unit Types
Technical Data
Typical Units
Components
21
DESCRIPTION
GENERAL
DME series Metal enclosed units which are produced by our company,have been
designed and tested to be used for all energy distribution systems till 24 Kv
Moduler Metal Enclosed units appear as the optimal solution with their easiness of
taking operation by means of their moduler structure and with their module appositi
on characteristic for companies
DME series Metal enclosed unit are manufactured according to IEC Standards
Optimal dimensions
Long term technical solitions for various applications
High level personal safety
APPLICATIONS
Manufacturing industry
Secondary electricy distribution networks
Shopping malls
MV / LV distribution transformer substations
Small size power plants
Wind power plants
Airports, hospitals, holiday village
Enclosure of cubicle is 2 mm galvanized steel sheet. If desired al-zinc is
also possible. No welding during the assembling of the structure.
SAFETY
There is a survelliance window on the front cover of the every cubicle to
check inside the cubicle without open the door / cover
STANDARDS
Compliance with standards IEC 62271 - 200
DESCRIPTION
STRUCTURES
1. Busbar compartment
2. Cable compartment
UNIT DIMENSIONS
1600
1600
375
940
940
750
1100
UNIT TYPES
DME 24 - 01
UNIT TYPES
DME 24 - 04
DME 24 - 05
DME 24 - 02
DME 24 - 03
DME 24 - 11
1600
940
500
UNIT TYPES
DME 24 - 01 /A
DME 24 - 07
DME 24 - 07 / A
DME 24 - 09
DME 24 - 09 / A
DME 24 - 11 / A
1600
940
750
UNIT TYPES
DME 24 - 05 / A
DME 24 - 08
DME 24 - 08 / A
UNIT TYPES
Type DME 24 - 01
Switch Unit
Type DME 24 - 02
Fuse Switch Combination Unit
Type DME 24 - 03
Switch Unit and Metering
Type DME 24 - 04
Circuit Breaker Unit
Type DME 24 - 05
Sectionalising Metering Unit
Type DME 24 - 05 / A
Sectionalising Metering Unit
with Disconnector Type
Type DME 24 - 07
Incoming Cable Connection Unit
Type DME 24 - 07 / A
Incoming Cable Connection Unit
Type DME 24 - 08
Metering Unit
Type DME 24 - 08 / A
Universal Metering Unit
Type DME 24 - 09
Bus Riser Unit
Type DME 24 - 09 / A
Bus Riser Unit
Type DME 24 - 11
Type DMH 24 - 11 / A
Direct Busbar Connection
Unit and Metering
TECHNICAL DATA
Rated voltage
kV
12
17.5
24
kV peak
75
95
125
85
110
145
28
38
50
32
45
60
50 / 60
50 / 60
50 / 60
- Busbar
630 / 1250
630 / 1250
630 / 1250
- Feeder / branch
630 / 1250
630 / 1250
630 / 1250
- Main circuit
20
20
20
- Earthing circuit
20
20
20
Rated frequency
kV eff
Hz
Rated current
kV eff
kA peak
50
50
50
1;3
1;3
1;3
kA
20
20
20
PI
PI
PI
LSC2A
LSC2A
LSC2A
IP3X
IP3X
IP3X
IP3X
IP3X
IP3X
- Maximum value
+40
+40
+40
+35
+35
+35
- Minimum value
-5
-5
-5
1000
1000
1000
Ambient temparature
25
5
Switch Unit
Type DME 24 - 01
DME 24 Series
1600
DME 01
DME 24 - 01
940
375
Opt: 500
Standart equipment
Optional equipments
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630
630
630
[kA]
20
20
20
[s]
Net Weight
kg
155
155
155
Gross Weight
kg
185
185
185
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
1600
DME 24 - 01/A
DME 01/A
940
500
Standart equipment
Optional Equipments
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
205
205
205
Gross Weight
kg
235
235
235
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
1600
DME 24 - 02
DME 02
940
375
Opt: 500
Standart equipment
Optional Equipments
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
200
200
200
[kA]
20
20
20
[s]
Net Weight
kg
170
170
170
Gross Weight
kg
200
200
200
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
1600
DME 24 - 03
DME 03
940
375
Opt: 500
Standart equipment
Optional Equipments
1. Earthing switch
2. Gas density indication
3. Gas density indication with alarm contact
4. Cable fault indication device
5. Arc-gas channel
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
300
300
300
Gross Weight
kg
330
330
330
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
Vacuum or SF6
DME
- 04
DME2404
1600
750
940
1100
Standart equipment
Optional Equipments
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
360
360
360
Gross Weight
kg
403
403
403
mm
800
800
800
mm
1170
1170
1170
mm
1750
1750
1750
10
DME 24 Series
Vacuum or SF6
DME 2405
- 05
DME
1600
750
940
1100
Standart equipment
Optional Equipments
Technical Data
11
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
400
400
400
Gross Weight
kg
443
443
443
mm
800
800
800
mm
1170
1170
1170
mm
1750
1750
1750
DME 24 Series
Type DME 24 - 05 / A
1600
DME 24 - 05/A
940
750
Standart equipment
Optional Equipments
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
440
440
440
Gross Weight
kg
483
483
483
mm
800
800
800
mm
1170
1170
1170
mm
1750
1750
1750
12
DME 24 Series
1600
DME 24 - 07
940
500
Opt: 375
Standart equipment
Optional Equipments
1. Earthing switch
2. Voltage transformers
3. Current transformers
Technical Data
13
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
110
110
110
Gross Weight
kg
140
140
140
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
1600
DME 24 - 07/A
940
500
Opt: 375
Standart equipment
Optional Equipments
1. Earthing switch
2. Voltage indicator device
3. Busbars
4. Earthing bar
5. Heater
6. Interlocking unit
1. Voltage transformers
2. Current transformers
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
110
110
110
Gross Weight
kg
140
140
140
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
14
Metering Unit
Type DME 24 - 08
DME 24 Series
1600
DME 24 - 08
940
750
Standart equipment
Optional Equipments
Technical Data
15
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630
630
630
[kA]
20
20
20
[s]
Net Weight
kg
420
420
420
Gross Weight
kg
463
463
463
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
DME 24 - 08 / A
1600
750
940
Standart equipment
Optional Equipments
1. Bushings
2. Current Transformers (toroidal or standard)
3. Voltage transformers
4. Busbars
5. Earthing bar
6. Ammeter ,Voltmeter
7. Heather
8. Interlocking unit
9. Voltage indicator device
1. Energymeter
2. Hv fuses
3. Surge arresters
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
370
370
370
Gross Weight
kg
413
413
413
mm
800
800
800
mm
1170
1170
1170
mm
1750
1750
1750
16
DME 24 Series
1600
DME 24 - 09
940
500
Standart equipment
Optional Equipments
1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
1. Voltage transformers
2. Current transformers
3. Earthing Switch
Technical Data
17
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
170
170
170
Gross Weight
kg
200
200
200
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
1600
DME 24 - 09 / A
940
500
Standart equipment
Optional Equipments
1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
1. Voltage transformers
2. Current transformers
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
170
170
170
Gross Weight
kg
200
200
200
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
18
DME 24 Series
1600
DME 24 - 11
DME 08
375
940
Standart equipment
Optional Equipments
1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
7. Cable entry with cable support
1. Current transformers
2. Earthing switch
3. Surge arresters
Technical Data
19
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
90
90
90
Gross Weight
kg
120
120
120
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
DME 24 Series
Type DME 24 - 11 / A
1600
DME 24 - 11/A
500
940
Standart equipment
Optional Equipments
1. Bushings
2. Current transformers
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
7. Cable entry with cable support
1. Earthing switch
2. Surge arresters
Technical Data
Rated voltage
[kV]
12
17,5
24
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
20
20
20
[s]
Net Weight
kg
170
170
170
Gross Weight
kg
200
200
200
mm
420
420
420
mm
1070
1070
1070
mm
1750
1750
1750
20
COMPONENTS
SF6 LOAD BREAK SWITCH & DISCONNECTOR
DYA 36 - X4 / DGA 36 - X4
Functioning concept:
DYA 36 - X4 switches are made of an epoxy cast
resin housing filled with SF6 gas at the pressure of
150 kPa abs., operative life sealed. (Standard IEC
60265-1)
The moving contact are fixed on the insulated
rotary shaft inside the cast resin body, while the fixed contacts are mounted directly on the cast resin
body.
The rotary motion of the shaft is made by an operating mechanism placed on the front. The switch
has three different positions: closed, open and earthed, which naturally prevent any wrong operations.
Charateristics:
DYA 36 - X4 switches use sulphur hexafluoride gas
(SF6) for insulation and breaking.
The active parts are placed in an insulating enclosure in accordance with the IEC standards for sealed
pressure systems.
IM6 products offer remarkable characteristics: Long
service life - Maintenance-free active parts
- Operating safety - Very low over-voltage level
Technical Data
21
Disconnector
DGA 36 - X4
Earthing Switch
Rated voltage
24 kV
24 kV
24 kV
Rated current
630 A
630 - 1250 A
20 kA - 1 sec
20 kA - 1 sec
20 kA - 1 sec
Electrical endurance
E2, E3
E2, E3
E1, E2
Mechanical endurance
M1
M1
M1
Applied standard
IEC 60265 - 1
1000 Operations
COMPONENTS
VACUUM CIRCUIT BREAKERS
DV X5
Current interruption in vacuum:
The vacuum circuit breaker does not require an
interrupting and insulating medium. In fact, the
interrupters do not contain ionisable material. In any
case, on separation of the contacts a metal vapour arc is
generated made up exclusively of melted and vaporised
contact material.
The metal vapour only remains supported by the
external energy until the current is cancelled in the
vicinity of natural zero. At that instant, the rapid reduction
in the load density carried and the rapid condensation
of the metallic vapour, leads to extremely rapid dielectric
recovery.
The vacuum interrupter therefore recovers the
insulating capacity and the capacity to withstand the
transient return voltage, definitively extinguishing the arc.
Since high dielectric strength can be reached in the vacuum, even with minimum distances,
interruption of the circuit is also guaranteed when separation of the contacts takes place a few
milliseconds before passage of the current through natural zero.
The special contacts design and material, as well as the limited duration and low voltage of the arc,
guarantee minimum contact wear and long life. Furthermore, the vacuum prevents their oxidation and
contamination.
Operating mechanism:
The low speed of the contacts, together with the reduced run and low mass, limit the energy required
for the operation and therefore guarantee extremely limited wear of the system. The circuit breaker is
therefore limited in maintenance.
The DV Y5 - DV X5 circuit breakers use a mechanical operating mechanism, with stored energy and
free release. These characteristics allow opening and closing operations
independent of the operator. The DV Y5 - DV X5 circuit breaker operating mechanism is of simple
conception and use and can be customised with a wide range of accessories which are easy and rapid
to install. This simplicity converts into greater reliability of the apparatus.
Technical Data DV X5
Rated voltage
12 kV
17.5 kV
24 kV
Rated frequency
[Hz]
50/60
50/60
50/60
[kV]
75
95
125
[kV]
28
38
50
Rated current
[A]
630/1600
630/1600
630/1600
[kA]
16 / 25
16 / 25
16 / 25
[kA]
40 / 63
40 / 63
40 / 63
[s]
Pole centres
[mm]
210
210
210
22
COMPONENTS
SF6 GAS CIRCUIT BREAKERS
DS 5AG 3
Introduction:
Demita SF6 gas circuit breakers are p roduced in
accordance with TSE 3039 also they have been tested at
CESI laboratory according to IEC 62271-100 and they
have the test certificate.
Presentation:
Demita SF6 gas circuit breakers are suitable for all
system requirements up to 36 kV rated voltage,
1250 A rated current. Sulphur hexafluoride for insulation
and breaking is used in Demita SF6 gas circuit breakers.
The extinguishing chamber and components are kept
in a sealed pressure system type envelopes with high
insulation.
23
12 kV
17.5 kV
24 kV
Rated frequency
[Hz]
50/60
50/60
50/60
[kV]
75
95
125
[kV]
28
38
50
Rated current
[A]
630/1250
630/1250
630/1250
[kA]
16 / 25
16 / 25
16 / 25
[kA]
40 / 63
40 / 63
40 / 63
[s]
Pole centres
[mm]
210
210
210
COMPONENTS
Earthing switch:
Rated voltage
12 kV - 17.5 kV - 24 kV
16 kA / 1 sn
Current
1 kA / 1 sn*
Standards applied
20 kA / 1 sn
Voltage transformers
The resin insulated voltage transformers are used for the feeding of
measuring instruments and protection. They are suitable either for
fixed installation or mounted on withdrawable trucks. They comply with
IEC 60044 - 2 Standards. The dimensions of the fixed version comply
with DIN standards 42600 Narrow Type. The withdrawable version
equipped with fuses is custom made. The voltage transformers can be
fitted either with one or two poles. Their performances and precision
classes comply with the functional requirements of the apparatus they
are connected to. The withdrawable version is equipped with medium
voltage protection fuses, their replacement can be carried out while the
switchboard is in service.
Current transformers
The current transformers are resin insulated and suitable for the
feeding of measuring instruments and protections. These transformers
can have a wound core or bushing bar with one or more cores. Their
performances and precision classes comply with the apparatus
requirements.
The current transformers comply with IEC 60044 - 1 Standard. Their
dimensions meet the requirements of DIN 42600 Standards. The
current transformers can be equipped also with a capacitive socket for
being connected to voltage indicator lambs.
The toroidal current transformers are resin insulated and suitable for
the feeding of measuring instruments and protection. These
transformers can have a ring or a split core. Their performances and
precision classes comply with the apparatus requirements. They are
suitable both for measuring phase currents and determining earth fault
currents. They meet the requirements of IEC 60044 - 1 Standards.
Protection relay
DEMTA
POWER SYSTEMS
Tel: +90 380 5412201
+90 380 5412655
Export Department: +90 541 5413086
Fax: +90 380 5412894
E-mail: demitas@demitas.com.tr
Internet: www.demitas.com.tr
Distributor Company