You are on page 1of 28

DME 24

12 - 24 kV
630 - 1250 A
16 kA

DEMTA
POWER SYSTEMS

METAL ENCLOSED SWITCHGEAR

MODULER UNIT

DEMTA
POWER SYSTEMS

CONTENTS

Description

Unit Dimensions

Unit Types

Technical Data

Typical Units

Components

21

DESCRIPTION
GENERAL
DME series Metal enclosed units which are produced by our company,have been
designed and tested to be used for all energy distribution systems till 24 Kv
Moduler Metal Enclosed units appear as the optimal solution with their easiness of
taking operation by means of their moduler structure and with their module appositi
on characteristic for companies
DME series Metal enclosed unit are manufactured according to IEC Standards
Optimal dimensions
Long term technical solitions for various applications
High level personal safety

APPLICATIONS
Manufacturing industry
Secondary electricy distribution networks
Shopping malls
MV / LV distribution transformer substations
Small size power plants
Wind power plants
Airports, hospitals, holiday village
Enclosure of cubicle is 2 mm galvanized steel sheet. If desired al-zinc is
also possible. No welding during the assembling of the structure.

SAFETY
There is a survelliance window on the front cover of the every cubicle to
check inside the cubicle without open the door / cover

The door / cover of the accessible compartments is mechanically interlocked


with the earthing switches
High voltage indication system in each cubicle

STANDARDS
Compliance with standards IEC 62271 - 200

Classification; (according to IEC 62271 - 200 )


Classification of service contunity: LSC 2A

Classification of the partitions: ( Partition: Insulation )


Classification of arc proofing: IAC A (FL), IAC A (FLR)
1

DESCRIPTION
STRUCTURES
1. Busbar compartment
2. Cable compartment

3. Low voltage compartment

4. Operating mechanism compartment


1. Busbar compartment
Busbar compartment is located on the top of the
cubicle. It contains the main busbar which
interconnect between cubicles. And also;
Tool based accessible compartment with regard
to accessibility, (it means that is not possible to
open the covers without using any tools)

Withstand to internal arc


Having IP 3X protection degree
2. Cable compartment
Cable compartment is located at the bottom of the cubicle. It contains switching
devices, measuring transformers., HV fuses, earthing devices, support insulators
according to the functional type of the cubicle.
Incoming / outgoing MV cable connection of the cubicle is made in this
compartment. The door has an inspection window. And also;
Procudure based accessible compartment with regard to accessibility, (it means
that it is possible to open the covers without using any tools)
Withstand to internal arc
Having IP 3X protection degree
3. Low voltage compartment
Low voltage compartment is located on the front - top of the cubicle having IP3X
protection degree.
According to the functional type of the cubicle, it contains, protection relays, LV
fuses, measurment instruments, auxilary relays, miniature circuit breakers, terminal
arrays, AC/DC supply, etc.
4. Operating mechanism compartment
Operating mechanism compartment is located on the front of the cubicle. According
to the functional type of the cubicle it contains; disconnector mechanism, switchdisconnector mechanism and same interlocking metal parts.
Circuit breakers has own mechanism, separately.
All metal parts of the operating mechanism are protected agains to corrosion.
2

UNIT DIMENSIONS

1600

1600

375

940

940

750

1100

UNIT TYPES
DME 24 - 01

UNIT TYPES
DME 24 - 04
DME 24 - 05

DME 24 - 02
DME 24 - 03
DME 24 - 11

1600

940

500

UNIT TYPES
DME 24 - 01 /A
DME 24 - 07
DME 24 - 07 / A
DME 24 - 09
DME 24 - 09 / A
DME 24 - 11 / A

1600

940

750

UNIT TYPES
DME 24 - 05 / A
DME 24 - 08
DME 24 - 08 / A

UNIT TYPES
Type DME 24 - 01
Switch Unit

Type DME 24 - 01/A


Switch Unit and Metering

Type DME 24 - 02
Fuse Switch Combination Unit

Type DME 24 - 03
Switch Unit and Metering

Type DME 24 - 04
Circuit Breaker Unit

Type DME 24 - 05
Sectionalising Metering Unit

Type DME 24 - 05 / A
Sectionalising Metering Unit
with Disconnector Type

Type DME 24 - 07
Incoming Cable Connection Unit

Type DME 24 - 07 / A
Incoming Cable Connection Unit

Type DME 24 - 08
Metering Unit

Type DME 24 - 08 / A
Universal Metering Unit

Type DME 24 - 09
Bus Riser Unit

Type DME 24 - 09 / A
Bus Riser Unit

Type DME 24 - 11

Type DMH 24 - 11 / A
Direct Busbar Connection
Unit and Metering

Direct Busbar Connection Unit

TECHNICAL DATA

Rated voltage

kV

12

17.5

24

Rated lighting impulse withstand voltage

kV peak

- Across phases and phase to neutr

75

95

125

- Across the isolating distance

85

110

145

- Across phases and phase to neutr

28

38

50

- Across the isolating distance

32

45

60

50 / 60

50 / 60

50 / 60

- Busbar

630 / 1250

630 / 1250

630 / 1250

- Feeder / branch

630 / 1250

630 / 1250

630 / 1250

- Main circuit

20

20

20

- Earthing circuit

20

20

20

Rated power frequency withstand voltage

Rated frequency

kV eff

Hz

Rated current

Rated short time withstand current

kV eff

Rated peak withstand current

kA peak

50

50

50

Rated duration of short circuit

1;3

1;3

1;3

Arc faulth current, 1 s

kA

20

20

20

Internal arc class


Partitions class

PI

PI

PI

Loss of the service continuity

LSC2A

LSC2A

LSC2A

Degree of protection, enclosure

IP3X

IP3X

IP3X

Degree of protection, partitions

IP3X

IP3X

IP3X

- Maximum value

+40

+40

+40

- Maximum value of 24 h mean

+35

+35

+35

- Minimum value

-5

-5

-5

1000

1000

1000

Ambient temparature

Altitude above sea level

25
5

A(FLR)/A(FL) A(FLR)/A(FL) A(FLR)/A(FL)

Switch Unit
Type DME 24 - 01

DME 24 Series

1600

DME 01
DME 24 - 01

940

375

Opt: 500
Standart equipment

Optional equipments

1. 3 Position SF6 load break switch


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Voltage indicator device
4. Heather
5. Earthing bar
6. Busbars
7. Interlocking unit
8. Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position
9. Cable entry with cable support

1. Remote control with cable (Opening and closing)


2. Remote control without cable (Opening and closing)
3. Gas density indication
4. Gas density indication with alarm contact
5. Motor operation device
6. Cable fault indication device
7. Surge arresters
8. Current transformers
9. Arc-gas channel

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630

630

630

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

155

155

155

Gross Weight

kg

185

185

185

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Switch Unit and Metering


Type DME 24 - 01/A

DME 24 Series

1600
DME 24 - 01/A

DME 01/A

940

500

Standart equipment

Optional Equipments

1. 3 Position SF6 disconnector


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Current transformers
4. Voltage indicator device
5. Heather
6. Earthing bar
7. Busbars
8. Interlocking unit
9. Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position
10.Cable entry with cable support

1. Gas density indication


2. Gas density indication with alarm contact
3. Motor operation device
4. Surge arresters
5. Cable fault indication device
6. Arc-gas channel

Technical Data

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

205

205

205

Gross Weight

kg

235

235

235

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Fuse Switch Combination Unit


Type DME 24 - 02

DME 24 Series

1600
DME 24 - 02

DME 02

940

375
Opt: 500

Standart equipment

Optional Equipments

1. 3 Position SF6 load break switch


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Earthing switch 2 kA
4. Fuse
5. Voltage indicator device
6. Heather
7. Earthing bar
8. Busbars
9. Interlocking unit
10. Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position
11. Cable entry with cable support

1. Remote control with cable (Opening and closing)


2. Remote control without cable (Opening and closing)
3. Gas density indication
4. Gas density indication with alarm contact
5. Motor operation device
6. Voltage transformers
7. Cable fault indication device
8. Arc-gas channel

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

200

200

200

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

170

170

170

Gross Weight

kg

200

200

200

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Switch Unit and Metering


Type DME 24 - 03

DME 24 Series

1600
DME 24 - 03

DME 03

940

375
Opt: 500

Standart equipment

Optional Equipments

1. 3 Position SF6 disconnector


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Voltage transformers
4. Fuse
5. Voltage indicator device
6. Heather
7. Earthing bar
8. Busbars
9. Interlocking unit
10.Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position

1. Earthing switch
2. Gas density indication
3. Gas density indication with alarm contact
4. Cable fault indication device
5. Arc-gas channel

Technical Data

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

300

300

300

Gross Weight

kg

330

330

330

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Circuit Breaker Unit


Type DME 24 - 04

DME 24 Series

Vacuum or SF6

DME
- 04
DME2404

1600

750

940
1100

Standart equipment

Optional Equipments

1. 3 Position SF6 disconnector


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Circuit breaker, vacuum or SF6 type
4. Current transformers (toroidal or
standard type )
5. Over current protection relay
6. Earthing switch 16 kA
7. Voltage indicator device
8. Heather
9. Earthing bar
10.Busbars
11. Interlocking unit
12. Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position
13. Cable entry with cable support

1. Remote control with cable (Opening and closing)


2. Remote control without cable (Opening and closing)
3. Gas density indication
4. Gas density indication with alarm contact
5. Voltage Transformers
6. Cable fault indication device
7. Surge arresters
8. Arc-gas channel

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

360

360

360

Gross Weight

kg

403

403

403

Width with pack

mm

800

800

800

Depth with pack

mm

1170

1170

1170

Height with pack

mm

1750

1750

1750
10

Sectionalising Metering Unit


Type DME 24 - 05

DME 24 Series

Vacuum or SF6

DME 2405
- 05
DME

1600

750

940
1100

Standart equipment

Optional Equipments

1. 3 Position SF6 disconnector


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Circuit breaker, vacuum or SF6 type
4. Current transformers (toroidal or
standard type )
5. Over current protection relay
6. Voltage indicator device
7. Heather
8. Earthing bar
9. Busbars
10.Interlocking unit
11. Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position

1. Remote control with cable (Opening and closing)


2. Remote control without cable (Opening and closing)
3. Gas density indication
4. Gas density indication with alarm contact
5. Voltage Transformers
6. Cable fault indication device
7. Arc-gas channel

Technical Data

11

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

400

400

400

Gross Weight

kg

443

443

443

Width with pack

mm

800

800

800

Depth with pack

mm

1170

1170

1170

Height with pack

mm

1750

1750

1750

Sectionalising Metering Unit

DME 24 Series

with Disconnector Type

Type DME 24 - 05 / A

1600
DME 24 - 05/A

940

750

Standart equipment

Optional Equipments

1. 3 Position SF6 disconnector


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Voltage transformers
4. Current transformers
5. Voltage indicator device
6. Heather
7. Earthing bar
8. Busbars
9. Interlocking unit
10.Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position

1. Gas density indication


2. Gas density indication with alarm contact
3. Motor operation device
4. Cable fault indication device
5. Surge arresters
6. Arc-gas channel

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

440

440

440

Gross Weight

kg

483

483

483

Width with pack

mm

800

800

800

Depth with pack

mm

1170

1170

1170

Height with pack

mm

1750

1750

1750

12

DME 24 Series

Incoming Cable Connection Unit


Type DME 24 - 07

1600

DME 24 - 07

940

500
Opt: 375

Standart equipment

Optional Equipments

1. Voltage indicator device


2. Busbars
3. Earthing bar
4. Heater
5. Interlocking unit

1. Earthing switch
2. Voltage transformers
3. Current transformers

Technical Data

13

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

110

110

110

Gross Weight

kg

140

140

140

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

DME 24 Series

Incoming Cable Connection Unit


Type DME 24 - 07 / A

1600

DME 24 - 07/A

940

500
Opt: 375

Standart equipment

Optional Equipments

1. Earthing switch
2. Voltage indicator device
3. Busbars
4. Earthing bar
5. Heater
6. Interlocking unit

1. Voltage transformers
2. Current transformers

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

110

110

110

Gross Weight

kg

140

140

140

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

14

Metering Unit
Type DME 24 - 08

DME 24 Series

1600
DME 24 - 08

940

750

Standart equipment

Optional Equipments

1. 3 Position SF6 load break switch


(open - closed - earthed)
2. Operating mechanism with
mechanical position indication
3. Voltage transformers
4. Current transformers
5. Bushing
6. Voltage indicator device
7. Heather
8. Earthing bar
9. Busbars
10.Interlocking unit
11.Auxiliary contacts for close
(2NO+2NC) and earth (2NO+2NC) position

1. Remote control with cable (Opening and closing)


2. Remote control without cable (Opening and closing)
3. Gas density indication
4. Gas density indication with alarm contact
5. Motor operation device
6. Cable fault indication device
7. Arc-gas channel

Technical Data

15

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630

630

630

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

420

420

420

Gross Weight

kg

463

463

463

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Universal Metering Unit


Type DME 24 - 08 / A

DME 24 Series

DME 24 - 08 / A

1600

750

940

Standart equipment

Optional Equipments

1. Bushings
2. Current Transformers (toroidal or standard)
3. Voltage transformers
4. Busbars
5. Earthing bar
6. Ammeter ,Voltmeter
7. Heather
8. Interlocking unit
9. Voltage indicator device

1. Energymeter
2. Hv fuses
3. Surge arresters

Technical Data

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

370

370

370

Gross Weight

kg

413

413

413

Width with pack

mm

800

800

800

Depth with pack

mm

1170

1170

1170

Height with pack

mm

1750

1750

1750
16

Bus Riser Unit


Type DME 24 - 09

DME 24 Series

1600
DME 24 - 09

940

500

Standart equipment

Optional Equipments

1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit

1. Voltage transformers
2. Current transformers
3. Earthing Switch

Technical Data

17

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

170

170

170

Gross Weight

kg

200

200

200

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Bus Riser Unit


Type DME 24 - 09 / A

DME 24 Series

1600
DME 24 - 09 / A

940

500

Standart equipment

Optional Equipments

1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit

1. Voltage transformers
2. Current transformers

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

170

170

170

Gross Weight

kg

200

200

200

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

18

Direct Busbar Connection Unit


Type DME 24 - 11

DME 24 Series

1600

DME 24 - 11

DME 08

375

940

Standart equipment

Optional Equipments

1. Bushings
2. Voltage indicator device
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
7. Cable entry with cable support

1. Current transformers
2. Earthing switch
3. Surge arresters

Technical Data

19

Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

90

90

90

Gross Weight

kg

120

120

120

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

Direct Busbar Connection

DME 24 Series

Unit and Metering

Type DME 24 - 11 / A

1600
DME 24 - 11/A

500

940

Standart equipment

Optional Equipments

1. Bushings
2. Current transformers
3. Heather
4. Earthing bar
5. Busbars
6. Interlocking unit
7. Cable entry with cable support

1. Earthing switch
2. Surge arresters

Technical Data
Rated voltage

[kV]

12

17,5

24

Rated current

[A]

630/1250

630/1250

630/1250

Rated short-time withstand current

[kA]

20

20

20

Maximum rated duration of short circuit

[s]

Net Weight

kg

170

170

170

Gross Weight

kg

200

200

200

Width with pack

mm

420

420

420

Depth with pack

mm

1070

1070

1070

Height with pack

mm

1750

1750

1750

20

COMPONENTS
SF6 LOAD BREAK SWITCH & DISCONNECTOR
DYA 36 - X4 / DGA 36 - X4
Functioning concept:
DYA 36 - X4 switches are made of an epoxy cast
resin housing filled with SF6 gas at the pressure of
150 kPa abs., operative life sealed. (Standard IEC
60265-1)
The moving contact are fixed on the insulated
rotary shaft inside the cast resin body, while the fixed contacts are mounted directly on the cast resin
body.
The rotary motion of the shaft is made by an operating mechanism placed on the front. The switch
has three different positions: closed, open and earthed, which naturally prevent any wrong operations.

Charateristics:
DYA 36 - X4 switches use sulphur hexafluoride gas
(SF6) for insulation and breaking.
The active parts are placed in an insulating enclosure in accordance with the IEC standards for sealed
pressure systems.
IM6 products offer remarkable characteristics: Long
service life - Maintenance-free active parts
- Operating safety - Very low over-voltage level

Technical Data

21

Load Break Switch


DYA 36 - X4

Disconnector
DGA 36 - X4

Earthing Switch

Rated voltage

24 kV

24 kV

24 kV

Rated current

630 A

630 - 1250 A

Rated short circuit withstand current

20 kA - 1 sec

20 kA - 1 sec

20 kA - 1 sec

Electrical endurance

E2, E3

E2, E3

E1, E2

Mechanical endurance

M1

M1

M1

Applied standard

IEC 60265 - 1
1000 Operations

IEC 62271 - 102


1000 Operations

IEC 62271 - 102


1000 Operations

COMPONENTS
VACUUM CIRCUIT BREAKERS
DV X5
Current interruption in vacuum:
The vacuum circuit breaker does not require an
interrupting and insulating medium. In fact, the
interrupters do not contain ionisable material. In any
case, on separation of the contacts a metal vapour arc is
generated made up exclusively of melted and vaporised
contact material.
The metal vapour only remains supported by the
external energy until the current is cancelled in the
vicinity of natural zero. At that instant, the rapid reduction
in the load density carried and the rapid condensation
of the metallic vapour, leads to extremely rapid dielectric
recovery.
The vacuum interrupter therefore recovers the
insulating capacity and the capacity to withstand the
transient return voltage, definitively extinguishing the arc.
Since high dielectric strength can be reached in the vacuum, even with minimum distances,
interruption of the circuit is also guaranteed when separation of the contacts takes place a few
milliseconds before passage of the current through natural zero.
The special contacts design and material, as well as the limited duration and low voltage of the arc,
guarantee minimum contact wear and long life. Furthermore, the vacuum prevents their oxidation and
contamination.

Operating mechanism:
The low speed of the contacts, together with the reduced run and low mass, limit the energy required
for the operation and therefore guarantee extremely limited wear of the system. The circuit breaker is
therefore limited in maintenance.
The DV Y5 - DV X5 circuit breakers use a mechanical operating mechanism, with stored energy and
free release. These characteristics allow opening and closing operations
independent of the operator. The DV Y5 - DV X5 circuit breaker operating mechanism is of simple
conception and use and can be customised with a wide range of accessories which are easy and rapid
to install. This simplicity converts into greater reliability of the apparatus.

Technical Data DV X5
Rated voltage

12 kV

17.5 kV

24 kV

Rated frequency

[Hz]

50/60

50/60

50/60

Rated lighting impulse withstand voltage

[kV]

75

95

125

Rated power frequency withstand voltage

[kV]

28

38

50

Rated current

[A]

630/1600

630/1600

630/1600

Rated short circuit breaking current

[kA]

16 / 25

16 / 25

16 / 25

Rated short circuit making current

[kA]

40 / 63

40 / 63

40 / 63

Rated short circuit duration

[s]

Pole centres

[mm]

210

210

210

22

COMPONENTS
SF6 GAS CIRCUIT BREAKERS
DS 5AG 3
Introduction:
Demita SF6 gas circuit breakers are p roduced in
accordance with TSE 3039 also they have been tested at
CESI laboratory according to IEC 62271-100 and they
have the test certificate.

Presentation:
Demita SF6 gas circuit breakers are suitable for all
system requirements up to 36 kV rated voltage,
1250 A rated current. Sulphur hexafluoride for insulation
and breaking is used in Demita SF6 gas circuit breakers.
The extinguishing chamber and components are kept
in a sealed pressure system type envelopes with high
insulation.

SF6 Gas and interrupting system:


SF6 gas has very delectric and normally it is (without the
effect of the electrial arc) non - toxic, odourless and has
electronegative fast regeneration features. The dielectric
strength of SF6 gas atmospheric pressure is appox. 2,5 or
2,6 times more than the air.

Circuit breaker pole:


The pole enclosures are produced from epoxy resin which has overpressure security factor higher than 10
times of the operational pressure. In the pole enclosures, the fixed contacts are at the top. The gas
leakages are kept at minimum level to ensure the operational security during the life of the pole. Measuring
the internal pressure, as needed ingas filling and gas addition operations, can be contolled with a valve
which is installed on the pole cover. The arc breaking system is self blowing (PUFFER) type. The pole
internal gas pressure is 1,5 - 3,5 bars. During the arc interrupting, pressure increases momentary just a little.
In the event of overpressure in a pole, the bottom cover will break at 1/3 of pole witstand pressure, allowing
excess pressure to escape instantaneously. In order to neutralise the chemical products which were created
during breaking, molecular sieves are put in the poles.

Technical Data DS 5AG 3


Rated voltage

23

12 kV

17.5 kV

24 kV

Rated frequency

[Hz]

50/60

50/60

50/60

Rated lighting impulse withstand voltage

[kV]

75

95

125

Rated power frequency withstand voltage

[kV]

28

38

50

Rated current

[A]

630/1250

630/1250

630/1250

Rated short circuit breaking current

[kA]

16 / 25

16 / 25

16 / 25

Rated short circuit making current

[kA]

40 / 63

40 / 63

40 / 63

Rated short circuit duration

[s]

Pole centres

[mm]

210

210

210

COMPONENTS
Earthing switch:
Rated voltage

12 kV - 17.5 kV - 24 kV

Rated short circuit withstand

16 kA / 1 sn

Current

1 kA / 1 sn*

Standards applied

IEC 62271 - 103

20 kA / 1 sn

*Used at switch fuse combination cubicle at the downstream

Voltage transformers

The resin insulated voltage transformers are used for the feeding of
measuring instruments and protection. They are suitable either for
fixed installation or mounted on withdrawable trucks. They comply with
IEC 60044 - 2 Standards. The dimensions of the fixed version comply
with DIN standards 42600 Narrow Type. The withdrawable version
equipped with fuses is custom made. The voltage transformers can be
fitted either with one or two poles. Their performances and precision
classes comply with the functional requirements of the apparatus they
are connected to. The withdrawable version is equipped with medium
voltage protection fuses, their replacement can be carried out while the
switchboard is in service.

Current transformers

The current transformers are resin insulated and suitable for the
feeding of measuring instruments and protections. These transformers
can have a wound core or bushing bar with one or more cores. Their
performances and precision classes comply with the apparatus
requirements.
The current transformers comply with IEC 60044 - 1 Standard. Their
dimensions meet the requirements of DIN 42600 Standards. The
current transformers can be equipped also with a capacitive socket for
being connected to voltage indicator lambs.

Toroidal current transformers

The toroidal current transformers are resin insulated and suitable for
the feeding of measuring instruments and protection. These
transformers can have a ring or a split core. Their performances and
precision classes comply with the apparatus requirements. They are
suitable both for measuring phase currents and determining earth fault
currents. They meet the requirements of IEC 60044 - 1 Standards.

Protection relay

DMC Series switchboards can be equipped with different brand relay


l ike PNC Microelettirica Sicientifica, ABB, SIEMENS or AREVA.
24

DEMTA
POWER SYSTEMS
Tel: +90 380 5412201
+90 380 5412655
Export Department: +90 541 5413086
Fax: +90 380 5412894
E-mail: demitas@demitas.com.tr
Internet: www.demitas.com.tr