39LA,LB,LC,LD,LF,LG,LH03-25
Indoor Air Handlers
Features/Benefits
Carrier delivers the air
handler components for
many stringent specification
requirements. The 39L series
air handlers are compact and
fully assembled; they
combine versatility with
economical, dependable
performance.
Dependable performance
Galvanized steel panels ensure
structural integrity under all operating
conditions. Double-walled hinged
access doors also enhance structural
stability and provide fast, easy access.
Sloped, double-wall stainless
steel drain pan controls condensate
and is self-draining; complies with
ASHRAE (American Society of
Heating, Refrigerating and Air Condi tioning Engineers) Standard 62.1.
712
Form 39L-6PD
Economy
Carriers 39L air handlers save
money. Factory assembled,
prealigned drives and fans eliminate
field installation expense.
Small envelope size is easy to rig
and ensures economical use of building
space. Quicker, easier installation and
set up reduce start-up costs.
High efficiency, precisionbalanced fans minimize air turbulence, surging, and unbalanced operation, cutting operating expenses.
Coil flexibility
The 39L units offer a wide selection of
coils for cooling, heating, preheat
with cooling, or cooling with reheat
application. Standard 39L coils have
galvanized steel casings; inlet and outlet connections are always on the same
end, regardless of circuiting, and can
be specified as right-hand or left-hand
connections.
Chilled water, hot water, and direct
expansion coils have non-ferrous
headers designed to minimize pressure
drop. All coils have 1/2-in. OD copper
tubes and Nu-Fin fins that are mechanically bonded to the coils for enhanced
heat transfer. Aluminum or copper
fins are available with spacings of 8,
11, or 14 fins-per-inch. Copper-fin
coils also have stainless steel casings.
Chilled water coils Large face
area coils are available with 4 or 6
rows, and small face area coils are
available with 4, 6, or 8 rows. Both
large and small face area coils offer
quarter, half, full, or double circuits for
maximum thermal performance with
minimum pressure drop. Quarter
circuits are available only with 4-row
coils; double circuits are available with
4, 6, or 8-row coils.
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2
AHRI Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,4
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-31
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-49
Typical Electric Heating Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . 50
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51,52
2
AHRI certification
Coils installed in the Carrier 39L air handlers are rated in
accordance with AHRI Standard 410 and a detailed description of this industry standard can be found in the
Carrier Central Station Air Handler Coils catalog.
25
HC
APW
Due to the complexity of the (18 position) 39L model number, use the verify model number function in the AHUBuilder software for a
detailed model explanation. The description below can be used as a general model guide.
Pos. 1-3:
Pos. 4:
Pos. 5-6:
Pos. 7-8:
Pos. 9-12
Pos. 13-15
Pos. 16
Pos. 17
Pos. 18
Quality Assurance
712
LEGEND
COMB. Combination
PH
Preheat
POS.
Position
Factory-installed option components
114
Application data
Vertical (indoor unit only)
Fans
The 39L central station air handlers use belt-driven centrifugal fans. A centrifugal fan is one in which the air flows
radially through the impeller. Centrifugal fans are classified
according to fan wheel and blade construction. The 39L
fan is selected as a double width, double inlet (DWDI) with
forward curved blades.
Laws of fan performance
Fan laws are used to predict fan performance under changing operating conditions or by fan size. They are applicable
to all types of fans.
The fan laws are stated below. The symbols used in the
formulas represent the following variables:
CFM Volume rate of flow through the fan.
RPM Rotational speed of the impeller.
P
Pressure developed by the fan.
Hp Horsepower input to the fan.
D
Fan wheel diameter. The fan size number can be
used if it is proportional to the wheel diameter.
W Air density, varying directly as the barometric pressure and inversely as the absolute temperature.
Application of these laws is limited to cases where fans
are geometrically similar.
FAN LAWS
VARIABLE
CONSTANT
LAW
Airflow varies directly with the Speed.
SPEED
(RPM)
Air Density
Fan Size
Distribution System
Air Density
Tip Speed
FAN SIZE
(D)
Air Density
Wheel Speed
AIR DENSITY
(W)
Pressure
Fan Size
Distribution System
Airflow
Fan Size
Distribution System
FORMULA
CFM1
CFM2
(
(
RPM1
RPM2
2
Hp1
=
Hp2
CFM1
Hp1
=
=
CFM2
Hp2
RPM1
D2
=
RPM2
D1
P1 = P2
CFM1
=
CFM2
P1
P2
Hp1
=
Hp2
Speed, Capacity, and Horsepower vary inversely as the square root of Density.
RPM1
CFM1
Hp1
=
=
=
RPM2
CFM2
Hp2
P1
Hp1
W1
=
=
P2
Hp2
W2
RPM1 = RPM2
RPM1
RPM2
)
)
( )
P1
=
P2
RPM1
RPM2
( )
( )
( )
D1
D2
D1
D2
D1
D2
D1
D2
( )
W2
W1
1/2
to a point of stall at minimum airflow and pressure conditions. The typical minimum airflow is half of the design
cooling airflow, which is also often equal to the heating
airflow. To determine and plot the minimum airflow versus
static pressure, use the following equation. This equation
solves for the static pressure at a specific airflow based on
a minimum static pressure set point:
((
CFMDESIGN
((
7,500
15,000
CFM1
(SPDESIGN SPMIN)
X (4 2)
) + SP
MIN
= SP1
) + 2 = 2.50 in. wg
CFM
100
90
80
70
60
50
15,000
13,500
12,000
10,500
9,000
7,500
VAV EXAMPLES
11
MSE
10
SC
9
T
O
T
A
8
7
N
4
RP
W
G
3
MP
2
1
0
0
10
12
14
16
18
20
MP Minimum Point
RP Rated Point
MSE Maximum Static Efficiency SC System Curve
22
24
26
28
39L SIZE 12 LA
7
MSE
6
SC
5
TOTAL IN. WG
4
RP
3
2
1
0
LEGEND
\
\
MSE
RP
SC
RPM
BHP
Max. Static Eff.
Rated Point
System Curve
6
12
8
10
AIRFLOW (1000 CFM)
14
16
18
RPM = 1333
BHP = 5.8
Max RPM = 1600
Max BHP = 15.0
RPMs (x 100, L to R): 6, 7, 8, 9, 10,
11, 12, 13, 14, 15, 16
BHPs (L to R): 1.5, 2, 3, 5, 7.5, 10,
15, 20
Fan application
Certain fans are more efficient in low static pressure systems, while others operate best in higher pressure systems.
Some fan types are designed to handle very large air volumes while others are more efficient at lower volumes. The
low cost 39L unit is designed for use with low static pressure systems and is only available with forward curve fans.
For higher static applications, specify 39M or 39R units.
Forward-curved (FC) fans are typically used for low to
medium pressure applications (0 to 5 in. wg total static
pressure [TSP]).
The FC fans are reasonably stable over a wide airflow
(cfm) range at constant speed. Because of the relatively flat
curve, FC fans tolerate modulation in airflow without large
increases in static pressure. Most important, FC fans are
lowest in first cost.
For 100% recovery of velocity pressure into static pressure, the straight portion of the discharge duct must be at
least at least 21/2 times the discharge diameter in length
for velocities of 2500 fpm or less. For each additional
1000 fpm, add one duct diameter to the length of the
straight portion of the ductwork.
As an example of how to size the straight portion of
duct, assume the fan has a 34 x 34 in. discharge outlet
(8.03 sq ft). The equivalent diameter is 39 in., so the
straight duct length required would be 8 ft long.
CUTOFF
DISCHARGE DUCT
CENTRIFUGAL
FAN
System parameters
Before a fan type or control is selected, the system must be
analyzed at both the design point and part load. The fan is
likely to be operating at part load a large percentage of the
time.
CHARACTERISTICS
Double-width, double-inlet (DWDI) construction.
Best at low or medium pressure (approximately
0 to 5 in. wg).
Horsepower increases continuously with
increase in air quantity (overloads) as static pressure
decreases.
Runs at relatively low speed, typically 400 to 1200 rpm.
Blades curve toward direction of rotation.
APPLICATION
10
FIRSTCOST RANK
TURNDOWN
RANGE
(Normal)*
SOUND
GENERATION
RANK
ENERGYSAVINGS
RANK
APPLICATION
RANGE NORMAL
FOR AIR COND.
FC Fan
Terminal Throttling
(Riding Fan Curve)
1
(Lowest Cost)
60-70%
FC Fan with
2-Speed Motor
(Not
Applicable)
FC Fan, With
Inlet Guide Vanes
25-35%
FC Fan
With Variable
Frequency Drive
10-15%
1
(Quietest)
1
(Best)
COMMENTS
For moderate turndown systems with
a flat fan curve and low to medium static
pressure and cfm range.
For systems with predictable 2-load
situations in low to medium static
pressure range. Controls are more
complicated. Starters are more costly.
For moderate turndown systems with
medium to high static pressure and
cfm range. Sound remains constant
or decreases as flow decreases.
For high turndown, low to medium static
pressure systems. Best energy savings.
Fast payback. Fan generates least sound.
LEGEND
FC Forward Curved
TSP Total Static Pressure
The Variable Frequency Fan Speed Control chart illustrates the results of fan speed reduction as operation shifts
from Point A to Point B. If duct pressure begins to fall due
to terminal units opening, the duct sensor signals the VFD
to increase fan speed.
This method of air volume control permits fan speed
reduction down to as low as 10% of the design speed. With
FC fans riding the fan curve at the lower rpm, airflow may
be as low as 10% of peak design, as long as motor rpm
is not less than 1/6 of motor synchronous speed.
The method may be applied to any size VAV system with
any type of fan. It is particularly cost effective on systems
with high turndown requirements where the full speed
reduction capability can be used.
DDC
CONTROL
BOX
VFD
MXB
OUTDOOR
AIR
LEGEND
DDC Direct Digital Control
MXB Mixing Box
VFD Variable Frequency
Drive
Static Pressure Pick-Up
MOTOR
RETURN
AIR
FILTER
COIL
SUPPLY FAN
11
Coils
Coil definitions
A coil, as the term is used with air-handling equipment, is a
heat exchange device. A heating or cooling medium passes
through the coil, where it either rejects heat to or absorbs
heat from the airstream passing over the coil, depending
upon the relative temperatures of medium and airstream.
Tube The tube is a small-diameter pipe through which
the heating or cooling medium passes as it rejects or
absorbs heat. Coil tubes are generally constructed of
copper but may be made of other metals.
Fin The coil fin is a thin metal plate attached to the tube
to improve the heat transfer efficiency from medium to airstream. Typically, it is made of either aluminum or copper.
AIRFLOW
DEPTH
TUBE
WIDTH
OUTLET
HEADER
INLET
NOM.
TUBE
LENGTH
FINNED
AREA
CASING
38ARS012
33%
6 row, 11 FPI, Half Circuit
1.68
2
Ethylene glycol
The effects of ethylene glycol usage on coil capacity and
pressure drop can be determined from the AHUBuilder
program. For a quick estimate of these effects, however,
use the chart below.
The chart is based on 6-row/14-fin coil performance
with the only variable being ethylene glycol concentration
by weight.
ETHYLENE GLYCOL EFFECTS
Filters
Air is contaminated in varying degrees by soil, organic
matter, spores, bacteria, smoke, dust, and fumes.
Air cleaning and filtration devices are required in order
to create a clean work environment, reduce cleaning costs,
and extend the life of machinery or equipment.
Filter ratings
Filters are rated according to efficiency and dust-holding
capacity.
The most commonly accepted method of testing filter
efficiency is per ASHRAE Standard 52. Previously used
methods include AFI (American Filter Institute) and NBS
(National Bureau of Standards) methods. Absolute, or
HEPA (High-Efficiency Particulate Air) filters, because of
the unusually small particles involved, are tested by the
DOP (Dioctylphthalate particle) test.
Filter dust-holding capacity is directly related to filter life.
The filter is replaced when the amount of dirt and dust it
contains builds up air resistance to an unacceptable level.
Air resistance build-up is measured by a filter air-resistance
gage.
Selection procedure
Size selection
SPECIFICATION WORKSHEET
This catalog has been designed to provide a quick and accurate means of selecting and specifying a central station
air-handling unit. Start with the information you have,
required airflow and preferred coil face velocity, to select a
nominal unit size. Contact your Carrier sales representative
for the AHUBuilder program. Next, refer to the component descriptions on pages 32-49. After determining the
unit size and unit configuration, use the worksheet on this
page to record dimension and weight information for each
section and to add the total unit weight and length.
CFM _________________
BHP ________
Total _________
CYCLES ______
FILTERS
SIZE ____________________
SIZE ____________________
COMPONENT SEQUENCE
RETURN ________
RETURN ________
QTY _________________
QTY _________________
LENGTH
WEIGHT
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
NOTES:
1. See AHUBuilder program for specific limitations.
2. Data shown is for general use in high latent conditions.
3. Coils with E-coated fins exhibit the same limitations as copper fins.
4. Units apply to clean, properly maintained coils.
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
____________________
+ _________
___________
MOTOR
____________________
+ _________
___________
COIL
____________________
+ _________
___________
__________
___________
14
TOTAL
COMMENTS: ______________________________________
_________________________________________________
_________________________________________________
PREPARED BY: ____________________________________
DATE: ____________________________________________
15
16
cfm
Max Air Face Velocity
= 4950 cfm
4950 cfm
= 6.19 sq ft
ATR
= 74.0 F
Actual Leaving
Entering Air
=
+ ATR
Air Temp (ta2)
Temp (ta1)
= 10 F + 74.0 F
ta2
= 64.7 F > 60 F required
IV Calculate grand total heat (GTH) of coil.
(See Steam Coil Selection Notes 1 and 2.)
Actual Coil = 1.1 x cfm x ATR
Capacity
= 1.1 x 4,950 x 74.0
= 402,930 Btuh > 374,220 Btuh
required
Steam Coil Selection Notes:
1. When coil selection has a coil capacity only
slightly in excess of that required, it is a valid
selection. If calculated capacity is less or considerably greater than that required, make a new
selection.
2. For applications with steam pressure of 5 psig,
the actual leaving-air temperature (ldb) may be
read from steam rating tables without calculation
of actual air temperature rise (ATR). Enter the
Steam Coil Ratings table at specified entering-air
temperature, assumed row depth and fin series.
Under the specified coil face velocity column
find actual (ldb) (ta2 in example) and corresponding MBtuh/sq ft. Interpolate as required. Calculate grand total heat (GTH) with formula below.
GTH = MBtuh/sq ft x Coil Face Area (sq ft)
V Determine air friction.
Enter Steam Coil Air Friction table, page 19, at row
depth and fin series (1 row, fin series 9). Under Coil
Face Velocity column (800) read the air friction
value = 0.38 in. wg.
17
3,000
650 Fpm
4.6 sq ft
3,000
4.9 sq ft
= 615 Fpm
(Actual Coil
Face Area)
75.9 MBtuh
3.413 MBtuh/kW
75.9
3.413
22.2 kW
18
78,500 Btuh
1.1 x 3,000 Cfm
= 23.8 F
VIII Calculate the actual leaving-air temperature.
Leaving Air Temp = Ent Air Temp + Air Temp Rise
= 54 + 23.8
= 77.8 F
IX Determine air friction loss of electric heating
coil.
Enter Electric Heating Coil Air Friction table,
page 19, and find (by interpolation) air friction loss
of electric heater at 615 fpm to be 0.02 in. wg.
X Voltage variations.
Variations from the rated voltage of the electric
heating coils can significantly affect the coils rated
output. The effects of voltage variation can be determined by the following formula.
kWa = kWr x
kWa
kWr
Va
Vr
=
=
=
=
Va
Vr
Performance data
ELECTRIC HEATING COIL AIR FRICTION
FINS
8
11
14
8
11
14
8
11
14
4
6
8*
300
0.15
0.19
0.23
0.23
0.29
0.34
0.30
0.38
0.46
700
0.66
0.79
0.90
1.00
1.18
1.36
1.33
1.57
1.81
FINS
1 or 2
8
11
14
300
0.08
0.09
0.12
400
0.13
0.15
0.19
500
0.19
0.22
0.27
1000
0.64
0.72
0.85
1100
0.75
0.85
0.99
FACE VELOCITY
(fpm)
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
STEAM COIL
AIR FRICTION (in. wg)
ROW FINS
DEPTH
1
6
9
12
300
0.03
0.07
0.12
400
0.05
0.11
0.18
500
0.07
0.17
0.27
AIR FRICTION
(in. wg)
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.03
0.03
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.08
0.08
0.09
0.09
0.10
0.11
0.12
250
650
NOTES:
1. Filters are field-supplied.
2. Do not exceed filter manufacturers velocity limits when selecting
filters.
3. Filters having cardboard-type frames are usually not suitable for
use in high velocity (flat) sections.
19
SATURATED
TEMP
(F)
212.0
218.5
227.1
239.4
249.8
258.8
266.8
274.0
280.6
286.7
297.7
307.3
316.0
323.9
331.1
337.9
352.9
365.9
377.4
LATENT
HEAT
(Btuh/lb)
970.3
966.2
960.6
952.6
945.7
939.5
934.0
928.9
924.2
920.0
911.9
904.6
898.0
891.9
886.1
880.7
868.3
857.2
847.0
10
10
20
30
40
50
60
70
80
90
100
1.021
1.050
1.088
1.142
1.188
1.227
1.263
1.294
1.323
1.350
1.398
1.441
1.479
1.514
1.546
1.576
1.641
1.699
1.749
0.977
1.006
1.044
1.098
1.144
1.183
1.219
1.250
1.279
1.306
1.354
1.397
1.435
1.470
1.502
1.531
1.597
1.655
1.705
0.933
0.962
1.000
1.054
1.100
1.139
1.175
1.206
1.235
1.262
1.310
1.353
1.391
1.426
1.458
1.487
1.553
1.611
1.661
0.889
0.918
0.956
1.010
1.055
1.095
1.130
1.162
1.191
1.218
1.266
1.309
1.347
1.382
1.414
1.443
1.509
1.567
1.617
0.845
0.874
0.912
0.966
1.011
1.051
1.086
1.118
1.147
1.174
1.222
1.265
1.303
1.338
1.370
1.399
1.465
1.523
1.573
0.801
0.830
0.868
0.922
0.967
1.007
1.042
1.074
1.103
1.130
1.178
1.221
1.259
1.294
1.326
1.355
1.421
1.479
1.529
0.757
0.786
0.824
0.878
0.923
0.963
0.998
1.030
1.059
1.086
1.134
1.177
1.215
1.250
1.282
1.311
1.377
1.435
1.485
0.713
0.742
0.780
0.834
0.879
0.919
0.954
0.986
1.015
1.042
1.090
1.133
1.171
1.206
1.238
1.267
1.333
1.391
1.441
0.669
0.698
0.736
0.790
0.835
0.875
0.910
0.942
0.971
0.998
1.046
1.089
1.127
1.162
1.194
1.223
1.289
1.346
1.397
0.625
0.654
0.692
0.746
0.791
0.831
0.866
0.898
0.927
0.954
1.002
1.045
1.083
1.118
1.150
1.179
1.245
1.302
1.353
0.581
0.610
0.648
0.702
0.747
0.787
0.822
0.854
0.883
0.910
0.958
1.001
1.039
1.074
1.106
1.135
1.201
1.258
1.309
0.537
0.566
0.604
0.658
0.703
0.743
0.778
0.810
0.839
0.866
0.914
0.957
0.995
1.030
1.062
1.091
1.157
1.214
1.265
0.493
0.522
0.560
0.614
0.659
0.699
0.734
0.766
0.795
0.822
0.870
0.913
0.951
0.986
1.018
1.047
1.113
1.170
1.221
*Based on:
Used as an air temperature rise correction multiplier for rated air temperature rise
(ATR). Actual coil capacity = coil capacity (tabular) x steam air temperature rise
constant.
20
10
10
15
20
25
30
40
50
60
70
80
FINS
PER IN.
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
6
9
12
Ldb
(F)
51.2
84.0
109.5
58.3
89.8
114.2
65.4
95.6
119.0
72.5
101.4
123.8
76.1
104.3
126.1
79.6
107.2
128.5
83.2
110.1
130.9
86.8
113.0
133.3
93.9
118.8
138.0
101.0
124.6
142.8
108.1
130.3
147.6
115.2
136.1
152.3
122.4
141.9
157.1
400
MBtuh/
sq ft
30.9
45.2
56.3
29.7
43.4
54.0
28.4
41.6
51.7
27.2
39.7
49.5
26.6
38.8
48.3
25.9
37.9
47.2
25.3
37.0
46.0
24.7
36.1
44.9
23.4
34.2
42.6
22.2
32.4
40.3
20.9
30.6
38.1
19.7
28.8
35.8
18.4
26.9
33.5
Ldb
(F)
42.5
71.4
95.1
50.0
77.7
100.5
57.5
84.0
105.8
64.9
90.3
111.2
68.7
93.5
113.8
72.4
96.6
116.5
76.1
99.8
119.2
79.9
102.9
121.8
87.3
109.2
127.2
94.8
115.5
132.5
102.3
121.8
137.9
109.7
128.1
143.2
117.2
134.4
148.5
500
MBtuh/
sq ft
34.0
49.7
62.6
32.6
42.7
60.1
31.2
45.7
57.5
29.9
43.7
55.0
29.2
42.7
53.7
28.5
41.6
52.5
27.8
40.6
51.2
27.1
39.6
49.9
25.7
37.6
47.4
24.4
35.6
44.9
23.0
33.6
42.3
21.6
31.6
39.8
20.2
29.6
37.3
LEGEND
Ldb
Leaving Air, Dry Bulb
MBtuh Btuh in Thousands
NOTES:
1. Calculate condensate flow rate (W) lb/hr for saturated steam applications
as follows:
rated MBtuh ft2 x 1000 x tabulated coil face area (sq ft)
W=
rated latent heat of vaporization (Btuh/lb)
20
Ldb
(F)
22.5
42.3
60.3
30.8
49.7
67.1
39.1
57.2
73.8
47.3
64.7
80.6
51.5
68.4
83.9
55.6
72.2
87.3
59.8
75.9
90.7
63.9
79.7
94.1
72.2
87.1
100.8
80.5
94.6
107.6
88.7
102.1
114.3
97.0
109.6
121.1
105.3
117.1
127.8
1000
MBtuh/
sq ft
45.2
67.7
87.3
44.3
64.9
83.8
42.5
62.2
80.2
40.6
59.5
76.7
39.7
58.1
74.9
38.7
56.7
73.2
37.8
55.4
71.4
36.9
54.0
69.6
35.0
51.3
66.1
33.1
48.5
62.6
31.2
45.8
59.0
29.4
43.0
55.5
27.5
40.3
52.0
5.0 Psig
227.1 F
960.7 Btu/lb
Ldb
(F)
19.0
36.3
52.2
27.5
44.1
59.2
35.9
51.8
66.3
44.3
59.5
73.4
48.5
63.4
76.9
52.7
67.2
80.5
56.9
71.1
84.0
61.1
74.9
87.6
69.6
82.7
94.6
78.0
90.4
101.7
86.4
98.1
108.8
94.8
105.8
115.9
103.2
113.5
123.0
1200
MBtuh/
sq ft
50.9
73.5
94.1
48.9
70.5
90.3
46.8
67.5
86.5
44.7
64.6
82.7
43.7
63.1
80.8
42.7
61.6
78.9
41.7
60.1
77.0
40.6
58.6
75.1
38.6
55.6
71.3
36.5
52.7
67.5
34.4
49.7
63.6
32.4
46.7
59.8
30.3
43.7
56.0
HEATER
AREA
(sq ft)
NO. OF
CONTROL
STEPS*
03
2.2
06
3.7
08
5.1
10
6.2
12
7.3
15
10.0
18
11.74
21
14.21
25
17.79
AHRI
FLA
MCA
MOCP
NEC
NOMINAL
HEATER COIL
FACE
COIL
VELOCITY
kW
(fpm)
9
500
15
500
17.2
500
8
500
10
500
17
500
19.9
500
27
500
29.8
500
36
500
15
500
25
500
35
500
39.9
500
43.2
500
51
500
15
500
25
500
39.9
500
47.3
500
51.8
500
59.8
500
19.9
500
29.8
500
39.9
500
43
500
51.8
500
72
500
19.9
500
29.8
500
39.9
500
45
500
51.8
500
65
500
86
500
19.9
500
25.8
500
35
500
45
500
51.8
500
78
500
94
500
19.9
500
25.8
500
35
500
45
500
51.8
500
79.8
500
92
500
116
500
30
500
39.9
500
50
500
65
500
79.8
500
96.5
500
110
500
145
500
TEMP
RISE
(F)
Total
FLA
26
44
50
14
17
29
34
47
51
62
19
31
44
50
54
64
15
26
41
49
53
62
17
26
35
38
45
63
13
19
25
29
33
42
55
11
14
19
25
28
43
51
9
12
16
20
23
36
41
52
11
14
18
23
29
35
39
52
25
42
48
22
28
47
55
75
83
100
42
69
97
111
120
142
42
69
111
131
144
55
83
111
119
144
55
83
111
125
144
55
72
97
125
144
55
72
97
125
144
83
111
139
181
222
268
208/3/60 VOLTS
No.
MCA Sub- MOCP
Ckt
31
1
35
52
1
60
60
1
60
28
1
30
35
1
35
59
1
60
69
2
70
94
2
100
104
2
110
125
3
150
52
1
60
87
2
90
122
3
125
139
3
150
150
3
175
177
3
200
52
1
60
87
2
90
139
3
150
164
3
175
180
3
200
69
2
70
104
2
110
139
3
150
149
3
150
180
3
200
69
2
70
104
2
110
139
3
150
156
3
175
180
3
200
69
2
70
90
2
90
122
3
125
156
3
175
180
3
200
69
2
70
90
2
90
122
3
125
156
3
175
180
3
200
104
2
110
139
3
150
174
3
175
226
4
250
277
5
300
335
6
350
Total
FLA
22
36
41
19
24
41
48
65
72
87
36
60
84
96
104
123
36
60
96
114
125
48
72
96
104
125
48
72
96
108
125
48
62
84
108
125
48
62
84
108
125
72
96
120
157
192
232
265
240/3/60 VOLTS
No.
MCA Sub- MOCP
Ckt
27
1
30
45
1
50
52
1
60
24
1
25
30
1
35
51
1
60
60
1
60
81
2
90
90
2
90
108
2
110
45
1
50
75
2
80
105
2
110
120
3
125
130
3
150
154
3
175
45
1
50
75
2
80
120
3
125
142
3
150
156
3
175
60
1
60
90
2
90
120
3
125
129
3
150
156
3
175
60
1
60
90
2
90
120
3
125
135
3
150
156
3
175
60
1
60
78
2
80
105
2
110
135
3
150
156
3
175
60
1
60
78
2
80
105
2
110
135
3
150
156
3
175
90
2
100
120
3
125
151
3
175
196
4
200
240
5
250
291
5
300
331
6
350
Total
FLA
11
18
21
10
12
20
24
33
36
43
18
30
42
48
52
61
18
30
48
57
62
72
24
36
48
52
62
87
24
36
48
54
62
78
104
24
31
42
54
62
94
113
24
31
42
54
62
96
111
140
36
48
60
78
96
116
132
175
480/3/60 VOLTS
No.
MCA Sub- MOCP
Ckt
14
1
20
23
1
25
26
1
30
12
1
20
15
1
20
26
1
30
30
1
30
41
1
45
45
1**
45
54
1**
60
23
1
25
38
1
40
53
1
60
60
2
70
65
2
70
77
2
80
23
1
25
38
1
40
60
2
70
71
2
80
78
2
80
90
2
100
30
1
30
45
1
45
60
2
70
65
2
70
78
2
80
108
2
110
30
1
30
45
1
45
60
2
70
68
2
70
78
2
80
98
2
100
129
3
150
30
1
30
39
1
40
53
1
60
68
2
70
78
2
80
117
2
125
141
3
150
30
1
30
39
1
40
53
1
60
68
2
70
78
2
80
120
3
125
138
3
150
175
3
175
45
1
50
60
2
70
75
2
80
98
2
100
120
3
125
145
3
150
166
3
175
218
4***
225
Total
FLA
14
23
26
12
15
26
30
41
45
55
23
38
53
61
66
78
23
38
61
72
79
91
30
45
61
65
79
110
30
45
61
68
79
99
131
30
39
53
68
79
119
143
30
39
53
68
79
121
140
46
61
76
99
121
147
167
221
380/3/50 VOLTS
No.
MCA Sub- MOCP
Ckt
17
1
20
29
1
30
33
1
35
15
1
20
19
1
20
32
1
35
38
1
40
51
1
60
57
1
60
68
2**
70
29
1
30
48
1
50
67
2
70
76
2
80
82
2
90
97
2
100
29
1
30
48
1
50
76
2
80
90
2
90
98
2
100
114
2
125
38
1
40
57
1
60
76
2
80
82
2
90
98
2
100
137
3
150
38
1
40
57
1
60
76
2
80
86
2
90
98
2
100
124
3
125
164
3
175
38
1
40
49
1
50
67
2
70
86
2
90
98
2
100
148
3
150
179
3
200
38
1
40
49
1
50
67
2
70
86
2
90
98
2
100
152
3
175
175
3
175
57
1
60
76
2
80
95
2
100
124
3
125
152
3
175
183
4***
200
209
4***
225
276
5
300
LEGEND
Air Conditioning, Heating and Refrigeration Institute
Full Load Amps
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code
*Standard control steps are listed under the Control Step heading. Free additional steps of
control are optionally available when the number of subcircuits exceeds the standard
number of control steps.
MCA = 1.25 x FLA; for proper wire sizing, refer to Table 310-16 of the NEC.
**2 control steps in this voltage.
3 control steps in this voltage.
***4 control steps in this voltage.
5 control steps in this voltage.
NOTES:
1. Subcircuits are internal heater circuits of 48 amps or less.
2. Electric heat performance is not within the scope of AHRI standard 430 certification.
3. To avoid damage due to overheating, minimum face velocity cannot fall below 350 fpm.
21
22
06
.94
1.10
.94
1.08
.94
1.05
.94
1.02
.94
1.00
.94
1.00
.96
1.00
.98
1.00
.99
1.00
.99
1.00
1.00
1.00
.96
.99
.96
.99
.96
.97
.95
.96
.95
.96
.96
.96
.97
.97
.98
.97
1.00
1.00
1.00
1.00
1.00
1.00
.97
1.02
1.00
1.08
1.00
1.07
.99
1.05
.98
1.03
.98
1.04
.97
1.04
.98
1.04
.98
1.04
1.00
1.02
1.00
1.00
25
.96
1.05
.94
1.02
.94
1.02
.94
1.02
.95
1.02
.95
1.00
.95
.98
.96
.97
.96
.97
.98
.97
1.00
1.00
25
.91
.91
.91
.91
.91
.91
.91
.91
.93
.93
.95
.96
.98
1.00
.99
1.00
1.00
1.00
1.00
1.00
1.00
1.00
.94
1.00
.94
1.00
.93
1.00
.93
1.00
.93
1.00
.94
1.00
.94
1.00
.96
1.00
.97
1.00
1.00
1.00
1.00
1.00
.96
1.05
.94
1.02
.94
1.02
.94
1.02
.95
1.02
.95
1.00
.95
.98
.96
.97
.96
.97
.98
.97
1.00
1.00
IGV*
03-18 21-25
1.13
1.45
1.11
1.37
1.10
1.21
1.08
1.17
1.06
1.14
1.03
1.10
1.02
1.08
1.01
1.05
1.01
1.02
1.00
1.01
1.00
1.00
.94
.97
.94
.97
.95
.98
.95
.99
.96
.99
.96
1.00
.96
1.00
.98
1.00
.98
1.00
.98
1.00
1.00
1.00
39LA03
BRAKE HORSEPOWER
SPEED (RPM)
23
SPEED (RPM)
24
39LA08
BRAKE HORSEPOWER
SPEED (RPM)
25
SPEED (RPM)
26
39LA12
BRAKE HORSEPOWER
SPEED (RPM)
27
SPEED (RPM)
28
39LA18
BRAKE HORSEPOWER
SPEED (RPM)
29
SPEED (RPM)
30
39LA25
BRAKE HORSEPOWER
SPEED (RPM)
31
Physical data
Dimensions
39LA UNIT
LEGEND
L.H. Left Hand
R.H. Right Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LA
03
06
08
10
12
15
18
21
25
32
3-415/16
4-013/16
4-811/16
4-811/16
4-811/16
6-07/16
6-85/16
6-85/16
6-43/8
3-17/8
3-93/4
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
2-01/4
2-43/16
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
1-23/16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
E
0- 93/8
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
0- 79/16
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
0-13/4
0-13/4
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
1-111/2
2- 37/16
2- 73/8
2- 73/8
2- 73/8
3- 31/4
3- 73/16
3- 73/16
3- 73/16
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
Dimensions (cont)
39LB UNIT
LEGEND
L.H. Left Hand
R.H. Right Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LB
03
06
08
10
12
15
18
21
25
2-51/8
2-91/16
3-1
3-1
3-1
3-87/8
4-013/16
4-013/16
4-811/16
3-17/8
3-93/4
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
2-01/4
2-43/16
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
1-23/16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
E
0- 93/8
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
0- 79/16
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
0-13/4
0-13/4
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
1-1111/16
1- 33/4
1- 79/16
1- 79/16
1- 79/16
2- 37/16
2- 73/8
2- 73/8
2-1115/16
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
33
LEGEND
L.H. Left Hand
R.H. Right Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LC
03
06
08
10
12
15
18
21
25
34
A
3-1
3-415/16
3-87/8
3-87/8
3-87/8
4-43/4
4-811/16
4-811/16
5-49/16
3-17/
2-01/
1-23/
93 /
79 /
0-13/
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
8
3-93/4
4
2-43/16
16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
08
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
016
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
4
0-13/4
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
1-79/
1-43/
2-115/16
3- 31/4
3- 73/16
3- 73/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
16
1-111/2
2- 37/16
2- 37/16
2- 37/16
4
1-811/16
K
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
Dimensions (cont)
39LD UNIT
LEGEND
L.H. Left Hand
R.H. Right Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LD
03
06
08
10
12
15
18
21
25
1-91/
3-17/
3-91/
1-23/
9 3/
7 9/
0-13/
16
3-93/
4-55/
0-13/
2-13/
2-51/8
2-51/8
2-51/8
3-1
3-415/16
3-415/16
4-013/16
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
2
16
5-11/4
5-11/4
5-11/4
6-415/16
7-013/16
7-013/16
8-45/8
16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
08
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
016
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
313/
016
0- 313/16
0- 313/16
0- 313/16
0- 313/16
0- 313/16
0- 313/16
0- 313/16
1-111/2
1-43/
4
1-811/
16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
35
LEGEND
L.H. Left Hand
R.H. Right Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LF,LH
03
06
08
10
12
15
18
21
25
36
1-91/4
2-13/16
2-51/8
2-51/8
2-51/8
3-1
3-415/16
3-415/16
4-013/16
3-17/8
3-93/4
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
3-91/2
4-55/16
5-11/4
5-11/4
5-11/4
6-415/16
7-013/16
7-013/16
8-45/8
1-23/16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
E
0- 93/8
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
0- 79/16
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
0-13/4
0-13/4
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
0- 313/16
0- 73/4
0-1111/16
0-1111/16
0-1111/16
0- 313/16
0- 313/16
0- 313/16
2-73/8
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
Dimensions (cont)
39LG UNIT
LEGEND
L.H. Left Hand
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39LG
03
06
08
10
12
15
18
21
25
1-91/4
2-13/16
2-51/8
2-51/8
2-51/8
3-1
3-415/16
3-415/16
4-013/16
3-17/8
3-93/4
4-111/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
2-01/4
2-43/16
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
1-23/16
1-313/16
1-41/2
1-81/2
1-53/4
2-01/2
2-55/8
2-55/8
3-01/2
E
0- 93/8
1- 05/16
1- 2
1- 29/16
1- 61/2
1- 615/16
1- 63/8
1-105/8
1- 93/8
0- 79/16
1-10
0-101/4
1- 13/4
1- 2
1- 33/8
1- 35/8
1- 65/8
1- 613/16
0-13/4
0-13/4
0-13/4
0-13/4
0-13/4
0-21/4
0-21/4
0-21/4
0-23/4
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1- 71/2
1-111/2
2- 37/16
2- 37/16
2- 37/16
2-1013/16
3- 23/4
3- 23/4
3-101/16
37
DIMENSIONS (ft-in.)
UNIT
39L03
06
08
10
12
15
18
21
25
1-91/4
3-1
3-87/8
4-013/16
4-811/16
5-49/16
5-49/16
5-49/16
6-43/8
6-43/8
2-13/16
2-51/8
2-51/8
2-51/8
3-1
3-415/16
3-415/16
4-013/16
AIR
INLET
0'-3" [77]
TYPICAL
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39L03
06
08
10
12
15
18
21
25
38
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2-117/16
2-117/16
2-117/16
3-17/8
3-93/4
4-111/16
4-99/16
5-57/16
5-57/16
5-57/16
6-51/4
6-51/4
2-01/4
2-43/16
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
1- 5
1-11
3- 1
3- 5
3-11
3-11
3-11
3-11
5- 4
1-5
1-5
1-5
1-5
1-5
1-9
2-3
2-5
2-5
F
000000000-
15/8
41/8
61/16
61/16
61/16
8
7
6
97/16
0-61/16
0-61/16
0-61/16
0-61/16
0-61/16
0-41/16
0-5
0-4
0-4
0-101/2
0-113/8
0- 63/8
0- 85/16
0- 91/4
0- 91/4
0- 91/4
1- 31/8
0- 65/8
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
1-51/4
2-11/4
3-31/4
3-71/4
4-11/4
4-11/4
4-11/4
4-11/4
5-61/4
1- 51/4
1- 71/4
1- 71/4
1- 71/4
1- 71/4
1-111/4
2- 51/4
2- 71/4
2- 71/4
(ANG)
ANGLE FILTER
(PHW)
PREHEAT WATER
(ACC)
ACCESS SECTION
(PHE)
PREHEAT ELECTRIC
*Add to other components for total unit length when assembled to base unit.
All FLT, ANG, and ACC doors are hinged and are on same side of unit as fan door (motor side).
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed while
facing the direction toward which air is flowing.
2. Dimensions in ( ) are in millimeters.
DIMENSIONS (ft-in.)
UNIT
39L-
03
06
08
10
12
15
18
21
25
2-01/4
2-43/16
2-81/8
2-81/8
2-81/8
3-4
3-715/16
3-715/16
4-313/16
DOOR
OPENING
B
1-43/4
1-811/16
2-05/8
2-05/8
2-05/8
2-81/2
3-07/16
3-07/16
3-85/16
39
DIMENSIONS (ft-in.)
SIZE
03
06
08
10
12
15
18
21
25
40
A
3-17/8
3-93/4
4-11/16
4-99/16
5-51/16
5-51/16
5-51/16
6-51/4
6-51/4
B
3-13/4
3-95/8
4-19/16
4-97/16
5-55/16
5-55/16
5-55/16
6-51/8
6-51/8
C
1-91/4
2-13/16
2-51/8
2-51/8
2-51/8
3-1
3-415/16
3-415/16
4-015/16
39LA
1- 711/16
1-115/8
2- 39/16
2- 39/16
2- 39/16
2-119/16
3- 33/8
3- 33/8
2- 39/16
D
39LB
0-77/8
0-77/8
0-77/8
0-77/8
0-77/8
0-77/8
0-77/8
0-77/8
0-77/8
39LC
1-33/4
1-33/4
1-33/4
1-33/4
1-33/4
1-33/4
1-33/4
1-33/4
1-33/4
E
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2- 39/16
2-117/16
2-117/16
2-117/16
Space requirements
ROUGHING-IN DIMENSIONS (in.)
39LA (Cooling)
39LB (Cooling)
39LC (Cooling/Heating)
(Heating/Cooling)
(Cooling Only)
39LD (Cooling)
39L
UNIT
SIZE
L
41
49
57
57
57
73
80
80
76
03
06
08
10
12
15
18
21
25
39L
UNIT
SIZE
W
38
46
50
58
65
65
65
77
77
H
24
28
32
32
32
40
44
44
52
L
29
33
37
37
37
45
49
49
57
39LF
(Cooling/Heating)
(Heating/Cooling)
(Cooling
Only)
03
06
08
10
12
15
18
21
25
L
21
25
29
29
29
37
41
44
49
W
38
46
50
58
65
65
65
77
77
W
38
46
50
58
65
65
65
77
77
H
24
28
32
32
32
40
44
44
52
L
37
41
45
45
45
53
57
57
65
H
46
53
61
61
61
77
85
85
101
L
21
25
29
29
29
37
41
41
49
W
38
46
50
58
65
65
65
77
77
W
38
46
50
58
65
65
65
77
77
H
24
28
32
32
32
40
44
44
52
L
21
25
29
29
29
37
41
41
49
W
38
46
50
58
65
65
65
77
77
H
46
53
61
61
61
77
85
85
101
39LH (Heating)
H
24
28
32
32
32
40
44
44
52
L
21
25
29
29
29
37
41
41
49
W
38
46
50
58
65
65
65
77
77
H
46
53
61
61
61
77
85
85
101
LEGEND
L Length
W Width
H Height
ANGLE
FILTER
20
20
20
20
20
20
20
20
20
FLAT
FILTER
8
8
8
8
8
8
8
8
8
ACCESS
20
20
20
20
20
20
20
20
20
PREHEAT
(Water)
8
8
8
8
8
8
8
8
8
PREHEAT
(Electric)
20
20
20
20
20
20
20
20
20
MIXING
BOX
28
28
28
28
28
28
35
35
35
FILTER-MIXING
BOX
28
28
28
28
28
28
35
35
35
41
03
9 1 /2
2500
3/
4
06
125/8
2000
13/16
08
125/8
2000
13/16
10
15
1600
13/16
12
15
1600
13/16
15
181/8
1400
17/16
18
20
1300
17/16
21
20
1100
17/16
25
25
1000
111/16
2.3
4.8
4.8
43
8.0
8.9
7.2
43
8.0
8.9
10
43
8.0
10.4
13
51
10.4
11.6
17
51
14.5
17.9
29
48
14.5
17.9
34
53
16.5
20.2
42
53
21.5
27.7
70
56
5
3
71/2
5
10
10
10
15
15
10
15
10
20
20
20
20
2
2
5
5
10
5
10
10
15
10
15
10
20
15
20
20
25
25
LEGEND
IGV Inlet Guide Vanes
ODP Open Drip Proof
TEFC Totally Enclosed Fan Cooled
*At fan sheave.
See Motor and Drive Package Data table below for drive type limitations.
03
IGV
OPTION
No IGV
No IGV
06
IGV
No IGV
08
IGV
No IGV
10
IGV
42
HP
REF
MOTOR
FRAME
1/
2
3/
4
56
56
143T
145T
145T
56
143T
145T
145T
182T
184T
56
143T
145T
145T
182T
184T
145T
145T
182T
184T
213T
215T
145T
145T
182T
184T
213T
145T
145T
182T
184T
213T
215T
145T
145T
182T
184T
213T
215T
1
1 1 /2
2
3 /4
1
1 1 /2
2
3
5
3 /4
1
1 1 /2
2
3
5
1 1 /2
2
3
5
7 1 /2
10
1 1 /2
2
3
5
7 1 /2
1 1 /2
2
3
5
7 1 /2
10
1 1 /2
2
3
5
7 1 /2
10
FAN
SHAFT
DIAM. (in.)
3 /4
13/16
13/16
13/16
13/16
13/16
13/16
CENTER LINE
DISTANCE (in.)
MAX WIDTH
SHEAVE (in.)
RPM RANGE
Max
6.8
6.8
6.8
6.8
6.8
9.25
9.25
9.25
9.25
8.2
8.2
9.25
9.25
9.25
9.25
8.2
8.2
11.25
11.25
9.8
9.8
9.1
9.1
11.25
11.25
9.8
9.8
9.1
11.25
11.25
9.8
9.8
9.1
9.1
11.25
11.25
9.8
9.8
9.1
9.1
ODP
3.8
3.8
3.8
3.8
3.8
5.0
5.0
5.0
5.0
5.0
5.0
3.8
3.8
3.8
3.8
2.7
2.7
5.0
5.0
5.0
5.0
5.0
4.5
3.8
3.8
3.8
3.8
3.5
4.9
4.9
4.9
4.9
4.9
4.3
5.7
5.7
5.7
5.7
4.9
4.4
Max
1745
1934
2143
2375
2500
1137
1260
1397
1548
1805
2000
1137
1260
1397
1548
1805
2000
1327
1470
1629
1900
2000
2000
1327
1470
1629
1900
2000
1238
1372
1520
1600
1600
1600
1238
1372
1520
1600
1600
1600
Min
5.5
5.5
5.5
5.5
5.5
8.25
8.25
8.25
8.25
7.0
7.0
8.25
8.25
8.25
8.25
7.0
7.0
9.5
9.5
8.4
8.4
7.5
7.5
9.5
9.5
8.4
8.4
7.5
9.4
9.4
8.3
8.3
7.4
7.4
9.4
9.4
8.3
8.3
7.4
7.4
TEFC
3.8
3.8
3.8
3.8
3.8
5.0
5.0
5.0
5.0
5.0
4.0
3.8
3.8
3.8
3.8
2.4
5.0
5.0
5.0
5.0
4.6
3.8
3.8
3.8
3.1
4.9
4.9
4.9
4.9
4.9
3.4
5.7
5.7
5.7
5.7
4.9
3.8
Min
993
1045
1158
1283
1422
836
836
880
926
975
1197
836
836
880
926
975
1197
836
836
926
1026
1197
1327
836
836
926
1026
1197
668
668
780
820
957
1061
668
668
740
820
957
1061
DRIVE AVAILABILITY
ODP
TEFC
Fix
Var
Fix
Var
X
X
IGV
OPTION
No IGV
12
IGV
No IGV
15
IGV
No IGV
18
IGV
No IGV
21
IGV
No IGV
25
IGV
Fix
IGV
ODP
TEFC
Var
HP
REF
MOTOR
FRAME
1 1 /2
2
3
5
7 1 /2
10
15
1 1 /2
2
3
5
7 1 /2
10
15
3
5
7 1 /2
10
15
3
5
7 1 /2
10
15
3
5
7 1 /2
10
15
20
3
5
7 1 /2
10
15
3
5
7 1 /2
10
15
20
3
5
7 1 /2
10
15
20
5
7 1 /2
10
15
20
25
5
7 1 /2
10
15
20
145T
145T
182T
184T
213T
215T
254T
145T
145T
182T
184T
213T
215T
254T
182T
184T
213T
215T
254T
182T
184T
213T
215T
254T
182T
184T
213T
215T
254T
256T
182T
184T
213T
215T
254T
182T
184T
213T
215T
254T
256T
182T
184T
213T
215T
254T
256T
184T
213T
215T
254T
256T
284T
184T
213T
215T
254T
256T
FAN
SHAFT
DIAM. (in.)
13/16
13/16
17/16
17/16
17/16
17/16
17/16
17/16
111/16
111/16
CENTER LINE
DISTANCE (in.)
MAX WIDTH
SHEAVE (in.)
RPM RANGE
Max
11.25
11.25
9.8
9.8
9.1
9.1
7.8
11.25
11.25
9.8
9.8
9.1
9.1
7.8
13.5
13.5
12.6
12.6
11.4
13.5
13.5
12.6
12.6
11.4
15.6
15.6
14.7
14.7
13.5
13.5
15.6
15.6
14.7
14.7
13.5
15.6
15.6
14.7
14.7
13.5
13.5
15.6
15.6
14.7
14.7
13.5
13.5
17.9
17.6
17.6
17.1
17.1
16.1
17.9
17.6
17.6
17.1
17.1
ODP
5.7
5.7
5.7
5.7
5.7
5.7
5.3
5.7
5.7
5.7
5.7
5.7
5.7
5.3
6.4
6.4
6.4
6.4
6.1
6.4
6.4
5.6
5.6
4.2
6.3
6.3
6.3
6.3
5.7
4.7
6.3
6.3
6.3
6.3
4.8
6.2
6.2
6.2
6.2
5.6
4.5
6.2
6.2
6.2
6.2
5.6
4.5
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
Max
1061
1238
1444
1600
1600
1600
1600
1061
1238
1444
1600
1600
1600
1600
1083
1264
1400
1400
1400
1083
1264
1400
1400
1400
906
1058
1235
1300
1300
1300
906
1058
1235
1300
1300
798
1043
1100
1100
1100
1100
798
1043
1100
1100
1100
1100
729
909
959
1000
1000
1000
729
909
959
1000
1000
Min
9.4
9.4
8.3
8.3
7.4
7.4
6.6
9.4
9.4
8.3
8.3
7.4
7.4
6.6
11.4
11.4
10.4
10.4
9.4
11.4
11.4
10.4
10.4
9.4
13.3
13.3
12.4
12.4
11.2
11.2
13.3
13.3
12.4
12.4
11.2
13.3
13.3
12.4
12.4
11.2
11.2
13.3
13.3
12.4
12.4
11.2
11.2
16.1
15.4
15.4
14.4
14.4
13.2
16.1
15.4
15.4
14.4
14.4
TEFC
5.7
5.7
5.7
5.7
5.7
5.7
3.9
5.7
5.7
5.7
5.7
5.7
5.7
3.9
6.4
6.4
6.4
6.4
5.4
6.4
6.4
5.6
4.9
6.3
6.3
6.3
6.3
5.7
4.7
6.3
6.3
6.3
5.0
6.2
6.2
6.2
6.2
5.6
4.5
6.2
6.2
6.2
6.2
5.6
4.5
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
Min
668
668
740
779
863
1008
1176
668
668
740
779
863
1008
1176
613
613
716
794
881
613
613
716
794
881
514
514
570
632
738
818
514
514
570
632
738
430
523
579
643
715
798
430
523
579
643
715
798
380
445
470
551
617
654
380
445
470
551
617
DRIVE AVAILABILITY
ODP
TEFC
Fix
Var
Fix
Var
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
LEGEND
Fixed Pitch Drive
Inlet Guide Vanes
Open Drip Proof
Totally Enclosed Fan Cooled
Variable Pitch Drive
43
03
06
08
10
12
15
18
21
25
1996
3.63
16
26.1
3245
5.90
20
34.0
4345
7.90
24
37.9
5247
9.54
24
45.8
6149
11.2
24
53.7
8200
14.9
32
53.7
9740
17.7
38
53.7
11,880
21.6
38
65.5
13,750
25.0*
22/22
65.5
1496
2.72
12
26.1
2596
4.72
16
34.0
3619
6.58
20
37.9
4372
7.95
20
45.8
5126
9.32
20
53.7
6666
12.1
26
53.7
7689
14.0
30
53.7
9405
17.1
30
65.5
11,275
20.5
36
65.5
1904
2.72
12
26.1
3304
4.72
16
34.0
4606
6.58
20
37.9
5565
7.95
20
45.8
6524
9.32
20
53.7
8470
12.1
26
53.7
9800
14.0
30
53.7
11,970
17.1
30
65.5
14,350
20.5
36
65.5
2.13
4
25.5
4.18
6
33.4
6.22
8
37.3
7.53
8
45.2
8.85
8
53.1
11.06
10
53.1
13.28
12
53.1
16.21
12
53.1
18.92
14
64.9
03
200
150
170
230
230
120
220
39LA
39LB
39LC
39LD
39LF
39LG
39LH
06
280
210
238
322
322
168
308
08
411
308
349
472
472
246
452
10
470
352
400
540
540
282
517
UNIT SIZE
12
540
405
459
621
621
324
594
15
620
465
527
713
713
372
682
18
695
521
590
799
799
417
764
21
740
555
629
851
851
444
814
25
820
615
697
943
943
492
902
21
159
86
87
53
87
272
340
25
185
90
92
57
89
311
395
20
211
25
269
03
75
37
48
36
49
139
150
06
82
43
55
42
56
164
173
08
97
48
60
43
61
193
208
10
107
50
64
46
66
219
227
12
114
55
68
49
72
226
245
15
134
74
74
52
74
244
279
18
140
75
77
54
76
283
327
44
1 /2
21
3/4
24
1
30
1 1 /2
32
2
36
3
56
5
70
7 1 /2
127
10
141
15
187
03
06
08
10
12
15
18
21
25
59
68
90
104
105
134
118
152
147
190
192
255
214
294
271
357
303
398
48
57
68
76
91
102
97
122
144
112
139
161
142
176
210
172
213
256
195
245
295
227
293
356
257
336
415
20
30
35
45
40
55
50
65
60
80
65
95
80
110
90
125
100
140
50
55
60
70
80
85
85
100
115
95
115
130
110
125
145
135
155
180
150
175
205
180
214
248
215
256
297
LEGEND
FPI Fins per inch
*Coils are 1/2-in. OD with 14 aluminum fins per inch on copper tubes.
Steam coils are one-row, 1-in. OD.
03
COIL
TYPE
4-ROW
6-ROW
COIL
TYPE
4-ROW
6-ROW
D
F
H
Q
CIRCUITING
Q
H
F
D
H
F
D
CIRCUITING
Q
H
F
D
H
F
D
No.
Circuits
4
8
16
8
16
3.63
Connection
Size
11/2
11/2
11/2
11/2
11/2
10
11/2
12
11/2
20
11/2
24
21/2
10
11/2
12
11/2
20
11/2
24
21/2
36
21/2
19
11/2
19
11/2
16
11/2
32
21/2
38
21/2
38
21/2
76
21/2
16
11/2
19
11/2
19
11/2
32
21/2
38
21/2
38
21/2
48
21/2
57
21/2
57
21/2
10
No.
Circuits
12
24
12
24
36
9.54
Connection
Size
11/2
21/2
11/2
21/2
21/2
12
No.
Circuits
12
24
12
24
36
11.18
Connection
Size
11/2
21/2
11/2
21/2
21/2
25
No.
Circuits
22
44
88
44
66
25.00
Connection
Size
11/2
21/2
21/2
21/2
21/2
LEGEND
Double Circuit
Full Circuit
Half Circuit
Quarter Circuit
NOTES:
1. Connection sizes are MPT inches.
2. Sizes 21 and 25 have 2 coils.
45
03
COIL
TYPE
4-ROW
6-ROW
8-ROW*
CIRCUITING
Q
H
F
D
H
F
D
H
F
D
No.
Circuits
3
6
12
6
12
6
12
2.72
Connection
Size
11/2
11/2
11/2
11/2
11/2
11/2
11/2
8
11/2
10
11/2
16
11/2
20
21/2
8
11/2
10
11/2
16
11/2
20
21/2
30
21/2
8
11/2
10
11/2
16
11/2
20
21/2
40
21/2
10
No.
Circuits
10
20
10
20
30
10
20
40
H
13
11/2
15
11/2
15
11/2
18
11/2
4-ROW
1
1
1
F
26
2 /2
30
2 /2
30
2 /2
36
21/2
D
60
21/2
72
21/2
H
13
11/2
15
11/2
15
11/2
11/2
6-ROW
F
26
21/2
30
21/2
30
21/2
36
21/2
D
39
21/2
45
21/2
45
21/2
54
21/2
H
13
11/2
13
11/2
11/2
11/2
8-ROW*
F
26
21/2
30
21/2
30
21/2
36
21/2
D
52
21/2
60
21/2
60
21/2
72
21/2
D
F
H
Q
LEGEND
Double Circuit
Full Circuit
Half Circuit
Quarter Circuit
46
7.95
Connection
Size
11/2
21/2
11/2
21/2
21/2
11/2
21/2
21/2
12
No.
Circuits
10
20
10
20
30
10
20
40
9.23
Connection
Size
11/2
21/2
11/2
21/2
21/2
11/2
21/2
21/2
UNIT SIZE
CIRCUITING TYPE
CFM AT 550 FPM
FACE AREA (sq ft)
TUBE FACE
TUBE LENGTH (in.)
NUMBER OF CIRCUITS
NUMBER OF TXVs
NUMBER OF CIRCUITS/TXV
SUCTION CONNECTIONS
(in. OD)
DISTRIBUTOR CONNECTIONS
(in. OD)
4-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
6-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
Qtr
10
Half
12
Full
Half
12
24
Full
6149
11.18
24
53.7
12
24
5247
9.54
24
45.8
2
2
2
4
2
8
2
5
2
10
2
6
2
12
2
6
2
12
2
6
2
12
7 /8
1 1 /8
1 3 /8
1 1 /8
1 3 /8
1 1 /8
1 5 /8
1 1 /8
1 5 /8
1 1 /8
1 5 /8
7 /8
7 /8
1 1 /8
7 /8
1 1 /8
7 /8
1 5 /8
7 /8
1 5 /8
7 /8
1 1 /8
52
26
32
34
18
40
20
45
23
11
13
2
11
15
2
11
16
3
13
18
4
15
18
4
13
18
5
15
18
5
13
18
6
15
18
6
39
20
47
24
51
26
59
30
67
34
11
15
2
11
16
3
11
16
3
13
18
3
13
18
4
15
21
4
13
18
5
15
21
5
13
18
6
15
21
6
L
2
5-6
25
Full
13,750
25.0
22U-22L
65.5
44
U
L
2
2
11
11
Half
22
Double
88
2
8
4*
8
2
9-10
4*
9-10
2
9-10
4*
9-10
U
2
5-6
1 1 /8
1 3 /8
1 3 /8
13/8
1 3 /8
1 1 /8
1 1 /8
1 1 /8
1 3 /8
1 3 /8
1 5 /8
1 5 /8
1 1 /8
1 1 /8
1 1 /8
11/8
1 1 /8
1 1 /8
7/
7/
1 3 /8
1 3 /8
1 3 /8
1 3 /8
45
23
45
23
54
26
54
54
26
26
12
21
8
15
23
5
15
23
5
U
4
11
L
4
11
15
26
8
16
16
4
16
28
10
16
16
5
16
28
10
163/4
163/4
5
12
21
8
67
34
67
34
81
40
40
40
15
23
8
16
16
4
16
28
10
18
18
5
16
28
10
181/2
181/2
5
15
22
5
15
22
5
LEGEND
L
Lower
TXV Thermostatic Expansion Valve
U
Upper
47
UNIT SIZE
CIRCUITING TYPE
CFM AT 550 FPM
FACE AREA (sq ft)
TUBE FACE
TUBE LENGTH (in.)
NUMBER OF CIRCUITS
NUMBER OF TXVs
NUMBER OF CIRCUITS/TXV
SUCTION CONNECTIONS
(in. OD)
DISTRIBUTOR CONNECTIONS
(in. OD)
4-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
6-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
8-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
UNIT SIZE
CIRCUITING TYPE
CFM AT 550 FPM
FACE AREA (sq ft)
TUBE FACE
TUBE LENGTH (in.)
NUMBER OF CIRCUITS
NUMBER OF TXVs
NUMBER OF CIRCUITS/TXV
SUCTION CONNECTIONS
(in. OD)
DISTRIBUTOR CONNECTIONS
(in. OD)
4-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
6-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
8-ROW COIL
Circuit Equivalent Length (ft)
Distributor Tube Length (in.)
Face Split
Row Split
Distributor Nozzle Size**
TXV
12
Full
Half
4372
7.95
20
45.8
Full
5126
9.32
20
53.7
10
2
5
20
2
10
10
2
5
20
2
10
7/
1 1 /8
7/
1 1 /8
1 3 /8
1 1 /8
1 3 /8
1 1 /8
1 3 /8
1 1 /8
1 3 /8
7/
7/
7/
7/
1 1 /8
7/
7/
7/
7/
7/
7/
26
62
32
34
18
40
20
45
23
11
11
1 1 /2
11
11
1 1 /2
11
11
2 1 /2
11
15
2 1 /2
11
16
4
18
18
4
11
16
5
18
18
5
11
16
5
18
18
5
58
39
47
24
51
26
59
30
67
34
111/2
111/2
1 1 /2
111/2
13
1 1 /2
111/2
15
2 1 /2
111/2
16
3
111/2
16
4
13
181/2
4
111/2
16
5
13
181/2
5
111/2
16
5
13
181/2
5
52
63
32
68
34
78
39
89
45
111/2
13
1 1 /2
111/2
15
2 1 /2
111/2
16
3
111/2
16
4
13
181/2
4
111/2
16
5
13
181/2
5
111/2
16
5
13
181/2
5
18
2
9
25
Full
11,275
20.5
36
65.5
36
4*
9
Half
Double
72
4*
18
13/8
1 3 /8
1 3 /8
1 3 /8
1 3 /8
1 3 /8
13/8
1 3 /8
1 5 /8
7/8
7 /8
7/8-11/8
7/8-11/8
7/8-11/8
7/8-11/8
11/8
1 1 /8
1 3 /8
45
23
45
23
54
26
54
26
13
21
6
16
16
3
13
23
8
16
16
4
13/15
231/2
8
16
16
4
16
26
8
15
15
4
67
34
67
34
81
40
40
13
21
6
16
16
3
13
231/2
8
16
16
4
13/15
231/2
8
16
16
4
163/4
163/4
4
89
45
89
45
54
54
26
163/4
163/4
16
16
8
13
21
6
52
16
16
3
15
231/2
8
LEGEND
Thermostatic Expansion Valve
48
10
Half
16
16
4
16
16
4
03
06
08
10
12
15
18
21
25
15
15
30
15
15
30
18
18
36
No. of Circuits
1-ROW
2-ROW
H
F
6
6
12
8
8
16
10
10
20
10
10
20
10
10
20
13
13
26
LEGEND
F Full Circuit
H Half Circuit
NOTE: All hot water coils have 11/2-in. MPT.
03
06
08
10
12
15
18
21
25
2.5
3.2
3.5
4.7
4.5
6.0
5.2
6.8
5.6
7.7
7.3
10.1
8.5
11.7
10.4
14.2
12.0
16.3
2.1
2.4
2.7
3.3
3.7
4.1
3.9
5.1
6.4
4.1
5.9
7.4
5.1
6.6
8.4
6.3
8.3
10.7
7.3
9.5
12.1
8.7
11.8
14.7
9.8
13.5
17.2
0.5
0.7
0.8
1.3
1.0
1.6
1.3
2.0
1.5
2.4
1.8
2.9
2.1
3.4
2.5
4.0
2.9
4.8
OPERATING CHARGE
39L UNIT SIZE
REFRIGERANT
4
ROW
6
8*
03
06
08
10
1-2
1-2
2-3
2-3
2-4
3-5
3-4
5-6
5-6
4-5
5-6
5-7
12
15
R-22 (lb)
4-5
5- 6
6-8
8-10
7-9
10-12
18
21
25
6- 7
9-11
12-14
6- 8
11-13
13-19
6- 9
11-16
16-24
FILTER DATA
39L UNIT SIZE
Angle Filter
QtySize (in.)
Nominal Face Area
(sq ft)
Filter Mixing Box
QtySize (in.)
Nominal Face Area
(sq ft)
Flat Filter
QtySize (in.)
Nominal Face Area
(sq ft)
03
06
08
10
12
15
18
21
25
216x25
416x20
616x20
916x20
1216x20
8.89
216x20
216x25
10.00
416x25
5.56
11.11
13.33
20.00
26.67
416x20
816x25
31.11
416x20
816x25
31.11
216x25
416x20
416x25
616x20
916x20
916x20
5.56
8.89
11.11
13.33
20.00
20.00
316x20
616x25
23.33
416x20
816x25
31.11
216x16
220x20
220x25
216x25
120x25
320x25
616x20
316x20
320x20
320x25
316x25
3.56
5.56
6.94
9.03
10.42
13.33
15.00
18.75
216x20
220x20
220x25
216x25
22.50
216x20
216x25
10.00
49
LEGEND
NEC National Electrical Code
NOTE: All wiring must be copper and conform to the National Electrical Code.
50
Guide specifications
2. Optional double wall construction shall be available with inner panels constructed of 20 gage
steel.
3. Hinged access doors shall be double wall with
1.5 lb dual-density fiberglass between galvanized steel panels.
4. Insulation for casing panels on unit shall be
1-in. minimum thickness dual-density fiberglass
insulation with a nominal density of not less
than 1.5 lb per cubic foot.
5. Insulation shall be secured to casing with waterproof adhesive.
6. Condensate drain pans shall be sloped to prevent standing water and constructed of stainless
steel; they shall have double wall construction
with threaded drain connection.
C. Fan Section:
1. Fan sections shall be constructed of galvanized
steel and shall have a formed channel base for
integral mounting of fan, motor, and casing
panels. Fan scroll, wheel, shaft, and bearings
are to be rigidly secured to the base unit.
2. Each unit shall have a single fan wheel and
scroll. Fans shall be double width, double
inlet type, with forward-curved blades. Wheels
shall be bonderized steel with baked enamel, or
galvanized steel.
3. Fan wheels shall be keyed to the shaft and shall
be designed for continuous operation at the
maximum rated fan speed and motor horsepower. Fan wheels and shafts shall be selected
to operate at least 25% below the first critical
speed, and shall be statically and dynamically
balanced as an assembly.
4. Fan shafts shall be solid steel, turned, ground
and polished.
5. Fan bearings shall be self-aligning, pillow-block
regreasable ball type selected for an average life
of 200,000 hours at design operation conditions, per ANSI Code B3.15.
6. Fan motor shall be mounted within the fan section casing on slide rails having 2 adjusting
screws. Motor shall be NEMA Design B with
sizes and electrical characteristics as shown on
the equipment schedule.
7. Fan drive shall be designed for a 1.5 service factor and shall be factory mounted and aligned.
Belt drive shall be variable or fixed-pitch type.
D. Coil Sections:
1. All coils shall have mill galvanized casings. Coils
shall be factory leak tested at 450 psig air
pressure.
2. Chilled water coils shall have aluminum plate
fins with belled collars bonded to 1/2-in. minimum OD copper tubes by mechanical expansion. Coils shall have galvanized steel casings
and copper headers with threaded steel pipe
913
51
114
5-05
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Section 8
Catalog No. 04-52390001-01
Printed in U.S.A.
Pg 52
Form 39L-6PD
Replaces: 39L-5PD
Tab
8a