You are on page 1of 6

SUPPLY | CRITICAL ROOM SOLUTIONS

CRFF | FAN FILTER UNIT


INTRODUCTION: CRFF Series
Kruegers CRFF and CRFF-E series of critical room fan filter
units are intended for environments that demand the highest
levels of cleanliness, such as laboratories, clean rooms and
microprocessor assembly areas just to name a few. Each unit
contains an integral HEPA filter for improving contaminant and
particulate removal from supply air. These devices combine
quiet operation, low power consumption and a space saving
low profile design to meet a variety of applications. Additionally,
these devices are modular and can be used in nominally sized
24 x 24 and 24 x 48 grid systems.

CRITICAL ROOM SOLUTIONS

CRFF Single Unit

models
MODEL CRFF

- Critical Room Fan Filter with HEPA


Filter
MODEL CRFF-ARS - Critical Room Fan Filter with HEPA
Filter and Room Side Access
MODEL CRFF-E
- Critical Room Fan Filter with HEPA
Filter and ECM Motor
MODEL CRFF-E-ARS - Critical Room Fan Filter with HEPA
Filter, ECM Motor, and Room Side
Access

CRFF Series FEATURES


Quiet Operation
Low Power Consumption
Space Saving Low Profile Design, less than 13 inches in







height (CRFF Only)


PSC Motor w/ Solid State Speed Control or 3-Speed Switch
Forward Inclined Centrifugal-Type Fan
High Efficiency Particulate Air (HEPA) Filter:
99.99% @ 0.3 micron
Snap-in Prefilter Facilitates Maintenance and Replacement
Walkable Plenum (excluding Prefilter)
Meets IEST Recommended Practices
UL Listed (120V, 277V) with Standard UL 900 Class 2 Filter
Available in 24 x 24 or 24 x 48

CRFF-E/CRFF-E-ARS Series Added FEATURES


ECM Brushless DC Motor: Programmed to Operate
Between 50 fpm and 130 fpm

Constant Airflow Over a Wide Range of External


Static Pressures

0.6wg (200Pa) of External Static Capability at


90 fpm (0.45 m/s)

CRFF-ARS/CRFF-E-ARS Series Added FEATURES

Constant Volume Airflow


The CRFF-E series of critical room fan filter units contain an
electronically commutative (ECM) brushless DC motor which
delivers constant airflow by adjusting the motor rpm and torque,
compensating for changes in static pressure, filter loading or
other local conditions. Further increasing ease of use, constant
airflow reduces the need for post installation adjustments.
Filter Options and Accessibility
With the ARS model option, through the perforated face which
can be removed for periodic cleaning, HEPA filters are easily
accessible and replaceable from the room side. Utilizing
industry proven gel seal filter technology these units possess
an integral continuous knife edge that penetrates the filters
gel filled pocket, delivering a leak proof sealed unit. The HEPA
filter is protected by an expanded metal face that minimizes
unnecessary and accidental contact with the filter media. To
increase particulate removal, a ULPA filter is available.

CRFF Series OPtions


Ultra-Low Penetration Air (ULPA) Filter:
99.9995% @ 0.12 micron

A/C Collar: Allows Direct Connection to


Air Conditioning Supply

Extruded Aluminum Plaster Frame for Hard Ceilings

(Model 5HCF23)
Stainless Steel Construction Available
British White Finish
Power Cord: Provides Convenient Plug-in
Monitoring & Control System: On-site or Remote
Monitoring and Adjustment
Challenge Port: Convenient Aerosol Challenge and
HEPA Filter Testing
Infrared Speed Control: Room-Side Airflow Adjustment
with Hand-Held Remote Control (CRFF-E Series Only)

FINISHES
Standard Finish is Mill Aluminum
Optional British White Finish

Room Side Access to HEPA Filter

KRUEGER 2006

C
R
F
F
O-66

Excellence in Air Distribution

www.krueger-hvac.com

SUPPLY | CRITICAL ROOM SOLUTIONS


CRFF | FAN FILTER UNIT
CRFF/CRFF-ARS Series DIMENSIONAL information
CRFF & CRFF-ARS, 24x48 PANEL, FACE VIEW
47.85 (1215)
45.37 (1152)

21.37 23.85
(543) (606)

CRITICAL ROOM SOLUTIONS

SNAP-IN PREFILTER

CRFF, 24x48 PANEL, SIDE VIEW


Panel Size
24 x 24
24 x 48

OA Face Dimension
23.63 x 23.63 (600 x 600 mm)
23.63 x 47.63 (600 x 1200 mm)

SOLID STATE
SPEED CONTROLLER

7/8 KNOCKOUT FOR


INCOMING POWER
ON/OFF SWITCH

12.51
(318)

9.47
(241)

47.63 (1210)

23.63 (600)

CRFF-ARS, 24x48 PANEL, SIDE VIEW


Panel Size
24 x 24
24 x 48

OA Face Dimension
23.63 x 23.63 (600 x 600 mm)
23.63 x 47.63 (600 x 1200 mm)

SOLID STATE
SPEED CONTROLLER

7/8 KNOCKOUT FOR


INCOMING POWER
ON/OFF SWITCH

14.57
(370)

11.53
(293)

47.63 (1210)

23.63 (600)

KRUEGER 2006

C
R
F
F
www.krueger-hvac.com

Excellence in Air Distribution

O-67

SUPPLY | CRITICAL ROOM SOLUTIONS


CRFF | FAN FILTER UNIT
CRFF-E/CRFF-E-ARS Series DIMENSIONAL information
CRFF-E & CRFF-E-ARS, 24x48 PANEL, FACE VIEW
47.85 (1215)
45.37 (1152)

CRITICAL ROOM SOLUTIONS

21.37 23.85
(543) (606)

SNAP-IN PREFILTER

CRFF-E, 24x48 PANEL, SIDE VIEW


Panel Size
24 x 24
24 x 48

OA Face Dimension
23.63 x 23.63 (600 x 600 mm)
23.63 x 47.63 (600 x 1200 mm)

VCU
CONTROLLER

7/8 KNOCKOUT FOR


INCOMING POWER
ON/OFF SWITCH

14.32
(364)

9.47
(241)

23.63 (600)

47.63 (1210)

CRFF-E-ARS, 24x48 PANEL, SIDE VIEW


Panel Size
24 x 24
24 x 48

OA Face Dimension
23.63 x 23.63 (600 x 600 mm)
23.63 x 47.63 (600 x 1200 mm)

VCU CONTROLLER

7/8 KNOCKOUT FOR


INCOMING POWER
ON/OFF SWITCH

16.43
(417)

11.58
(294)

47.63 (1210)

23.63 (600)

KRUEGER 2006

C
R
F
F
O-68

Excellence in Air Distribution

www.krueger-hvac.com

SUPPLY | CRITICAL ROOM SOLUTIONS


CRFF | FAN FILTER UNIT
CRFF Series PERFORMANCE DATA
IP/METRIC DATA: CRFF/CRFF-ARS SERIES
Unit Type

CRFF
CRFF-ARS

Nominal Motor
Unit Size
Hp
24x24
24x48
24x24
24x48
24x48

1/5
1/5

Voltage
115V
115V
115V
115V
277V

Average
Airflow
CFM
m3/Hr

Watts
@
90 fpm

Heat
Gain
(BTU/Hr)
@ 90 fpm

Max
Amps

325 (550)
650 (1100)
325 (550)
650 (1100)
650 (1100)

150
190
120
200
200

512
648
409
682
682

3.0
3.0
3.0
3.0
1.2

Total Unit Sound


Weight
Level
Lb (kg)
dBA
41 (19)
66 (30)
44 (20)
71 (32)
71 (32)

48.0
50.3
48.0
50.3
50.3

Octave Band Sound


@ 90 fpm
2

45
57
45
57
57

51
52
51
52
52

49
49
49
49
49

36
44
36
44
44

32
36
32
36
36

25
30
25
30
30

Test data taken with an electronic micromanometer with Velgrid attachment; eight readings in unloaded conditions.
Custom-sized units are also available.

Unit Type

CRFF-E

CRFF-E-ARS

Nominal Motor
Unit Size
Hp
24x24
24x48
24x48
24x24
24x48
24x48

1/3

1/3

Voltage
115V
115V
277V
115V
115V
277V

Average
Airflow
CFM
m3/Hr

Watts
@
90 fpm

Heat
Gain
(BTU/Hr)
@ 90 fpm

Max
Amps

325 (550)
650 (1100)
650 (1100)
325 (550)
650 (1100)
650 (1100)

80
105
105
110
140
140

273
358
358
375
477
477

3.4
3.4
1.7
3.4
3.4
1.7

Total Unit Sound


Weight
Level
Lb (kg)
dBA
41 (19)
66 (30)
66 (30)
44 (20)
71 (32)
71 (32)

46.5
48.0
48.0
46.5
48.0
48.0

Octave Band Sound


@ 90 fpm
2

48
53
53
48
53
53

48
50
50
48
50
50

49
47
47
49
47
47

44
40
40
44
40
40

38
38
38
38
38
38

30
35
35
30
35
35

Test data taken with an electronic micromanometer with Velgrid attachment; eight readings in unloaded conditions.
Custom-sized units are also available.

CRITICAL ROOM SOLUTIONS

IP/METRIC DATA: CRFF-E/CRFF-E-ARS SERIES

CRFF Series ARRAy VIEW


Shown left is a typical installation of multiple CRFF fan filter
units mounted above the service area, completely blanketing the critical area with clean,
filtered supply air. For spot applications, a single CRFF can
be mounted over a work bench
or table to reduce particulatecounts.

KRUEGER 2006

C
R
F
F
www.krueger-hvac.com

Excellence in Air Distribution

O-69

SUPPLY | CRITICAL ROOM SOLUTIONS


CRFF | FAN FILTER UNIT

CRITICAL ROOM SOLUTIONS

CRFF Series SUGGESTED SPECIFICATION & CONFIGURATION


CRFF
The critical room fan filter unit shall be Krueger model CRFF of
the sizes shown on the plans or outlet schedule. The unit shall
be configured to deliver uniform filtered laminar flow over the
face of the unit. A patented air baffle system will be furnished
as an integral part of the fan plenum housing. The fan filter unit
shall be UL 507 listed, possessing a UL Class 2 filter. The lid
shall be constructed of .080 (2.0 mm) aluminum with (6.4
mm)-20 threaded inserts in four corners for suspension. The
filter housing will be constructed of 0.063 (1.6 mm) inch thick
aluminum. The unit will be furnished with a 30% (20 PPI) polyurethane foam, washable prefilter (to be removed with A/C collar option). The unit will contain an integral factory tested HEPA
filter, which will be rated 99.99% efficient in removal of particles
0.3 micron and larger; leak free in accordance with the latest
I.E.S.T. recommended practices. The HEPA filter shall be auto
scanned for efficiency and leakage prior to assembly of the fan
filter unit. HEPA filter media shall be microglass fiber with hot
melt separators, sealed to the aluminum housing. The fan/motor will be direct drive; forward curve centrifugal type with permanently lubricated sealed ball bearings. Bearings are rated
for L-10 life of 80,000 hours. The motor shall be a permanent
split capacitor type, rated for continuous duty, furnished with
thermal overload protection and Solid State Speed Control or
3speed control optional.

1. SERIES: (XXXX)
CRFF - Critical Room Fan Filter Unit with HEPA Filter
2. PANEL: (XX)x(XX)
24x24
24x48
3. FRAME: (XXX)
F23 - Lay-in T-Bar
4. HEPA: (XXXX)
HEPA - HEPA Filter
5. ROOM SIDE ACCESS: (XXX)
000 - None
6. MOTOR: (X)
1 - 115V PSC Motor with Solid State Speed Controller

7. FINISH: (XX)
01 - Mill
44 - British White

ULPA Filters (Rated 99.9995% at 0.12 Micron), UL 900 Class


1 and 2 (HEPA and ULPA), PTFE (45mm and 68mm packs)
are also available.
Total weight of the standard (24 x 48) unit, excluding optional
accessories shall be less than 66 lbs. (30 kg).
FINISH
The filter face guard will be epoxy powder coated expanded
steel. Both the fan plenum and filter housing shall have a mill
finish (powder coat paint or stainless steel exterior-optional),
and sealed airtight.
PERFORMANCE
The unit shall meet or exceed the requirements/specifications
of the following industry standards: ISO Class 5(Class 100
(M 3.5)) air per the latest IEST 14644-1 (Airborne Particulate
Cleanliness Classes). I.E.S.T. Recommended Practices (Laminar Flow Clean Air Devices). Average measured air velocity
will be 90(10) ft/min (.45 m/s), when measured using a Velgrid
(eight readings) 6 in. (152mm) below the filter face. All measured values shall fall within 20% of the measured average.
The sound level shall be approximately 51 dBA (below NC 45))
on low speed or with the optional speed control, measured at
30 in. (762 mm) from the filter face, with the fan delivering an
average air flow velocity of 90 ft/min (.45 m/s). Ambient sound
level less than 35 dBA. Noise measurements are taken with a
clean filter with no external static pressure. Vibration level will
not exceed .09 MILS RMS at 90 ft/min (0.45 m/s).
KRUEGER 2006

C
R
F
F

SAMPLE CONFIGURATION: CRFF - 24x48 - F23 - HEPA - 000 - 1 - 44

O-70

Excellence in Air Distribution

www.krueger-hvac.com

SUPPLY | CRITICAL ROOM SOLUTIONS


CRFF | FAN FILTER UNIT
CRFF-ARS/CRFF-E/CRFF-e-ARS AVAILABLE CONFIGURATIONs
1. SERIES: (XXXX-X)
CRFF-E - Critical Room Fan Filter Unit with

ECM Motor and HEPA Filter

2. PANEL: (XX)x(XX)
24x24
24x48

2. PANEL: (XX)x(XX)
24x24
24x48

3. FRAME: (XXX)
F23 - Lay-in T-Bar

3. FRAME: (XXX)
F23 - Lay-in T-Bar

4. HEPA: (X)
HEPA - HEPA Filter

4. HEPA: (XXXX)
HEPA - HEPA Filter

5. ROOM SIDE ACCESS: (XXX)


ARS - Room Side Access to Filter

5. ROOM SIDE ACCESS: (XXX)


000 - None

6. MOTOR: (X)
1 - 115V PSC Motor with Solid State Speed Controller
3 - 277V PSC Motor with Solid State Speed Controller*

7. FINISH: (XX)
01 - Mill
44 - British White

6. MOTOR: (XX)x(XX)
4 - 115V ECM Motor with Solid State Speed Controller
6 - 277V ECM Motor with Solid State Speed Controller

7. FINISH: (XX)
01 - Mill
44 - British White

*Only available on 24x48 panel size.

*Only available on 24x48 panel size.

CRITICAL ROOM SOLUTIONS

1. SERIES: (XXXX-XXX)
CRFF-ARS - Critical Room Fan Filter Unit with

HEPA Filter and Room Side Access

1. SERIES: (XXXX-X-XXX)
CRFF-E-ARS - Critical Room Fan Filter Unit with

ECM Motor, HEPA Filter, and Room

Side Access
2. PANEL: (XX)x(XX)
24x24
24x48
3. FRAME: (XXX)
F23 - Lay-in T-Bar
4. HEPA: (XXXX)
HEPA - HEPA Filter
5. ROOM SIDE ACCESS: (XXX)
ARS - Room Side Access

KRUEGER 2006

6. MOTOR: (XX)x(XX)
4 - 115V ECM Motor with Solid State Speed Controller
6 - 277V ECM Motor with Solid State Speed Controller

7. FINISH: (XX)
01 - Mill
44 - British White

C
R
F
F

SAMPLE CONFIGURATION: CRFF-ARS - 24x24 - F23 - HEPA - ARS - 1 - 01


SAMPLE CONFIGURATION: CRFF-E - 24x48 - F23 - HEPA - 000 - 6 - 44
SAMPLE CONFIGURATION: CRFF-E-ARS - 24x24 - F23 - HEPA - ARS - 4 - 44
www.krueger-hvac.com

Excellence in Air Distribution

O-71

You might also like