You are on page 1of 2

RCP phase control,

RCI current control,


RCU voltage control and
RCC compressor control relays

energy management

function

RCP

RCU

The phase control relay monitors phase


order and asymmetry as well as voltage
presence on all 3 phases of a three-phase
circuit (motor supply, etc.). It reports phase
loss or reversal.

The voltage control relay monitors the


potential difference of a circuit and reports
when the preset threshold is reached.

RCI

The compressor control relay monitors the


compressor power supply and prevents its
immediate restart on detection of a voltage
break or drop.

The current control relay monitors the


current flowing in a circuit and reports when
the preset threshold is reached.

description

common technical data

# parameter setting:
5 on the front face
5 by direct scale
5 using a screwdriver
# display accuracy: 10 % full scale
# utilisation frequency: 5060 Hz
# utilisation temperature: -5+55 C
# consumption: 3 VA
# indication:
5 green LED for power ON
5 red LED for fault
# output by 8 A changeover switch under
250 V AC (cos = 1)

for rigid
# connection: tunnel terminals
2
cables from 1.5 to 6mm

RCC

RCU

# measurement:
5 range: 10...500 V
5 automatic recognition of ac and dc voltage
5 2 measurement ranges selected by wiring:
- 10...50 V
- 50...500 V
# overvoltage and undervoltage monitoring
(selection by selector switch)
# threshold adjustable from 10...100 %
# hysteresis adjustable from 5...50 %
# failsafe contact
# time delay on threshold reached: 0.1...10s
# supply voltage: 230 V AC
# optional fault memorisation with reset

RCC

# operating voltage: 230 V AC


# threshold setting:

specific technical data

RCP

# operating voltage: 400 V AC, 15 %


# phase asymmetry threshold setting:

515 % voltage drop

# time delay on threshold reached:

3 or 6 minutes (selection by wiring)

5...25 %
# hysteresis: fixed, 5% of asymmetry
threshold
# phase rotation direction monitoring
# 3 phase presence monitoring
# time delay on tripping: 0.3 s

RCI

# measurement:
5 range: 0.15...10 A
5 automatic recognition of ac and dc current
5 2 measurement ranges selected by wiring:

- 0.15...1.5 A
- 1...10 A
# overcurrent and undercurrent monitoring
(selection by selector switch)
# threshold adjustable from 10...100 %
# hysteresis adjustable from 5...50 %
# failsafe contact
# time delay on threshold reached: 0.1...10 s
# power supply: 230 V AC
# optional fault memorisation with reset
# compatible with TI current transformers
with an X/5 ratio

90165E.fm/2

Updated: 26/06/02

Schneider Electric

RCP phase control,


RCI current control,
RCU voltage control and
RCC compressor control relays

energy management

catalogue numbers

type

RCP

catalogue
number

width in
mod. of 9 mm

21180

21181

21182

21183

L1
L2
L3
F= 60 Hz
1 3 5 7
21180

6 8

RCI

L
circuit to control
0.15 A Ir 1.5 A
1 A Ir 10 A

1 3 5 7

21181

4 6 8

N
RCU

L
circuit to control
10100 V CA/CC
50500 V CA/CC

1 3 5 7

21182

6 8

N
RCC

6 min
3 min

1 3 5 7
21183

6 8

additional
information
Schneider Electric

dimensions: page 90148/2


practical advice: page 92407/2

current transformers: page 92068/2

Updated: 26/06/02

90165E.fm/3