Professional Documents
Culture Documents
Bus Protection
11/14/2014
Bus Protection
A fault at the busbar is quite rare but can cause enormous damage.
When protective relays operate to isolate the busbar from the system, there is a large
disruption to- the loads.
Because of the low probability of busbar faults, for many years, it was considered
unnecessary to provide explicit protection to busbars. However, as the system voltage
went on increasing and short-circuit capacities went on building up, it was no. longer
advisable to leave busbars unprotected on a primary basis.
11/14/2014
The CT ratios of all the CTs are equal and are based on the primary current of that feeder
which carries the maximum current
11/14/2014
CT Behavior
11/14/2014
At low values of primary current, voltage E to be induced by the secondary winding is quite
low.
The working flux in the CT is also very low. Thus the magnetizing current requirement is
correspondingly low.
If the primary current increases, initially, the secondary current also increases proportionately.
This causes the secondary induced voltage to increase as well.
Increased secondary voltage can only be met with an increase in the working flux of the CT.
As the flux increases, the transformer needs to draw a higher magnetizing current.
Because of the nonlinear nature of the B-H curve for the CT, as the knee of the excitation
characteristics is passed, any further increase in flux demand causes a disproportionately large
increase in the magnetizing current requirement of the CT.
11/14/2014
11/14/2014
External Fault
One CT gets
saturated and the
other two are
operating normally
11/14/2014
The stabilizing resistance should be of such a value that under the worst
case of maximum external fault and full saturation of one CT, the
current through the OC relay is less than its pick-up value.
Under this condition, the current through the relay be less than or equal to its
pick-up value Ipu
11/14/2014
Assuming n feeders and further assuming that the magnetizing current of each unsaturated CT
is same and equal to I0 and noting that the transformation ratio of all the CTs is same and equal
to N, the general expression:
1
Where the subscript k varies from 1 to n - 1, n being the total number of feeders terminating on the bus.\
Ignoring I0,
"#
is the maximum external fault current up to which the
$
%,',('
Determine the minimum internal fault current %,)*+,*)(*, that can be detected by the high impedance
busbar differential scheme.
11/14/2014
10
11/14/2014
.
.
.
I01 I02 I03
%,(),-
%,(),*)(
3I4
%,(),*)( 34
%,(),*)( 34
For the general case of n feeders terminating on the busbar, the minimum internal fault current
that can be detected by the high impedance busbar differential scheme will be given by
%,(),*)(
4
Stability Ratio
The stability ratio S of the high impedance busbar differential scheme is defined as the ratio of
maximum external fault current for which the scheme remains stable to the minimum internal
fault current for which it operates.
%,'*+,(')((
%,)*+,())((
The higher the value of stability ratio S, the better is the quality of differential protection.
Stability ratios of a few tens are common in EHV busbar differential schemes.
11